Delta SOLIVIA 2.5 AP G3 TR Operation And Installation Manual

Page 1
SOLIVIA 2.5 AP G3 TR
Operation and installation manual
Page 2
Page 3
EN
1
Operation and installation manual SOLIVIA 2.5 AP G3 TR
SOLIVIA 2.5 AP G3 TR
The manual is subject to change.
Please check our website at www.solar-inverter.com for the most up-to-date manual version.
Delta Energy Systems (Germany) GmbH
Tscheulinstraße 21
79331 Teningen
Germany
© Copyright – Delta Energy Systems (Germany) GmbH - All rights reserved.
This manual accompanies our equipment for use by the end users.
The technical instructions and illustrations contained in this manual are to be treated as
condential and no part may be reproduced without the prior written permission of Delta
Energy Systems Service engineers and end users may not divulge the information con­tained herein or use this manual for purposes other than those strictly connected with correct use of the equipment.
All information and specications are subject to change without notice.
Page 4
2
Operation and installation manual SOLIVIA 2.5 AP G3 TR
Page 5
EN
3
Operation and installation manual SOLIVIA 2.5 AP G3 TR
Table of Contents
1. About this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 Purpose of this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Warnings and symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2. Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3. General safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4. Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5. System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.1 Data evaluation and communication . . . . . . . . . . . . . . . . . . . . . . . . 8
5.2 Technical structure of the solar inverter . . . . . . . . . . . . . . . . . . . . . . 8
5.3 Equipment overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
6. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
7. Installation of equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
7.1 Installation location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
7.2 Minimum requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
7.3 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
7.4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
7.5 Ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
7.6 Grid connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
7.7 Connection of PV modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
7.7.1 Output power over PV voltage . . . . . . . . . . . . . . . . . . . . . .14
7.7.2 Output power over AC voltage . . . . . . . . . . . . . . . . . . . . . .15
7.7.3 Efciency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
7.8 Interface connection RS485 (EIA485) . . . . . . . . . . . . . . . . . . . . . . .16
7.9 Electrical connection and operational start-up . . . . . . . . . . . . . . . . . . .18
7.10 Setup / settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
7.11 LED operation and fault display . . . . . . . . . . . . . . . . . . . . . . . . . .21
8. Operating concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
8.1 The display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
8.2 Navigation in the display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
8.3 Main menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
8.3.1 Submenu N (Now). . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
8.3.2 Submenu D (Day) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
8.3.3 Submenu W (Week). . . . . . . . . . . . . . . . . . . . . . . . . . . .26
8.3.4 Submenu M (Month) . . . . . . . . . . . . . . . . . . . . . . . . . . .26
8.3.5 Submenu Y (Year). . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
8.3.6 Submenu T (Total). . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
8.3.7 Submenu S (Setup) . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
8.3.7.1 Submenu S: Solar ISO / GND ..........................29
8.3.7.2 Submenu S: Country settings ..........................30
8.3.7.3 Submenu S: Firmware ................................31
Page 6
4
Operation and installation manual SOLIVIA 2.5 AP G3 TR
9. Diagnostics and data evaluation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
9.1 Malfunction rectication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
9.2 Display messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
10. Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
11. Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
11.1 Connection examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
11.2 Overview of connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . .38
12. Glossary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
13.Certicates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Page 7
EN
5
Operation and installation manual SOLIVIA 2.5 AP G3 TR
1. About this manual
This manual allows you to become acquainted with the product.
Observe the safety regulations applicable for each country. You can contribute to the durability and reliability of the product during its use by handling it carefully. These are basic prerequisites for optimum use of your product.
1.1 Purpose of this manual
This manual is part of the product and is only valid for the SOLIVIA 2.5 AP G3 TR.
Store the manual in a safe place.
Read the manual carefully and thoroughly and follow the instructions contained therein. The manual contains important information on the installation and operation of the solar inverter.
Take note of and follow the information on safe use (see „3. General safety instruc-
tions“, page 6).
The installer and the operator must have access to this manual and must be familiar with the safety instructions.
1.2 Warnings and symbols
The following section explains the warnings and symbols used in this manual.
DANGER
Indicates a dangerous situation. An accident will lead to death or severe physical injuries.
WARNING
Indicates a dangerous situation. An accident can lead to death or severe physical injuries.
CAUTION
Indicates a dangerous situation. An accident can lead to medium or light physical injuries.
ATTENTION
Indicates a dangerous situation that can result in material damage.
NOTE
Contains general information on using the solar inverter. A note does not indicate dangerous situations.
Page 8
6
Operation and installation manual SOLIVIA 2.5 AP G3 TR
This symbol warns of a danger of electric shock due to the presence of high voltages.
This symbol is a warning of general dangers.
2. Intended use
The solar inverter connects a photovoltaic system to the public power grid. The solar inverter converts DC electricity into AC electricity, which is then fed into the public power grid.
The solar inverter is intended for use in photovoltaic systems connected to a power grid. The solar inverter is not intended for mobile use.
The solar inverter can be used indoors and in protected outdoor areas with ambient conditions according to IP65.
The solar inverter may only be used within the specied power range and under the specied ambient conditions.
The solar inverter contains monitoring devices, including an anti-islanding device.
The solar inverter may only be used for the specied intended purpose.
3. General safety instructions
DANGER
Danger of death from hazardous voltage
Hazardous voltage is applied to the solar power inverter during op­eration. Hazardous voltage is still present 5 minutes after all power sources have been disconnected.
► Never open the solar inverter. The solar inverter contains no com-
ponents that are to be maintained or repaired by the operator or installer. Opening the cover will void the warranty.
Incorrect handling can lead to physical injuries and material damage!
The installation and commissioning work may be performed only by qualied elec- tricians.
The solar inverter can be operated safely and normally only if it is installed and operated in accordance with this manual (see IEC 62109-5.3.3). Delta Energy
Page 9
EN
7
Operation and installation manual SOLIVIA 2.5 AP G3 TR
Systems is not responsible for damage incurred by failure to comply with the instal­lation and operating instructions in this manual.
The solar inverter contains no components that are to be maintained or repaired by the operator or installer. All repairs must be performed by Delta.
Observe all points in this installation and operation manual!
Before working on the solar inverter, you must disconnect it from the grid and the PV modules.
Do not disconnect any cables when the solar inverter is under load, as there is a risk of an arc fault.
To prevent lightning strikes, follow the regulations applicable in your country.
The surface of the solar inverter can get very hot.
The solar inverter is heavy (see „10. Technical data“, page 34). The solar inverter must always be lifted by two people.
The solar inverter has a high leakage current value (see „10. Technical data“,
page 34). The ground wire MUST be connected before the start of operation.
