This manual contains important instructions and warnings that you should
follow during the installation, operation, storage and maintenance of this
product. Failure to heed these instructions and warnings will void the warranty.
Please comply with all warnings and operating instructions in this manual strictly.
Save this manual properly and read carefully the following instructions before
installing the unit. Do not operate this unit before reading through all safety
information and operating instructions carefully.
1.1 Transportation
z
z
Please transport the UPS system only in the original package to protect against
shock and impact.
1.2 Preparation
z
z
Condensation may occur if the UPS system is moved directly from cold to warm
environment. The UPS system must be absolutely dry before being installed.
Please allow at least two hours for the UPS system to acclimate the environment.
z
z
Do not install the UPS system near water or in moist environments.
z
z
Do not install the UPS system where it would be exposed to direct sunlight or
near heater.
z
z
Do not block ventilation holes in the UPS housing.
1.3 Installation
z
z
Do not connect appliances or devices which would overload the UPS system (e.g.
laser printers) to the UPS output sockets.
z
z
Please do not attached half-sinewave load or motor load to the UPS.
z
z
Place cables in such a way that no one can step on or trip over them.
z
z
Do not connect domestic appliances such as hair dryers to the UPS output sockets.
z
z
The UPS can be operated by any individuals with no previous experience.
z
z
Connect the UPS system only to an earthed shockproof outlet which must be
easily accessible and close to the UPS system.
z
z
Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of
your computer) to connect the UPS system to the building wiring outlet (shock-
Amplon INX Series
1
Chapter 1 Important Safety Warnings
proof outlet).
z
z
Please use only VDE-tested, CE-marked power cables to connect the loads to
the UPS system.
z
z
When installing the equipment, it should ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3.5mA.
1.4 Operation
z
z
Do not disconnect the mains cable on the UPS system or the building wiring
outlet (shockproof socket outlet) during operations since this would cancel the
protective earthing of the UPS system and of all connected loads.
z
z
The UPS system features its own, internal current source (batteries). The UPS
output sockets or output terminals block may be electrically live even if the UPS
system is not connected to the building wiring outlet.
z
z
In order to fully disconnect the UPS system, rst press the OFF/ ENTER button
to disconnect the mains.
z
z
Prevent no uids or other foreign objects from inside of the UPS system.
1.5 Maintenance, Service and Faults
z
z
The UPS system operates with hazardous voltages. Repairs may be carried out
only by qualied maintenance personnel.
WARNING:
Risk of electric shock. Even after the unit is disconnected from the mains
(building wiring outlet), components inside the UPS system are still
connected to the battery and electrically live and dangerous.
z
z
Before carrying out any kind of service and/ or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in
the terminals of high capability capacitor such as BUS-capacitors.
z
z
Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
WARNING:
Risk of electric shock. The battery circuit is not isolated from the input
voltage. Hazardous voltages may occur between the battery terminals and
the ground. Before touching, please verify that no voltage is present!
2
z
z
Batteries may cause electric shock and have a high short-circuit current. Please
take the precautionary measures specied below and any other measures necessary when working with batteries:
- remove wristwatches, rings and other metal objects
- use only tools with insulated grips and handles.
z
z
When changing batteries, install the same number and same type of batteries.
z
z
Do not attempt to dispose of batteries by burning them. This could cause battery
explosion.
z
z
Do not open or destroy batteries. Escaping electrolyte can cause injury to the
skin and eyes. It may be toxic.
z
z
Please replace the fuse only with the same type and amperage in order to avoid
re hazards.
z
z
Do not dismantle the UPS system.
1.6 Packing List
1
No.ItemQ’ty
1
2
3
4
5
6
Amplon INX Series
2
3
4
5
6
UPS1 PC
Input cable1 PC
USB cable1 PC
User manual1 PC
Battery cable (for Extended Runtime Model only)1 PC
Screws and nuts (for Extended Runtime Model
only)
3
2 Sets
Chapter 2 Installation and Setup
1 kVA
2 kVA
3 kVA
Chapter 2 : Installation and Setup
NOTE :
Before installation, please inspect the unit. Be sure that nothing inside the
package is damaged. Please keep the original package in a safe place for
future use.
