IFD9507
Ethernet Communication Module
Application Manual
Ethernet Communication Module IFD9507
Warn ing
Please read this instruction carefully before use and follow this instruction to operate the device in order to prevent
damages on the device or injuries to staff.
Switch off the power before wiring.
IFD9507 is an OPEN TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity,
electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g.
key or specific tools are required for operating the enclosure) in case danger and damage on the device may occur.
IFD9507 is to be used for controlling the operating machine and equipment. In order not to damage it, only
qualified professional staff familiar with the structure and operation of IFD9507 can install, operate, wire and
maintain it.
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check
all the wirings again before switching on the power and DO NOT touch any terminal when the power is switched
on. Make sure the ground terminal
1 INTRODUCTION...................................................................................................................................4
2 PRODUCT PROFILE & OUTLINE .......................................................................................................6
Table of Contents
1.1 Features ......................................................................................................................................4
1.2 Specifications ..............................................................................................................................4
2.1 Dimension ...................................................................................................................................6
2.2 Product Profiles...........................................................................................................................6
2.3 LED Indicators.............................................................................................................................6
2.4 RJ-11 PIN Definition ....................................................................................................................7
2.5 RJ-45 PIN Definition....................................................................................................................7
2.6 RS-232 PIN Definition .................................................................................................................7
2.7 Address Switch ...........................................................................................................................7
is correctly grounded in order to prevent electromagnetic interference.
2.8 Data Format ................................................................................................................................8
2.9 Baud Rate for Modbus Communication ......................................................................................8
2.10 Feed-through Terminal PIN Definition .........................................................................................8
3 INSTALLATION & WIRING ..................................................................................................................9
3.1 How to Install...............................................................................................................................9
3.2 How to Connect IFD9507 to Network..........................................................................................9
4 REGISTERS IN IFD9507....................................................................................................................10
4.1 Basic Registers (BR).................................................................................................................10
4.2 Explanations on BR...................................................................................................................10
4.3 Alarm Registers (AL) in IFD9507 ..............................................................................................13
DVP-PLC Application Manual
1
Ethernet Communication Module IFD9507
4.4 In buffer registers (IN) in IFD9507 ............................................................................................ 14
4.5 Out buffer registers (OUT) in IFD9507 ..................................................................................... 15
5 MONITORING FUNCTIONS.............................................................................................................. 15
5.1 Monitor Bit Registers (MB) ....................................................................................................... 15
5.2 Monitor Word Registerss (MW) ................................................................................................ 16
6 SETTING UP DEVICE ADDRESS AND RELAY ADDRESS IN SLAVE MODE (FOR MODBUS TCP
PROTOCOL ONLY)...........................................................................................................................17
7 SETTING UP DEVICE ADDRESS AND OTHER NETWORK SETTINGS IN SLAVE MODE........... 17
8 MODBUS COMMUNICATION ........................................................................................................... 18
8.1 Function Codes Supported....................................................................................................... 18
8.2 Exception Codes Supported..................................................................................................... 18
8.3 Device Type & Device Address................................................................................................. 18
9 ETHERNET/IP COMMUNICATION.................................................................................................... 19
9.1 Service code supported............................................................................................................ 19
9.2 Object supported ...................................................................................................................... 19
9.3 CIP General Status Code (Reference Volume 1:CIP Common Specification Appendix B) ...... 20
9.4 Connection Manager Service Request Error Codes (Reference Volume 1:CIP Common
Specification Table3-5.29) .................................................................................................................. 20
10 SETTING UP THE SOFTWARE - DCISOFT..................................................................................... 21
10.1 Setting up Communication & Searching for Modules in DCISoft.............................................. 21
10.2 Basic Settings........................................................................................................................... 23
10.3 Network Settings ...................................................................................................................... 24
10.4 Setting up E-Mails .................................................................................................................... 26
10.5 Monitoring Settings................................................................................................................... 27
10.6 IP Filter ..................................................................................................................................... 28
10.7 Ethernet/IP settings .................................................................................................................. 29
10.8 User Defined Settings............................................................................................................... 31
10.9 Virtual COM .............................................................................................................................. 33
10.10 Security Settings....................................................................................................................... 36
10.11 Returning to Default Settings.................................................................................................... 37
11 SETTING UP CONFIGURATION BY HOMEPAGE...........................................................................38
11.1 Webpage connection................................................................................................................ 38
11.2 Basic settings ........................................................................................................................... 39
11.3 Setting up E-Mails .................................................................................................................... 40
11.4 IP filter....................................................................................................................................... 41
11.5 Security Settings....................................................................................................................... 42
11.6 Returning to default setting....................................................................................................... 43
11.7 Monitoring settings ................................................................................................................... 43
11.8 Ethernet/IP................................................................................................................................ 45
11.9 User Define............................................................................................................................... 47
2
DVP-PLC Application Manual
Ethernet Communication Module IFD9507
12 APPLICATION EXAMPLES – DCISOFT ...........................................................................................49
12.1 Setting up & Unlocking Password .............................................................................................49
12.2 Password Loss (Returning to Default Settings by RS-232).......................................................51
12.3 IP Filter Protection.....................................................................................................................51
12.4 Application of E-Mail .................................................................................................................53
12.5 Monitoring Mode .......................................................................................................................54
12.6 Application of Virtual COM Port.................................................................................................56
13 APPLICATION EXAMPLES – AB SOFTWARE (REVISION:2.10.118.0)..........................................61
13.1 Serial Slave ...............................................................................................................................61
13.2 Serial Master .............................................................................................................................64
DVP-PLC Application Manual
3
Ethernet Communication Module IFD9507
1 Introduction
Thank you for choosing Delta’s IFD9507 module. To correctly install and operate IFD9507, please read the
manual carefully before using the module.
