Delta UPS202R2000B0B2, UPS102R2000B1B1, UPS302R2000B0B1, UPS202R2000B0B1, UPS302R2000B1B1 Installation & Operation Manual

...
Delta UPS - Amplon Family
R Series, Single Phase
1/ 2/ 3 kVA
Installation & Operation Quick Guide
ENGLISH
1
ON
ON
SETUP
OFF
1kVA 2kVA
ON
SETUP
OFF
3kVA
The R series UPS, available in 1kVA, 2kVA and 3kVA, is a single-phase on­line Uninterruptable Power Supply (UPS) system, which outputs reliable sine wave power to your electrical equipment. The product is designed with advanced technology and high quality components. Its output power factor is up to 0.9, and efficiency in on-line mode reaches 93% (for 2kVA/ 3kVA). The unit not only protects your electrical equipment by providing secure and reliable uninterruptable power supply but also produces greater electric power
efciency at less cost.
The Amplon Family R series UPS is a light, compact and easy to use solution for IT applications and features rated nominal power capacities of 1kVA, 2kVA and 3kVA. Each kVA model has internal batteries and each model can be connected to the optional Delta external battery pack(s). The nominal rating voltage of the internal batteries is 24V (1kVA), 48V (2kVA) and 72V (3kVA). Please see the table below for details.
Model No. Power Rating Remarks
UPS102R2000B0B1 UPS102R2000B1B1
1kVA
UPS102R2000B0B2
UPS202R2000B0B1 UPS202R2000B1B1
2kVA
UPS202R2000B0B2
SETUP
OFF
With internal batteries (2 pcs 9Ah sealed lead-acid batteries; battery voltage: 24Vdc)
With internal batteries (4 pcs 9Ah sealed lead-acid batteries; battery voltage: 48Vdc)
Model No. Power Rating Remarks
UPS302R2000B0B1 UPS302R2000B1B1 UPS302R2000B0B2
3kVA
With internal batteries (6 pcs 9Ah sealed lead-acid batteries; battery voltage: 72Vdc)
NOTE:
1. The R Series UPS can connect to the optional Delta external battery pack(s).
2. For more information about the optional Delta external battery pack(s), please contact your dealer.
Safety Instructions
2
z
z
Placement and Installation
1. Read the Quick Guide carefully to ensure correct and safe usage of the product.
2. Install the UPS in a well-ventilated area, away from rain, excess moisture,
dust, ammable gas or explosives.
3. To reduce the risk of re or electric shock, install the UPS in a temperature
and humidity controlled indoor area free of conductive contaminants. Please
Technical Specifications
refer to
10
for operating temperature and relative
humidity.
4. Leave adequate space at least 15cm around each side of the UPS for proper ventilation.
z
z
Connection warnings
1. Make sure the UPS is well grounded to avoid a possible risk of current leakage.
2. The installation of protective devices (a DC non-fuse breaker or a DC fuse) is highly recommended when the UPS is connected to the power source and critical loads.
3. The protective devices connecting to the UPS must be installed near the UPS and must be easily accessible for operation.
4. Do not use extension cord to connect the UPS to an AC outlet.
5. Do not plug the UPS input power cord into its own output receptacles.
6. Prior to moving or reconnecting the UPS, disconnect the AC input power and ensure the UPS is powered off; otherwise, hazardous voltage may still exist at the output receptacles of the UPS, which presents a possible risk of current leakage.
7. Please ensure the length of the output power cord is shorter than 10m.
z
z
Usage warnings
1. The UPS is an EMC Class A product, which may cause wireless interference in your living environment. Precautions need to be taken to prevent possible interference.
2. The UPS can be used to power computers and associated peripheral devices, such as monitors, modems, cartridge tape drives, external hard drives, etc.
3. It is strictly forbidden to connect the UPS to:
- regenerative loads
- loads with half-wave controlled rectier circuit
- loads with asymmetrical current
4. The external slits and openings in the UPS are provided for ventilation. To ensure reliable operation of the UPS and to protect the UPS from overheating, these slits and openings must not be blocked or covered.
5. Before usage, you must allow the UPS to adjust to room temperature (20°C~25°C) for at least one hour.
6. Do not splash any liquid on the UPS and be sure to prevent any foreign material from dropping into the UPS. Do not put beverages on or nearby the UPS.
OFF
7. In an emergency, hold and press the
button, and release it after you
hear one beep to turn off the UPS. Meanwhile, cut off the mains to shut down the UPS.
