The DELTA DORE sensor range covers all applications.
These sensors are interchangeable:
Self-adhesive projecting ambient temperature sensor
Built-in projecting ambient temperature sensor (Mosaic)
Ambient temperature sensor for places of assembly
Ambient temperature sensor for industrial premises
Outdoor sensor
Ground/piping/blower sensor
Because of changes in standards and equipment, the characteristics given in the text and the illustrations of this document are not binding unless
confirmed by Delta Dore.
Device complying with the requirements of the directives:
2004/108/EEC (electromagnetic compatibility)
and 2006/95/EEC (low voltage safety).
T1C-2 digit is mounted on a DIN rail in an electrical cabinet.
• Power supply 230 V ± 10%, 50 Hz
• Insulation class II
• Consumption: 2 VA
• 1 changeover contact output, 5 A, 230 V
• Setpoint adjustable from -9.5 °C to +90 °C
• Differential adjustable from 0.2 °C to 2 °C in
0.1 °C steps
• Sensor input: NTC type 1000Ω at 25 °C
• Digital display (setpoint or measured
temperature, output state)
• Modular case: 3 modules, h = 58 mm
• DIN rail mounting
• Protection index: IP 40
T1C-2 Digit
Digital display electronic thermostat
1. Description
2. Mounting
The T1C-2 digit is a snap action electronic ther mostat.
It is suitable for all cases where temperature control is necessary, including rooms, air
ducts, liquids, solids...
7. Technical characteristics
8. Sensors
*2702300_Rev.1*
10
1 2
3
9
8
4
5
67
Sensor input
1
Selector switch :
2
User mode/Installer mode
Output state : Lit = On
3
Temperature display
4
5
Scroll button
Changeover relay output
6
Power supply
7
Fault indicator (flashing)
8
9
Modification buttons
Displayed temperature type indicator
10
(On = Setpoint, Off = Measured temperature)
Bonnemain - 35270 COMBOURG - France
E-mail : deltadore@deltadore.com
DELTA DORE
T1C-2 digit continuously compares
the setpoint temperature displayed on
the thermostat with the temperature
measured by the sensor.
When the measured temperature
exceeds the setpoint temperature,
the output switches to Off.
When the measured temperature
falls below (setpoint temperature -
Δt), the output switches to On.
Δt = Differential (set during
commissioning)
User mode
T1C-2 digit continuously displays the current setpoint
temperature.
The measured temperature can be displayed by pressing
the button.
Note : The display can be reversed (refer to § “Installer
Commissioning”).
"Informed" user mode
To change the setpoint temperature.
Press the and buttons simultaneously (for approximately 5 seconds) until the
display starts flashing.
Release the buttons.
Press the or button to set the temperature that you want.
Press to accept the value.
Place the switch in the PROG position.
Press the ou buttons to display the required value.
Press to accept and go to the next parameter.
When all the settings have been defined, the switch must be returned to the
position.
CAUTION :
If the setpoint is above 70 °C, do not program a differential of less than 1 °C.
For clarity, only schematic diagrams are given here.They do not show the
protective devices and other accessories required by the standards.
- The UTE C15-100 standard and good practice must be complied with.
- Connected or adjacent appliances must not generate excessive
interference (directive 2004/108/EEC).
3. Connection
4. Installer commmissioning
5. Using
The "Alarm" warning light flashes to indicate that a fault has occurred.
6. Alarm
Sensor
NL
12
230 V~
50 Hz
NL
34
230 V~
5A max
567
PROG
T1C-2 Digit
Heat source
Cold source
PROG
Function no. Description
Setpoint
temperature
Differential
Displayed
temperature
Sensor correction
From - 9.5 ˚C to + 90 ˚C
in 0.5 ˚C steps
From + 0.2 ˚C to + 2 ˚C
in 0.1 ˚C steps
0 = Setpoint temperature
1 = Measured temperature
From - 2 ˚C to + 2 ˚C
in 0.5 ˚C steps 0 ˚C
Setting Default value
+ 20˚C
0,2˚C
0
0˚C
Measured
temperature (Tm)
T
Setpoint (Tc)
On
Off
Outpu
state
1
1
Problem
When the measured
temperature is
PROG
consulted, the
thermostat displays:
When the measured
temperature is
consulted, the
thermostat displays:
The temperature display is correct,
but the "Alarm" light is flashing.
The sensor is cut off
Check the sensor or its connection.
The sensor is short-circuited
Check the sensor or its connection.
There is a problem inside the thermostat
Switch off, then switch on again.
If the problem persists, contact the installer.
Diagnosis / Solution