IFD9507 is an Ethernet communication module for remote setting and communication through Delta’s DCISoft
1.01.
IFD9507 has 3 digital input contacts which will send messages to designated E-Mail addresses after being
triggered. IFD9507 supports Modbus TCP communication protocol and can conduct remote monitoring by using
graphic software or human machine interface. IFD9507 can be the master of Modbus TCP, sending out Modbus
TCP instructions and controlling the peripheral equipment. IFD9507 supports Ethernet/IP communication protocol
and can control device between Ethernet/IP protocols with Modbus protocol. IFD9507 can be a slave as well,
receiving Modbus instructions sent from other masters and transferring them to another Modbus communication
network or Ethernet/IP communication network through Ethernet. In addition, under MDI/MDI-X auto-detection, it
does not need to jump wire in selecting the network cable. See the contents below for more detailed instructions
on IFD9507 module.
1.1 Features
z Auto-detects 10/100 Mbps transmission speed; MDI/MDI-X auto-detection
z The monitor table temporarily stores the monitored data for the user to fast save or acquire the data.
z Supports Modbus TCP protocol (supports Master and Slave mode)
z Supports Ethernet/IP protocol (supports Master and Slave mode)
z Able to send out emails after being triggered.
z The station address, RS-485 communication format and baud rate can be set up externally
1.2 Specifications
Network interface
Item Specification
Interface RJ-45 with Auto MDI/MDIX
Number of ports 1 Port
Transmission method IEEE802.3, IEEE802.3u
Transmission cable Category 5e
Transmission speed 10/100 Mbps Auto-Detection
Communication
protocol
ICMP, IP, TCP, UDP, DHCP, SMTP, Modbus TCP, Ethernet/IP
Serial communication interface (COM1)
Item Specification
Interface Mini Dim
Number of ports 1 Port
Transmission method RS-232
Transmission cable DVPACAB215 / DVPACAB230 / DVPACAB2A30
Transmission speed 110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Communication
protocol
4
Modbus, Delta Configuration, User Define
DVP-PLC Application Manual
Ethernet Communication Module IFD9507
Serial communication interface (COM2)
Item Specification
Interface RJ-11
Number of ports 1 Port
Transmission method RS-485
Transmission speed 110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Communication
protocol
Terminal block
Item Specification
Interface Feed-through terminal 10PIN
Transmission method RS-485
Transmission distance 1,200m
Transmission speed 110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Communication
protocol
Max. number of
stations
Modbus, User Define
Modbus, User Define
32
Environment
Item Specification
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: ± 2KV, Digital Input: ±2KV,
Communication I/O: ±2KV
Noise immunity
Operation temperature 0°C ~ 55 oC (temperature), 50 ~ 95% (humidity), pollution degree 2
Storage temperature -25°C ~ 70 oC (temperature), 5 ~ 95% (humidity)
Vibration/shock
immunity\
Certificates IEC 61131-2, UL508
Electrical specifications
Item Specification
Power voltage 24VDC (-15% ~ 20%) supplied by feed-through terminal
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1GHz, 10V/m. 1.4GHz ~ 2.0GHz,
10V/m
Conducted Susceptibility Test (EN61000-4-6, IEC61131-2 9.10): 150KHz ~
80MHz, 3V/m
Surge Test (Biwave IEC61132-2, IEC61000-4-5):
Power line 0.5KV DM, Ethernet 0.5KV CM, RS-485 0.5KV CM
