This manual contains important instructions and warnings that you should
follow during the installation, operation, storage and maintenance of this
product. Failure to heed these instructions and warnings will void the warranty.
Before installation and usage, please read this User Manual thoroughly. This
helps you to use the product correctly and safely.
z
z
Install the UPS in a well-ventilated area, away from excess moisture, heat, dust,
ammable gas or explosives.
z
z
To avoid re accidents and electric shock, please install the UPS in a temperate
and humidity well-controlled indoor area free of conductive contaminants. For
the temperature and humidity specications, please refer to Appendix 1 : Tech-
nical Specications.
z
z
Leave adequate space (at least 50cm) around all sides of the UPS for proper
ventilation.
Connection Warnings
z
z
The UPS must be well grounded due to a possible risk of current leakage.
z
z
The installation of upstream and downstream protective devices is highly recommended when the UPS is connected to the mains and the loads.
z
z
The protective devices connecting to the UPS must be installed near the UPS
and must be easily accessible for operation.
z
z
If you need to move the UPS or perform re-wiring, please turn o the AC input
power and ensure that the UPS has been safely shutdown. Otherwise, the output end might still be energized, which might cause electric shock.
Usage Warnings
z
z
This is a class-A product. In a domestic environment, this product may cause radio interference, in which case, the user is required to take adequate measures.
z
z
The UPS can be used to power computers and associated peripheral devices,
such as monitors, modems, cartridge tape drives, external hard drives, etc.
1
z
z
It is strictly forbidden to connect the UPS with:
1. Any regenerative loads.
2. Any asymmetrical loads.
z
z
To ensure reliable operation of the UPS and to protect the UPS from overheating, the slits and openings in the UPS must not be blocked or covered.
z
z
Before usage, you must allow the UPS to adjust to room temperature for at least
one hour to avoid moisture condensing inside the UPS.
z
z
Do not pour and splash any liquid on the UPS. Do not insert any object into
the UPS’s slits and openings. Do not put beverage containers on or around the
UPS.
z
z
When an emergency occurs, (1) press and hold the ON/ OFF button ( ) for
3 seconds, (2) release it after you hear one beep, (3) use the Scrolling UP or
Down button (
/ ) to select
'Yes'
, and (4) press the Enter button ( ) to
conrm your selection to turn o the UPS. After that, cut o the input power to
completely shut down the UPS.
z
z
Do not use any cleaning liquid or cleaning spray to clean the UPS. Before cleaning, please make sure that the UPS has been completely shut down, the UPS’s
input power cord has been unplugged, and the batteries have been disconnected.
z
z
All maintenance services must be performed by qualied service personnel.
z
z
Forbid opening or removing the cover of the UPS yourself to avoid high voltage
electric shock.
z
z
You must contact qualied service personnel if either of the following events occurs:
1. Liquid is poured or splashed on the UPS.
2. The UPS does not run normally after this User Manual is carefully
observed.
NOTE :
If you use the UPS in an area that generates or incurs dust, you should
install a dust lter (optional) in the 5/ 6kVA UPS and two in the 8/ 10kVA
UPS to ensure normal product life and function.
Amplon RT Series
2
Chapter 1 Important Safety Instructions
100
%
100
%
Battery Warnings
z
z
Keep the batteries away from heat sources. Do not open or mutilate the batteries.
z
z
Do not dispose of batteries in a re. The batteries may explode.
z
z
The released electrolyte is harmful to the skin and eyes and may be toxic.
z
z
A battery can present a risk of electric shock and high short-circuit current.
z
z
Servicing of batteries and battery packs must be performed or supervised by
qualified service personnel knowledgeable in batteries, battery packs and the
required precautions. Keep unauthorized personnel away from batteries and
battery packs.
z
z
The risk of electric shock and short-circuit current is possible when the batteries
are connected to the UPS. Before maintenance, disconnect all batteries to cut
o the battery power.
z
z
For battery replacement, only use the same number and type of batteries.
z
z
Observe the following before replacing the batteries:
1. Remove watches, rings, or other metal objects.
2. Use tools with insulated handles.
3. Wear rubber gloves and boots.
4. Do not lay tools or metal parts on the top of batteries.
5. Disconnect charging source prior to connecting or disconnecting battery
terminals.