8. Never use cleaning liquid or spray to clean the UPS. Before cleaning, make sure you have (1) completely shut down the UPS, (2) unplugged the UPS from the power outlet, and (3) disconnected the unit from the Delta external battery pack(s).
9. Only qualied personnel can perform maintenance service. Do not open
or remove the covers or panels of the UPS to avoid high voltage electric shock.
10.You must contact Delta customer service if either of the following events occur:
- Liquid is poured or splashed on the UPS.
- The UPS does not run normally after carefully following the instructions
in this Quick Guide.
z
z
Battery Precautions
1. Do not dispose of the battery or batteries in a fire. The batteries may explode. Do not open or damage the battery or batteries. The released electrolyte is harmful to the skin and eyes and may be toxic.
2. Servicing batteries and battery packs should be performed or supervised
by qualied service personnel who are knowledgeable in batteries, battery
packs and the required precautions.
3. The risk of dangerous voltage is possible when the batteries are still connected to the UPS even though the UPS is disconnected from the mains. Do not forget to disconnect the battery cable to completely cut off the battery source.
4. To ensure battery performance, idle batteries must be fully recharged every three month if the UPS needs to be stored for an extended period of time. Whenever you recharge the batteries (internal and external), please fully charge them until the Battery Level Bar Graph
shown on the UPS’s
LCD is fully on.
5. Since new batteries often do not provide full capacity after an initial charge, it may be necessary to carry out a number of discharge/ recharge cycles before optimum performance is achieved.
www.deltapowersolutions.com
5013252501
1/8
Continue to the Next Page

6. Only use the same type of batteries from the same supplier. Never use old, new and different Ah batteries at the same time.
7. A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries:
- Remove watches, rings or other metal objects.
- Use tools with insulated handles.
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Disconnect the charging source prior to connecting or disconnecting
battery terminals.
8. Do not reverse or short circuit the polarity + and – when connecting the batteries because this will destroy the device and constitute a risk of electric
shock or re.
WARNING:
1. Even though the UPS is disconnected from the mains, a battery may still present electrical shock and short circuit current hazard. Ensure to cut off the battery source prior to the UPS maintenance.
2. When the Delta external battery pack(s) is(are) connected to the UPS, the installation of the protective devices (a DC non-fuse breaker or a DC fuse) is required to protect the unit.
Standard Compliance
3
z
z
CE
z
z
IEC/ EN 62040-1
z
z
IEC/ EN 62040-2 Category C2
Packaging List
4
The UPS package contains the following items. Please check if any item is missing. If there is anything missing, please immediately contact the dealer.
z
z
UPS102/ 202/ 302R2000B0B1
No. Item Q’ty 1K 2/ 3K
1
UPS 1 PC
Installation & Operation
2
Quick Guide
3
Bracket Ear 1 SET
4
USB Cable 1 PC
5
Input Power Cord 10A 1 PC X
6
Input Power Cord 16A 1 PC X
z
z
UPS102/ 202/ 302R2000B1B1
1 3
ON
SETUP
OFF
2
Delta UPS - Amplon Family
R Series, Single Phase
1/ 2/ 3 kVA
Installation & Operation Quick Guide
ENGLISH
1 PC
×2
4
×4
×4
×4
No. Item Q’ty 1K 2/ 3K
1
UPS 1 PC
Installation & Operation
2
Quick Guide
3
Bracket Ear 1 SET
4
USB Cable 1 PC
5