Only equipment in accordance with SELV (EN 60950) may be connected to the RS485 interfaces.
Do not remove any warning signs that the manufacturer has installed on the solar inverter.
In order for IP65 protection to be granted, all used and unused connections must
be sufciently sealed.
4. Scope of delivery
SOLAR INVERTER SOLIVIA 2.5 AP G3 TR
Mounting plate
Operation and installation manual
AC connector
5. System
The solar inverter converts direct current from the solar cells into alternating current. This enables you to feed your self-produced solar energy into the public grid.
Thanks to efcient MPP tracking, maximum capacity utilization of the solar energy plant
is ensured even in the case of cloudy sky conditions.
The string concept means that PV modules are always connected in series (in a string) and/or that strings with the same voltage are connected in parallel to the solar inverter
with the aim of signicantly reducing the photovoltaic system’s cabling requirements.
Page 10
8
Operation and installation manual SOLIVIA 2.5 AP G3 TR
The fact that the modules are connected in strings also means that the photovoltaic
system can be perfectly matched to the solar inverter’s input voltage range.
5.1 Data evaluation and communication
The integrated data display, processing and communication of the device enables easy operation of the solar inverter. Monitoring of the operational status and signaling of operational failures are capable of being called up over the device display. The data interface enables the downloading of data which can be evaluated with a PC system and guarantees continuous recording of operating data.
The best way of accessing this functionality is via the available accessories; compre­hensive and seamless solar inverter monitoring is ensured.
The data read-out over the integrated interface and the display is possible only in solar operation.
5.2 Technical structure of the solar inverter
A galvanical isolation of the solar inverter from the grid is achieved through a DC/AC converter with an integrated high-frequency transformer. The photovoltaic voltage is adjusted so that the maximum power output of the PV modules is also achieved with varying solar irradiation levels and temperatures (MPP-Tracking).
The MPP range of the solar inverter is between 150 V and 450 V. This facilitates the use of PV modules by a variety of manufacturers. Measures must be taken to ensure that the maximum open-circuit voltage of 540 VDC is never exceeded. Please note that the maximum open-circuit voltage will occur at the lowest temperatures anticipated. You
will nd more detailed information about temperature dependency in the data sheet of the PV modules. The device’s power consumption is kept to a minimum.
The high-quality aluminum casing corresponds to protection class IP65 (water-jet-proof
and dust-proof) and is protected against weathering processes by surface renement. The cooling characteristic prole is designed so that operation of the inverter is possible
with ambient temperatures from -25°C to +70°C.
A cooling characteristic prole is used for the removal of the power dissipation caused
through the voltage conversion. An internal temperature control protects the device against excessive temperatures in the interior of the solar inverter. In case of high ambi­ent temperatures, the maximum transferable power is limited.
The solar inverter is controlled by microcontrollers, which also implement interface com­munication and the monitoring of values and messages on the display.
Two independent and redundant microcontrollers control the monitoring of the grid, which is consistent with the feed-in directives of your local utility company. This enables an installation of the solar inverter in the in-house electrical grid.
Operator protection requirements are met by electrically isolating the grid from the PV module. The electrical isolation between the grid and the PV module is equivalent to basic insulation. Maximum operator protection is ensured by reinforced isolation
Page 11
EN
9
Operation and installation manual SOLIVIA 2.5 AP G3 TR
between the grid, PV modules and accessible interfaces (display, RS485 interface). Relevant standards concerning electromagnetic compatibility (EMC) and safety are
fullled.
The solar inverter is functional in on-grid operation exclusively. An automated isolation
point, which is approved by a certication agency, guarantees secure disconnection in
case of circuit isolation or interruptions in power supply and avoids isolated operation.
The disconnection equipment allows for automatic isolation for in-plant generation sys-
tems of nominal power ≤ 4.6 kVA, with single-phase parallel feed-in through the solar
inverter into the grid.
5.3 Equipment overview
1. Connections for PV modules
2. Grid connection
3. Interface connection RS485 (EIA485)
4. Display for status messages and keypad for operation
5. Light-emitting diodes for operational status display
(3)(2)(1)
(4)
(5)
Page 12
10
Operation and installation manual SOLIVIA 2.5 AP G3 TR
6. Installation
Installation and commissioning must only be carried out by qualied electrical experts.
The recommended local and national safety regulations should be complied with.
To carry out an energy measurement, a meter must be attached between the grid feed­in point and the solar inverter (in accordance with all local and national safety regula­tions).
By means of the integrated anti-islanding protection, the function of the recommended section switch is fullled in accordance with all local and national safety regulations.
For details, please see „10. Technical data“, page 34.
Caution: The secondary short-circuit current rating is increased at the transfer connec­tion point to the public electricity supply system by the nominal current of the connected solar inverter.
7. Installation of equipment
7.1 Installation location
Install the device on a non-ammable support base.
Avoid installation on resonating bodies (light construction walls etc.).
Installation is possible both indoors and in protected outdoor areas.
An increased ambient temperature can reduce the efciency of the PV system.
The inverter may produce moderate noise during operation. Please select installa-
tion location with care.
Ensure legibility of the LEDs and the display (check read-off angle and installation
height).
Although the unit is tted with UV resistant components, direct exposure to sunlight
should be avoided.
Despite having an IP65 enclosure and being certied in accordance with soiling
category III, the unit must not be allowed to become heavily soiled.
Dusty conditions can impair the unit’s performance.
NOTE
According to the Australian / New Zealand Standard AS/NZS 5033:2005 (§ 3.1), PV arrays for installation on domestic dwellings in Australia or New Zealand shall not have maximum voltages greater than 600 V.
Page 13
EN
11
Operation and installation manual SOLIVIA 2.5 AP G3 TR
7.2 Minimum requirements
Free convection around the solar inverter must not be impaired.
For proper air circulation to dissipate heat, allow a clearance of approx. 10 cm to the side and approx. 50 cm above and below the unit.
The grid impedance requirement at the supply terminal is to be observed (cable length, cable cross-section).
The recommended installation position is to be adhered to (vertical).
Unused DC connectors and interfaces must be sealed airtight with sealing plugs to ensure protection class IP65 for the whole system (inverter & cables).
50 cm
10 cm
50 cm
10 cm
Wall
Wall
7.3 Maintenance
Make sure that the device remains uncovered while in operation. To avoid the casing of the solar inverter becoming soiled, it should be cleaned periodically.
User serviceable parts are not contained in the device. Under no circumstances should
the solar inverter be opened!
7.4 Installation
You should utilize the delivered mounting plate for problem-free installation of the solar inverter. Installation to the wall should be implemented with the proper screws. Mount the wall bracket so that the solar inverter only has to be simply attached. After that, the device is to be bolted on securely.