6. Remove battery grounds during installation and maintenance to reduce
likelihood of shock. Remove the connection from ground if any part of the
battery is determined to be grounded.
z
z
Do not connect the batteries in reverse; otherwise, a risk of electric shock or re
accidents might occur.
z
z
The batteries might lose their power during shipment or storage. Before you use
the UPS for the rst time, please fully charge the batteries until the battery ca-
)
(
pacity percentage shown on the UPS’s LCD is 100%
. If the UPS needs to
be stored for an extended period of time, please charge the batteries every three
months and ensure that, every time after charging, the battery capacity percent-
(
age shown on the UPS’s LCD is 100%
)
.
3
WARNING:
100
%
1. The risk of electric shock and short-circuit current is possible when
the batteries are still connected to the UPS even though the UPS
is disconnected from the mains. Do not forget to cut off the battery
source before maintenance.
2. When the UPS is connected to external battery packs, the installation
of appropriate protective devices, such as a DC fuse or a DC non-fuse
breaker, is required.
1.2 Standard Compliance
z
z
z
z
CE
UL, cUL
z
z
EN 62040-1
z
z
EN 62040-2 Category C2
1.3 Storage
z
z
Prior to installation
If the UPS needs to be stored prior to installation, it should be placed in a dry
and well-ventilated area. The allowable storage temperature is between -15°C
and +50°C (5°F~122°F).
z
z
After usage
(1) Press and hold the ON/ OFF button (
you hear one beep, (3) use the Scrolling UP or Down button (
select 'Yes', and (4) press the Enter button (
turn o the UPS. Make sure the UPS is shutdown, disconnect the UPS from the
utility AC power, remove all loads/ equipment from the UPS, and store the UPS
in a dry and well-ventilated area at a temperature between -15°C and +50°C
(5°F~122°F).
Idle batteries must be recharged fully approximately every three months if the
UPS needs to be stored for an extended period of time. Ensure that, every time
after charging, the battery capacity percentage shown on the UPS’s LCD is
100%
.
(
)
) for 3 seconds, (2) release it after
/ ) to
) to conrm your selection to
Amplon RT Series
NOTE :
After storage and before start-up of the UPS, you must allow the UPS to
adjust to room temperature (20°C~25°C or 68°F~77°F) for at least one
hour to avoid moisture condensing inside the UPS.
4
Chapter 2 Introduction
Chapter 2 : Introduction
2.1 General Overview
The RT series UPS is a single-phase input, single-phase output on-line uninterruptible power supply which provides reliable and consistent sine-wave quality power
to your electronic equipment. It adopts the latest technology and the highest quality
components providing output power factor up to unity, and its eciency in on-line
mode reaches up to 95.5%. The UPS not only provides safe, reliable and uninterruptible power to your sensitive electronic equipment at all times, but also produces
greater electronic power efficiency at less cost. There are four different ratings,
5kVA, 6kVA, 8kVA and 10kVA, for your selection.
2.2 Exterior & Dimensions
The product that you receive is composed of three parts, a UPS, a battery pack and
a PDB (Power Distribution Box). Please refer to Figure 2-1 and Figure 2-2.
NOTE :
When handling or moving the product, please note that the force area of the
product is at the bottom of the battery pack, but not at the PDB.
UPS
565mm
176mm
(Figure 2-1: Standard Runtime Model - 5/ 6KVA Exterior & Dimensions)
ESC
BATTERY PACK
440mm
665mm
5
PDB
88mm
Battery Pack
UPS
565mm
PDB
130mm
218mm
ESC
BATTERY PACK
440mm
750mm
Battery Pack
(Figure 2-2: Standard Runtime Model - 8/ 10KVA Exterior & Dimensions)
2.3 Package List
The package contains the following items. Please check if any item is missing. If
there is anything missing, please contact the dealer immediately.