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 &
IEC 68-2-27 (TEST Ea)
Power consumption 3W
Insulation voltage 500V
Weight (g) 140g
DVP-PLC Application Manual
5
Ethernet Communication Module IFD9507
2 Product Profile & Outline
2.1 Dimension
Unit: mm
2.2 Product Profiles
9
1 Communication ports: RS-485, Ethernet, RS-232 6 RS-485 indicator, Reset button, Ethernet indicator
2 Power indicator 7 Module name
3 Address setup rotary switch。
4 Communication format/baud rate setup switch 9 DIN rail connector
5 Message display
8 RS-485 connector, digital input points, power input
point, earth point
2.3 LED Indicators
Name Color Function
POWER Green Power status
RS-485 Green Status of series communication port
LINK/ACT Green Status of network communication
6
DVP-PLC Application Manual
2.4 RJ-11 PIN Definition
RJ-11 sketch PIN. Signal Definition
Ethernet Communication Module IFD9507
1 -- N/C
2 -- N/C
3 D+ Positive pole for data
4 D- Negative pole for data
2.5 RJ-45 PIN Definition
RJ-45 sketch PIN Signal Definition
2.6 RS-232 PIN Definition
PIN Signal Content
1 -- N/C
2 -- N/C
3 -- N/C
4 Rx Reception data
5 Tx Transmission data
6 -- N/C
7 -- N/C
8 GND Ground
5 GND Reference
6 -- N/C
1 Tx+ Positive pole for data transmission
2 Tx- Negative pole for data transmission
3 Rx+ Positive pole for data receiving
4 -- N/C
5 -- N/C
6 Rx- Negative pole for data receiving
7 -- N/C
8 -- N/C
2.7 Address Switch
Switch setting Content
01…F7 Valid node address setting
DVP-PLC Application Manual
7
Ethernet Communication Module IFD9507
2.8 Data Format
Switch setting Format Switch setting Format
0 7-N-1 8 7-N-2
1 8-N-1 9 8-N-2
2 7-O-1 A 7-O-2
3 8-O-1 B 8-O-2
6 7-E-1 E 7-E-2
7 8-E-1 F 8-E-2
2.9 Baud Rate for Modbus Communication
Switch setting Baud rate Switch setting Baud rate
1 110 7 4,000
2 150 8 9,600
3 300 9 19,200
4 600 A 38,400
5 1,200 B 57,600
6 2,400 C 115,200
2.10 Feed-through Terminal PIN Definition
PIN Signal Content
1 SG Reference ground of signal
2 D- Data-
3 D+ Data-
4 X2 Digital input 2
5 X1 Digital input 1
6 X0 Digital input 0
7 S/S Reference ground of digital input
8 24V +24V input
9 0V 0V input
10 Earth ground
8
DVP-PLC Application Manual
3 Installation & Wiring
This section gives instructions on how to connect IFD9507 with other devices and how to connect IFD9507 to
the network.
3.1 How to Install
Ethernet Communication Module IFD9507
3.2 How to Connect IFD9507 to Network
Connect IFD9507 to the Ethernet hub by twisted pair cable CAT-5e. IFD9507 has auto MDI/MDIX function;
therefore, IFD9507 does not need to jump wire if selecting CAT-5e.The network connection between the PC and
IFD9507:
PC Master
Ethernet
DVP-PLC Application Manual
RS-485 (Master Mode)
AC motor
driver
RS-485 (Master Mode) RS-485 (Slave Mode)
Temperature
controller
Human
machine
interface
9
Ethernet Communication Module IFD9507
4 Registers in IFD9507
4.1 Basic Registers (BR)
BR#
Attribute
0 R Model name
1 R Firmware version
2 R
3 Reserved
4 R/W
5 R/W Baud rate See the table of baud rate setting No
6 R/W Address For setting up the station address No
7 R
8 Reserved
9 R Error code Displaying the errors. See the table of error codes. 0 No
10 Reserved
11 R/W
12 R/W
13 R/W Keep alive time
14 R/W I/O Enable Flag
15 R/W IP Index Destination IP index 1 Yes
Content Explanation
Set up by the system; read only. The model code of
IFD9507= H’0201
Displaying the current firmware version in hex, e.g. V1.2 is
indicated as high byte = 0x01 and low byte = 0x20.