Input Power Cord 1 PC
z
z
UPS102/ 202/ 302R2000B0B2
1 3
2
1 PC
4
Rear Panel
5
UPS102R2000B0B1
1
2
5
UPS202R2000B0B1
1
2
3 4 6
INPUT BREAKER
250
RS-232
AC INP UT
3
RS-232
V AC
.10A
5
6
MINI SLOT
MINI SLOT
EXTERNAL BATT. CONNE CTOR
24V DC 40A
7
5
AC INPUT
EXTERNAL BATT. C ONNECTO R
48V DC 40A
4
INPUT BREAKER
250V AC.20A
OUTPUT SOC KET
7
8
OUTPUT SOCKET
8
10A MAX. PER OUTLE T
UPS302R2000B0B1
1
5
2
3
RS-232
6
MINI SLOT
5
AC INPUT
EXTERNAL BATT. C ONNECTO R
72V DC 40A
7
4
INPUT BREAKER
250V AC.20A
8
OUTPUT SOC KET
10A MAX. PER OUTLE T
1
ON
SETUP
OFF
4
www.deltapowersolutions.com
2
Delta UPS - Amplon Family
R Series, Single Phase
1/ 2/ 3 kVA
Installation & Operation Quick Guide
ENGLISH
5
×2
Delta UPS - Amplon Family
3
×4
×4
ON
SETUP
OFF
R Series, Single Phase
1/ 2/ 3 kVA
Installation & Operation Quick Guide
ENGLISH
×2
×4
×4
×4
×4
6
No. Item Q’ty 1K 2/ 3K
1
UPS 1 PC
Installation & Operation
2
Quick Guide
3
Bracket Ear 1 SET
4
USB Cable 1 PC
5
Input Power Cord 1 PC
1 PC
UPS102R2000B1B1
1
2
3
RS-232
4
INPUT BREAKER
250
V AC
.10A
AC INPUT
5
6
MINI SLOT
EXTERNAL BATT. C ONNECTO R
24V DC 40A
7
Continue to the Next Page

8
OUTPUT SOC KET
2/8
UPS202R2000B1B1
Hz
KW
KVA
AH
MIN
V
%
SETIN OUTBATT°CLOAD TEST
W
KVA
AH
N
%
SETIN OUT BATT°CLOADTEST
IN
1
2
3 4
RS-232
UPS302R2000B1B1
1
2
3 456
RS-232
UPS102R2000B0B2
1
2
3 4
RS-232
UPS202R2000B0B2
1
2
3
RS-232
INPUT BREAKER
250
V AC
AC INPUT
5
6
MINI SLOT
MINI SLOT
.10A
MINI SLOT
AC INPUT
5
AC INPUT
EXTERNAL BATT. C ONNECTO R
AC INPUT
EXTERNAL BATT. C ONNECTO R
6
MINI SLOT
EXTERNAL BATT. C ONNECTO R
24V DC 40A
7
46
INPUT BREAKER
250V AC.20A
5
48V DC 40A
7
72V DC 40A
7
INPUT BREAKER
250V AC.20A
INPUT BREAKER
250V AC.20A
8
OUTPUT SOCKET
8
OUTPUT SOCKET
OUTPUT SOCKET
EXTERNAL BATT. C ONNECTO R
48V DC 40A
OUTPUT SOCKET(10A MAX. PER OUTLE T)
UPS302R2000B0B2
INPUT BREAKER
250V AC.20A
5
4
OUTPUT SOCKET(10A MAX. PER OUTLE T)
1
3 7
RS-232
6
MINI SLOT
AC INPUT
2
No. Item Functions
1
RS-232 Port
Communicates with a PC, so you can monitor the status of the UPS. (UPSentry 2012 Software is required. Please download it from http://www. deltapowersolutions.com/en/mcis/software-center.
EXTERNAL BATT. C ONNECTO R
72V DC 40A
8
Operational Panel
6
IN
RUN TIME
MIN
V
SETUP
ECO
SET
IN OUT BATT
ON
LOAD
TEST
OFF
°C
AH V Hz KVA KW MIN
1
%
3
2
php).
2
USB Port
NOTE: Do not use the USB port and the RS-
232 port at the same time. If you connect the USB cable to the USB port, the RS-232 port will be disabled right away.
1
6.1 LED Indicators
2
6.2 Multi-function Buttons
6.3 LCD Display
3
Fan Cools and ventilates the UPS.
8
3
6.4 7-segment Display
Prevents the UPS from damage caused by high
4
Input Breaker
current and protects the utility power from further
6.5 16-segment Display
damage when the UPS fails.
AC Input
5
(Input Socket)
6
Mini Slot
Connects the UPS to the mains.
Connects a Mini SNMP, a Mini Relay I/O or a Mini MODBUS card (optional) to manage the UPS.
6.1 LED Indicators
Icon(s) Description
Indicates the output status.
z
z
ON (green): Output; OFF: No output.
Connects the Delta external battery pack(s) to
87
External Batt.
7
Connector
extend back up time (+, -, and included).
1 kVA : 24Vdc.40A
terminals are
2 kVA : 48Vdc.40A 3 kVA : 72Vdc.40A
Output
8
Sockets
Connect the loads to the UPS.
1. ON: The UPS detects an internal fault or an environmental fault. The error code will appear on the 16-segment display.
2. Flashing: When the icon is ashing, it would be accompanied with other icon(s) to indicate the according warning message(s). For example:
a. (
): There is no battery or battery replacement is required.