Assembly instructions
1. Mount the mounting plate with appropriate screws (max. Ø 6mm) into at least four
of the eight holes to x the wall bracket in place. You can employ the mounting
plate as a template for marking the positions of the boreholes.
2. As the solar inverter weighs 21.5 kg, it should be lifted out of the transport crate by at least two persons.
Page 14
12
Operation and installation manual SOLIVIA 2.5 AP G3 TR
3. Place the solar inverter onto the mounting plate with at least two persons.
4. Fasten the supplied mounting nuts and washers on the threaded bolt intended for securing the device.
5. Check that the solar inverter is securely sealed.
319.5
150
320
200
6.5
12
Ø
12.5
90
38
12
410 ± 0.5
7.5 Ambient temperature
The solar inverter can be operated in an ambient temperature between -25°C to +70°C.
The device should be installed in a well-ventilated, cool and dry location.
7.6 Grid connection
The grid (AC output) is connected over a Wieland RST25i3S AC connector. You can
nd the correct allocation on the screw-type terminal connection of the connector. The
solar inverter must be connected to the grid over a three-core line (L, N, PE). The con­nected AC line must be switched potential-free before the disconnection or the insertion of the AC connector.
The connection to the Wieland AC connector must be made with a exible line and a
conductor cross section of min. 2.5 mm² to max. 4.0 mm².
An automatic circuit breaker is to be provided in the line L upstream of every device, with a nominal current of 25 A and tripping characteristic type B or C (please refer to
Mounting plate
Locking screw
Locking screw
Page 15
EN
13
Operation and installation manual SOLIVIA 2.5 AP G3 TR
your local country installation requirements and regulations for correct tripping char­acteristic type). In addition, attention is to be paid to the selectivity of the fuse unit attached upstream of the automatic circuit breaker.
The solar inverter must be grounded via the AC connector’s PE conductor. To do this,
connect the PE conductor to the designated terminal. If you wish to integrate more than one inverter into the installation, please proceed as illustrated in the drawings in the appendix.
Please note the cable length and the cable cross-section, due to the risk of undesirable temperature rise and power losses.
The AC connector is protected from unintentional disconnection by a clip mechanism which can be released with a screwdriver.
7.7 Connection of PV modules
Before the photovoltaic system is connected, the polarity of the PV voltage at the Multi­Contact connectors must be checked to ensure that it is correct.
The connection of the PV module is implemented using Multi-Contact MC4 connectors, where the DC negative pole is located on the connector upper row and the DC positive pole on the connector lower row. The connectors are coded to prevent you from acci­dentally plugging them into the wrong terminal.
Please ensure the following at all times:
That there is never any risk of anyone coming into contact with the solar inverter connection terminals, due to the risk of dangerous voltages across them.
That under no circumstances are the PV modules to be disconnected from the
solar inverter under load. If a disconnection should be necessary, rst switch the
grid off so that the solar inverter cannot absorb any further power. Next, open the upstream DC disconnector.
The maximum input voltage of the solar inverter is 540 V. The maximum current load of each individual Multi-Contact MC4 connector is 18 A.
The solar inverter has an insulation and grounding monitoring on the DC side. The
options can be congured in the Setup menu “S -> Solar ISO / GND” (see „8.3.7.1 Sub-
menu S: Solar ISO / GND“, page 29).
The insulation monitoring has two modes:
ISO-ON-Error (the solar inverter is disconnected from the grid in the event of an insulation fault)
ISO-ON-Warning (the solar inverter indicates the fault but is not disconnected from the grid).
Deltas solar inverters are factory-set to ISO-ON-Warning mode on delivery.
The grounding monitoring has two modes:
PV+ grounding (grounding monitoring of the positive pole of the PV generator)
Page 16
14
Operation and installation manual SOLIVIA 2.5 AP G3 TR
PV- grounding (grounding monitoring of the negative pole of the PV generator).
In these modes the solar inverter remains in feed-in operation and will not be discon-
nected from the grid in case of a fault. The error message “PV+ grounding fault” or “PV­grounding fault” will appear on the display.
If you need to connect the positive or negative pole of the PV system to meet require­ments set out by the module manufacturer, you can do this. Earth continuity must be implemented close to the inverter. We suggest using Deltas grounding kit “Grounding
Set A Solar” (EOE99000275). The grounding connection is monitored and should be congured in the Setup menu (see „8.3.7 Submenu S (Setup)“, page 28).
Alternatively, it is possible to turn off the insulation- and grounding monitoring:
ISO / GND OFF.
Required cable coupler types for DC cable connection to inverter:
CABLE COUPLER POLARITY
WIRE SIZE
2.5 MM
2
(AWG 14)
WIRE SIZE
4.0 MM2 -
6.0 MM² (AWG 12-10)
FEMALE CABLE COUPLER
MALE CABLE COUPLER
MULTI-CONTACT ORDER NUMBER
Plus coupler
32.0010P0001-UR
32.0012P0001-UR
Minus coupler
32.0011P0001-UR
32.0013P0001-UR
Plus coupler
32.0014P0001-UR
32.0016P0001-UR
Minus coupler
32.0015P0001-UR
32.0017P0001-UR
7.7.1 Output power over PV voltage
150 VDC
200 VDC 250 VDC
300 VDC
350 VDC 400 VDC 450 VDC
2500 W
2700 W
2900 W
3100 W
3300 W
3500 W
3700 W
Page 17
EN
15
Operation and installation manual SOLIVIA 2.5 AP G3 TR
7.7.2 Output power over AC voltage
2500 W
2700 W
2900 W
3100 W
3300 W
3500 W
3700 W
190 VAC
210 VAC 230 VAC 250 VAC
270 VAC
7.7.3 Efciency
The best efciency of the solar inverter is obtained at input voltages >250 V.
84 %
86 %
88 %
90 %
92 %
94 %
96 %
0 W
400 W
800 W
1200 W
1600 W
2000 W
2400 W
2500 W @ 150 V
2500 W @ 250 V
2500 W @ 350 V
2500 W @ 450 V
Page 18
16
Operation and installation manual SOLIVIA 2.5 AP G3 TR
7.8 Interface connection RS485 (EIA485)
The interfaces not used must always be closed off. In case of utilization of an interface,
only the counterpart tting on the interface connector is to be employed.
Mating connector supplier HARTING Deutschland GmbH & Co. KG (P.O. 2451, 32381 Minden; Germany; www.harting.com).