Displaying the date in decimal form. 10,000s digit and
Release date of
the version
Communication
format
Number of
DI/DO points
Communication
time-out
Communication
delay time
1,000s digit are for “month”; 100s digit and 10s digit are for
“day”. For 1s digit: 0 = morning; 1 = afternoon.
Example: 12191 indicates the version released in the
afternoon of December 19.
See the table of communication format setting No
DI: high byte; DO: low byte 0x300 Yes
For setting up the communication time-out (unit: ms) in
Modbus
For setting up the minimum interval time between every
communication datum
For setting up the communication time-out (unit: second) in
TCP connections
High byte is input buffer enable flag. Low byte is output
buffer enable flag. The flag will be cleared when data was
sent.
Default Latched
Yes
Yes
Yes
5,000 Yes
0 Yes
30 Yes
0 No
16~32 Reserved
33 R/W
Symbol “R” refers to read only; “R/W” refers to read and write.
Returning to
default setting
0 No
4.2 Explanations on BR
BR#0: Model Name
Explanations:
1. Model code of IFD9507 = H'0201.
2. You can read the model code in the program to see if the extension module exists
BR#1: Firmware Version
Explanations:
The firmware version of IFD9507 is displayed in hex, e.g. H’0100 indicates version V1.00.
10
DVP-PLC Application Manual
Ethernet Communication Module IFD9507
BR#2: Release Date of the Version
Explanations:
Displaying the date in decimal form. 10,000s digit and 1,000s digit are for “month" ; 100s digit and 10s digit
are for “day" . For 1s digit: 0 = morning; 1 = afternoon.
Example: 12191 indicates the version released in the afternoon of December 19.
BR#4: Communication Format
Explanations:
BR4 low byte
b7 ~ b4 b3 b2 ~ b1 b0
Stop bit
Explanation Reserved
0000 (0) 7-N-1 0011 (3) 8-O-1 1000 (8) 7-N-2 1011 (B) 8-O-2
Content
b7 B6 ~ b4 B3 b2 b1 b0
Explanation
0001 (1) 8-N-1 0110 (6) 7-E-1 1001 (9) 8-N-2 1110 (E) 7-E-2
0010 (2) 7-O-1 0111 (7) 8-E-1 1010 (A) 7-O-2 1111 (F) 8-E-2
RS-485
User
Define
0: Disable
1: Enable
Reserved
0: 1 stop bit
1: 2 stop bits
BR4 high byte
RS-232
User
Define
0: Disable
1: Enable
COM2 RS-485
setting
0: Serial Master
Ethernet Server
1: Serial Slave
Ethernet Client
Parity bit
00: none parity bit
01: odd parity bit
11: even parity bit
COM1 RS-232 setting
0: Delta Configuration
1: Modbus
Data bit
0: 7 data bits
1: 8 data bits
Mode
0: ASCII
1: RTU
Content
00000000 (0) Disable Disable Serial Master
00000001 (1) Disable Disable Serial Master
00000010 (2) Disable Disable Serial Master
00000011 (3) Disable Disable Serial Master
00000100 (4) Disable Disable Serial Slave
00000101 (5) Disable Disable Serial Slave
00000110 (6) Disable Disable Serial Slave
00000111 (7) Disable Disable Serial Slave
00001000 (8) Disable Enable Serial Master
: : : :
10000111 (135)
10001000 (136) Enable Enable Serial Master Delta configuration ASCII
10001001 (137) Enable Enable Serial Master Delta configuration RTU
10001010 (138) Enable Enable Serial Master Modbus ASCII
10001011 (139) Enable Enable Serial Master Modbus RTU
10001100 (140) Enable Enable Serial Slave Delta configuration ASCII
10001101 (141) Enable Enable Serial Slave Delta configuration RTU
10001110 (142) Enable Enable Serial Slave Modbus ASCII
10001111 (143) Enable Enable
Enable
Disable Serial Slave
Serial Slave Modbus RTU
Delta configuration
Delta configuration
Modbus
Modbus
Delta configuration
Delta configuration
Modbus
Modbus
Delta configuration
:
Modbus
ASCII
RTU
ASCII
RTU
ASCII
RTU
ASCII
RTU
ASCII
:
RTU
DVP-PLC Application Manual
11
Ethernet Communication Module IFD9507
BR#5: Baud Rate
Explanations:
BR#5 low byte for baud rate of COM1
Communication
interface
Baud rate
(bps)
Content
RS-232
BR#5 high byte for baud rate of COM2
Content RS-485 same as low byte
Data
0x01 110 0x06 2,400 0x0B 57,600
0x02 150 0x07 4,800 0x0C 115,200
0x03 300 0x08 9,600
0x04 600 0x09 19,200
0x05 1,200 0x0A 38,400
Explanation
Data
Baud rate
(bps)
Data
Baud rate
(bps)
BR#6: Address
Explanations:
For filling in or reading the Modbus address. The address will be displayed in the message display after being
set up.