V Hz
b.
c. (
(
RUN TIME
: Overload.
)
K MI
): Charging voltage is too high or too low.
www.deltapowersolutions.com
3/8
Continue to the Next Page

6.2 Multi-function Buttons
SETUP
Icon(s) Description
z
z
Buzzer Off: When the buzzer is on, press the button for 0.1 second to turn the buzzer off. Please note that the buzzer will automatically turn on when a new alarm occurs. The buzzer can’t be manually turned on after it has been muted.
In setup mode, the button is used to conrm or change your parameter. For more details,
please refer to 6.2.1 Setup Mode.
z
z
ON
OFF
Turn On: Press and hold the button for 3 seconds, and release it after you hear one beep.
z
z
Battery Test: Only applicable for on-line mode. Press and hold the button for 3 seconds, and the UPS will transfer to run in battery mode to perform a battery test. After the battery test completes, the LCD will show the test result and the UPS will return to on-line mode automatically.
z
z
Scrolling Up/ Increasing Number: Press the button for 0.1 second to go to the previous display or to increase number. In setup mode, press the button for 0.1 second to go to the previous parameter.
z
z
Turn Off: Press and hold the button for 3 seconds, and release it after you hear one beep.
z
z
Fault Clear: When the UPS has a fault condition, press and hold the button for 3 sec­onds, release it after you hear one beep and the UPS will clear the fault condition.
z
z
Scrolling Down/ Decreasing Number: Press the button for 0.1 second to go to the next display or to decrease number. In setup mode, press the button for 0.1 second to go to the next parameter.
NOTE: The UPS will not perform the battery test if the batteries are not fully charged.
NOTE: When the UPS clears the fault condition, it means that the buzzer/ warning
message has been turned off. To eliminate the fault detected, please refer
Troubleshooting
to
8
for relevant solutions.
6.2.1 Setup Mode
Please note that only qualied service personnel can perform setup action. In setup mode, you can set up the following
items. For some settings, they can’t be set in certain operation modes. Please refer to the table below for relevant information.
Setup Item
The code
shown on the
16-segment
Meaning
Standby
mode
On-line
mode
Bypass
mode
Battery
mode
ECO
mode
display
INV
INV
COV
STB
*1
*1
Inverter Voltage
Setup
Inverter Frequency
Setup
Frequency Converter
Setup
Standby Bypass
Setup
V X V X X X
V X V X X X
V X V X X X
V V V V V V
ECO ECO Setup V V V V V X
ALM
Overload Alarm
Setup
V V V V V V
BUZ Buzzer Setup V V V V V V
BYP
CAP
STG
Bypass Range
Setup
Battery Capacity
Setup
Battery String
Setup
V V V V V V
V V V V V V
V V V V V V
Frequency
converter
mode
ON
NOTE:
1. When the LCD display gets dim, press any of the above-mentioned buttons to wake up the LCD display and enable each button function.
2. Only qualied service personnel can perform setup action.
3. For more information about the setup mode, please refer to 6.2.1 Setup Mode.
www.deltapowersolutions.com
z
z
Entering into the setup mode
Press the
and ON buttons at the same time for 3 seconds
into the setup mode.
z
z
Exiting from the setup mode
When the UPS is in setup mode, press the seconds to exit the setup mode.
and the UPS will enter
and ON buttons at the same time for 3
4/8
AST
PF
RST
Auto-Start To On-line
Setup
Power Factor
Setup
Restore Default
Setup
V X V X X X
V X V X X X
V X V X X X
NOTE:
1
*
Both of the 'Inverter Voltage Setup' and 'Inverter Frequency Setup' use the same code, but you can tell whether the UPS is in 'Voltage' or in 'Frequency' setup by checking the information shown on the 7-segment display.
Continue to the Next Page

The table below lists each setup item's setting parameters.
