Delta Electronics 3KVA, 700VA User Manual

SHEET 1 TO 2
DELTA DOC CENTER
SHEET 2 TO 3
1. IMPORTANT SAFETY INSTRUCTIONS
1-1 UL safety instructions
SAVE THESE INSTRUCTIONS - This manual contains important instructions for our UPS that should be followed during installation a nd maintenance of the UPS and batteries.
-
To reduce the risk of electric shock, install this UPS in a temperature and humidity controlled indoor area free of conductive contaminants. Ambient temperature must not exceed 40°C (104°F).
-
The AC output of the UPS need a disconnect switch such as a breaker which has to be provided by others.
-
The over-current protection for the output AC circuit has to be provided by others. All of our UPS has an e lectronic protection of AC output short circuit.
[1KVA MODEL]Federal Communications Commission Interference State ment This equipment has been tested and f ound to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equip ment gene r ate s, us es a nd ca n ra dia te ra di o fre qu enc y e nergy a nd, if no t i nstal le d an d used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of the following measures:
-
Reorient or relocate the receiving antenna
-
Increase the separation between the equipment and receiver.
-
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
-
Consult the dealer or an experienced radio/TV technician for help.
FCC Caution: To assure continued compliance, (example-use only shielded interface cables when connecting to computer or peripheral devices ). Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment. This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1)this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
DELTA PRODUCTS CORPORATIION CALIFORNIA (DPC) 4405 CUSHING PARKWAY FREMONT, CA94538, U.S.A. TEL: 1-510-668-5100
1
DELTA DOC CENTER
SHEET 3 TO 4
Other safety notes:
-
Examin e the pac king c ontaine r for d amage. Notify t he carr ier imm edia tely if da mage is present.
-
Do not disassemble the UPS.
-
Plug the UPS into a grounded 3-wire AC receptacle only.
-
Do not use extension cords.
-
Do not operate in area near water or excessive humidity.
-
Keep liquid and foreign objects from getting inside the UPS.
-
Install UPS in a well-ventilated area. Do not block air vents in front of UPS or air exhausts in the back.
-
Do not operate close to gas or electric half bridge rectified load, into the UPS receptacles.
-
Do not plug appliances, such as half bridge rectified load, into the UPS receptacles.
-
Do not operate if the uni t i s leaking liquid or if a white powdery residue is present.
-
Batteries may contain metals and other chemical hazardous waste. For proper disposal, consult your local state and federal EPA and other environmental laws and regulations.
-
Use only the power supply cord provided with this unit. The power cord for UPS is wired in accordance with National Elec trical Code (NEC) specifications. Be sure that the wall outlet is wired to these specif ic ations into the wall outlet.
-
The UPS contains its own e nergy source (battery). The output recept acles may be live even when the UPS is not connecte d to an AC supply.
-
Once you have connected the batte ry connectors, do not attempt to lift the cabinets.
-
Do not connect or disconnect the battery cabinets while the UPS is operating from battery.
[2,3KVA MODELS] Federal Communications Commiss ion Interf ere nce Statement This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment gene rates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. FCC Caution: To assure continued compliance, (example-use only shielded interface cables when connecting to computer or peripheral devices ). Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment.
2
DELTA DOC CENTER
SHEET 4 TO 5
1-2 TUV safety instructions
Please observe the following precautions to ensure personnel safety and reliable equipment operation:
-
The sound pressure level at the operators position according to IEC 704-1:1982 is equal or less than 70dB(A).
-
Der arbeitsplatzbezogene Schalldruckpegel dieses Gerätes nach DIN 45635 beträgt 70dB (A) oder weniger.
For installation:
-
The unit should be installed from service personnel.
-
Dieses Gerät ist durch Elektrofachkräfte zu installieren.
-
To prevent an overbalance of this equipment, the stabilizer must be mounted at the bottom of the enclosure.
-
Upon installation, it should be e nsured that the sum of the leakage current of the UPS and the connected consumer does not exceed 3.5mA.
-
Bei der Installation dieses Gerätes ist da ra uf zu acht en, daβ die Ableitströme der USV und der angeschlossenen Verbraucher den Maximalwert von 3.5 mA nicht
ü
berschreiten.
-
The socket-outlet shall be near the equipme nt and easily access ibl e.
-
Die Gerätesteckdose muβ nahe dem Gerät angebracht und leicht zugänglich sein.
Other safety instructions:
-
The UPS contains voltages which are potentially hazardous. All repairs should be performed by qualified service personnel. The UPS has its own internal energy source (Battery). The output receptacles may be alive even when the UPS is not connected to the mains.
-
Die USV enthält Spannungen die möglicherweise gefährlich sind. Alle Reparaturen sollten nur von ausgebildeten Monteuren durchgeführt werden. Die USV hat eine interne Stromversorgung (Batterien). Die Ausgangsanschlüsse können daher unter Strom stehen auch wenn die USV nicht an das Versorgungsnetz angeschlossen ist.
