Delta Electronics AE57BSTD, AE57GSTD, AS38BSTD, AS57BSTD Quick Start Manual

English-1
Preface
Thank you for purchasing DELTA’s DOP-A, AE and AS series. This quick start will be helpful in the installation, wiring and inspection of Delta HMI. Before using the product, please read this quick start to ensure correct use. You should thoroughly understand all safety precautions before proceeding with the installation, wiring and operation. Place this quick start in a safe location for future reference. Please observe the following precautions:
Install the product in a clean and dry location free from corrosive and inflammable gases or liquids. Ensure that all wiring instructions and recommendations are followed. Ensure that HMI is correctly connected to a ground. The grounding method must comply with the
electrical standard of the country.
Do not modify or remove wiring when power is applied to HMI. Do not touch the power supply during operation. Otherwise, it may cause electric shock. For the information of HMI software operation, software installation and hardware wiring, please
refer to the HMI software manual.
If you have any questions during operation, please contact our local distributors or Delta sales representative.
The content of this quick start may be revised without prior notice. Please consult our distributors or download the most updated version at http://www.delta.com.tw/industrialautomation
.
Safety Precautions
Carefully note and observe the following safety precautions when receiving, inspecting, installing, operating, maintaining and troubleshooting. The following words, DANGER, WARNING and STOP are used to mark safety precautions when using the Delta’s HMI product. Failure to observe these precautions may void the warranty!
Installation
¾ Comply with quick start for installation. Otherwise it may cause equipment damage. ¾ Do not install the product in a location that is outside the stated specification for the HMI. Failure to
observe this caution may result in electric shock, fire, or personal injury.
Wiring
¾ Connect the ground terminals to a class-3 ground (Ground resistance should not exceed 100).
Improper grounding may result in communication error, electric shock or fire.
Operation
¾ The users should use Delta Screen Editor software to perform editing in Delta's HMI product. To
perform editing and confirming HMI programs without using Delta Screen Editor software in Delta's HMI product may result in abnormal operation.
¾ Do not modify wiring during operation. Otherwise it may result in electric shock or personal injury. ¾ Never use a hard or pointed object to hit or strike the screen as doing this may damage the screen
and let the screen has not respond at all, and then cause HMI to work abnormally..
English-2
Maintenance and Inspection
¾ Do not touch any internal or exposed parts of the HMI as electrical shock may result. ¾ Do not remove operation panel while power is on. Otherwise electrical shock may result. ¾ Wait at least 10 minutes after power has been removed before touching any HMI terminals or
performing any wiring and/or inspection as an electrical charge may still remain in the HMI with hazardous voltages even after power has been removed.
¾ Turn the power off before changing backup battery and check system settings after finishing change.
(all data will be cleared after changing battery).
¾ Be sure the ventilation holes are not obstructed during operation. Otherwise malfunction may result
due to bad ventilation or overheating troubles.
Wiring Method
¾ Remove the terminal block from the HMI before wiring. ¾ Insert only one wire into one terminal on the terminal block. ¾ If the wiring is in error, perform the wiring again with proper tools. Never use force to remove the
terminals or wires. Otherwise, it may result in malfunction or damage.
¾ For the power line that forced to take out, ensure to check wiring again and restart.
Communication Wiring
¾ Comply with communication wiring specification for wiring. ¾ Wiring length should comply with the stated specification for the HMI. ¾ Proper grounding to avoid bad communication quality.
Installation and Storage Conditions
The product should be kept in the shipping carton before installation. In order to retain the warranty coverage, the HMI should be stored properly when it is not to be used for an extended period of time. Some storage suggestions are:
Store in a clean and dry location free from direct sunlight. Store within an ambient temperature range of -20°C to +60°C (-4°F to 140°F).
Store within a relative humidity range of 10% to 90% and non-condensing. Do not store the HMI in a place subjected to corrosive gases and liquids. Correctly packaged and placed on a solid and durable surface. Do not mount the HMI adjacent to heat-radiating elements or in direct sunlight. Do not mount the HMI in a location subjected to corrosive gases, liquids, or airborne dust or metallic
particles.
Do not mount the HMI in a location where temperatures and humidity will exceed specification. Do not mount the HMI in a location where vibration and shock will exceed specification. Do not mount the HMI in a location where it will be subjected to high levels of electromagnetic
radiation.
Installation
Installation Note:
Improper installation will result in malfunction and greatly reduce the life of the HMI. Be sure to
follow the guidelines in this quick start when installing the HMI.