SETUP
SETUP
3
22456
345
6
32456
32456
32456
32456
32456
32456
32456
32456
32456
32456
32456
8
8
8
8
8
8
8
8
8
8
8
8
8
z
z
For setup procedures, please refer to the following:
The code
shown on the
16-segment display
INV Inverter Voltage Setup 200V, 208V, 220V (Default), 230V, 240V
INV Inverter Frequency Setup 50Hz (Default), 60Hz
COV Frequency Converter Setup OFF (Default), ON
STB Standby Bypass Setup OFF, ON (Default)
ECO ECO Setup OFF (Default), ON
ALM Overload Alarm Setup 60%, 70%, 80%, 85%, 90%, 95%, 100%, 105% (Default)
BUZ Buzzer Setup ENA (Enable) (Default), DIS (Disable)
BYP Bypass Range Setup
CAP Battery Capacity Setup
STG Battery String Setup 0 (Default), 1, 2, 3, 4, 5, 6, 7, 8, 9
AST Auto-Start To On-line Setup OFF (Default), ON
PF Power Factor Setup 70, 80, 90 (Default)
RST Restore Default Setup NA (Default), DEF
Setup Item
Meaning
Setting Parameters
5%, 6%, 7%, 8%, 9%, 10%, 11%, 12%, 13%, 14%, 15% (Default),
HI1, HI2, HI3
0AH (Default), 5AH, 7AH, 9AH, 12AH, 15AH, 24AH, 33AH, 38AH,
40AH, 50AH, 65AH, 80AH, 100AH, 120AH, 150AH, 200AH
*1
*2
*3
*4
*5
*5
*6
*7
1
Simultaneously press the two buttons
2
Press the ON button for 0.1 second or press the
3
Press the button for 0.1 second to enter the item that you want to set up.
4
Press the ON button for 0.1 second or press the
ON
for 3 seconds to enter the setup mode.
OFF
button for 0.1 second to view the previous or the next display.
OFF
button for 0.1 second to increase or decrease the parameter
value.
5
Press the button for 0.1 second to conrm your parameter setup.
6
After that, press the ON button for 0.1 second or press the
OFF
button for 0.1 second to go to the previous or the
next setup item.
7
In setup mode, simultaneously press the two buttons
8
In setup mode, if you don’t press any button for more than 2 minutes, the LCD will exit from the setup mode and go
ON
for 3 seconds, the LCD will exit from the setup mode.
back to the original display automatically.
z
z
Setup Mode Flow Chart
Original Display
1
Inverter Voltage Setup
Inverter Frequency Setup
Frequency Converter Setup
Standby Bypass Setup
7
or
7
or
7
or
7
or
NOTE:
1
: The setting parameters are described in text format; please refer to actual icons or codes shown on the LCD
1. * display when performing the setup action.
2
2. *
: If the setting is set to 'ON', the UPS will automatically disable the bypass function.
3
: If the setting is set to 'OFF', the UPS will run in standby mode whenever the utility AC power is connected to the
3. * UPS or whenever you press the OFF
OFF
button in on-line mode.
If the setting is set to 'ON', the UPS will run in bypass mode whenever the utility AC power is connected to the UPS or whenever you press the OFF
OFF
button in on-line mode.
In standby mode, the UPS has no output voltage; in bypass mode, the UPS has output voltage. In either standby mode or bypass mode, the batteries will be charged.
4
4. *
: The percentage here indicates the bypass tolerance range for the current 'Inverter Voltage' setting. For HI1, the
tolerance range is -20% ~ +15%; for HI2, -25% ~ +15%; for HI3, 120Vac ~ 276Vac.
5
5. *
: If the UPS is not connected to the Delta external battery pack(s), you don’t need to adjust the setting. Just keep the
default setting as '0'.
If the UPS is connected to the Delta the external battery pack(s), you have to set up 'CAP' and 'STG' these two items based on the battery capacity and the strings of the Delta external battery pack(s). Only use the parameters of the Delta external battery pack(s) for the battery setting but not those of the UPS’s internal batteries. If the parameters of the Delta external battery pack(s) do not match the UPS’s built-in setting options, please choose the closest parameters for the battery setting.
6
6. *
: This setup item only affects the UPS’s operation mode whenever the utility AC power is connected to the UPS.
If the setting is set to 'OFF', the UPS will operate according to the 'STB' setting.
If the setting is set to 'ON', the UPS will start up and run in on-line mode automatically.
7
: When you select 'DEF', each of the parameters will be restored to the default value. If any setting deviates from the
7. * default value or is different from what you expect, you may adjust the setting.
ECO Setup
Overload Alarm Setup
Buzzer Setup
Bypass Range Setup
Battery Capacity Setup
Battery String Setup
Auto-Start To On-line Setup
1
*
Power Factor Setup
Restore Default Setup
Continue to the Next Page
7
or
7
or
7
or
7
or
7
or
7
or
7
or
7
or
7
or

www.deltapowersolutions.com
5/8
NOTE:
Hz
KW
KVA
AH
MIN
V
%
SETIN OUT BATT°CLOAD TEST
ECO
1
*
In standby mode or in bypass mode, if you change the 'AST' setting
from 'OFF' to 'ON' and execute the step
5
to confirm such change, the UPS will exit from the setup mode and run in 'Auto-Start to On-line' mode right away.
