Delta airconditioners 21UT024C24, 21UT036C24, 21UT048C24, 21UT060C24 Instruction Manual

Vogue Ultra Universal 21UT Series
INSTRUCTION MANUAL
WARNING!
Read and follow all safety precautions in Instruction Manual - improper use can cause serious injury.
www.delta-dct.com
CONTENTS
1 Safety Precautions ......................................................................................... 1
2 Outline of the Unit and Main Parts................................................................... 2
3 Preparative for Installation ............................................................................... 3
3.1 Standard Accessory Parts .......................................................................... 3
3.2 Selection of the Installation Location .......................................................... 3
3.3 Connection Pipe Requirement ................................................................... 5
3.4 Electrical Requirement ............................................................................... 5
4 Installation of the Unit ...................................................................................... 7
4.1 Installation of the Indoor Unit ...................................................................... 7
4.2 Installation of the Outdoor Unit ................................................................... 9
4.3 Matters need Attention ............................................................................. 10
4.4 Installation of the Connection Pipe ........................................................... 10
4.5 Vacuum and Gas Leakage Inspection ...................................................... 14
4.6 Installation of the Drain Pipe .................................................................... 16
4.7 Electrical Wiring ........................................................................................ 18
5 Installation of Controllers ............................................................................... 22
5.1 Installation of Controllers Mainbord Code Setting: .................................. 22
6 Test Running ..................................................................................................23
6.1 Trial Operation and Testing ......................................................................23
6.2 Working Temperature Range .................................................................... 25
7 Troubleshooting and Maintenance ................................................................ 26
7.1 Troubleshooting ........................................................................................ 26
7.2 Routine Maintenance ............................................................................... 27
Floor Ceiling Air-Conditioning Unit
1
1 Safety Precautions
WARNING!
This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of the user.
CAUTION!
This mark indicates procedures which, if improperly performed, might possibly result in personal harm to the user, or damage to property.
WARNING!
① .
For operating the air conditioner pleasantly, install it as outlined in this installation manual.
② .
Connect the indoor unit and outdoor unit with the room air conditioner piping and
cord available from our standard parts. This installation manual describes the correct
connections using the installation set available from our standard parts.
③ .
Installation work must be performed in accordance with national wiring standards by
authorized personnel only.
④ .
If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant
comes in contact with a ame, it produces toxic gas.
⑤ .
Do not power on until all installation work is complete.
⑥ .
During installation, make sure that the refrigerant pipe is attached rmly before you run the
compressor.
Do not operate the compressor under the condition of refrigerant piping not attached properly with
2-way or 3-way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
⑦ .
During the pump-down operation, make sure that the compressor is turned off before you
remove the refrigerant piping.
Do not remove the connection pipe while the compressor is in operation with 2-way or 3-way valve open. This may cause abnormal pressure in the refrigerant cycle that leads to breakage and even injury.
⑧ .
When installing and relocating the air conditioner, do not mix gases other than the specied
refrigerant (R410A) to enter the refrigerant cycle.
If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to an
abnormally high value and cause breakage, injury, etc.
Floor Ceiling Air-Conditioning Unit
2
2 Outline of the Unit and Main Parts
Fig.1
Notes:
① .
The connection pipe and duct for this unit should be prepared by the user.
② .
This unit is standard equipped with the rectangular duct.
Floor Ceiling Air-Conditioning Unit
3
3 Preparative for Installation
3.1 Standard Accessory Parts
The standard accessory parts listed below are furnished and should be used as required.
Table 1
Indoor Unit Accessories
No. Name Appearance Q'ty Usage
1 Nut with Washer 8
To x the hook on the cabinet of the
unit.
2
Wireless
Controller+Battery
1+2 To control the indoor unit
3 Insulation 1 To insulate the gas pipe
4 Insulation 1 To insulate the liquid pipe
5
Installation
Paperboard
1 To insulate the drain pipe
6 Fastener 4 To fasten the sponge
7
Corrugated pipe
(48/60K)
1
Used to connect indoor and outdoor gas pipes
8 Damping Block 1
Used to cover the throttle to lower
the airow noise of refrigerant
3.2 Selection of the Installation Location
WARNING!
The unit must be installed where strong enough to withstand the weight of the unit and xed securely,
otherwise the unit would topple or fall off.