Order designation:
09 45 145 1510, Cable Manager Blue IP67 Push-Pull Data Plug
09 45 145 1500, Cable Manager White IP67 Push-Pull Data Plug
-
~
-
~
-
~
-
~
230 V - House connection line
RS485 (EIA485) - Connection
Datalogger
RS485 (EIA485) terminating resistor
8
1
Pin
1 Reserved 2 Reserved 3 Reserved 4 GND (RS485) 5 Reserved 6 RX_B (RS485) 7 TX_A (RS485) 8 Reserved
Top View
Connector pin assignment RS485 (EIA485)
Page 19
EN
17
Operation and installation manual SOLIVIA 2.5 AP G3 TR
+5V
Reserved
Reserved
0R
0R
TX_A
RX_B
GND
Pin 7
Pin 6
100 ... 150 Ohm, 0,25W
When several devices are connected in series and the total length of the data line measures 2 m or more, the following option is available for terminating the RS485 (EIA485) interface:
Power controller
Operating- and system control
MPP­Tracker
-
-
Booster
-
-
Isolation
DC-Bus
­~
Solar inverter
DC
DC
DC
DC
String A
String B
String C
String D
AC
Public grid
Anti-islanding protection
Communication
Page 20
18
Operation and installation manual SOLIVIA 2.5 AP G3 TR
7.9 Electrical connection and operational start-up
The electrical connection is utilized on this solar inverter using the connector contacts which are attached to the casing. In no case must the device be opened!
In order to connect the device electrically, the following procedures must be followed:
1. DC connection: First, connect the PV module strings to the DC disconnector (not included in the scope of delivery).
2. Connect the DC disconnector to the solar inverter (ensure correct polarity).
3. AC connection: Please install the Wieland AC mating connector to the AC output cable and then put the AC connector to the solar inverter. Please make sure, that
the sleeve nut is properly xed and tighten.
4. Before switching on the power, check all feeders and connections one last time.
5. Close the DC disconnector.
6. Close the circuit breaker on the AC output side.
7. In case of sufcient PV voltage (UPV > 150 V), the device now goes into the start- up mode.
8. In case of a new installation the time and date have to be set in sub-menu S (Setup) (see „8.3.7 Submenu S (Setup)“, page 28).
NOTE
To ensure protection conforming to IP65 all unused connections and interfaces must be closed using the provided sealing plugs.
Page 21
EN
19
Operation and installation manual SOLIVIA 2.5 AP G3 TR
7.10 Setup / settings
The default display language for solar inverters leaving the Delta factory is set to Eng­lish.
After connecting to correct DC voltage and running through self-test, you will be asked to specify the network ID and to select the desired country (see „8.3.7.2 Submenu S:
Country settings“, page 30) (countries available: India, Australia, Australia PL
1)
).
The selection has to be conrmed another time by the user. Once conrmed, the net­work ID and the country selection are stored to the controller memory – and the solar inverter is ready for operation.
NOTE
Please note that the enter keys on the display are locked, if there is no input entry within 5 minutes. The following display message appears:
“Block selection”. To unlock the enter keys, you need to switch off the
DC voltage and then switch it on again (see „9.2 Display messages“,
page 32).
1) In certain states in Australia, power limitation is required.
With power limitation, the output (AC) power of SOLIVIA 2.5 AP G3 TR will be as followed :
Power limitation setting AU PL -> Max. power: 2490 W
To activate power limitation, please select dedicated country “Australia PL“ (Installed settings are password protected):
Select unit ID = [1] & press <ENTER> key
Select country = [Australia PL] & press <ENTER> key
Conrm country selection by pressing <ENTER> key
One of the following labels that are enclosed in the box of the inverter MUST be sticked next to the model label:
at maximal output power of: 2.49kW
For Australia PL This product has been power limited
To check if power limitation has been activated, please go to the menu S (Setup) and press the „UP“ or „DOWN“ buttons to
nd the following display message:
S -> Country Set
AU L
Down
Up
AUstralia Limitation
Page 22
20
Operation and installation manual SOLIVIA 2.5 AP G3 TR
Country selection
Increase network ID Decrease network ID
Down *
Up *
Enter network ID
ENTER *
ESC *
Select country
Next country Country before
Down *
Up *
ENTER *
Normal mode
* Timeout if no key is pressed (within 5 minutes)
NOTE
Please note, that once the country has been selected and conrmed,
it is only possible to change the country by following the steps as listed below:
1. Please click ESC + for few seconds to get the key information.
2. Provide the key code to the Solar Support Team at
support.australia@solar-inverter.com or support.india@solar­inverter.com to get the PIN code (valid for one use only!).
3. Once you get the PIN code, you need to press ESC + .
4. Then, you will be asked to insert the PIN code and to conrm it twice.
5. After conrmation, you will then be able to select the desired country.
NOTE
These steps must be executed without interruption. Otherwise, you will stay in the country selection mode.
Page 23
EN
21
Operation and installation manual SOLIVIA 2.5 AP G3 TR
7.11 LED operation and fault display
Three light-emitting diodes (LEDs), which display the operational state of the solar inverter, are attached on the front:
Operation (A)
Earth Fault (B)
Failure (C)
LED (A), green: „Operation“ displays the operational state.
LED (B), red: „Earth Fault“ displays an insulation resistance fault or PV grounding (GND) fault on the DC side.
LED (C), yellow: „Failure“ displays existing faults internally or externally and whether the grid feed-in operation has been inter­rupted.
LED STATUS OPERATIONAL STATE EXPLANATION
green: <off> red: <off> yellow: <off>
Night disconnection.
The input voltage (UPV) is lower than
100 V. The solar inverter is not feeding power to the grid.
green: <on> red: <on> yellow: <on>
Initialization
Input voltages: UPV: 100 V to 150 V (self
test ongoing).
green: <ashes> red: <off> yellow: <off>
Input- and grid monitoring. Starting conditions are tested.
green: <on> red: <off> yellow: <off>
Feed-in operation.
Normal operational state: UPV: 150 V to
450 V.
green: <off> red: <on/off> yellow: <on/off>
Equipment fault.
Internal or external fault (interrupted feed). See also „9.2 Display messages“,
page 32.
green: <off> red: <on/off> yellow: <on>
General error condition.
Solar inverter is not connected to the grid. No power is delivered. See also „9.2 Display
messages“, page 32.
green: <on/off> red: <on/off> yellow: <ashes>
Warning message.
You can carry on using the solar inverter. See also „9.2 Display messages“,
page 32.
8. Operating concept
8.1 The display
The display on the device indicates varied information. The enter keys are used for the adjustment of the device and for the retrieval of information. The indicated data can deviate with a tolerance of up to 5 %.
Page 24
22
Operation and installation manual SOLIVIA 2.5 AP G3 TR
ESC
(A) (B) (C) (D)
Key (A), ESC: To switch from the menu items to the main menu and to exit each sub-menu.
Key (B) and (C): For scrolling in the individ- ual menu items and/or carrying out adjust­ments in the setup menu.