1. If there is any damage or anything missing, please immediately contact
the dealer from whom you purchased the unit.
2. If the UPS needs to be returned, carefully repack the UPS and all of the
accessories using the original packing material that came with the unit.
8/ 10kVA
(035)
7
Chapter 3 : Operation Panel
On the front panel of the UPS, you’ll see two LED indicators, a LCD display, and
multi-function buttons.
3.3
LCD Display
ONLINE
%
100
Input
Output
ESC
232.0V50.0Hz
232.0V50.0Hz
(Figure 3-1: Operation Panel)
1
%
75
3.1 LED Indicators
No. LEDDescription
1
2
1. ON: The output is protected.
2. OFF: The output is not protected.
1. ON: The UPS detects an internal fault or an
environmental fault.
2. OFF: The UPS is in normal state.
3. Flashing: The UPS shows the warning message(s).
Please check the corresponding warning
message(s) in Chapter 11: Troubleshooting.
3.1
LED Indicators
3.2
Multi-function
Buttons
Amplon RT Series
8
3.2 Multi-function Buttons
Multi-
No.
function
Button
The button has multiple functions. Please refer to the following
for detailed information.
1. Turn-on
z
z
In standby/ bypass mode, press and hold the button for 3
seconds, release it after you hear one beep and the UPS
will run in on-line mode.
z
z
Cold start: When there is no AC input, press and hold the
button for 3 seconds, release it after you hear one beep
and the UPS will run in battery mode.
2. Turn-o
z
z
In on-line mode, (1) press and hold the button for 3
seconds, (2) release it after you hear one beep, (3) use
the Scrolling UP or Down button
1
ON/ OFF
Button
and (4) press the Enter button
tion. After that, the inverter will be off and the UPS will
transfer to run in standby or bypass mode.
The UPS will keep charging the batteries when the UPS
is in standby/ bypass mode. To fully turn o the UPS, it is
advised to disconnect the UPS from the AC power.
z
z
In battery mode, (1) press and hold the button for 3
seconds, (2) release it after you hear one beep, (3) use
the Scrolling UP or Down button (
and (4) press the Enter button (
tion. After that, the UPS will be turned o.
3. Fault Clear
z
z
When the UPS has a fault condition, press and hold the
button for 3 seconds, release it after you hear one beep
and the UPS will try to clear the fault condition.
Description
Chapter 3 Operation Panel
(
/ )
to select 'Yes',
to conrm your selec-
)
(
) to select ‘Yes’,
/
) to conrm your selec-
9
No.
2
Multi-
function
Button
Enter
Button
Description
NOTE :
1. When the UPS clears the fault condition, it
means that the buzzer/ warning message has
been turned o. To eliminate the fault detected,
please refer to Chapter 11: Troubleshooting
for relevant solutions.
2. The function mentioned above is only applicable to the condition when the UPS has a
fault situation and the inverter is o.
The button has multiple functions. Please refer to the following
for detailed information.
1. Entering into the setup mode
In the Main Screen (that shows the current operation mode),
press the button for 0.1 second and the UPS will enter into
the Main Menu (setup mode). Please refer to Chapter 9: LCD Display & Settings.
2. Selecting and conrming the parameter in setup mode
In setup mode, press the button to choose the parameter
you want to change, and the parameter will ash. Press the
Scrolling Up or the Scrolling Down button to change the
parameter and press the button again to conrm the change.
3
Scrolling
Up Button
Amplon RT Series
The button has multiple functions. Please refer to the following
for detailed information.
1. Scrolling Up/ Increasing Number
z
z
In the Main Screen, press the button for 0.1 second and
the UPS will directly enter into the Measurement Menu’s
level 3 (see Figure 9-1: Menu Tree), which contains
related Output information.
z
z
In setup up mode, the button is used to navigate the setting items. Press the button for 0.1 second to go to the
previous setting item.
10
No.
