
Delta UPS - Amplon Family
R Series, Single Phase
1/ 2/ 3 kVA
Installation & Operation Quick Guide
ENGLISH
Product Introduction
1
ON
ON
SETUP
OFF
1kVA 2kVA
ON
SETUP
OFF
3kVA
The R series UPS, available in 1kVA, 2kVA and 3kVA, is a single-phase online Uninterruptable Power Supply (UPS) system, which outputs reliable
sine wave power to your electrical equipment. The product is designed with
advanced technology and high quality components. Its output power factor
is up to 0.9, and efficiency in on-line mode reaches 93% (for 2kVA/ 3kVA).
The unit not only protects your electrical equipment by providing secure and
reliable uninterruptable power supply but also produces greater electric power
efciency at less cost.
The Amplon Family R series UPS is a light, compact and easy to use solution
for IT applications and features rated nominal power capacities of 1kVA, 2kVA
and 3kVA. Each kVA model has internal batteries and each model can be
connected to the optional Delta external battery pack(s). The nominal rating
voltage of the internal batteries is 24V (1kVA), 48V (2kVA) and 72V (3kVA).
Please see the table below for details.
Model No. Power Rating Remarks
UPS102R2000B0B1
UPS102R2000B1B1
1kVA
UPS102R2000B0B2
UPS202R2000B0B1
UPS202R2000B1B1
2kVA
UPS202R2000B0B2
SETUP
OFF
With internal batteries (2
pcs 9Ah sealed lead-acid
batteries; battery voltage:
24Vdc)
With internal batteries (4
pcs 9Ah sealed lead-acid
batteries; battery voltage:
48Vdc)
Model No. Power Rating Remarks
UPS302R2000B0B1
UPS302R2000B1B1
UPS302R2000B0B2
3kVA
With internal batteries (6 pcs
9Ah sealed lead-acid batteries;
battery voltage: 72Vdc)
NOTE:
1. The R Series UPS can connect to the optional Delta external battery
pack(s).
2. For more information about the optional Delta external battery pack(s),
please contact your dealer.
Safety Instructions
2
z
z
Placement and Installation
1. Read the Quick Guide carefully to ensure correct and safe usage of the
product.
2. Install the UPS in a well-ventilated area, away from rain, excess moisture,
dust, ammable gas or explosives.
3. To reduce the risk of re or electric shock, install the UPS in a temperature
and humidity controlled indoor area free of conductive contaminants. Please
Technical Specifications
refer to
10
for operating temperature and relative
humidity.
4. Leave adequate space at least 15cm around each side of the UPS for proper
ventilation.
z
z
Connection warnings
1. Make sure the UPS is well grounded to avoid a possible risk of current
leakage.
2. The installation of protective devices (a DC non-fuse breaker or a DC fuse)
is highly recommended when the UPS is connected to the power source and
critical loads.
3. The protective devices connecting to the UPS must be installed near the UPS
and must be easily accessible for operation.
4. Do not use extension cord to connect the UPS to an AC outlet.
5. Do not plug the UPS input power cord into its own output receptacles.
6. Prior to moving or reconnecting the UPS, disconnect the AC input power and
ensure the UPS is powered off; otherwise, hazardous voltage may still exist
at the output receptacles of the UPS, which presents a possible risk of current
leakage.
7. Please ensure the length of the output power cord is shorter than 10m.
z
z
Usage warnings
1. The UPS is an EMC Class A product, which may cause wireless interference
in your living environment. Precautions need to be taken to prevent possible
interference.
2. The UPS can be used to power computers and associated peripheral devices,
such as monitors, modems, cartridge tape drives, external hard drives, etc.
3. It is strictly forbidden to connect the UPS to:
- regenerative loads
- loads with half-wave controlled rectier circuit
- loads with asymmetrical current
4. The external slits and openings in the UPS are provided for ventilation.
To ensure reliable operation of the UPS and to protect the UPS from
overheating, these slits and openings must not be blocked or covered.
5. Before usage, you must allow the UPS to adjust to room temperature
(20°C~25°C) for at least one hour.
6. Do not splash any liquid on the UPS and be sure to prevent any foreign
material from dropping into the UPS. Do not put beverages on or nearby
the UPS.
OFF
7. In an emergency, hold and press the
button, and release it after you
hear one beep to turn off the UPS. Meanwhile, cut off the mains to shut
down the UPS.
8. Never use cleaning liquid or spray to clean the UPS. Before cleaning,
make sure you have (1) completely shut down the UPS, (2) unplugged the
UPS from the power outlet, and (3) disconnected the unit from the Delta
external battery pack(s).