2.1 Rear Panel View
z
z
Standard Runtime Model
4
z
z
Extended Runtime Model
1 kVA2 kVA3 kVA
No.Item
1
2
3
4
5
6
7
8
AC input
Input circuit breaker
USB port
RS-232 port
Mini slot
Output socket
External battery connector
Output terminal
Amplon INX Series
5
Chapter 2 Installation and Setup
2.2 Operating principle
The operating principle of the UPS is shown as below
2.3 Setup the UPS
Step 1: Connect battery wires
If UPS is extended runtime model, please connect
external batteries as below chart.
Please refer to below chart to secure battery cable to
the terminal with supplied screws and nuts.
6
Step 2: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using
extension cords.
z
z
The power cord is attached to the UPS. For the type of power cord, please refer
to the table below.
UPSType of Power Cord
1kVAPlug 10A INDIA
Standard Runtime
Model
2kVAPlug 10A INDIA
3kVAPlug 16A INDIA
1kVAPlug 10A INDIA
Extended Runtime
Model
2kVAPlug 16A INDIA
3kVAPlug 16A INDIA
Step 3: UPS output connection
z
z
For socket-type outputs, simply connect devices to the outlets.
z
z
For terminal-type outputs, please follow below steps for the wiring conguration:
1. Remove the small cover of the terminal block
2. Suggest using AWG12 ~ 10 or 3.3mm
Please also install a circuit breaker (40A) between the mains and AC input
of the UPS in 3kVA for safety operation.
3. Upon completion of the wiring conguration, please check whether the wires
are securely afxed.
4. Put the small cover back to the rear panel.
Amplon INX Series
2
~ 5.3mm2 power cords for 3kVA.
7
Chapter 2 Installation and Setup
Step 4: Communication connection
USB port
Mini slot
MINI SLOT
RS-232 port
RS-232
To allow for unattended UPS shutdown/ start-up and status monitoring, connect
the communication cable one end to the USB/ RS-232 port and the other to the
communication port of your PC. With the monitoring software installed, you can
schedule UPS shutdown/ start-up and monitor UPS status through PC.
The UPS is equipped with mini slot perfect for Delta mini SNMP, Relay I/O, Modbus
or TVSS cards (optional). When installing mini card in the UPS, it will provide
advanced communication and monitoring options.
NOTE :
1. The USB port and RS-232 port can’t work at the same time.
2. If you choose to use the USB port rather than RS-232 port, please install
the USB driver software in your computer after connecting your computer
to the UPS’s USB port. The software can be downloaded from http://www.
deltapowersolutions.com/en-in/mcis/1kva-3kva-single-phase-ups-inx-
series-downloads.php.
Step 5: Turn on the UPS
Press the ON/ MUTE button on the front panel for two seconds to power on the
UPS.
NOTE :
The battery charges fully during the rst ve hours of normal operation. Do
not expect full battery run capability during this initial charge period.
8
Step 6: Install software
For optimal computer system protection, install UPS monitoring software to fully
congure UPS shutdown. Please download the software from
http://www.deltapowersolutions.com/en/mcis/software-center.php.
2.4 Battery Replacement
WARNING :
1. This rack UPS is equipped with internal batteries and user can replace
the batteries without shutting down the UPS or connected loads (hotswappable battery design). Replacement is a safe procedure, isolated
from electrical hazards.
2. Consider all warnings, cautions, and notes before replacing batteries.
NOTE :
outages.
Upon battery disconnection, equipment is not protected from power
Amplon INX Series
9
Chapter 3 : Operation
3.1 Button Operation
ON / MUTESELECTOFF / ENTER
ButtonFunction
z
z
Turn on the UPS: Press and hold the ON/ MUTE button for at
least 2 seconds to turn on the UPS.
z
z
Mute the alarm: When the UPS is in battery mode, press and
hold this button for at least 5 seconds to disable or enable the
ON/ MUTE
Button
alarm system. But it’s not applied to the situations when warnings or errors occur.
z
z
Up key: Press this button to display previous selection in UPS
setting mode.
z
z
Switch to UPS self-test mode: Press and hold this button for
5 seconds to enter UPS self-testing while in AC mode, ECO
mode, or converter mode.