-
When replacing batteries, always use the same type and quantity as the previous one. Batteries of GP1270-F2(CSB), NP7-12(YUASA) , 1234W(CSB).
-
Falls Sie die Batterien austauschen, verwenden Sie bitte ausschlieβlich die gleiche Anzahl und die folgenden Batterietypen: GP1270-F2(CSB), NP7-12(YUASA), 1234W(CSB).
-
Do not dispose the battery or batteries in fire as this may explode.
-
Werfen Sie niem als die Batterien in das Feuer, die Batterien könnten explodieren.
-
Do not open or mutilate the battery or batteries as released electrolyte is toxic and harmful to skin and eyes.
Ö
-
ffnen oder beschädigen Sie nicht die Batte rien, ausflieβendes Elektrolyt ist schädlich
für Haut und Augen.
3
DELTA DOC CENTER
SHEET 5 TO 6
-
A battery can present a risk of electric shock and high short circuit current. The following precaution should be observed when working on batteries.
-
Eine Batterie kann eine Gefahr eines elektrischen Schlages und sehr groβer Kurzsc hlu ströme beinhalten. Folgende Vorkehrungen s ollten getroffen werden, wenn Sie mit der Batterie arbeiten.
-
The equipment is to be operated by fully trained personnels.
-
Diese Gerät ist nur durch unterwiesenes Personal zu bediene n.
-
EC conformity declaration
-
These devices comply with the regulations of the following guide-lines:
-
73/23/EEC guide-line of the Council for approximation of the legal regulations of the EC countries concerning the electrical apparatus within certain voltage tolerances, modified by the guide-line RL 93/68/EEC of the Council.
Remove watches, rings or other metal objects . Use tools with insulated handles.
Entfernen Sie Uhren, Ri nge und andere metallische Obj e kte.
Verwenden Sie Werkzeug mit isollierten Griffen.
β
-
89/336/EEC guide-line of the Council for approximation of the legal regulations of the EC countries concerning the electromagnetic compatibility, modified by the
guide-lines RL 91/236/EEC,.... ..... and 93/68/E EC of the Council.
-
The compliance with the following standards proves the conformity:
-
EN 50091-1-1
-
EN 55022/EN 55011, class B.
4
DELTA DOC CENTER
SHEET 6 TO 7
2 INTRODUCTION
2-1 Theory of operation
The main topology of the UPS consists of bypass path, AC-DC converter, DC-AC inverter, battery charger, DC-DC converter, control circuit and detection circuit. Moreover, the intelligent power managem ent software is also optional. The function and efficiency are superior to the traditional UPS.
Description of block diagram
BYPASS
PFC Control
Circuit
LED Board
To Control Board
To Auxiliary Power
Control Board
Breaker
AC
I/P
EMI
Filter
Relay
AC-DC Double
Booster
Battery Bank
Charger DC-DC Converter
To Control Board
To Control Board
To External Battery Bank
Auxiliary
Power
Half-bridge DC-AC Inverter
BYPASS
RELAY
O/P
AC
Fig. 2.1 is the ha rdware block diagram of the UPS.
The UPS operation is desc ribed as below: When the utility power is applied into the UPS, it was di vided into two ways a fter going through the breaker and EMI filter. One way is connected to AC-DC converter which converts the utility AC power into a DC voltage which is called DC-BUS voltage then divide into two path. One path goes to charger which converts the DC-BUS voltage into a proper DC voltage to c harge the UPS battery. The other path goes into DC-AC half bridge inverter. The other way works as a bypass path. The bypass relay near the output will choose either the bypass path or inverter output. In general, the UPS will internally do the self-diagnosis. If there is no problem, the bypass relay will choose the inverter output. This is so called “
ON-LINE mode”.
5
DELTA DOC CENTER
In case the utility power fail, the AC-DC converter and charger will be off duty. The
SHEET 7 TO 8
DC-DC converter works and converts the battery voltage into DC-BUS voltage. The DC-AC inverter converts the DC-BUS voltage into AC voltage. This is so called “
ON-BATTERY mode”.
The auxiliary power circuit suppl ies the designated power to al l the control circuits. Because the DC-AC inverter is always working, the DC-DC convert er can work rapidly
and replace the AC-DC converter while the utility power fails. Furthermore, the bypass relay continuously keeps in the posi tion of inverter output to supply the regulated power for the load. There i s no power failure to loading e quipment.
2-2 Feature
The UPS, available in 700VA, 1KVA, 2KVA and 3KVA, is an advanced on-line UPS providing reliable and consistent sine-wave quality power to vital equipment. It supports personal computers, networks, servers, telecommunication equipment and a variety of other facilities. With its out standing protection features, the unit keeps your applications safe and running smoothl y a t all times.