CAUTION!
① .
Do not install where there is a danger of combustible gas leakage.
② .
Do not install the unit near heat source, steam, or ammable gas.
③ .
Children under 10 years old must be supervised not to operate the unit.
Floor Ceiling Air-Conditioning Unit
4
Decide the installation location with the customer as follows:
3.2.1 Indoor Unit
(1) Install the unit at a place where is strong enough to withstand the weight of the unit. (2) The air inlet and outlet of the unit should never be clogged so that the airow can reach
every corner of the room.
(3) Leave service space around the unit as required in Fig.2.
Floor type
>600
>1000
>300
>600
>1500
Ceiling type
>300
>600
>600
>1500
>200>2300
Fig.2
(4) Install the unit where the drain pipe can be easily installed.
(5) The space from the unit to the ceiling should be kept as much as possible so as for more
convenient service.
3.2.2 Outdoor Unit
WARNING!
① .
Install the unit where it will not be tilted by more than 5°.
② .
During installation, if the outdoor unit has to be exposed to strong wind, it must be xed
securely.
(1) Outdoor Unit must be xed on stable and solid surface of oor.
(2) Don’t install Outdoor Unit under window or between buildings, and prevent the operation
noise from room.
(3) There should be no obstructions at both air inlet and outlet of indoor and outdoor units for
maintaining well air ventilation.
Floor Ceiling Air-Conditioning Unit
5
(4) When installing indoor unit, make sure that the hanging parts at top are strong enough to
stand the weight of unit.
>1000mm>1000mm
>1000mm >1000mm
Floor
Floor
>3000mm
>800mm
Fig.3
3.3 Connection Pipe Requirement
CAUTION!
The maximum length of the connection pipe is listed in the table below. Do not place the units between which the distance exceeds the maximum length of the connection pipe.
Table 2
Model
Connecting Pipe (inch)
Maximum
length
(m)
Maximum
height
(m)
Drainage pipe(Outer Diameter ×
wall thickness) (mm)
Liquid Gas
21UT024C24 3/8 5/8 15 15 17×1.75
21UT036C24 3/8 3/4 30 15 17×1.75
21UT048C24 3/8 7/8 30 15 17×1.75
21UT060C24 1/2 7/8 30 15 17×1.75
The connecting pipe should be thermally insulated properly.
The pipe wall thickness shall be 0.5-1.0 mm and the pipe wall shall be able to withstand
the pressure of 6.0 MPa. The longer the connecting pipe, the lower the cooling and heating
effect performs.
3.4 Electrical Requirement
Electric Wire Size and Fuse Capacity.
Table 3
Indoor Units
Power Supply Fuse Capacity Breaker Capacity Min. Power Supply Cord
V/Ph/Hz A A mm
2
220/230/1/60 1.46 15 1.3
220/230/1/60 1.46 15 1.3
220/230/1/60 3.60 15 1.3
220/230/1/60 3.60 15 1.3
21UT024C24
21UT036C24
21UT048C24
21UT060C24
Floor Ceiling Air-Conditioning Unit
6
Table 4
Outdoor Units
Power Supply Fuse Capacity
Breaker
Capacity
Min. Power
Supply Cord
V/Ph/Hz A A mm
2
31VA024C24 220/230/1/60 24.83 20 2.10
31VA036C24 220/230/1/60 41.93 40 5.30
31VA048C24 220/230/1/60 51.88 50 8.40
31VA060C24 220/230/1/60 65.83 60 8.40
“*” the fuse is located on the main board.
Notes:
① .
Install the disconnect device with a contact gap of at least 3 mm in all poles nearby the units
(Both indoor unit and outdoor unit).The appliance must be positioned so that the plug is
accessible.
② .
The specications of the breaker and power cable listed in the table above are determined
based on the maximum power (maximum amps) of the unit.
③ .
The specications of the power cable listed in the table above are applied to the conduit-
guarded multi-wire copper cable (like, YJV copper cable, consisting of PE insulated wires and
a PVC cable jacket) used at 40°С and resistible to 90°С(see IEC 60364-5-52). If the working condition changes, they should be modied according to the related national standard.
④ .
The specifications of the breaker listed in the table above are applied to the breaker with
the working temperature at 40°С. If the working condition changes, they should be modied
according to the related national standard.