Chapter 3 Operation
OFF/ ENTER
Button
z
z
Turn off the UPS: Press and hold this button at least 2 seconds
to turn off the UPS. The UPS will switch to either standby mode
or bypass mode according to your setting of bypass function. If
you enable the bypass function, the UPS will transfer to bypass
mode; if you disable the bypass function, the UPS will transfer
to standby mode without any output. Please refer to 3.5 UPS Setting- 06: Bypass enable/ disable when the UPS is off.
10
ButtonFunction
z
z
Conrm selection key: Press this button to conrm selection in
UPS setting mode.
z
z
Switch LCD message: Press this button to change the LCD
message for input voltage, input frequency, battery voltage, output voltage and output frequency. It will return back to default
display when pausing for 10 seconds.
SELECT
Button
z
z
Setting mode: Press and hold this button for 5 seconds to enter
UPS setting mode when the UPS is in standby mode or bypass
mode.
z
z
Down key: Press this button to display next selection in UPS
setting mode.
z
z
ON/ MUTE
+ SELECT
Buttons
Switch to bypass mode: When the main power is normal, press
the ON/ MUTE and SELECT buttons simultaneously for 5 seconds. Then the UPS will enter to bypass mode. This action will
be ineffective when the input voltage is out of acceptable range.
3.2 LCD Panel
123
8
4
7
Amplon INX Series
5
6
11
Display Function
1
Remaining backup time information
Indicates the remaining backup time in pie chart.
Indicates the remaining backup time in numbers.
H: hour, M: minute, S: second
2
Fault information
Indicates that the warning and fault occurs.
Indicates the warning and fault codes, and the codes are
listed in details in 3.7 UPS Setting.
3
Mute operation
Indicates that the UPS alarm is disabled.
4
Output & Battery voltage information
Indicates the output voltage, frequency or battery voltage.
Vac: output voltage, Vdc: battery voltage, Hz: frequency
Chapter 3 Operation
5
Load information
Indicates the load level by 0-25%, 26-50%, 51-75%, and
76-100%.
Indicates overload.
Indicates the load or the UPS output is short circuit.
6
Mode operation information
Indicates the UPS connects to the mains.
Indicates the battery is working.
Indicates the bypass circuit is working.
12
Display Function
Indicates the ECO mode is enabled.
Indicates the inverter circuit is working.
Indicates the output is working.
7
Battery information
Indicates the battery level by 0-25%, 26-50%, 51-75%, and
76-100%.
Indicates the battery is fault.
Indicates low battery level and low battery voltage.
8
Input & Battery voltage information
Indicates the input voltage or frequency or battery voltage.
Vac: Input voltage, Vdc: battery voltage, Hz: input frequency
3.3 Audible Alarm
ConditionAlarm
Battery ModeSounding every 4 seconds
Low BatterySounding every second
OverloadSounding twice every second
FaultContinuously sounding
Bypass ModeSounding every 10 seconds
Amplon INX Series
13
3.4 LCD Display Wordings Index
AbbreviationDisplay ContentMeaning
Chapter 3 Operation
ENA
DIS
ESC
HLS
LLS
BAT
CF
TP
CH
FU
EE
Enable
Disable
Escape
High loss
Low loss
Battery
Converter
Temperature
Charger
Bypass frequency unstable
EEPROM error
14
3.5 UPS Setting
There are three parameters to set up the UPS.
Parameter 1
Parameter 2Parameter 3
Parameter 1: It’s for program alternatives. Refer to below table.
Parameter 2 and Parameter 3 are the setting options or values for each program.
z
z
01: Output voltage setting
Parameter 3: Output voltage
For 200/208/220/230/240 VAC models, you may choose the following output
voltage:
200: presents output voltage is 200Vac
208: presents output voltage is 208Vac
220: presents output voltage is 220Vac
230: presents output voltage is 230Vac (Default)
240: presents output voltage is 240Vac
Amplon INX Series
15
Chapter 3 Operation
z
z
02: Frequency converter enable/ disable
Parameter 2 & 3: Enable or disable converter mode. You may choose the
following two options.
CF ENA: converter mode enable
CF DIS: converter mode disable (Default)
z
z
03: Output frequency setting
Parameter 2 & 3: Output frequency setting.
You may set the initial frequency in battery mode.