BR#7: Number of DI/DO Points
Explanations:
Read the number of DI/DO points from BR#7.
BR#9: Error Code
Explanations:
Error code = 0 refers to no error occurring.
Code Indication How to correct
01 ~ F7
F0 Returning to default setting -F1 IFD9507 being powered -F2 Power supply in low voltage Check if the power supply of the module works normally.
F3 Internal memory detection error
F4 Internal error. Manufacturing error.
F5 Network connection error Check if IFD9507 is connected normally to the network.
F6
F7 UART setting error.
E1 Alarm 1 triggered Check alarm input point 1.
Node address of the scan module
(when operating normally)
Full number of devices connected
in the network.
--
1. Re-power IFD9507. If the error still exists, try step 2.
2. Reset IFD9507. If the error still exists, send the
module back to the factory for repair.
1. Re-power IFD9507. If the error still exists, try step 2.
2. Reset IFD9507. If the error still exists, send the
module back to the factory for repair.
Check if the number is too much.
Check if the RS-485, RS-232 communication format is
correct.
12
DVP-PLC Application Manual
Ethernet Communication Module IFD9507
Code Indication How to correct
E2 Alarm 2 triggered Check alarm input point 2.
E3 Alarm 3 triggered Check alarm input point 3.
1. Check if IFD9507 is normally connected to RS-485.
04 CRC error
0B No response from the station
BR#11: Communication Time-out (ms)
Explanations:
or setting up the communication time-out in Modbus. Default = 5,000ms. For example, if you wish to set up
the communication time-out as 7 seconds manually, write 7,000 into BR11.
BR#12: Communication Delay Time (ms)
2. Make sure the transmission speed of IFD9507 is
consistent with that of other nodes on the network.
1. Check if IFD9507 is normally connected to RS-485.
2. Make sure the transmission speed of IFD9507 is
consistent with that of other nodes on the network.
Explanations:
For setting up the minimum interval time between every Modbus communication datum. Default = 0ms. For
example, if you wish to set up the communication delay time as 100ms manually, write 100 into BR12.
BR#13: Keep Alive Time (s)
Explanations:
For setting up the communication time-out in TCP connections. Default = 30s. For example, if you wish to set
up the communication time-out as 7 seconds manually, write 7 into BR13.
BR14: I/O Enable Flag
Explanations:
Setting up input buffer and output buffer enable or not. Default = 0. Setting high byte to 1 can enable input
buffer and setting low byte to 1 can enable output buffer.
BR15: IP index
Explanations:
Destination IP index is used in a TCP connection. Default = 1. In delta DCISoft, there are 4 items can be set
therefore the index is 1 to 4. User can select one of items to connect with others Ethernet/IP device.
BR#33: Returning to Default Setting
Explanations:
IFD9507 will return to default setting when "1” is written into BR#33. BR#33 will be cleared to “0” automatically
after the returning.
4.3 Alarm Registers (AL) in IFD9507
AL# Attribute Content Explanation Default Latched
0 R/W Alarm point 1 0 Yes
DVP-PLC Application Manual
13
Ethernet Communication Module IFD9507
AL# Attribute Content Explanation Default Latched
1 R/W Alarm point 2 0 Yes
2 R/W Alarm point 3 0 Yes
Symbol “R” refer to read only; “R/W” refers to read and write.
AL#0: Alarm Point 1
Explanations:
You can designate one RX extension point as the alarm point by setting up the AL register in IFD9507. When
the alarm point is triggered, IFD9507 will execute its corresponding function. When b15 of AL0 is set as “1”,
the Gateway will execute the event immediately. When RX point is triggered, the Gateway will only execute
the triggered event once.
Device Function Setting Attribute Default Latched
b15
b4 ~ b14 Reserved
b2 ~ b3
AL#0
b1 Reserved Reserved
b0
Enabling the
function
Type of event
enabled when
RX alarm point
is triggered
Condition for
triggering RX
b15 = 1: Enabling
b15 = 0: Disabling
b3 b2
Reserved 0 0
Trigger E-Mail 0 1
Reserved 1 0
Reserved 1 1
The setting will be invalid when
thealarm function is being executed.
b0 = 0: Triggered when RX input
point is low
b0 = 1: Triggered when RX input
point is high
R/W 0 Yes
R/W 0 No
R/W 0 Yes
R/W 0 Yes
AL#1: Alarm Output 2
Explanations:
The settings for AL#1 are the same as those in AL#0.