Floor Ceiling Air-Conditioning Unit
7
4 Installation of the Unit
4.1 Installation of the Indoor Unit
4.1.1 Indoor Unit Dimension
WARNING !
① .
Install the indoor unit in a location which can withstand a load of at least five times the
weight of the main unit and which will not amplify sound or vibration.
② .
If the installation location is not strong enough, the indoor unit may fall and cause injuries.
③ .
If the job is done with the panel frame only, there is a risk that the unit will come loose.
Please be careful.
Fig.4
Table 5
Unit:mm
Model A B C D H
1220 225 1158 280 700
1220 225 1158 280 700
1420 245 1354 280 700
1420 245 1354 280 700
21UT024C24
21UT036C24
21UT048C24
21UT060C24
Floor Ceiling Air-Conditioning Unit
8
4.1.2 Indoor Unit Installation
(1) Determine the location of the hanger through the paper template, and then remove the
paper template.
Paper template

Anchor bolt
Fig.5
(2) Insert the anchor bolts into the drilled holes, and drive the pins completely into the anchor
bolts with a hammer.
(3) Remove the right and left side panels.
(4) Put the hanger bolt into the clasp of the indoor unit and tighten screws on the hanger to
prevent the indoor unit from moving.
(5) Reinstall and tighten the right and left side panels.
Floor type
Wall
Left side panel
Right side panel
Paper template
Fig.6
Floor Ceiling Air-Conditioning Unit
9
Ceiling type
40
Ceiling
Suspension bolt
Spring washer
Nut
Nut
Hanger
Right side
panel
Left side panel
Fig.7
(6) Adjust the height of the unit to make the drain pipe slant slightly downward so that the
drainage will become much smoother.
4.2 Installation of the Outdoor Unit
WARNING!
① .
Install the unit where it will not be tilted by more than 5°.
② .
During installation, if the outdoor unit has to be exposed to strong wind, it must be xed
securely.
Outdoor Unit Dimension:
A
B
C
Fig.8
Floor Ceiling Air-Conditioning Unit
10
Table 6
Unit: mm
Item
Model
A B C
610 546 546
735 610 610
735 710 710
735
710 710
4.3 Matters need Attention
(1) Before installation, make sure that the power supply comply with in nameplate and check
the security of the power supply.
(2) Do not use or place combustible and explosive gas or liquid near the air conditioner.
(3) Do not attempt to install Air Conditioner by yourself to guarantee the Air Conditioner can be
permanent use.
(4) In the event of malfunction(burning smell, etc.),stop operation immediately and turn off the
power switch.
(5) Do not insert ngers or objects into the outlet port or inlet grillers.
(6) Do not check or repair the Air Conditioner when it is running.
(7) Do not sprinkle water on the Air Conditioner or operate it with wet hands.
(8) Do not climb or place objects on the air conditioner.
4.4 Installation of the Connection Pipe
4.4.1 Gas pipe connection of 48/60k unit
(1) A 7/8” gas pipe is used for connection.
(2) Cut the connection pipe with the pipe cutter and remove the burrs.
(3) Take out the corrugated pipe subassembly from the attached bag. (4) Insert 7/8” gas pipe into the corrugated pipe and x them well by welding.
Note: Refer to the diagram shown in the attachment
4.4.2 Flare Processing
(1) Cut the connection pipe with the pipe cutter and remove the burrs.
(2) Hold the pipe downward to prevent cuttings from entering the pipe. (3) Remove the are nuts at the stop valve of the indoor unit, then insert them to the connection
pipe, after that, are the connection pipe with a aring tool.
(4) Check if the are part is spread evenly and there are no cracks, as shown in the Fig.9.
Fig.9
31VA024C24
31VA036C24
31VA048C24
31VA060C24
Floor Ceiling Air-Conditioning Unit
11
4.4.3 Bending Pipes
(1) The pipes are shaped by your hands. Be careful not to collapse them.
Fig.10
(2) Do not bend the pipes in an angle more than 90°. (3) When pipes are repeatedly bent or stretched, the material will harden, making it difcult to
bend or stretch them any more. Do not bend or stretch the
pipes more than three times.
(4) When bending the pipe, do not bend it as is. The pipe will
be collapsed. In this case, cut the heat insulating pipe
with a sharp cutter as shown in Fig.11, and bend it after
exposing the pipe. After bending the pipe as you want, be
sure to put the heat insulating pipe back on the pipe, and
secure it with tape.