3
4
Multi-
function
Button
Scrolling
Up Button
Scrolling
Down
Button
Chapter 3 Operation Panel
Description
z
z
The button is also used to navigate or set up the setting
parameter. Press the button for 0.1 second to go to the
previous display or to increase a number. If the button
is pressed for more than 2 seconds, the number will be
increased single digit every 0.2 second automatically until
the button is released or the number reaches its highest
value.
2. LCD Reset
z
z
Press the Scrolling Up and the Scrolling Down buttons
together for 3 seconds to reset the LCD display.
The button has multiple functions. Please refer to the following
for detailed information.
1. Scrolling Down/ Decreasing Number
z
z
In the Main Screen, press the button for 0.1 second and
the UPS will directly enter into the Measurement Menu’s
level 3 (see Figure 9-1: Menu Tree), which contains
related Output information.
z
z
In setup up mode, the button is used to navigate the setting items. Press the button for 0.1 second to go to the
next setting item.
z
z
The button is also used to navigate or set up the setting
parameter. Press the button for 0.1 second to go to the
next display or to decrease a number. If the button is
pressed for more than 2 seconds, the number will be decreased single digit every 0.2 second automatically until
the button is released or the number reaches its lowest
value.
2. LCD Reset
z
z
Press the Scrolling Up and the Scrolling Down buttons
together for 3 seconds to reset the LCD display.
11
Multi-
No.
5
function
Button
ESC
Escape
Button
The button has multiple functions. Please refer to the following
for detailed information.
z
z
Back to the Previous Menu Level
In setup mode, press the button for 0.1 second to go back to
the previous menu level.
Description
NOTE :
If the LCD display goes dim, press any button mentioned above for 0.1
second to wake up the LCD display and enable each button function.
3.3 LCD Display
Amplon RT Series
ONLINE
Input
Output
100
232.0V
232.0V
12
%
50.0Hz
50.0Hz
1
75
%
Chapter 3 Operation Panel
1
1
100
%
100
%
75%
3.3.1 Icon/ Display Denition
No. Icon/ DisplayDescription
1
2
3
Input
Output
4
Battery disconnected
0x1003
!
X
232.0V 50.0Hz
232.0V 50.0Hz
5 seconds
Indicates that the load bank status is ON.
Indicates that the load bank status is OFF.
Indicates the battery capacity level.
Indicates that the battery is abnormal and needs
replacement. If the battery is abnormal, the bat-
tery capacity icon
(
will be o.
)
Indicates the load level (%).
When the UPS runs normally, the display will
show the input/ output voltage and frequency.
When the UPS has abnormalities or is in fault
condition, the display will show an error code
and its corresponding fault or warning message.
NOTE :
The error code and the fault/ warning
message will appear alternatively for
every 5 seconds.
5
Indicates that the buzzer is muted.
13
3.3.2 Operation Mode Diagram Denition
ECO
No. DiagramDescription
1
2
3
ONLINE
Input
Output
ECO
Input
Output
BATTERY
Runtime
168
min
Input
Output
100
232.0V
232.0V
100
232.0V
232.0V
100
0.0V
230.0V
%
%
%
50.0Hz
50.0Hz
50.0Hz
50.0Hz
0.0Hz
50.0Hz
1
75
Indicates ONLINE mode.
%
Indicates ECO mode.
NOTE :
1
In ECO mode, the diagram’s
power ow will change according
to the UPS input voltage and
75
%
frequency. However, the ECO
icon (
) shown on the
upper-left corner will not change
even if the UPS transfers to online
mode or battery mode.
1
75
Indicates BATTERY mode.
%
4
Amplon RT Series
BYPASS
Input
Output
100
232.0V
232.0V
%
50.0Hz
50.0Hz
1
75
Indicates BYPASS mode.
%
14
Chapter 3 Operation Panel
No. DiagramDescription
5
6
STANDBY
Input
Output
Freq. Conv.
Input
Output
100
232.0V
0.0V
100
232.0V
232.0V
%
%
50.0Hz
0.0Hz
50.0Hz
50.0Hz
1
Indicates AC STANDBY mode.