Key (D), ENTER: ENTER key for changing into the menu levels and for input acknow­ledgement in the setup menu.
8.2 Navigation in the display
Lighting of the display
After pressing the ENTER key in automatic operation, the display lighting is switched on. If no key is pressed within 30 seconds, the display lighting automatically goes out. The setup menu enables selection between continuous or automatic lighting. Through pressing the ENTER key, the display lighting is switched on again.
8.3 Main menu
The main menu consists of 7 menu items which are subdivided into submenus:
Menu N (Now)
Menu D (Day)
Menu W (Week)
Menu M (Month)
Menu Y (Year)
Menu T (Total)
Menu S (Setup)
Handling of the menu items:
You can scroll the main menu by activating the selector keys
.
Press the ENTER key to select the submenus. In order to exit the menus again, acti­vate the ESC key.
Page 25
EN
23
Operation and installation manual SOLIVIA 2.5 AP G3 TR
User menu
Menu N - Now (act data)
Menu D - Day statistic
Menu W - Week statistic
Menu M - Month statistic
Menu Y - Year statistic
Menu T - Total statistic
Menu S - Setup inverter
Down
Down
Down
Down
Down
Down
Up
Up
Up
Up
Up
Up
Down to 2
1
Up to 1
2
Submenu N - Now
Submenu D - Day
Submenu W - Week
Submenu M - Month
Submenu Y - Year
Submenu T - Total
Submenu S - Setup
ESC
ESC
ESC
ESC
ESC
ESC
ESC
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
Remarks:
ESC in main menu jumps to first entry of corresponding sub menu
Page 26
24
Operation and installation manual SOLIVIA 2.5 AP G3 TR
8.3.1 Submenu N (Now)
This menu item displays the active values.
Main menu N - Now actual data
N -> AC-Power Value (W)
N -> AC-Voltage Value (V)
N -> AC-Current Value (A)
N -> AC-Frequency Value (Hz)
N -> PV-Voltage Value (V)
N -> PV-Current Value (A)
N -> Time (HH:MM:SS)
N -> Date (WD.DD.MM.YYYY)
Down
Down
Down
Down
Down
Down
Down
Up
Up
Up
Up
Up
Up
Up
Down to 2
1
Up to 1
2
Submenu N - Now
ESC
ESC
ESC
ESC
ESC
ESC
ESC
Remarks:
ESC in main menu N jumps to first entry of sub menu N
ESC
ENTER
Display of the active output power
Display of the active output voltage
Display of the active output current
Display of the active mains frequency
Display of the active PV cell voltage
Display of the active PV cell current
Display of the current time
Display of current day of the week and date
Page 27
EN
25
Operation and installation manual SOLIVIA 2.5 AP G3 TR
8.3.2 Submenu D (Day)
This menu item displays the daily values for the grid feed.
Main menu D - Day statistic
D -> Energy Value (Wh)
D -> AC-Revenue Value (AUD)
D -> AC-Power-Max Value (W)
D -> AC-Volt-Max Value (V)
D -> AC-Volt-Min Value (V)
D -> AC-Curr-Max Value (A)
D -> AC-Freq.-Max Value (Hz)
D -> Runtime Value (Min)
Down
Down
Down
Down
Down
Down
Down
Up
Up
Up
Up
Up
Up
Up
Down to 2
1
Up to 1
2
Submenu D - Day
ESC
ESC
ESC
ESC
ESC
ESC
ESC
Remarks:
ESC in main menu D jumps to first entry of sub menu D
ESC
ENTER
D -> AC-Freq.-Min Value (Hz)
ESC
Down
Up
Display of the daily energy gain
Display of the daily revenue
Display of the daily maximum output power
Display of the daily max. output voltage
Display of the daily min. output voltage
Display of the daily maximum output current
Display of the daily maximum output frequency
Display of the daily minimum output frequency
Display of the daily operating time of the solar inverter
Page 28
26
Operation and installation manual SOLIVIA 2.5 AP G3 TR
8.3.3 Submenu W (Week)
This menu item displays the average values of the current week.
Main menu W - Week statistic
W -> Energy Value (kWh)
W -> AC-Revenue Value (AUD)
W -> Runtime Value (h)
Down
Down
Up
Up
Down to 2
1
Up to 1
2
Submenu W - Week
ESC
ESC
Remarks:
ESC in main menu W jumps to first entry of sub menu W
ESC
ENTER
Display of the weekly energy gain
Display of the weekly revenue
Display of the weekly operating time of the solar inverter
8.3.4 Submenu M (Month)
This menu item displays the average values of the current month.
Main menu M - Month statistic
M -> Energy Value (kWh)
M -> AC-Revenue Value (AUD)
M -> Runtime Value (h)
Down
Down
Up
Up
Down to 2
1
Up to 1
2
Submenu M - Month
ESC
ESC
Remarks:
ESC in main menu M jumps to first entry of sub menu M
ESC
ENTER
Display of the monthly energy gain
Display of the monthly revenue
Display of the monthly operating time of the solar inverter
8.3.5 Submenu Y (Year)
This menu item displays the average values of the current year.
Main menu Y - Year statistic
Y -> Energy Value (kWh)
Y -> AC-Revenue Value (AUD)
Y -> Runtime Value (h)
Down
Down
Up
Up
Down to 2
1
Up to 1
2
Submenu Y - Year
ESC
ESC
Remarks:
ESC in main menu Y jumps to first entry of sub menu Y
ESC
ENTER
Display of the annual energy gain
Display of the annual revenue
Display of the annual operating time of the solar inverter
Page 29
EN
27
Operation and installation manual SOLIVIA 2.5 AP G3 TR
8.3.6 Submenu T (Total)
This menu item shows cumulated and maximum/minimum values since rst use.
Main menu T - Total statistic
T -> Energy Value (kWh)
T -> Revenue Value (AUD)
T -> PV-Vol. Max Value (V)
T -> PV-Cur. Max Value (A)
T -> PV-Pow. Max Value (W)
T -> Isolation Max Value (kOhm)
T -> Isolation Min Value (kOhm)
T -> Runtime Value (Min)
Down
Down
Down
Down
Down
Down
Down
Up
Up
Up
Up
Up
Up
Down to 2
1
Up to 1
2
Submenu T - Total
ESC
ESC
ESC
ESC
ESC
ESC
ESC
Remarks:
ESC in main menu T jumps to first entry of sub menu T
ESC
ENTER
Up
Display of the total energy gain
Display of the total revenue
Display of the max. PV cell voltage
Display of the max. PV cell current
Display of the max. PV cell power
Display of the largest insulation resistance
Display of the smallest insulation resistance
Display of the total operating time of the solar inverter
Page 30
28
Operation and installation manual SOLIVIA 2.5 AP G3 TR
8.3.7 Submenu S (Setup)
This menu item is used for changing the presettings of the solar inverter.