Fig.11
Pipe
Cutter
Cutt line
Heat insulating
pipe
CAUTION!
① .
To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of curvature of 150 mm or over.
② .
If the pipe is bent repeatedly at the same place, it will break.
4.4.4 Connecting the Pipe at the Indoor Unit Side
Detach the caps and plugs from the pipes.
CAUTION!
① .
Be sure to apply the pipe against the port on the indoor unit correctly. If the centering is
improper, the are nut cannot be tightened smoothly. If the are nut is forced to turn, the
threads will be damaged.
② .
Do not remove the are nut until the connection pipe is to be connected so as to prevent
dust and impurities from coming into the pipe system.
Centering the pipe against port on the indoor unit, turn the are nut with your hand. When the are nut is tightened properly by your hand, use a torque wrench to nally tighten it.
Floor Ceiling Air-Conditioning Unit
12
Fig.12
Table.7 Flare nut tightening torque
Pipe Diameter
(inch)
Tightening Torque
(N·m)
3/8 35-40
1/2 45-50
5/8 60-65
3/4 70-75
7/8 85-90
Note: After all ,cover the throttle by a damping block from the attached bag to lower the airow
noise of refrigerant.
4.4.5 Connecting the Pipe at the Outdoor Unit Side (Fig.13)
(1) Refer to Table.8 for eld tubing diameters. The pipe must remain round. Do not crimp end of
the line.
Table.8 Refrigerant Line Set Inches (mm)
Model
Valve Field Connections
Liquid Line Gas Line
3/8 inch 5/8 inch
3/8 inch 3/4 inch
3/8 inch 7/8 inch
1/2 inch 7/8 inch
Line set size matches service valve connection
Do not crimp service valve connector whenpipe is smaller than connection
Fig.13
31VA024C24
31VA036C24
31VA048C24
31VA060C24
Floor Ceiling Air-Conditioning Unit
13
(2) Remove service cap and core from both the gas and liquid line service ports.
Service port core
Service port cap
Liquid line service valve
Gas line service valve
Service port core
Service port cap
Fig.14
(3) Flow regulated nitrogen (at 1 to 2 psig) through the low−side refrigeration gauge set into the
liquid line service port valve, and out of the gas line service port valve.
Liquid line
Use regulator to flow nitrogen at 1 to 2 psig
Liquid line service valve
Gas line service valve
Gas service port must be open
to allow exit point for nitrogen
Gas line
OUTDOOR UNIT
INDOOR UNIT
Fig.15
(4) To help protect service valve seals during brazing, wrap water saturated cloths around
service valve bodies and copper tube stubs. Water saturated cloths must remain water
saturated throughout the brazing and cool−down process.
Braze line to the service valve.
When brazing line set to service valves, point flame away from service valve.
Water saturated cloth
Fig.16
After all connections have been brazed, disconnect manifold gauge set from service ports.
Apply water saturated cloths to both services valves to cool piping. Once piping is cool, remove all
water saturated cloths. Reinstall service cap and core. Refer to the unit installation instructions for
the next step in preparing the unit.
Floor Ceiling Air-Conditioning Unit
14
4.4.6 Checking the Pipe Connections for Gas Leaking
For both indoor and outdoor unit side, check the joints for gas leaking by the use of a gas
leakage detector without fail when the pipes are connected.
4.4.7 Heat Insulation on the Pipe Joints (Indoor Side Only)
Stick coupler heat insulation (large and small) to the place where connecting pipes.
Fig.17
4.5 Vacuum and Gas Leakage Inspection
CAUTION!
Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation! There
is no extra refrigerant in the outdoor unit for air purging!
4.5.1 Vacuum
(1) Remove the caps of the liquid valve, gas valve and also the service port.
(2) Connect the hose at the low pressure side of the manifold valve assembly to the service
port of the unit’s gas valve, and meanwhile the gas and liquid valves should be kept closed
in case of refrigerant leak.
(3) Connect the hose used for evacuation to the vacuum pump.
(4) Open the switch at the lower pressure side of the manifold valve assembly and start the
vacuum pump. Meanwhile, the switch at the high pressure side of the manifold valve
assembly should be kept closed, otherwise evacuation would fail.