BAT 50: presents output frequency 50Hz
BAT 60: presents output frequency 60Hz
If converter mode is enabled, you may choose the following output frequency.
CF 50: presents output frequency 50Hz
CF 60: presents output frequency 60Hz
16
z
z
04: ECO enable/ disable
Parameter 3: Enable or disable ECO function. You may choose the following
two options.
ENA: ECO mode enable
DIS: ECO mode disable (Default)
z
z
05: ECO voltage range setting
Parameter 2 & 3: Set the acceptable high voltage point and low voltage point
for ECO mode by pressing the Down key or Up key.
HLS: High loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in parameter
3 is from +7V to +24V of the nominal voltage.(Default: +12V)
LLS: Low loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in parameter
3 is from -7V to -24V of the nominal voltage. (Default: -12V)
Amplon INX Series
17
Chapter 3 Operation
z
z
06: Bypass enable/ disable when the UPS is off
Parameter 3: Enable or disable bypass function. You may choose the following
two options.
ENA: Bypass enable
DIS: Bypass disable (Default)
z
z
07: Bypass voltage range setting
Parameter 2 & 3: Set the acceptable high voltage point and acceptable low
voltage point for bypass mode by pressing the Down key or Up key.
HLS: Bypass high voltage point
For 200/208/220/230/240 VAC models:
230-264: setting the high voltage point in parameter 3 from 230Vac to
264Vac. (Default: 264Vac)
LLS: Bypass low voltage point
For 200/208/220/230/240 VAC models:
170-220: setting the low voltage point in parameter 3 from 170Vac to
220Vac. (Default: 170Vac)
18
z
z
08: Autonomy limitation setting
Parameter 3: Set up backup time in battery mode for general outlets.
0 ~ 999: setting the backup time in minutes from 0 ~ 999 for general outlets in
battery mode.
0: When setting as “0”, the backup time will be only 10 seconds.
999: When setting as “999”, the backup time setting will be disabled (Default).
z
z
09: Total battery AH
Parameter 3: Set up total battery AH value of the UPS. (unit: AH)
7-999: setting the total battery capacity from 7 to 999. Please set up this gure
if external battery pack is connected.
If the UPS is standard runtime model, the default setting is 9AH.
If the UPS is extended runtime model, the default setting is 65AH.
Amplon INX Series
19
z
z
00: Exit Setting
Exit the setting mode.
3.6 Operating Mode Description
z
z
Online Mode
When the input voltage is within
acceptable range, the UPS will
provide pure and stable AC power
to output. The UPS will also charge
the battery in online mode.
Chapter 3 Operation
z
z
ECO Mode
Energy saving mode:
When the input voltage is within
voltage regulation range, the UPS
will run in bypass mode to supply
power to output for energy saving.
z
z
Frequency Converter Mode
When the input frequency is
within 40 Hz to 70 Hz, the UPS
can be set at a constant output
frequency, 50 Hz or 60 Hz. The
UPS will still charge batteries
under this mode.
20
z
z
Battery Mode
When the input voltage is
beyond the acceptable range or
power failure occurs, the UPS
will backup power from batteries and the alarm is sounding
every 4 seconds.
z
z
Bypass Mode
When the input voltage is within
acceptable range but the UPS
is overloaded, the UPS will
enter bypass mode or bypass
mode can be set via the front
panel. The alarm is sounding
every 10 seconds.
z
z
Standby Mode
The UPS is powered off and
there is no output, but the batteries can still be charged.
3.7 Faults Reference Code
Fault EventFault Code Icon
Bus start fail01x
Bus over02x
Bus under03x
Bus unbalance04x
Inverter soft start failure11x
Inverter voltage high12x
Inverter voltage Low13x
Inverter output short14
Amplon INX Series
21
Chapter 3 Operation
Fault EventFault Code Icon
Battery voltage too high27
Battery voltage too low28
Over temperature41x
Overload43
Charger failure45x
3.8 Warning Indicator
WarningIcon (ashing)Alarm
Low battery
Overload
Battery is not connected
Over charge
Over temperature
Charger failure
Battery fault
Out of bypass voltage range
Bypass frequency unstable
EEPROM error
Sounding every second
Sounding twice every second
Sounding every second
Sounding every second
Sounding every second
Sounding every second
Sounding every second
Sounding every second
Sounding every second
Sounding every second
22
Chapter 4 : Troubleshooting
If the UPS system does not operate correctly, please solve the problem by using the
table below.