AL#2: Alarm Output 3
Explanations:
The settings for AL#2 are the same as those in AL#0.
4.4 In buffer registers (IN) in IFD9507
IN# Attribute Content Explanation Default Latched
0~255 R/W Data input buffer Ethernet/IP input data 0 No
Symbol “R” refers to read only; “R/W” refers to read and write.
Explanations:
The input data was sent to Ethernet.
14
DVP-PLC Application Manual
4.5 Out buffer registers (OUT) in IFD9507
OUT# Attribute Content Explanation Default Latched
0~255 R Data output buffer 0 No
Symbol “R” refers to read only; “R/W” refers to read and write.
Explanations:
The output data was sent to RS-485.
5 Monitoring Functions
5.1 Monitor Bit Registers (MB)
MB# Attribute Content Explanation Default Latched
0 R/W
1 R/W
2 R/W
3 ~ 32 R/W
33 ~ 200 R/W Reserved
201 R Monitored value
202 ~ 213 R Reserved
214 R Monitored status
Symbol “R” refer to read only; “R/W” refers to read and write.
MB#0: Number of Devices Monitored
Number of devicees
monitored
No. of station
monitored
Address of the
device monitored
No. of station
monitored, address
of the device
monitored
Ethernet Communication Module IFD9507
Cache mode normally enabled (b15=1),
monitoring data in max. 16 slaves.
No. of the station to be monitored 0 Yes
Recording the address of the device
monitored.
No. of the station to be monitored;
recording the address of the device
monitored.
Every MB records the value in the 16-bit
device.
Every MB records the status in the 16-bit
device. 1 = normal; 0 = abnormal
0 Yes
0 Yes
0 Yes
0 No
0 No
Explanations:
For setting up the number of devices to be monitored. Max. data in 16 slaves can be monitored.
b15 is read only (Default =1: normally enabled cache mode)
MB# (Odd Number): No. of Station Monitored
Explanations:
MB#1, MB#3, MB#5…MB#33 are for setting up the station No. (0 ~ 255) to be monitored.
MB# (Even Number): Address of Device Monitored
Explanations:
MB#2, MB#4, MB#6…MB#34 are for setting up the address of the device to be monitored.
MB#201: Monitored Value
Explanations:
Every MB records the values in the 16-bit device.
DVP-PLC Application Manual
15
Ethernet Communication Module IFD9507
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Device
MB#214: Monitored Status
Explanations:
Every MB records the status in the 16-bit device. 1 = normal; 0 = abnormal.
Device
5.2 Monitor Word Registerss (MW)
33 ~ 200 R/W Reserved
201 ~ 216 R Monitored value
216 ~ 300 R Reserved
Symbol “R” refers to read only; “R/W” refers to read and write.
Device
16
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Device
16
15
15
Device
14
Device
14
Device
13
Device
13
Device
12
Device
12
Device
11
Device
11
Device
10
Device
10
Device 9 Device 8 Device 7 Device 6 Device 5 Device 4 Device 3 Device 2 Device
Device 9 Device 8 Device 7 Device 6 Device 5 Device 4 Device 3 Device 2 Device
MW# Attribute Content Explanation Default Latched
0 R/W
1 R/W
2 R/W
Number of devices
monitored
No. of station
monitored
Address of the
device monitored
Cache mode normally enabled (b15=1),
monitoring data in max. 16 slaves.
No. of the station to be monitored 0 YES
Recording the address of the device
monitored
No. of station
3 ~ 32 R/W
monitored, address
of the device
No. of the station to be monitore; recording
the address of the device monitored.
monitored
Every MW records the monitored value in 1
register
301 R Monitored status
Every MW records the status in a 16-bit
register. 1 = normal; 0 = abnormal
1
1
0 YES
0 YES
0 YES
0 NO
0 NO
16
MW#0: Number of Devices Monitored
Explanations:
For setting up the number of devices to be monitored. Max. data in 16 slaves can be monitored.
b15 is read only (Default =1: normally enabled cache mode)
MW# (Odd Number): No. of Station Monitored
Explanations:
MW#1, MW#3, MW#5…MW#33 are for setting up the station No. (0 ~ 255) to be monitored.