(5) The evacuation duration depends on the unit’ capacity, generally, 30 minutes for the 24/36K
units, 45 minutes for the 42/48/60 units. And verify if the pressure gauge at the low pressure
side of the manifold valve assembly reads -1.0Mp (-75cmHg), if not, it indicates there is leak
somewhere. Then, close the switch fully and then stop the vacuum pump.
(6) Wait for some time to see if the system pressure can remain unchanged, 5 minutes for the
24K units, 10 minutes for 48/60K units. During this time, the reading of the pressure gauge
at the low pressure side can not be larger than 0.005Mp (0.38cmHg).
(7) Slightly open the liquid valve and let some refrigerant go to the connection pipe to balance
the pressure inside and outside of the connection pipe, so that air will not come into the
Floor Ceiling Air-Conditioning Unit
15
connection pipe when removing the hose.
Note: that the gas and liquid valve can be opened fully only after the manifold valve assembly is
removed.
(8) Place back the caps of the liquid valve, gas valve and also the service port.
Hose with the valve pin
gauge manifold
pipe
pipe
Fig.18
Note: For the large-sized unit, it has the service port for both the gas valve and the liquid valve.
During evacuation, it is available to connect two hoses of the manifold valve assembly to two
service ports to quicken the evacuating speed.
Floor Ceiling Air-Conditioning Unit
16
4.5.2 Additional Charge
Refrigerant suitable for a piping length of 5m is charged in the outdoor unit at the factory.
When the piping is longer than 7 m, additional charging is necessary.
For the additional amount, see Table 9.
Table 9
Item
Model
Additional Refrigerant Amount for Extra Pipe Length
54 g/m
54 g/m
54 g/m
110 g/m
4.6 Installation of the Drain Pipe
4.6.1 Precautions When Doing the Piping Work
(1) Keep piping as short as possible and slope it downwards at a gradient of at least 1/100 so
that air may not remain trapped inside the pipe.
(2) Keep pipe size equal to or greater than that of the connecting pipe.
(3) Install the drain piping as shown and take measures against condensation. Improperly
rigged piping could lead to leaks and eventually wet furniture and belongings.
Extension drain piping
(commercially available)
Insulating tube (commercially available)
Indoor unit drain hose
Insulating tape (accessory)
Fig.19
(4) Connect the drain hose.(Fig.20)
Drain hose must slope downward.
Allow no trap to form in the piping
Do not allow end of hose to touch water
Fig.20
31VA024C24
31VA036C24
31VA048C24
31VA060C24
Floor Ceiling Air-Conditioning Unit
17
4.6.2 Installing the Drain Pipes
(1) For determining the position of the drain hose, perform the following procedures.
(2) Insert the drain pipe to the drain outlet of the unit and then tighten the clamp securely with
tape. (Fig.21)
(3) Connect the extension drain pipe to the drain pipe and then tighten the clamp with tape.
Drain pan
Seal
Drain hose
1 2
3
4mm
1
2
Fig.21
Fig.22
Fig.23
Tighten the clamp until the screw head is less than 4 mm from the hose.(Fig.22)
① -
Metal clamp
② -
Drain hose
③ -
Grey tape
Insulate the pipe clamp and the drain hose using heat insulation sponge.(Fig.23)
① -
Metal clamp
② -
Insulation sponge
(4) When drain hose requires extension, obtain an extension hose commercially available.
(5) After connecting the local drain hose, tape the slits of the heat insulation tube.
(6) Connect the drain hose to the local drain pipe. Position the inter connecting wire in the
same direction as the piping.
4.6.3 Connecting the Drain Hose
(1) Connect the extension auxiliary pipe to the local piping.
(2) Prepare the local piping at the connection point for the drain pipe, as shown in the
installation drawings.
Note: Be sure to place the drain hose as shown in the diagram below, in a downward sloping
direction.
Fig.24
Floor Ceiling Air-Conditioning Unit
18
4.6.4 Testing of Drain Piping
(1) After piping work is nished, check if drainage ows smoothly. (2) As shown in the gure, pour water into the drain pan from the right side to check that water
ows smoothly from the drain hose.

Ceiling type Floor type
Fig.25 Fig.26
4.7 Electrical Wiring
4.7.1
Wiring Precautions
WARNING !