High power density
Other than traditional UPS adopting 0.7 output power factor, the UPS uses the latest technology and highest quality components giving output power factor up to 0.8. Compared to other UPS (1000VA/700W), these UPS series boosts a 12% more output power. This UPS with its compact size, generates higher power density thus giving convenience to the users. Moreover, through the use of advanced technology, the UPS efficiency increases to more than 87%. Compared with other traditional UPS wit h only 80 to 85% efficiency, this UPS produces greater electric power efficiency at less electric costs.
PFC (Power Factor Correction)
With this function, the investment in the capacity of circuit breakers can be reduced, specially it will be highly regarded as an important feature in critical load applications.
Complete Protection
On-line double conversion design, pure sinewave output and zero transfer ti me provide best protection. With a built-in s urge, spike and line noise protection, the UPS prevents destructive hardware damage and extends system life. The EMI/RFI filtering design prevents electrical noise from affecting computer operation and data files. Besides, the UPS provides built-in Fax/Network cable (RJ11/RJ45) jacks protecting your hardware from surge, spikes and line-noise which travel along communication lines, therefore providing you a complete “back door” prote c tion.
6
DELTA DOC CENTER
SHEET 8 TO 9
Intelligent design
Integrated with a microprocessor, the UPS is able to perform intelligent functions. The UPS triggers over-voltage protection function and transfers to “ when utility voltage exceeds 300V for 200V-series. In addition, the UPS can accept large voltage variation of 65V to 138V for 100V-series or 130V to 275V for 200V-series. Wide input volta ge range means less battery power usage frequency and longer battery life-span. Besides, programmable outlet design, suitable for power ma nagement, is als o included in this unit.
Considerate design
Battery start function allows startup of the UPS even when there is no AC line available. In addition, the UPS which was shut down by remote cont rol during power line blackout will restart automatically when AC power recovers. Using our automatic frequency sensing function to match input and out put frequency, users don't need to set either 50Hz or 60Hz. Other features, such as UPS self-diagnosis and flexible external battery pack, are also included.
Green function design
The UPS comes with an intelligent fan design, which can have variable fan speed depending on load status, thereby saving the use of power and reducing audible noise. Besides, the operation in sleeping mode is designed to just keep charging which saves the energy a lot.
On- Battery mode
” even
User friendly interface
The UPS provides a variety of functions which meet users’ needs. Users can instantly understand the status of the UPS via the informative LED display. Audible alarms, bar meters and status indicators, such as battery replace indication, UPS fault, line condition, overload etc. are simple and easy for user to understand. Moreover, users can simply reset the circuit breaker instead of having to replace a fuse in the e vent of output overload.
Safety approvals
The UPS has passed va rious safety regulations. UL/cUL, TUV/EMC, TUV/GS, CE mark and other safety approvals, proves that the UPS is a safe reliable solution to your power problems.
Network Management
Build-in communication interface port supporting enhances the reliability and manageability of the UPS over all major operating systems, including Windows 95/98, Windows NT, Netware, Unix, and others. Besides, the UPS also supports the Simple Network Management Protocol and Hyper Text Transfer
rotoc ol via p l uggi ng a
P
SNMP/HTTP
adapter into the build-in
RS232
and
SNMP
Dry contact
slot.
protocols
7
DELTA DOC CENTER
SHEET 9 TO 10
2-3 Annotation and symbol
The two signs shown on the manual indicating important instruction need to be followed.
Read before Operation Maybe Dangerous/Follow Instructions
PROTECTIVE GROUNDING TERMINAL: A terminal which must be connected to earth ground prior to making any other connection to the equipment.
This symbol indicates the word “phase” .
This symbol indicates t he principal on/off switch is in the “ON” position.
This symbol indicates the principal on/off switch is in the “STANDBY” position.
2-4 FRONT PANEL
!
Operation panel
Fig 2-1.1 Front Panel for 700VA or 1KVA
8
DELTA DOC CENTER
Operation Panel
SHEET 10 TO 11
Fig 2-1.2 Front Panel for 2KVA or 3KVA
2-5 OPERATI O N PANEL
B. 6 B. 7
B. 11
A. 1 A. 2
B. 10
B. 1 B. 2
Fig 2-2 Operation Panel
OPERATION PANEL
A. Button:
1.
1/TEST:
function in “ for silence.
2. 0: The button is used for turning off UPS. B. LED display:
The button is used for turning on the UPS, it also can perform the test
ON-LINE mode
”. In backup mode, this button can turn off the buzzer
B. 5
B. 8
B. 9 B. 3
B. 4
1.
Bypass:
The LED indicates UPS in “
BYPASS mode
9
”.