Main menu S - Setup
S -> LCD-Contrast 0 ... 9
S -> LCD-Backlight Auto / On
S -> Menu-Mode Now ... Setup
S -> Cash per kWh Value (AUD)
S -> ID-Number 001 ... 254
S -> Solar ISO / GND
S -> Baudrate 2400 ... 38400
Down
Down
Down
Down
Down
Down
Up
Up
Up
Up
Up
Down to 2
1
Up to 1
2
Submenu S - Setup
ESC
ESC
ESC
ESC
ESC
ESC
ESC
ENTER
Up
S -> Time (HH:MM:SS)
Down
ESC
Up
S -> Date (WD.DD.MM.YYYY)
Down
ESC
Up
S -> Firmware
Down
ESC
Up
Adjustment of the firmware
Adjustment of the brightness of the LCD display between 0 ... 9
Adjustment of the LCD background lighting
Selection of the start menu on restart of the device
Entry of feed-in remuneration in AUD per kWh
Input of the ID number of the solar inverter
Adjustment of the baud rate between 2400 ... 38400 Baud
Adjustment of the internal clock
Adjustment of current day of the week and date
ISO / GND Setup Menu
S -> Country settings Name of country
ESC
Down
Adjustment of the country parameters
Up
Page 31
EN
29
Operation and installation manual SOLIVIA 2.5 AP G3 TR
8.3.7.1 Submenu S: Solar ISO / GND
More detailed information on the Solar ISO / GND menu within the submenu S (Setup).
Submenu Setup Solar ISO / GND
S -> Solar ISO / GND ISO ON-Warning
S -> Solar ISO / GND ISO ON-Failure
S -> Solar ISO / GND ISO GND-OFF
S -> Solar ISO / GND PV+ grounded
S -> Solar ISO / GND PV- grounded
Down
Down
Down
Down
Up
Up
Up
Up
Down to 5
6
Up to 6
5
ESC
ESC
ESC
ESC
ESC
ENTER
Use old setting
ENTER
ENTER
ENTER
ENTER
ENTER
Use new value
Page 32
30
Operation and installation manual SOLIVIA 2.5 AP G3 TR
8.3.7.2 Submenu S: Country settings
More detailed information on the country settings menu within the submenu S (Setup).
Submenu Setup Country settings Name of country
S -> Country settings Critical undervoltage x(V) < x.xx(s)
S -> Country settings Undervoltage x(V) < x.xx(s)
S -> Country settings Overvoltage x(V) < xmin
S -> Country settings Critical overvoltage x(V) < x.xx(s)
S -> Country settings Low frequency xx.xx(Hz) < x.xx(s)
S -> Country settings High frequency x.xx(Hz) < x.xx(s)
S -> Country settings Islanding Active / Not active
Down
Down
Down
Down
Down
Down
Down
Up
Up
Up
Up
Up
Up
Up
Down to 5
6
Up to 6
5
ESC
ESC
ESC
ESC
ESC
ESC
ESC
ENTER
S -> Country settings DC injection x(mA) < x.xx(s)
ESC
Up
S -> Country settings Sync time x(s)
ESC
Down
Page 33
EN
31
Operation and installation manual SOLIVIA 2.5 AP G3 TR
8.3.7.3 Submenu S: Firmware
More detailed information on the rmware menu within the submenu S (Setup).
Submenu Setup Firmware
S -> Firmware
AC-Ctrl maj.min.bug
Down
Down
Down
Up
Up
Up
Down to 4
3
Up to 3
4
ESC
ESC
ESC
ESC
ENTER
S -> Firmware
DC-Ctrl maj.min.bug
S -> Firmware
SC-Ctrl maj.min.bug
S -> Firmware
Display-Ctrl maj.min.bug
9. Diagnostics and data evaluation
9.1 Malfunctionrectication
The solar inverter is provided with an automatic diagnostics system which indepen-
dently identies certain faults and which can make them visible on the display.
Troubleshooting in the eld
In principle, it is always worth attempting a reset by reinitializing the solar inverter whenever an error message appears on the display.
To reset the device, proceed as follows:
1. Isolate the solar inverter from the grid (open automatic circuit breaker).
2. Switch off the DC disconnector.
3. Wait: approx. 1 minute.
4. Switch DC disconnector back on.
5. Switch in grid (close automatic circuit breaker).
Page 34
32
Operation and installation manual SOLIVIA 2.5 AP G3 TR
(In the eld, the rst step is to scan for potential fault causes that could be picked up by
the solar inverter and result in tripping.)
Various key parameters can be scanned via the display, thereby enabling conclusions to be drawn about potential fault causes.
Current values in the N menu
AC Voltage -> Display of current output voltage -> Voltage limiting values
AC Frequency -> Display of current grid frequency -> Frequency limiting values
Solar Voltage -> Display of current PV cell voltage -> Switch-in threshold
9.2 Display messages
LED STATUS
DISPLAY MESSAGE
CAUSE ELIMINATION
green: <on> red: <on> yellow: <on>
Display communication faulty.
If the fault persists after the device has been reset, please inform your service technician.
green: <off> red: <off> yellow: <on>
AC frequency failure
Grid frequency overshoo­ting or undershooting
specied limit range.
Check the grid frequency via the display in the N menu.
green: <off> red: <off> yellow: <on>
AC voltage failure
Grid voltage overshooting
or undershooting specied
limit range.
Check the grid voltage via the display in the N menu. If no voltage present, check grid automatic circuit breaker.
green: <off> red: <off> yellow: <on>
AC relay failure
One of the anti-islanding protection output relays is faulty / defective.
The solar inverter is defective. Return the device.
green: <ashes> red: <off> yellow: <off>
Calibration ongoing
Check internal settings. Normal function before input mode.
green: <off> red: <off> yellow: <on>
DC injection failure
DC component of input­side alternating current is too high.
If the fault persists after the device has been reset, please inform your service technician.
green: <off> red: <off> yellow: <on>
Error # 301
Internal communication error or hardware fault.
If the fault persists after the device has been reset, please inform your service technician.
green: <off> red: <off> yellow: <on>
Error # 302
The device trips and reverts to grid input mode once the temperature has dropped.
Check the installation site (no direct sunlight, air circulation).
green: <off> red: <on> yellow: <off>
Error # 506 Error # 508
Isolation resistance fault on the DC side during start-up phase (# 508) or running phase (# 506).
Check the isolation resistance on the DC side of the PV modules.
green: <on> red: <on> yellow: <off>
Isolation start-up warning Isolation run­ning warning
Isolation resistance fault on the DC side during start-up phase or running phase.