① .
Before obtaining access to terminals, all supply circuits must be disconnected.
② .
The rated voltage of the unit is as shown as Table 4 and Table 5
③ .
Before turning on, verify that the voltage is within the 198~264V range(for single phrase
unit) .
④ .
Always use a special branch circuit and install a special receptacle to supply power to the
air conditioner.
⑤ .
Use a special branch circuit breaker and receptacle matched to the capacity of the air
conditioner.
⑥ .
The special branch circuit breaker is installed in the permanent wiring. Always use a circuit
that can trip all the poles of the wiring and has an isolation distance of at least 3 mm
between the contacts of each pole.
⑦ .
Perform wiring work in accordance with standards so that the air conditioner can be
operated safely and positively.
⑧ .
Install a leakage special branch circuit breaker in accordance with the related laws and
regulations and electric company standards.
CAUTION !
① .
The power source capacity must be the sum of the air conditioner current and the current
of other electrical appliances. When the current contracted capacity is insufcient, change
the contracted capacity.
② .
When the voltage is low and the air conditioner is difficult to start, contact the power
company to raise the voltage.
Floor Ceiling Air-Conditioning Unit
19
4.7.2 Electrical Wiring
(1) For solid core wiring (Fig.27)
1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation about 25
mm (15/16”) .
2) Using a screwdriver, remove the terminal screw(s) on the terminal board.
3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw.
4) Shape the loop wire properly, place it on the terminal board and tighten securely with the
terminal screw using a screwdriver.
(2) For strand wiring (Fig.27)
1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation about 10
mm (3/8”) .
2) Using a screwdriver, remove the terminal screw (s) on the terminal board.
3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped
wire end.
4) Position the round terminal wire, and replace and tighten the terminal screw with a
screwdriver. (Fig.28)
Fig.27
Fig.28 Fig.29
Floor Ceiling Air-Conditioning Unit
20
(3) How to x connection cord and power cord with cord clamp
After passing the connection cord and power cord through the insulation tube, fasten it with the
cord clamp.(Fig.29)
WARNING!
① .
Before starting work, check that power is not being supplied to the indoor unit and outdoor unit.
② .
Match the terminal block numbers and connection cord colors with those of the indoor unit side.
③ .
Erroneous wiring may cause burning of the electric parts.
④ .
Connect the connection cords rmly to the terminal block. Imperfect installation may cause a re.
⑤ .
Always fasten the outside covering of the connection cord with cord clamps. (If the insulator
is not clamped, electric leakage may occur.)
⑥ .
Always connect the ground wire.
(4) Electric wiring between the indoor and outdoor units
Model:31VA024C24+21UT024C24; 31VA036C24+ 21UT036C24;
Indoor Unit
POWER 220/230V 1PH
60HZ
POWER
220/230V
1PH
60HZ
Outdoor Unit
Fig.30
Model:31VA048C24+21UT048C24; 31VA060C24+ 21UT060C24;
POWER
220/230V
1PH 60HZ
POWER 220/230V 1PH
60HZ
Indoor Unit
Outdoor Unit
Fig.31
Floor Ceiling Air-Conditioning Unit
21
(5) Electric wiring of indoor unit side
Remove the left cover plate and the electric box cover then insert the end of the communication
cord and the power cable into the terminal board.
Fig.32
CAUTION!
① .
The power cord and the wire of the fresh air valve are high-voltage, while the
communication cord and connection wire of the wired controller are low-voltage. They
should run separately against electromagnetic interference.
② .
The high-voltage and low-voltage lines should pass through the rubber rings at different
electric box covers.
③ .
Do not bundle the connection wire of the wired controller and the communication cord
together, or arrange them in parallel, otherwise improper operation would occur.
④ .
The high-voltage and low-voltage lines should be fixed separately and securely, with
internal big clamps for the former and small clamps for the latter.
⑤ .
Tighten the indoor/outdoor connection cord and power cord respectively on the terminal
boards with screws. Faulty connection may cause a re.
⑥ .
If the indoor unit connection cord (to the outdoor unit) and power supply are wired
incorrectly, the air conditioner may be damaged.
⑦ .
Connect the indoor unit connection cord properly based on the corresponding marks as
shown in Fig.31.
⑧ .