6.3 LCD Display
IN
RUN TIME
ECO
MIN
V
SET IN OUT BATT
Icon(s) Naming Description
AC Icon Indicates the input power status.
1. ON: Within the acceptable bypass range.
2. Flashing: Out of the acceptable bypass range but sufcient to let the UPS operate in on-line mode.
3. OFF: Out of the acceptable bypass range
and not sufcient to let the UPS operate in
on-line mode.
Output Icon Indicates the output status.
1. ON: There is output.
2. OFF: There is no output.
Battery Power Icon
Indicates the battery power status.
1. ON: The battery power is on.
2. OFF: The output is not supplied by the batteries.
ECO
Standby Mode Graph
Illuminates when the UPS is operating in standby mode.
LOAD TEST
AH
V Hz KVA KW MIN °C
%
Icon(s) Naming Description
ECO
Bypass Mode Graph
Illuminates when the UPS is operating in bypass mode.
ECO Mode Illuminates when the UPS is operating in ECO
mode.
1. ON: ECO function is enabled and the connected loads are fed by the utility AC power.
2. Flashing: ECO function is enabled and the connected loads are fed by the double conversion.
Buzzer Off
Illuminates when the buzzer is disabled.
Icon
Load Level Bar Graph
Indicates the load level status.
ON: load level (%)
1
.
*
NOTE: When the UPS is overloaded,
the warning icon 7-segment display will flash with a load level value.
Battery Level Bar Graph
Indicates the battery level status.
1. ON (
2. Flashing (
3. Flashing (
): The remaining battery capacity (%)
): Low battery.
): There is no battery or battery
replacement is required
NOTE:
1
1. *
means that: 1%~25%: the 1st segment will illuminate.
26%~50%: the rst two segments will illuminate.
51%~75%: the rst three segments will illuminate.
76%~100%: all segments will illuminate.
2
2. *
If you need to replace the batteries or the Delta external battery pack(s), please contact service personnel.
will flash and the
2
.
*
NOTE:
Please read the columns A, B and C together to understand the LCD information, such as input voltage, estimated remaining backup time, etc.
Column A Meaning Column C Meaning
The 7-segment
display shows
AH Ampere hour
readings or words.
Column B Meaning V Voltage
SET Setup mode % Percentage
IN Input Hz Frequency
OUT Output KVA k VA
BATT Battery KW kW
LOAD Load MIN Minute
TEST Test °C
1
.
*
6.5 16-segment Display
IN
RUN TIME
V
MIN
ECO
SET IN OUT BATT
LOAD TEST
The UPS’s internal
AH
%
V Hz KVA KW MIN
°C
temperature
Display Meaning
The 16-segment display shows numbers or error codes.
IN Input
ECO
ECO
ECO
ECO
On-line Mode Graph
Battery Mode Graph
ECO Mode Graph
Frequency Converter Mode
www.deltapowersolutions.com
Illuminates when the UPS is operating in on-line mode.
Illuminates when the UPS is operating in battery mode.
Illuminates when the UPS is operating in ECO mode.
Illuminates when the UPS is operating in frequency converter mode (the icon
will ash while these two icons
&
remain on).
6.4 7-segment Display
IN
RUN TIME
ECO
MIN
V
SET IN OUT BATT
LOAD TEST
Column B
SET IN OUT BATT°CLOAD TEST
AH
%
V Hz KVA KW MIN
°C
AH V Hz KVA KW MIN
%
RUN TIME Estimated remaining backup time.
V Voltage
MIN Minute
7-segment Display Column A Column C
Continue to the Next Page

6/8
Display Meaning
Hz
KW
KVA
AH
MIN
V
%
SETIN OUTBATT°CLOAD TEST
KVA
SETIN OUT BATT°CLOADTEST
Warning icon
1. ON: The UPS detects an internal fault or an environmental fault. The error code will appear on the 16-segment display.
2. Flashing: When the icon is ashing, it would be accompanied with other icon(s) to indicate the according warning message(s).
For example:
): There is no battery or battery replacement is
a. (
required
b. (
c. (
IN
1
.
*
AH
%
V Hz
): Overload.