You must check the isolation resistance on the DC side of the PV modules. Solar inverter is still feeding!
Page 35
EN
33
Operation and installation manual SOLIVIA 2.5 AP G3 TR
LED STATUS
DISPLAY MESSAGE
CAUSE ELIMINATION
green: <on> red: <on> yellow: <off>
PV+ groun­ding fault PV- groun­ding fault
Connection PV+ (PV-) to GND is interrupted or wrong pole is connected to GND.
Check that the GND connection has been made correctly and/or check the fuse in the grounding path. Change the fuse if necessary. The solar inverter remains in feed­in operation.
green: <off> red: <off> yellow: <on>
Revision error
Versions of hard- and soft­ware are not compatible.
If the fault persists after the device has been reset, please inform your service technician.
green: <on> red: <on> yellow: <on>
Self test ongoing
Initialization of solar inver­ter on start-up.
The rst time the solar inverter is
started up: Normal function with a PV cell vol­tage of between 100 V and 150 V.
green: <ashes> red: <off> yellow: <off>
PV power too low
Insufcient input power.
Insufcient insolation (dawn/twi-
light). Check the PV cell voltage via the display in the N menu.
green: <ashes> red: <off> yellow: <off>
PV voltage too low
PV generator voltage bet­ween 100 V and 150 V.
Insufcient insolation.
Check the PV cell voltage via the display in the N menu.
green: <ashes> red: <off> yellow: <off>
Synchronize to AC
Checks grid voltage and grid frequency for grid input mode.
Normal function before input mode.
green: <on> red: <off> yellow: <ashes>
Varistor warning
Internal varistor at the DC input is defective.
Although you can, in theory, carry on using the solar inverter, the varistors should be replaced at the earliest opportunity. This will involve returning the device.
green: <off> red: <off> yellow: <on>
Block selection
Enter keys on the display are locked, if there is no input entry within 5 minutes.
To unlock the enter keys, you need to switch off the DC voltage and then switch it on again.
NOTE
Please follow the instructions above before contacting your service technician!
z
Page 36
34
Operation and installation manual SOLIVIA 2.5 AP G3 TR
10. Technical data
INPUT (DC) AUSTRALIA INDIA
Max. recommended PV power
3100 W
P
Nominal power 2750 W
Voltage range 125 ... 540 V
Full power MPP range
150 ... 450 V
Nominal current 9.8 A
Max. current 18 A
OUTPUT (AC) AUSTRALIA INDIA
Max. power 2640 W
1), 2)
Nominal power 2500 W
2)
Voltage range 210 ... 264 V 184 ... 264.5 V
Max. current 11.9 A
Nominal current 10.9 A
Nominal frequency 50 Hz
Frequency range 48 ... 52 Hz 47.3 ... 52.7 Hz
Power factor > 0.99 @ nominal power
Total harmonic distortion (THD)
< 3 % @ nominal power
GENERAL SPECIFICATION
AUSTRALIA INDIA
Model name SOLIVIA 2.5 AP G3 TR
Part number Delta EOE45010272
Max. efficiency 96 %
Efficiency EU 94.8 %
Operating temperature
-25 ... +70 °C
Storage temperature
-25 ... +80 °C
Humidity 0 ... 98 %
Max. operating altitude
2000 m (above sea level)
1) The maximum AC power value indicates the power an inverter might be able to deliver. However, such a maximum AC power may not necessarily be achieved.
2) In certain states in Australia, power limitation is required. With power limitation, the output (AC) power of SOLIVIA 2.5 AP G3 TR will be as followed:
Power limitation setting AU PL -> Max. power 2490 W, Nominal power: 2350 W
Page 37
EN
35
Operation and installation manual SOLIVIA 2.5 AP G3 TR
MECHANICAL DESIGN
AUSTRALIA INDIA
Size (L x W x D) 410 x 410 x 180 mm
Weight 21.5 kg
Cooling Convection
AC connector Wieland RST25i3S
DC connector 4 pairs of Multi-Contact MC4
Communication interfaces
2 x RJ45 / RS485
Display 3 LEDs, 2-line LCD
STANDARDS / DIRECTIVES
AUSTRALIA INDIA
Protection degree IP65
Safety class I
Configurable trip parameters
Yes
Insulation monitoring
Yes
Overload behavior Current limitation; power limitation
Anti-islanding protection / Grid regulation
AS 4777.2; AS 4777.3; IEC 60255.5 VDE 0126-1-1
EMC
AS 4777.1; AS 4777.2; AS 4777.3; EN 61000-6-2; IEC / EN 61000-6-3
IEC / EN 61000-6-2; IEC / EN 61000-6-3
Safety
AS/NZS 60950; AS/NZS 3100; AS 4777.2; AS 4777.3
IEC 62103; EN 50178; IEC 62109-1, IEC 62109-2
Page 38
36
Operation and installation manual SOLIVIA 2.5 AP G3 TR
11. Appendix
11.1 Connection examples
House connection box
House connection line
Low-voltage network ~ 400 / 220 V Low-voltage network ~ 400 / 230 V
VNB
Customer
Owner boundary
Z (1)
Z (2)
Measurement unit
(1) Meter for power consumption (2) Meter for power feed-in with back stop in each case
Remark: A meter can also be employed which registers both energy directions separately
=
~
~ 400 / 220 V ~ 400 / 230 V
Consumer equipment of the customer
Photovoltaic generator with power inverter max. 4.6 kVA
Switching equipment
Electric circuit distributor
Anti-islanding protection with voltage and frequency monitoring, as well as network impedance measurement
Short-circuit protection Overload protection
Individual in-plant generation system in parallel operation without isolated operation possibility, single-phase feed with anti-islanding protection.
Page 39
EN
37
Operation and installation manual SOLIVIA 2.5 AP G3 TR
House connection box
House connection line
VNB
Customer
Owner boundary
Z (1)
Z (2)
Measurement unit
(1) Meter for power consumption (2) Meter for power feed-in with back stop in each case
Remark: A meter can also be employed which registers both energy directions separately.
(3) Meter for power take-off of the customer system
=
~
Consumer equipment of the customer
Photovoltaic generator with power inverter max. 4.6 kVA
Switching equipment
Electric circuit distributor
Anti-islanding protection with voltage and frequency monitoring, as well as network impedance measurement
Short-circuit protection Overload protection
Individual in-plant generation system in parallel operation without isolated operation possibility, single-phase feed with anti-islanding protection, separate feed.