Indicates Frequency Conversion
mode.
NOTE :
1
In Frequency Conversion mode,
the diagram’s power ow will
change according to the UPS
75
%
input voltage and frequency.
However, the text Freq. Conv.
(
Freq. Conv.
) shown on the
upper-left corner will not change
even if the UPS transfers to
battery mode.
15
Chapter 4 : Rear Panel
NORMAL
EXTERNAL BATT. CONNECTOR 192V DC 29A
NORMAL
EXTERNAL BATT. CONNECTOR192V DC 35A
z
z
Model: UPS502R2RT0B0B8
123
DRY CONTACT
MINI SLOT
OUTPUT SOCKET-3
24A MAX. PER OUTLET
OUTPUT SOCKET-2
20A MAX.
10
z
z
Model: UPS602R2RT0B0B8
123
DRY CONTACT
MINI SLOT
17
8
456
RS-232
RS-485
REPO
P2P3P4P1
MANUAL BYPASS SWITCH
WARNING:
OPENING THIS COVER PLATE WILL CAUSE
ONLY AUTHORIZED SERVICE PERSONNEL
CAN OPEN AND OPERATE IT.
OUTPUT BREAKER-2
250V AC 20A
7
INVERTER SHUTDOWN.
1112
(Figure 4-1: 5kVA Rear Panel)
456
RS-232
RS-485
REPO
P2P3P4P1
MANUAL BYPASS SWITCH
7
OUTPUT BREAKER-1
250V AC 30A
L6-30P
9
OUTPUT SOCKET-1
29A MAX.
TMOV
AC I NPU T
98
16
15
OUTPUT SOCKET-1
30A MAX.
TMOV
L
1
AC INPUT
L2
Amplon RT Series
OUTPUT SOCKET-3
29A MAX.
L
L2
1
AC INPUT
WARNING:
OPENING THIS COVER PLATE WILL CAUSE
ONLY AUTHORIZED SERVICE PERSONNEL
CAN OPEN AND OPERATE IT.
OUTPUT BREAKER-3
OUTPUT SOCKET-2
20A MAX.
10
250V AC 30A
OUTPUT BREAKER-2
7
250V AC 20A
INVERTER SHUTDOWN.
L1L2
UPS OUTPU T
11
12
L1L2
UPSOUTP UT
13
14
(Figure 4-2: 6kVA Rear Panel)
16
z
NORMAL
NORMAL
z
Models: UPS502R2RT0B035 & UPS602R2RT0B035
Chapter 4 Rear Panel
123
DRY CONTACTRS-485REPO
MINI SLOT
OUTPUT SOCKET-4 / 10A MAX. PER OUTLET
OUTPUT SOCKET-3 / 10A MAX. PER OUTLET
10
456
P2P3P4P1
RS-232
MANUAL BYPASS SWITCH
OUTPUT
BREAKER-2
250V AC 25A
OUTPUT
BREAKER-3
250V AC 20A
OUTPUT
BREAKER-4
250V AC 20A
OUTPUT SOCKET-2 / 16A MAX. PER OUTLET
11
7
98
OUTPUT SOCKET-1
16A MAX.
WARNING:
OPENING THIS COVER PLATE WILL CAUSE
ONLY AUTHORIZED SERVICE PERSONNEL
CAN OPEN AND OPERATE IT.
INVERTER SHUTDOWN.
(Figure 4-3: 5kVA/ 6kVA Rear Panel)
z
z
Models: UPS802R2RT0B0B8 & UPS103R2RT0B0B8
123
DRY CONTACTRS-485REPO
MINI SLOT
OUTPUT BREAKER-4
250V AC 30A
OUTPUT BREAKER-3
250V AC 30A
4567
P2P3P4P1
RS-232
OUTPUT BREAKER-2
250V AC 20A
OUTPUT BREAKER-1
250V AC 30A
TMOV
AC IN PUT
UPS OU TPU T
8
N L
N L
7
OUTPUT BREAKER-1
250V AC 20A
9
OUTPUT SOCKET-1
30A MAX.