KW MIN
RUN TIME
): Charging voltage is too high or too low.
NOTE:
1
*
If you need to replace the batteries or the Delta external battery
pack(s), please contact service personnel.
Turn-on/ Turn-off Procedures
7
Turn-on Procedures Turn-off Procedures
If you don’t connect the Delta external battery pack(s) to the UPS:
1. Verify if the UPS’s input cord meets with N, L & G of the wall socket.
2. Plug the UPS’s input cord into the wall socket.
3. Press and hold the seconds
and release it after you hear
ON
button for 3
one beep.
4. The UPS starts self-inspection. When the graph
appears on the display, the UPS runs in on-line mode.
If you connect the Delta external battery pack(s) to the UPS:
1. Verify if the UPS’s input cord meets with N, L & G of the wall socket.
2. Check the '+' and '-' poles of the Delta external battery pack(s) and ensure that wiring is correct.
3. Connect the Delta external battery pack(s) to the UPS.
4. Plug the UPS’s input cord into the wall socket.
If you don’t connect the Delta external battery pack(s) to the UPS:
1. Make sure all loads connected to the UPS have been completely shut down.
2. Press and hold the
OFF
button for 3 seconds, and release it after you hear one beep.
3. Disconnect the UPS from the AC power.
If you connect the Delta external battery pack(s) to the UPS:
1. Make sure all loads con­nected to the UPS have been completely shut down.
2. Press and hold the
OFF
button for 3 seconds, and release it after you hear one beep.
Turn-on Procedures Turn-off Procedures
5. Press and hold the ON button for 3 seconds and release it after you hear
one beep.
6. The UPS starts self-inspection. When the graph
appears on the
3. Disconnect the UPS from the AC power.
4. Disconnect the UPS from the Delta external battery pack(s).
display, the UPS runs in on-line mode.
NOTE:
For more information about the connections of the Delta external battery pack(s), please refer to the Delta External Battery Pack for Amplon R 1/ 2/ 3kVA UPS Installation & Operation Quick Guide.
Troubleshooting
8
When you see the following problems occur, please follow the solutions shown below.
A. About the error codes shown on the 16-segment display:
Error Code
E11
Meaning Possible Cause Solution
Charger Warning
Charging voltage is too high or too low.
Please contact service personnel.
1. Check if foreign matter is stuck in the fan. If yes,
E12 Fan Fault Fan is damaged or stuck.
please remove it.
2. Please contact service personnel.
1. Check whether the UPS has adequate ventilation.
2. Decrease the loads.
3. Check whether the fan runs normally.
E13
Temperature Out of Range
The UPS temperature is out of range.
4. Clean the lters (if you
have installed any).
+/- DC BUS
E14
High/ Low
E16 Inverter Fault
E18 DC-DC Fault
1. There are inductive loads such as trans­formers connected to the UPS output.
2. Abnormalities are detected in the UPS.
Abnormalities are detected in the UPS.
Abnormalities are detected in the UPS.
1. Turn on the UPS after the loads have been con­nected to the UPS in bypass mode.
2. Please contact service personnel.
Please contact service personnel.
Please contact service personnel.
Error Code
Meaning Possible Cause Solution
Abnormal
E19
Output/ Inverter Voltage
E21 O/P Short
Charger
E77
Fault
MBB
MBB
Shutdown
Overload
OVL
Shutdown
REPO
SD0
Shutdown
SD1 RPO Shutdown
'Shutdown After'
SD2
Shutdown
'Battery Save'
SD3
Shutdown
Battery Low
SD4
Shutdown
'Cold Start
SD5
Battery Empty' Shutdown
Abnormalities are detected in the UPS.
A short-circuit issue has been detected in output.
Charger is damaged.
The cover of the manual bypass box is removed.
The UPS is overloaded.
Emergent shutdown is executed.
Remote shutdown is executed from dry contact.
UPS delay shutdown is triggered.
Shutdown is enabled after the UPS has run in battery mode for a
specic time.
The UPS transfers into battery mode due to AC utility abnormality. However, the battery power is almost used up.
The batteries are damaged or battery lifetime is due.
Please contact service personnel.
1. Check whether the output has a short­circuit issue.
2. Contact service personnel.
Please contact service personnel.
Please contact service personnel.
Decrease the connected loads.
After emergent events are eliminated, follow the turn-on procedures to start up the UPS.
After the remote shutdown events are eliminated, follow the turn-on procedures to start up the UPS.
Please contact service personnel.