In order to ensure the HMI being well ventilated, make sure that the ventilation holes are not
obstructed and must provide sufficient free space around HMI.
For use on a flat surface of a Type 4X "Indoor Use Only" enclosure or equivalent.
English-3
Installation Method:
Step 1: Ensure to put waterproof gasket into HMI and then insert the HMI into the panel cutout.
Step 2: Ensure to insert fasteners into the HMI’s insertion slots and turn the screw till screws touch panel cutout.
Step 3: Turn the screw with less than torque 0.7N.M to avoid damage to plastic box.
Torque: 6.17lb-inch(0.7N-M)
Power Line Installation
Recommended wiring is in the table below:
Type Wire Gauge (AWG) Stripped length Torque
Solid 28~12 7~8 mm 4.5 lb-in
Stranded 28~12 7~8 mm 4.5 lb-in
Be sure to plug power line into HMI according to following arrow direction.
DOP-AS38BSTD(-W) DOP-A(E)57G(B)(C)STD(-W)
English-4
Basic Inspection
Item Content
General Inspection
Periodically inspect the screws of the connection between the HMI and device.
Tighten screws as necessary as they may loosen due to vibration and varying temperatures.
Ensure that oil, water, metallic particles or any foreign objects do not fall inside the
HMI, control panel or ventilation slots and holes. As these will cause damage.
Ensure the correct installation and the control panel. It should be free from
airborne dust, harmful gases or liquids.
Inspection before
operation (power is
not applied)
Ensure that all wiring terminals are correctly insulated. Ensure that all wiring is correct or damage and or malfunction may result. Visually check to ensure that there are not any unused screws, metal strips, any
conductive or inflammable materials inside HMI.
Ensure to lower electromagnetic interference when devices are influenced by it. Ensure that the external applied voltage to HMI is correct and matched to the
controller.
Inspection before
operation (power is
applied)
Check if power LED lights. Check if the communication among devices is normal. Please contact your local Delta sales representative if there are any abnormal
conditions.
Pin Definition of Serial Communication
COM1 Port [A, AE and AS57BSTD Series]
Contact
COM Port PIN
RS-232 1 2 RXD 3 TXD 4 5 GND 6 7 RTS 8 CTS 9
Note: Blank = No Connection.
DOP-A80THTD1 DOP-AE80THTD DOP-AE94BSTD DOP-A(E)10THTD1
DOP-AS57BSTD
Pin
English-5
COM2 Port [A Series]
MODE1 MODE2 MODE3
COM Port PIN
RS-232 RS-422 RS-485 1 RXD- D­2 RXD RXD+ D+ 3 TXD TXD+ D+ 4 TXD- D­5 GND 6 RTS- 7 RTS RTS+ 8 CTS CTS+ 9 CTS-
Note 1: Blank = No Connection. Note 2: When selecting Mode3 (for RS-485), D+ indicates that PIN 2 and PIN 3 is connected, and D-
indicates that PIN 1 and PIN 4 is connected.
COM2 and COM3 Port [AE, A80THTD1 and A10THTD1 Series]
MODE1 MODE2 MODE3 MODE4 MODE5 MODE6
COM Port PIN
RS-232 RS-422 RS-485 RS-232*2 RS-422*2 RS-485*2 1 RXD- D- RXD1- D1­2 RXD RXD+ D+ RXD1 RXD1+ D1+ 3 TXD TXD+ D+ TXD1 TXD1+ D1+
COM2
4 TXD- D- TXD1- D1-
5 GND
6 RTS- TXD2- D2­7 RTS RTS+ TXD2 TXD2+ D2+ 8 CTS CTS+ RXD2 RXD2+ D2+
COM3
9 CTS- RXD2- D2-
Note 1: Blank = No Connection. Note 2: When selecting Mode3 (for RS-485), D+ indicates that PIN 2 and PIN 3 is connected, and D-
indicates that PIN 1 and PIN 4 is connected. When selecting Mode6 (for RS-485), D1+ indicates that PIN 2 and PIN 3 is connected, D1- indicates that PIN 1 and PIN 4 is connected, D2+ indicates that PIN 7 and PIN 8 is connected, and D2- indicates that PIN 6 and PIN 9 is connected.
COM1 and COM3 [AS38BSTD Series]
MODE1 MODE2
COM Port PIN
RS-232 RS-232*2 1 2 RXD RXD1 3 TXD TXD1
COM1
4
5 GND
6 7 RTS TXD2 8 CTS RXD2
COM3
9
Note: Blank = No Connection.