SymptomPossible CauseRemedy
No indication and alarm
even though the mains
is normal.
The icons
are ashing on the LCD
display and the alarm is
sounding every second.
Fault code is shown as
27 or 28 and the icon
is lighting on the
LCD display and the
alarm is continuously
sounding.
The icons
are ashing on the LCD
display and the alarm
is sounding twice every
second.
and
and
The AC input power is not
connected well.
The AC input is connected
to the UPS output.
The external or internal batteries are incorrectly connected.
Battery voltage is too high/
low or the charger is fault.
The UPS is overloaded.Remove excess loads
The UPS is overloaded.
Devices connected to the
UPS are fed directly by the
electrical network via the
bypass.
Check if the input
power cord rmly connected to the mains.
Plug the AC input
power cord to the AC
input correctly.
Check if all batteries
are connected well.
Contact your dealer.
from the UPS output.
Remove excess loads
from the UPS output.
Amplon INX Series
After repetitive overloads,
the UPS is locked in bypass mode. Connected
devices are fed directly by
the mains.
23
Remove excess loads
from the UPS output
rst. Then shut down
the UPS and restart it.
Chapter 4 Troubleshooting
SymptomPossible CauseRemedy
Fault code is shown as
43 and the icon
is
lighting on the LCD
display and the alarm is
continuously sounding.
Fault code is shown as
14 and the icon
is
lighting on the LCD
display and the alarm is
continuously sounding.
Fault code is shown as
01, 02, 03, 04, 11, 12,
13, 41 or 45 on the LCD
display and the alarm is
continuously sounding.
Battery backup time is
shorter than nominal
value.
The UPS shuts down automatically because of overload at the UPS output.
The UPS shuts down automatically because short
circuit occurs on the UPS
output.
An UPS internal fault has
occurred. There are two
possible results:
1. The load is still supplied,
but directly from AC
power via bypass.
2. The load is no longer
supplied by the power.
Batteries are not fully
charged.
Remove excess loads
from the UPS output
and restart it.
Check output wiring and if connected
devices are in short
circuit status.
Contact your dealer.
Charge the batteries
for at least 5 hours
and then check capacity. If the problem still
persists, consult your
dealer.
Batteries are damaged.Contact your dealer to
replace the batteries.
24
Chapter 5 : Storage and Maintenance
z
z
Operation
The UPS system contains no user-serviceable parts. If the battery service life
(3~5 years at 25°C ambient temperature) has been exceeded, the batteries
must be replaced. In this case, please contact your dealer.
Be sure to deliver the spent battery to a recycling facility or ship
it to your dealer in the replacement battery packing material.
z
z
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in
a cool, dry location. During storage, recharge the battery in accordance with the
following table:
1. * At 110~160Vac, linear de-rating between 60 ~ 100% load is required.
2. **De-rate capacity to 80% of capacity when the output voltage is adjusted to
200VAC or 208VAC
3. Please refer to the rating label for the safety rating.
4. All specications are subject to change without prior notice.
Amplon INX Series
27
Chapter 7 Warranty
Chapter 7 : Warranty
Seller warrants this product, if used in accordance with all applicable instructions,
to be free from original defects in material and workmanship within the warranty
period. If the product has any failure problem within the warranty period, Seller will
repair or replace the product at its sole discretion according to the failure situation.
This warranty does not apply to normal wear or to damage resulting from improper
installation, operation, usage, maintenance or irresistible force (i.e. war, fire,
natural disaster, etc.), and this warranty also expressly excludes all incidental and
consequential damages.
Maintenance service for a fee is provided for any damage out of the warranty
period. If any maintenance is required, please directly contact the supplier or Seller.
WARNING:
The individual user should take care to determine prior to use whether the
environment and the load characteristic are suitable, adequate or safe for
the installation and the usage of this product. The User Manual must be
carefully followed. Seller makes no representation or warranty as to the
suitability or tness of this product for any specic application.
Version Date : 2018_02_07
28