161315
TMOV
N L
AC I NPUT
L
N
EXTERNAL BATT. CONNECTOR 192V DC 35A
12
UPSO UTP UT
14
13
15
UPS OU TPUTAC INP UT
L2 L1 L1 L2
14
16
OUTPUT SOCKET-4
30A MAX.
7
OUTPUT SOCKET-3
30A MAX.
OUTPUT SOCKET-2
20A MAX.
10
MANUAL BYPASS SWITCH
WARNING:
OPENING THIS COVER PLATE WILL CAUSE
ONLY AUTHORIZED SERVICE PERSONNEL
CAN OPEN AND OPERATE IT.
INVERTER SHUTDOWN.
11
EXTERNAL BATT. CONNECTOR 240V DC 46A
12
(Figure 4-4: 8kVA/ 10kVA Rear Panel)
17
z
NORMAL
z
Models: UPS802R2RT0B035 & UPS103R2RT0B035
P2P3P4P1
OUTPUT BREAKER-3
250V AC 25A
OUTPUT SOCKET-3
16A MAX. PER OUTLET
45677
RS-232
OUTPUT BREAKER-2
250V AC 25A
OUTPUT SOCKET-2
16A MAX. PER OUTLET
MANUAL BYPASS SWITCH
OUTPUT SOCKET-1
16A MAX.
11
TMOV
OUTPUT BREAKER-1
250V AC 20A
WARNING:
OPENING THIS COVER PLATE WILL CAUSE
ONLY AUTHORIZED SERVICE PERSONNEL
CAN OPEN AND OPERATE IT.
INVERTER SHUTDOWN.
12
123
DRY CONTACTRS-485REPO
MINI SLOT
250V AC 20A
OUTPUT BREAKER-4
250V AC 20A
OUTPUT SOCKET-4
10A MAX. PER OUTLET
OUTPUT BREAKER-5
OUTPUT SOCKET-5
10A MAX. PER OUTLET
10
(Figure 4-5: 8kVA/ 10kVA Rear Panel)
No. Item Functions
Connects to a Mini SNMP IPv6 / Mini Relay I/
1
MINI Slot
O/ Mini MODBUS card. For more information,
please refer to 5.3 MINI Slot.
1. Output dry contacts: Receive the UPS’s
event information to indicate the UPS
status or internal messages.
2
Dry Contacts
2. Input dry contacts: Let the UPS to receive
external control signals.
3. For more information, please refer to 5.5 Dry Contacts.
89
13
15
UPS OU TPUT
EXTERNAL BATT. CONNECTOR 240V DC 46A
14
N L
AC IN PUT
L N
16
Amplon RT Series
3
REPO Port
4
RS-485 Port
When emergency events occur, it can shut
down the UPS safely and immediately. Please
refer to 5.2 REPO Port for details.
Connects to a computer so you can monitor
the UPS status.
18
No. Item Functions
Connects to a computer so you can build up
RS-232 communication, congure the UPS
and upgrade the UPS rmware.
5
RS-232 Port
Please refer to 5.1 RS-232 Port for more
information.
NOTE :
The USB port and the RS-232 port
must not be used simultaneously.
Connects to a computer so you can monitor
the state of the UPS, congure the UPS
parameters and update the management
6
(USB Port)
software. Please refer to 5.4 USB Port for
more information.
NOTE :
The USB port and the RS-232 port
must not be used simultaneously.
Chapter 4 Rear Panel
7
Output Breaker(s)
8
Output Socket (with
9
load bank function)
10
Output SocketsConnect to the loads.
Manual Bypass
11
Switch
Prevent(s) the output socket from damage
caused by overload.
For input TMOV’s grounding.
Connects to the loads.
Switches the UPS into manual bypass
mode for maintenance without power supply
interruption.
Connects to the external battery pack
(optional).
External Batt.
12
Connector
5K: 192V DC 29A
6K: 192V DC 35A
8K: 240V DC 37A
10K: 240V DC 46A
19
Loading...
+ 51 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.