9. Only qualied personnel can perform maintenance service. Do not open
or remove the covers or panels of the UPS to avoid high voltage electric
shock.
10.You must contact Delta customer service if either of the following events
occur:
- Liquid is poured or splashed on the UPS.
- The UPS does not run normally after carefully following the instructions
in this Quick Guide.
z
z
Battery Precautions
1. Do not dispose of the battery or batteries in a fire. The batteries may
explode. Do not open or damage the battery or batteries. The released
electrolyte is harmful to the skin and eyes and may be toxic.
2. Servicing batteries and battery packs should be performed or supervised
by qualied service personnel who are knowledgeable in batteries, battery
packs and the required precautions.
3. The risk of dangerous voltage is possible when the batteries are still
connected to the UPS even though the UPS is disconnected from the
mains. Do not forget to disconnect the battery cable to completely cut off
the battery source.
4. To ensure battery performance, idle batteries must be fully recharged
every three month if the UPS needs to be stored for an extended period of
time. Whenever you recharge the batteries (internal and external), please
fully charge them until the Battery Level Bar Graph
shown on the UPS’s
LCD is fully on.
5. Since new batteries often do not provide full capacity after an initial
charge, it may be necessary to carry out a number of discharge/ recharge
cycles before optimum performance is achieved.
www.deltapowersolutions.com
5013252501
1/8
Continue to the Next Page

6. Only use the same type of batteries from the same supplier. Never use old,
new and different Ah batteries at the same time.
7. A battery can present a risk of electrical shock and high short circuit current.
The following precautions should be observed when working on batteries:
- Remove watches, rings or other metal objects.
- Use tools with insulated handles.
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Disconnect the charging source prior to connecting or disconnecting
battery terminals.
8. Do not reverse or short circuit the polarity + and – when connecting the
batteries because this will destroy the device and constitute a risk of electric
shock or re.
WARNING:
1. Even though the UPS is disconnected from the mains, a battery may
still present electrical shock and short circuit current hazard. Ensure
to cut off the battery source prior to the UPS maintenance.
2. When the Delta external battery pack(s) is(are) connected to the
UPS, the installation of the protective devices (a DC non-fuse breaker
or a DC fuse) is required to protect the unit.
Standard Compliance
3
z
z
CE
z
z
IEC/ EN 62040-1
z
z
IEC/ EN 62040-2 Category C2
Packaging List
4
The UPS package contains the following items. Please check if any item is
missing. If there is anything missing, please immediately contact the dealer.
z
z
UPS102/ 202/ 302R2000B0B1
No. Item Q’ty 1K 2/ 3K
1
UPS 1 PC
Installation & Operation
2
Quick Guide
3
Bracket Ear 1 SET
4
USB Cable 1 PC
5
Input Power Cord 10A 1 PC X
6
Input Power Cord 16A 1 PC X
z
z
UPS102/ 202/ 302R2000B1B1
1 3
ON
SETUP
OFF
2
Delta UPS - Amplon Family
R Series, Single Phase
1/ 2/ 3 kVA
Installation & Operation Quick Guide
ENGLISH
1 PC
×2
4
×4
×4
×4
No. Item Q’ty 1K 2/ 3K
1
UPS 1 PC
Installation & Operation
2
Quick Guide
3
Bracket Ear 1 SET
4
USB Cable 1 PC
5
Input Power Cord 1 PC
z
z
UPS102/ 202/ 302R2000B0B2
1 3
2
1 PC
4
Rear Panel
5
UPS102R2000B0B1
1
2
5
UPS202R2000B0B1
1
2
3 4 6
INPUT BREAKER
250
RS-232