Ground both the indoor and outdoor units by attaching a ground wire.
⑨ .
Unit shall be grounded in compliance with the applicable local and national codes.
⑩ .
The signal line of the wire controller must be separated from the power line.
Floor Ceiling Air-Conditioning Unit
22
5 Installation of Controllers
Refer to the Installation Manual of the controller for more details.
Functions for Remote Controller 29FRC-100A
Available Function
Run Mode
Temperature Setting
Fan Speed
"Up-down" Swing
Timer Sleep
"Left-right" Swing ×
Health/Energy-saving ×
Dry ×
Turbo ×
Switch among indoor/outdoor/setting Temp. ×
Lighting ×
Note:
"√" means the function is available for this series unit; "×" means the function is unavailable.
Please refer to the remote controller manual for specic function setting.
5.1 Installation of Controllers Mainbord Code Setting:
Please nd the corresponding mainboard according to the unit type and then check whether
the mainboard code is correctly set.
The relation between mainboard type and unit type:
Duct type indoor unit mainboard: Z4G25A
Code location and meaning:
Please nd the corresponding mainboard according to the complete unit type and then check
whether the mainboard code only. The third code remains in “3”. Please refer to the following gure
for detailed coding.
Fig.33
Floor Ceiling Air-Conditioning Unit
23
6 Test Running
6.1 Trial Operation and Testing
Turn on the crankcase heater 12 hours before the startup of the whole system.
Indoor Unit:
LED Board Display as shown in Fig.34 and Table.10.
Fig.34
Table.10
① .
Indication LED of “POWER”
The LED will go on when the unit is power on.
The LED will go off when the unit is power off.
② .
Indication LED of “COOL”
The LED is on under “COOL” mode operating.
The LED is off when “COOL” mode is not operating.
③ .
Indication LED of “HEAT”
The LED is on under “HEAT” mode operating.
The LED is off when “HEAT” mode is not operating.
④ .
Display of temperature or malfunction code.
When a malfunction happens except that the FAN mode continues at the mode of COOL,
DRY, HEAT, the outdoor unit and fan motor will stop, which will not affect the LCD display. When
the controller displays a malfunction, please turn off the unit and contact the service center. The
meaning of error codes as shown Table.11:
Table.11
Error code Error code description
E2 Indoor anti-freezing protection
E6 Communication malfunction E9 Water overow protection
F0 Indoor unit ambient sensor malfunction at air return opening
F1 Evaporator sensor malfunction
Outdoor Unit: When a malfunction happens during the operation, the state(Off, On, Flashing) of
two LEDs on the control board(D1[Red] and D2 [Red]) indicate diagnostics conditions that are
described in Table.12.
Floor Ceiling Air-Conditioning Unit
24
Table.12
D1 [Red] D2 [Red] Trouble Case Origin of Trouble Measure
OFF OFF Power problem
No power (24V) to demand control board terminals R
and C or demand
control board
failure.
1.Check control transformer power (24V).
2.If power is available to demand control board and LED(s) do not light, replace control board.
0.5s
Circulating
Flash
OFF
Actuation of high
pressure switch
High pressure
switch
Abnormality is detected when the contact of the high pressure switch opens for 3 sec. The system will be shut down. The
unit will report this fault. For the rst two
faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.
OFF
0.5s
Circulating
Flash
Actuation of low pressure switch
Low pressure
switch
When the unit runs more than 4 minutes or does not run, the low pressure switch opens for more than3sec and the system will be shut down..The unit will report
this fault. For the rst two faults within
30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.
0.5s
Circulating
Flash
Continuous
Light
Air discharge
high-temperature
protection of
compressor
Exhaust over-
temperature
Protection
The exhaust temperature is higher than
125°C for more than 5s, the system will be shut down. After stopping the
compressor for 3 mins, if the exhaust
temperature is lower than 90°C for more than 5s, the compressor will re-start.
For the rst two faults within 30 minutes,
the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.
Continuous
Light
OFF
Malfunction of
exhaust Temp.
Sensor
Exhaust
temperature
sensor
If the exhaust temperature sensor is
detected of open circuit 5 seconds successively after the compressor is started for 3 minutes or short circuit 5 seconds successively at any time The system will be shut down. After the fault is eliminated, the system can automatically resume to operation.