MW# (Even Number): Address of Device Monitored
Explanations:
MW32, MW34, MW#36…MW#34 are for setting up the address of the device to be monitored.
MW#201~#216: Monitored Value
DVP-PLC Application Manual
Ethernet Communication Module IFD9507
Explanations:
Every MW records the values in 1 register.
MW#201 MW#202 MW#203 MW#204 MW#205 MW#206 MW#207 MW#208 MW#209 MW#210
Device 1 Device 2 Device 3 Device 4 Device 5 Device 6 Device 7 Device 8 Device 9 Device 10
MW#211 MW#212 MW#213 MW#214 MW#215 MW#216
Device
11
Device
12
Device
13
Device
14
Device
15
Device
16
MW#301: Monitored Status
Explanations:
Every MW records the status in a 16-bit register. 1 = normal; 0 = abnormal.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Device
16
Device
15
Device
14
Device
13
Device
12
Device
11
Device
10
Device 9 Device 8 Device 7 Device 6 Device 5 Device 4 Device 3 Device 2 Device
1
6 Setting up Device Address and Relay Address in Slave Mode (For Modbus TCP protocol
only)
MIP# Attribute Content Explanation Default Latched
0 ~ 50 R/W
Corresponding
address
50 ~ 249 R/W Relay IP address
Symbol “R” refers to read only; “R/W” refers to read and write.
MIP#0: Corresponding Address
Explanations:
The low bytes of MIP#0 are for the first address, and the high byte are for the second address, and so on.
MIP#51 ~ #52: Corresponding IP for the 1st Device Address
Explanations:
Example 1: If you wish to convert “192.168.0.1” into C0A80001 (hex), write A8C0 into MIP50 and H0100 into
MIP51.
Max. 100 addresses are allowed. High
byte for 1 address and low byte for 1
address.
Total 100 IPs. Every address (1 byte)
corresponds to 1 IP address (4 bytes).
0 Yes
0 Yes
Example 2: Data in address 1 have to correspond to 192.168.0.8. Data in address 2 have to correspond to
192.168.0.6. To complete such settings, write H0102 into MIP0, H0800 into MIP50, HA8C0 into MIP51, H0600
into MIP52, and HA8C0 into MIP53.
7 Setting up Device Address and Other Network Settings in Slave Mode
Parameter Explanation
Device address Address of Modbus device
Relay IP address Corresponding IP address for a device
Priority/Time Tick Scale of time. Unit: ms
Timeout Tick Scale of timeout
Timeout Timeout = Time Tick × Timeout Tick (Unit: ms)
DVP-PLC Application Manual
17
Ethernet Communication Module IFD9507
Parameter Explanation
Multiple Max. timeout times
Trigger Cyclic, changing status, application object
OÆ T packet interval Packet interval between originator and target
TÆ O packet interval Packet interval between originator and target
8 Modbus Communication
8.1 Function Codes Supported
Function code Explanation Devices supported
0x02 Read discrete input RX
0x03 Read holding register BR, AL, MB, MW, MIP
0x06 Write single holding register BR, AL, MB, MW, MIP
0x10 Write multiple holding register BR, AL, MB, MW, MIP
0x17 Read/write multiple holding register BR, AL, MB, MW, MIP
8.2 Exception Codes Supported
Exception code Explanation
0x01 Illegal function
0x02 Illegal data addresss
0x03 Illegal data value
0x04 Slave device failure
0x0A Gateway path unavailable
0x0B Gateway target device failed to respond
8.3 Device Type & Device Address
Device
type
RX 0x0400 ~ 0x0402 11025 ~ 11027 101025 ~ 101027 3
Device
type
BR 0x0000 ~ 0x00FF 40001 ~ 40256 400001 ~ 400256 64
AL 0x0200 ~ 0x0202 40513 ~ 40515 400513 ~ 400515 3
X 0x0400 ~ 0x0402 41025 ~ 41027 401025 ~ 401027 3
IN 0x0500 ~ 0x05FF 41281 ~ 41536 401281 ~ 401536 256
OUT 0x0600 ~ 0x06FF 41537 ~ 41791 401537 ~ 401791 256
MB 0x2000 ~ 0x20FF 48193 ~ 48448 408193 ~ 408448 256
MW 0x2200 ~ 0x23FF 48705 ~ 49216 408705 ~ 409216 512
MIP 0x2400 ~ 0x24FF 49217 ~ 49471 409217 ~ 409471 256
Modbus address
(Hex)
Modbus address
(Hex)
Discrete input
5-digit Modbus address (Dec)
Holding register
5-digit Modbus address (Dec)
6-digit Modbus address
(Dec)
6-digit Modbus address
(Dec)
Number
Number
18
DVP-PLC Application Manual
9 Ethernet/IP Communication
9.1 Service code supported
Ethernet Communication Module IFD9507
Service
Code
ID
Message Router Object
Assembly Object
Connection Manager
Object
0x01
0x05 ID Reset Invokes the Reset service for the device.