Please contact service personnel.
1. Check the main AC source and the status of the input power cord.
2. Please contact service personnel.
Please contact service personnel.
www.deltapowersolutions.com
7/8
Continue to the Next Page

B. About other problems that might happen:
Technical Specifications
10
Model R-1K R-2K R-3K
No. Problem Possible Cause Solution
1 Overload
The UPS is overloaded.
Decrease your connected loads.
1. Please contact service personnel.
2. Connect the internal battery cables and
2 Battery Missing
Internal battery cables are not connected or
not rmly connected.
connect them rmly.
Weak Battery/
3
Battery Replacement
Abnormal Input
4
(when the AC icon
is ashing)
The batteries are damaged or battery lifetime is due.
The AC input voltage or frequency is out of the acceptable bypass range.
Please contact service personnel.
1. Check if the AC input voltage or frequency is abnormal.
2. Please contact service personnel.
NOTE:
If all possible causes are eliminated but the alarm still appears, please contact your local dealer or customer service.
Optional Accessories
9
Model R-1K R-2K R-3K
Power Rating 1kVA/0.9kW 2kVA/1.8kW 3kVA/2.7kW
Waveform Pure Sine Wave
Input
Nominal
Voltage
Voltage Range
1
200*
/208*1/220/230/240 Vac
175 ~ 280 Vac (100% load);
80 ~ 175 Vac (50% ~ 100% load)
Frequency 50/60 Hz (± 10 Hz)
Power Factor > 0.99 (full load)
Input iTHD < 3%
Power Factor 0.9
1
/208*1/220/230/240 Vac
± 1% (linear load)
Output
Voltage 200*
Voltage
Regulation
Frequency 50/60 Hz (± 0.05 Hz)
Battery Voltage 24 Vdc 48 Vdc 72 Vdc
Backup Time*
(Internal
2
6.5 minutes 7 minutes 7 minutes
Batteries Only)
Battery
Recharge Time
(Internal
3 hours to 90%
Batteries Only)
Charge Current 1.5A
Audible Noise*
3
< 40 dBA < 43 dBA < 43 dBA
Display LED indicators & LCD display
Communication Interfaces MINI Slot x 1, RS-232 Port x 1, USB Port x 1
Physical
Dimensions
(W × D × H )
440 x 335 x
88 mm
440 x 430 x
88 mm
440 x 565 x
88 mm
Weight 11.5 kg 20.6 kg 27.5 kg
Environment
Operating
Altitude
Operating
Temperature
1000 meters (without derating)
0 ~ 50°C*
4
No. Item Function
1 Mini SNMP Card
Monitors and controls the status of the UPS via a network system.
2 Mini Relay I/O Card Increases the quantity of dry contacts.
3 Mini MODBUS Card
Cable & Wire Mount
4
Assembly
Lets the UPS have MODBUS communication function.
Fastens an IEC output cable to prevent the cable from coming off.
5 Tower Stands Sustain the UPS vertically.
6 Rail Kit Fixes the UPS in a rack cabinet rmly.
NOTE: For more details, please contact your local dealer or customer
service.
www.deltapowersolutions.com
vTHD < 3% (linear load)
Overload
Capability
< 105%: continuous; 105% ~ 125%: 1 minute;
125% ~ 150%: 30 seconds
Cress Factor 3 : 1
Output
Connection
Sufx B0B1
Connection
Sufx B1B1
Connection
Sufx B0B2
IEC C13 x 4
Brazilian
socket x 3
Argentinian
socket x 3
IEC C13 x 6
IEC C19 x 1
Brazilian socket x 4
Argentinian socket x 4
IEC C13 x 6
IEC C19 x 1
Efciency On-line Mode 91% Up to 93%
8/8
Relative
Humidity
5% ~ 95% (non-condensing)
NOTE:
1
1. *
When the UPS is de-rated to 90% of its capacity.
2
When the total load of the UPS reaches 75%.
2. *
3
If the UPS is runnning in room temperature and below 75% load
3. * capacity.
4
When the operating temperature is at 40~50°C, the UPS will be de-
4. * rated to 80% of its capacity.
5. Please refer to the rating label for the safety rating.
6. All specications are subject to change without prior notice.
Copyright © 2018 by Delta Electronics Inc. All rights reserved. Changes may be made periodically to the information in this Quick Guide without obligation to notify any person of such revision or changes.
No. 501325250102 Version : V 1.2 Release Date : 2018_04_27
Loading...