Z (3)
Low-voltage network ~ 400 / 220 V Low-voltage network ~ 400 / 230 V
~ 400 / 220 V ~ 400 / 230 V
Page 40
38
Operation and installation manual SOLIVIA 2.5 AP G3 TR
11.2 Overview of connection diagrams
+
-
DC terminal strip
DC disconnector
-
~
3 3
Z
Meter for power feed-in
3
Z
3
3
3
Meter for power consumption
House connection box
Selective main line circuit breaker
House connection line
Consumer equipment
Automatic circuit breaker type B 25 A
+
-
PV generator
PV generator
+
-
Solivia 2.5
DC disconnector
-
~
Automatic circuit breaker type B 25 A
PV generator
DC disconnector
-
~
Automatic circuit breaker type B 25 A
PV generator
kWh
kWh
Customer
Meter for power feed-in
Meter for power consumption
Solivia 2.5 Solivia 2.5
Page 41
EN
39
Operation and installation manual SOLIVIA 2.5 AP G3 TR
DC disconnector
-
~
1
2
3
PV generator
-
~
-
~
L1 N PE
L2 N PE
L3 N PE
Fuse
L1
N
n
...
PE
L2 L3
Solivia 2.5
Page 42
40
Operation and installation manual SOLIVIA 2.5 AP G3 TR
12. Glossary
AC
Abbreviation for „Alternating Current“.
Anti-islanding protection
This is a unit for grid monitoring with assigned switching elements (anti-islanding pro­tection) and is an automatic isolation point for small power generation systems (to 30 kWp).
CE
With the CE identication code, the manufacturer conrms the conformity of the product with the valid EC Guideline and compliance with the signicant requirements stipulated
therein.
DC
Abbreviation for „Direct Current“.
EMC
The Electro-Magnetic Compatibility (EMC) concerns the technical and legal basics of
the mutual inuencing of electrical devices through electromagnetic elds caused by
them in electrical engineering.
Initialization
Under initialization (cf. English to initialize) is understood the part of the loading process
of a program, in which the storage space required for the execution (e.g. variable, code,
buffers ...) for the program is reserved and is lled with initial values.
Local utility company
By local utility company is meant a company which generates electrical energy and distributes it over the public grid.
MPP
The Maximum Power Point is the point of the current-voltage diagram of a PV cell at which the largest power can be tapped off, i.e. the point at which the product of current and voltage has its maximum value.
Page 43
EN
41
Operation and installation manual SOLIVIA 2.5 AP G3 TR
Nominal power
Nominal power is the maximum permissible continuous power output indicated by the
manufacturer for a device or a system. Usually the device is also optimized so that the efciency is at its maximum in case of operation with nominal power.
Nominal current
Nominal current is the absorbed current in case of electrical devices if the device is supplied with the nominal voltage and yields its nominal power.
PE
In electric systems and cables a protective earth conductor is frequently employed. This is also called grounding wire, protective grounding device, soil, grounding or PE (Eng­lish „protective earth“).
Photovoltaics (abbr.: PV)
The conversion of PV energy into electrical energy.
The name is composed of the component parts: Photos - the Greek word for light - and Volta - after Alessandro Volta, a pioneer in electrical research.
Potential isolation
No conductive connection between two component parts.
Power dissipation
Power dissipation is designated as the difference between absorbed power and power of a device or process yielded. Power dissipation is released mainly as heat.
PV cell
PV cells are large-surface photodiodes which convert light energy (generally sunlight) into electrical energy. This comes about by utilization of the photoelectric effect (photo­voltaics).
PV generator
System comprising a number of PV modules.
Page 44
42
PV module
Part of a PV generator; converts PV energy into electrical energy.
RJ45
Abbreviation for standardized eight-pole electrical connector connection. RJ stands for Registered Jack (standardized socket).
RS485 (EIA485)
Differential voltage interface on which the genuine signal is transmitted on one core and the negated (or negative) signal on the other core.
Separate grid system
Energy supply equipment which is completely independent of an interconnected grid.
Solar inverter
is an electrical device which converts DC direct voltage into AC voltage and/or direct current into alternating current.
String
Designates a group of electrical PV modules switched in series.
String solar inverter (solar inverter concept)
The PV generator is divided up into individual strings which feed into the grid over their own string solar inverters in each case. In this way, the installation is considerably facilitated and the gain decrease, which can arise from the installation or from different shading conditions of the PV modules, is considerably reduced.
TAB (2000)
The TAB 2000 are the technical regulations governing connection to the low-voltage grid operated by distribution system operators in Germany. These Technischen Anschlussbestimmungen or TAB for short have been in force since the year 2000. They
dene the requirements imposed by DSOs on the electrical systems operated by the
end customers of utility companies.
Page 45
43
13. Certicates
QUALSURE CONSULTANTS A division of Blulen Pty Ltd (ACN 090 692 354) Registered Office 18 Hood Street Rosedale Vic. 3847 CF3388/3-1
Supplier’s declaration of conformity
For compliance levels 1, 2 and 3 in Australia
As required by notices under:
section 182 of the Australian Radiocommunications Act 1992.
Instructions for completion
This completed form remains with the supplier as part of the documentation required for the compliance records. Do not return this form to the
ACMA.
Supplier’s details
Qualsure Consultants
(AGENT)
of
18 Hood Street Rosedale Vic.
ACMA supplier code number N136
Product details
Product description – brand name, type, model, lot, batch or serial number (if available)
Brand Name
Delta
Model Number
SOLIVIA2.5APG3
Description
Solar Inverter
Compliance with Radiocommunications (Electromagnetic Compatibility) Standard 2008
The above mentioned product complies with the requirements of the Radiocommunications (Electromagnetic Compatibility) Standard 2008. Evidence of compliance is demonstrated by test reports to the following applicable standards.
Applicable standards
Standard title, number and, if applicable, number of the test report
Standard Test Report Number
AS/NZS CISPR 11:2004 06KFS054/VDE 0126-1-1
Declaration
I hereby declare that the product mentioned above complies with the requirements of the Radiocommunications (Electromagnetic Compatibility) Standard 2008. All products supplied under this declaration will be identical to the product identified above.
Gordon Slimmon Director
30 Nov 10
Page 46
44
Page 47
Page 48
5012218310 10
SUPPORT - ASIA-PACIFIC
Delta Energy Systems (Australia) Pty. Ltd.
Unit 6, 25 Howleys Road
Notting Hill VIC3168 Australia Phone: +61 3 9543 3053 Fax: +61 3 9544 0606 Support Email: support.australia@solar-inverter.com
Delta Energy Systems (India) Pvt. Ltd.
Ozone Manay Tech Park
‘A’ Block, 3rd Floor, Survey No, 56/18 & 55/9
Hosur Road, Hongasandra Village Bangalore – 560068, Karnataka Phone: +9180 67164711 Phone: +9180 67164777
Support Email: support.india@solar-inverter.com
25 October 2012
www.solar-inverter.com
Loading...