Pin
Pin
Pin
English-6
COM2 Port [AS38BSTD Series]
MODE1 MODE2
COM Port PIN
RS-422 RS-485
R- RXD- D-
R+ RXD+ D+
T- TXD- D-
T+ TXD+ D+
G GND
Note 1: When selecting Mode2 (for RS-485), D+ indicates that R+ and T+ is connected, and D-
indicates that R- and T- is connected.
COM2 and COM3 Port [AS57BSTD Series]
MODE1 MODE2
COM Port PIN
RS-422 RS-485
R- RXD- D-
R+ RXD+ D+
T- TXD-
T+ TXD+
G
GND
(for COM2 and COM3 both)
Note: Blank = No Connection.
Dimensions
DOP-AS38BSTD(-W)
118.8
+0.04+1
(4.68 )
140.8
104.8
0
0
(3.65 )
T=1.6mm(0.06in) ~
92.8
0
+1
3.0mm(0.12in)
NOTE:
0
+0.04
T
4-R3
36.7
R-
COM3
COM2
Units:mm
English-7
DOP-AS57BSTD
0.12in(3.0mm)
T=0.06in(1.6mm) ~
(5.21 )
+1
0
+0.04
0
(6.79 )
0
+1 +0.04
0
144.1(5.67)
184.1(7.25)
6.1(0.24)39.0(1.54)
172.4
132.4
4-R3(0.12)
T
NOTE:
DOP-A(E)57G(B)(C)STD(-W)
3.0mm(0.12in)
T=1.6mm(0.06in) ~
(5.21 )
+1
0
+0.04
0
(6.79 )
0
+1 +0.04
0
144.1(5.67)
184.1(7.25)
6.1(0.24)39.0(1.54)
172.4
132.4
4-R3(0.12)
T
NOTE:
DOP-A80THTD1 / DOP-AE80THTD
T=1.6mm(0.06in) ~
3.0mm(0.12in)
(1.75)
178.1(7.01)
243.1(9.57)
0
+1
231.4
0
(9.11 )
+0.04
+0.04
(6.55 )
0
+1
166.4
0
NOTE:
4
-
R
3
.
0
(
0
.
1
2
)
44.4
T
6.1(0.24)
Units:mm
Units:mm
Units:mm
English-8
DOP-AE94BSTD
(8.27 )
210.2
0
+1
+0.04
0
285.2
0
+1
(11.22 )
+0.04
0
4
-
R
3
.
0
NOTE:
T=1.6mm(0.06in) ~
3.0mm(0.12in)
T
DOP-A(E)10THTD1
3.0mm(0.12in)
+0.04
(11.22 )
+1
0
0
T=1.6mm(0.06in) ~
(8.27 )
+1
0
+0.04
0
210.2
285.2
4
-
R
3
.
0
(
0
.
1
2
)
NOTE:
T
297.1(11.70)
222.1(8.74)
43.1(1.70) 6.1(0.24)
Units:mm
Units:mm
English-9
Specifications
MODEL AS38BSTD(-W) AS57BSTD A(E)57BSTD(-W) A(E)57GSTD(-W)
Display Type
3.8” STN LCD
(8 shades of blue)
5.7” STN LCD
(8 shades of blue)
5.7” STN LCD
(8 shades of blue)
5.7” FSTN LCD
(16 shades of gray)
Resolution 320 x 240 pixels
Back Light
LED Back Light
(about 10 thousand
hours at 25oC)
CCFL Back Light (about 50 thousand hours at 25oC)
LCD MODULE
Display Size
3.8”
(76.8 x 57.6mm)
5.7” (115.17 x 86.37mm)
Operation System
Windows Base Real Time OS
MCU
32-bit RISC Micro-controller
NOR Flash ROM
NOR Flash ROM 2 Mbytes
(System: 1MB / User: 1MB
NOR Flash ROM 4 Mbytes
(System: 1MB / User: 3MB)
SDRAM
4 Mbytes 16Mbytes
Backup Memory
(Bytes)
128K
A: 256K
AE: 512K
SM Card
3 3
EXT.