AC INP UT
3
RS-232
V AC
.10A
5
6
MINI SLOT
MINI SLOT
EXTERNAL BATT. CONNE CTOR
24V DC 40A
7
5
AC INPUT
EXTERNAL BATT. C ONNECTO R
48V DC 40A
4
INPUT BREAKER
250V AC.20A
OUTPUT SOC KET
7
8
OUTPUT SOCKET
8
10A MAX. PER OUTLE T
UPS302R2000B0B1
1
5
2
3
RS-232
6
MINI SLOT
5
AC INPUT
EXTERNAL BATT. C ONNECTO R
72V DC 40A
7
4
INPUT BREAKER
250V AC.20A
8
OUTPUT SOC KET
10A MAX. PER OUTLE T
1
ON
SETUP
OFF
4
www.deltapowersolutions.com
2
Delta UPS - Amplon Family
R Series, Single Phase
1/ 2/ 3 kVA
Installation & Operation Quick Guide
ENGLISH
5
×2
Delta UPS - Amplon Family
3
×4
×4
ON
SETUP
OFF
R Series, Single Phase
1/ 2/ 3 kVA
Installation & Operation Quick Guide
ENGLISH
×2
×4
×4
×4
×4
6
No. Item Q’ty 1K 2/ 3K
1
UPS 1 PC
Installation & Operation
2
Quick Guide
3
Bracket Ear 1 SET
4
USB Cable 1 PC
5
Input Power Cord 1 PC
1 PC
UPS102R2000B1B1
1
2
3
RS-232
4
INPUT BREAKER
250
V AC
.10A
AC INPUT
5
6
MINI SLOT
EXTERNAL BATT. C ONNECTO R
24V DC 40A
7
Continue to the Next Page
8
OUTPUT SOC KET
2/8

UPS202R2000B1B1
Hz
KW
KVA
AH
MIN
V
%
SETIN OUTBATT°CLOAD TEST
%
SETIN OUT BATT°CLOADTEST
1
2
3 4
RS-232
UPS302R2000B1B1
1
2
3 456
RS-232
UPS102R2000B0B2
1
2
3 4
RS-232
UPS202R2000B0B2
1
2
3
RS-232
INPUT BREAKER
250
V AC
AC INPUT
5
6
MINI SLOT
MINI SLOT
.10A
MINI SLOT
AC INPUT
5
AC INPUT
EXTERNAL BATT. C ONNECTO R
AC INPUT
EXTERNAL BATT. C ONNECTO R
6
MINI SLOT
EXTERNAL BATT. C ONNECTO R
24V DC 40A
7
46
INPUT BREAKER
250V AC.20A
5
48V DC 40A
7
72V DC 40A
7
INPUT BREAKER
250V AC.20A
INPUT BREAKER
250V AC.20A
8
OUTPUT SOCKET
8
OUTPUT SOCKET
OUTPUT SOCKET
EXTERNAL BATT. C ONNECTO R
48V DC 40A
OUTPUT SOCKET(10A MAX. PER OUTLE T)
UPS302R2000B0B2
INPUT BREAKER
250V AC.20A
5
4
OUTPUT SOCKET(10A MAX. PER OUTLE T)
1
3 7
RS-232
6
MINI SLOT
AC INPUT
2
No. Item Functions
1
RS-232 Port
Communicates with a PC, so you can monitor
the status of the UPS. (UPSentry 2012 Software
is required. Please download it from http://www.
deltapowersolutions.com/en/mcis/software-center.
EXTERNAL BATT. C ONNECTO R
72V DC 40A
8
Operational Panel
6
IN
RUN TIME
MIN
V
SETUP
ECO
SET
IN OUT BATT
ON
LOAD
TEST
OFF
°C
AH
V
Hz
KVA
KW
MIN
1
%
3
2
php).
2
USB Port
NOTE: Do not use the USB port and the RS-
232 port at the same time. If you connect the
USB cable to the USB port, the RS-232 port
will be disabled right away.
1
6.1 LED Indicators
2
6.2 Multi-function Buttons
6.3 LCD Display
3
Fan Cools and ventilates the UPS.
8
3
6.4 7-segment Display
Prevents the UPS from damage caused by high
4
Input Breaker
current and protects the utility power from further
6.5 16-segment Display
damage when the UPS fails.
AC Input
5
(Input Socket)
6
Mini Slot
Connects the UPS to the mains.
Connects a Mini SNMP, a Mini Relay I/O or a Mini
MODBUS card (optional) to manage the UPS.
6.1 LED Indicators
Icon(s) Description
Indicates the output status.
z
z
ON (green): Output; OFF: No output.
Connects the Delta external battery pack(s) to
87
External Batt.
7
Connector
extend back up time (+, -, and
included).
1 kVA : 24Vdc.40A
terminals are
2 kVA : 48Vdc.40A
3 kVA : 72Vdc.40A
Output
8
Sockets
Connect the loads to the UPS.
1. ON: The UPS detects an internal fault or an environmental
fault. The error code will appear on the 16-segment display.
2. Flashing: When the icon is ashing, it would be accompanied
with other icon(s) to indicate the according warning message(s).
For example:
a. (
): There is no battery or battery replacement is required.
V
Hz
b.
c. (
(
RUN TIME
: Overload.
)
K
MI
): Charging voltage is too high or too low.
www.deltapowersolutions.com
3/8
Continue to the Next Page