0x0E
0x10
0x4E
0x54
BR
AL
MB
MW
TCP Interface
TCP Link
ID
Message Router Object
Assembly Object
Connection Manager
Object
BR
AL
MB
MW
TCP Interface
TCP Link
Assembly Object
BR
AL
MB
MW
TCP Interface
Connection Manager
Object
Connection Manager
Object
Object Service Description
Get_Attribute_All Returns a predefined listing of this objects
attributes
Get_Attribute_Single Return the contents of the specified
attribute.
Set_Attribute_Single Used to modify an attribute.
Forward_Close Closes a connection.
Forward_Open Opens a connection, maximum data size
is 511 bytes.
9.2 Object supported
Object Name Class ID Code Instance Code
ID 0x01 0x01 Identity Attribute Get
Message Router Object 0x02 0x01 Router Command
Assembly Object
Connection Manager Object 0x06 0x01 Connection
RX Digital input Discrete input Get
BR 0x64 0x01 Basic registers Attribute Get/Set
AL 0x64 0x02 Alarm function Attribute Get/Set
MB 0x64 0x03 Bit monitor Attribute Get/Set
MW 0x64 0x04 Register monitor Attribute Get/Set
TCP Interface 0xF5 0x01 TCP/IP Interface
DVP-PLC Application Manual
Function
Description
0x04 0x64 Assembly GO Set
0x04 0x65 Input device object GI Get
monitor object
Object
Object Type Attribute
Attribute Get/Set
19
Ethernet Communication Module IFD9507
Object Name Class ID Code Instance Code
TCP Link 0xF6 0x01 TCP/IP Link
Function
Description
Object
Object Type Attribute
Object Get
9.3 CIP General Status Code (Reference Volume 1:CIP Common Specification Appendix B)
General
Status Code
(in hex)
00 Success Service was successfully performed by the object specified.
01 Connection failure A connection related service failed along the connection path.
02 Resource unavailable Resources needed for the object to perform the requested
04 Path segment error The path segment identifier or the segment syntax was not
05 Path destination
08 Service not supported The requested service was not implemented or was not
09 Invalid attribute value Invalid attribute data detected
0E Attribute not settable A request to modify a non-modifiable attribute was received.
13 Not enough data The service did not supply enough data to perform the
14 Attribute not supported The attribute specified in the request is not supported
15 Too much data The service supplied more data than was expected
16 Object does not exist The object specified does not exist in the device.
20 Invalid parameter A parameter associated with the request was invalid. This code
26 Path Size Invalid The size of the path which was sent with the Service Request
Status Name Description of Status
service were unavailable
understood by the processing node. Path processing shall stop
when a path segment error is encountered.
The path is referencing an object class, instance or structure
unknown
element that is not known or is not contained in the processing
node. Path processing shall stop when a path destination
unknown error is encountered.
defined for this Object Class/Instance.
specified operation.
is used when a parameter does not meet the requirements of
this specification and/or the requirements defined in an
Application Object Specification.
is either not large enough to allow the Request to be routed to
an object or too much routing data was included.
9.4 Connection Manager Service Request Error Codes (Reference Volume 1:CIP Common Specification
Table3-5.29)
General
Status
0x00 Service completed successfully
0x01 0x0100 CONNECTION IN USE OR DUPLICATE FORWARD OPEN
0x01 0x0103 TRANSPORT CLASS AND TRIGGER COMBINATION NOT
0x01 0x0108 INVALID NETWORK CONNECTION PARAMETER
20
Extended Status Explanation and Description
This extended status code shall be returned when an originator is
trying to make a connection to a target with which the originator may
have already established a connection
SUPPORTED
A transport class and trigger combination has been specified which
is not supported by the target. Routers shall not fail the connection
based on the transport class and trigger combination. Only targets
shall return this extended status code.
This extended status code shall be returned as the result of
specifying a connection type, connection priority, redundant owner
or fixed / variable that is not supported by the target application.
Only a target node shall return this extended status code.
DVP-PLC Application Manual