Memory
USB Host
(Ver 1.1)
3 3
Extension Interface
3 (AE) 3 (AE)
USB for Download
[USB Client]
1 USB Client Ver 1.1
USB for Data
Storage / Printer
[USB Host]
3 3
COM1
RS-232
COM2
RS-422 / RS-485 RS-232 / RS-422 / RS-485
Serial
COM
Port
COM3
RS-232 RS-422 / RS-485 RS-232 / RS-422 / RS-485 (AE)
Function Key User defined key x 4 + System key x 1
Operation Voltage
DC +24V (-10% ~ +15%) (Please use isolated power supply)
(Note 2)
Backup Battery
3V lithium battery CR2032 x 1 / battery life: 5 years
Buzzer 85dB
Perpetual Calendar
(RTC)
Built-in
Cooling Method Natural air circulation
Safety Approval
(Waterproof for
front panel)
IP65 / NEMA4 / CE, UL
(Note 1)
Operation Temp.
0°C ~ 50°C
Storage Temp.
-20°C ~ +60°C
English-10
MODEL AS38BSTD(-W) AS57BSTD A(E)57BSTD(-W) A(E)57GSTD(-W)
Ambient Humidity
10% ~ 90% RH [0 ~ 40°C], 10% ~ 55% RH [41 ~ 50°C]
Pollution Degree 2
Vibration
Resistance
IEC 61131-2 Compliant
5Hz≦f<9Hz = Continuous: 1.75mm / Occasional: 3.5mm
9Hz≦f≦150Hz = Continuous: 0.5g / Occasional: 1.0g
X, Y, Z directions for 10 times
Dimensions
(W) x (H) x (D) mm
140.8 x 104.8 x
44.8
184.1 x 144.1 x 47
Panel Cutout (W) x (H) mm
118.8 x 92.8 172.4 x 132.4
Weight Approx. 310g Approx. 760g
NOTE
1) DOP-AE94BSTD this model is not UL recognized.
2) Users please use isolated power supply except DOP-A80THTD1, DOP-AE80THTD, DOP-AE94BSTD, and
DOP-A(E)10THTD1 these models.
3) Users can download the Screen Editor, the program editor of Delta HMI product and the user manual via the
following link: http://www.delta.com.tw/industrialautomation/.
4) The content of this quick start may be revised without prior notice. Please consult our distributors or download the
most updated version at http://www.delta.com.tw/industrialautomation/.
English-11
MODEL A(E)57CSTD(-W)
A80THTD1 AE80THTD
AE94BSTD A(E)10THTD1
Display Type
5.7” STN LCD (256 colors)
8” TFT LCD
(65536 colors)
9.4” STN LCD
(8 shades of blue)
10.4” TFT LCD (65536 colors)
Resolution 320 x 240 pixels 640 x 480 pixels
Back Light
CCFL Back Light
(about 50 thousand
hours at 25oC)
CCFL Back Light
(about 50 thousand
hours at 25oC)
CCFL Back Light
(about 30 thousand
hours at 25oC
CCFL Back Light
(about 30 thousand
hours at 25oC
LCD MODULE
Display Size
5.7” (115.17 x
86.37mm)
8” (162.2 x
121.7mm)
9.4” (192.0 x
144.0mm)
10.4” (211.2 x
158.4mm)
Operation System
Windows Base Real Time OS
MCU
32-bit RISC Micro-controller
NOR Flash ROM
NOR Flash ROM 4
Mbytes (System:
1MB / User: 3MB)
NOR Flash ROM 8 Mbytes (System: 1MB / User: 7MB)
SDRAM
16 Mbytes 32 Mbytes 16Mbytes 32 Mbytes
Backup Memory
(Bytes)
A: 256K
AE: 512K
512K 512K 512K
SM Card
3
3 (AE)
EXT.
Memory
USB Host
(Ver 1.1)
3 3 3
Extension Interface
3 (AE)
3 (AE)
3
3 (AE)
USB for Download
[USB Client]
1 USB Client Ver 1.1
USB for Data
Storage / Printer
[USB Host]
3 3 3
COM1
RS-232
COM2
RS-232 / RS-422 / RS-485
Serial
COM
Port
COM3
RS-232 / RS-422 /
RS-485 (AE)
RS-232 / RS-422 / RS-485
Function Key
User defined key x
4 + System key x 1
User defined key x 6 + System key x 1
User defined key x
11 + System key x
1
User defined key x
7 + System key x 1
Operation Voltage
DC +24V (-10% ~ +15%) (Please use isolated power supply)
(Note 2)
Backup Battery
3V lithium battery CR2032 x 1 / battery life: 5 years
Buzzer 85dB
Perpetual Calendar
(RTC)
Built-in
Cooling Method Natural air circulation
Safety Approval
(Waterproof for
front panel)
IP65 / NEMA4 / CE, UL
(Note 1)
Operation Temp.
0°C ~ 50°C
Loading...