0.5s
Circulating
Flash
0.5s
Circulating
Flash
Normal operation
Unit operating
normally or in
standby mode.
None required
To stop test running, press the ON/OFF button.
For the operation method, refer to the operating manual and perform operation check.
Check that there are no abnormal sounds or vibration during the test running.
Floor Ceiling Air-Conditioning Unit
25
6.2 Working Temperature Range
Table.13
Test condition
Indoor side Outdoor side
DB(°С) WB(°С) DB(°С) WB(°С)
Nominal cooling 26.7 19.4 35 23.9
Rated cooling 26.7 19.4 46.1 23.9
Low temp cooling 19.4 13.9 19.4 13.9
Notes:
① .
The design of this unit conforms to the requirements of EN14511 standard.
② .
The air volume is measured at the relevant standard external static pressure.
③ .
Cooling (heating) capacity stated above is measured under nominal working conditions
corresponding to standard external static pressure. The parameters are subject to change
with the improvement of products, in which case the values on nameplate shall prevail.
④ .
In this table, there are two outside DB values under the low temp cooling conditions, and the
one in the brackets is for the unit which can operate at extreme low temperature.
Floor Ceiling Air-Conditioning Unit
26
7 Troubleshooting and Maintenance
7.1 Troubleshooting
If your air-conditioning unit suffers from abnormal operation or failure, please rst check the
following points before repair:
Table 14
Failure Possible Reasons
The unit cannot be
started.
① .
The power supply is not connected.
② .
Electrical leakage of air-conditioning unit causes tripping of the leakage
switch.
③ .
The operating keys are locked.
④ .
The control loop has failure.
The unit operates for a
while
and then stops.
① .
There is obstacle in front of the condenser.
② .
The control loop is abnormal.
③ .
Cooling operation is selected when the outdoor ambient temperature is
above 48°C.
Poor cooling effect.
① .
The air lter is dirty or blocked.
② .
There is heat source or too many people inside the room.
③ .
The door or window is open.
④ .
There is obstacle at the air intake or outlet.
⑤ .
The set temperature is too high .
⑥ .
There is refrigerant leakage.
⑦ .
The performance of room temperature sensor becomes worse
Note: After carrying out the check of the above items and taking relevant measures to solve the
problems found but the air-conditioning unit still does not function well, please stop the operation
of the unit immediately and contact the local service agency designated by DELTA. Only ask
professional serviceman to check and repair the unit.
Floor Ceiling Air-Conditioning Unit
27
7.2 Routine Maintenance
WARNING !
① .
Do turn off the unit and cut off the main power supply when cleaning the air conditioner, otherwise electric shock may happen.
② .
Do not make the air conditioner wet or electric shock may be lead; Ensure that the air conditioner will not be cleaned by water rinsing under any circumstance.
③ .
Volatile liquid like thinner or gasoline would damage the appearance of air conditioner. (So,
only soft dry cloth and wet cloth moistened by neutral cleaning uid could be used to clean
the surface panel of air conditioner.)
(1) Cleaning the Indoor Unit
1) Remove the suction grille.
2) Slide both knobs simultaneously and then pull them downward slowly.
3) Remove the air lter from the unit (Fig.35)
4) Clean the air lter
5) Use a vacuum or water to clean the air filter when it is too dirty. If necessary, neutral
detergent can be used. After that, air dry it at a shady place.
6) Clean the suction grille by a soft brush with water and detergent, and then air dry it.
Fig.35 Fig.36
7) Reinstall the lter and suction grille as before.
(2) At the Start of the Seasonal Use
1) Check if there is blockage at the inlet or outlet vent of air conditioner.
2) Check if the earth wire has been attached reliably by the skilled serviceman.
3) Check if the exhausted batteries of the wireless controller have been replaced.
4) Check if the air lter had been installed well by professional.
Keep the power switch “On” 8 hours before the startup of the unit which has not been used for
a long period.
Note: all above should be operated by the skilled serviceman.
(3) At the End of the Seasonal Use
1) Cut off the power supply main switch
2) Clean the air lters and other parts by the skilled serviceman.
3) Leave the fan running for 2-3 hours to dry the inside of the unit.
Note: all above should be operated by the skilled serviceman.
Thank you for Choosing
airconditioners
Perfectly engineered for your comfort.
www.delta-dct.com
Loading...