Delta S31 User Manual

M4 EARTH
FIXING
CRS.
SPACERS (SUPPLIED LOOSE
WHEN APPLICABLE)
70 (2.75)
10 (0.39)
70 (2.75)
ELECTRICAL ENTRY
M4 EARTH
SPACERS (SUPPLIED LOOSE
70 (2.75)
BROWN
BLUE
BROWN
RED
BROWN
COM
NO
COM
NO
COM
NO
FRONT
SPDT
SPDT
NO
DIM A
50 (1.96)
50 (1.96)
100 (3.93)
FIXING CENTRES
M5 EAR TH
ELE CTR ICA L
MOUNT ING HO LE S
LID LO CK ING SET SCR EW (M 4)
SPA CE RS (SU PPL IED LOO SE
65 (2.5 5)
195 (7 .67 )
180 (7 .08 )
205 (8 .07 )
DC, DD ,
EA
PR OC ES S
FIG 7
52 (2 .04)
73 (2.87)
108 (4.25)
FIG 9
64 (2.51)
42 (1.65)
95 (3.74)
To remove lid on enclosures H, R, T, U & B
rotate lid locking mechanism and where lid is
tight use a flat bar (see below) or edge of a ring
GENERAL
The unit is manufactured, checked and supplied in accordance with our published specification, and when installed and used in normal or prescribed applications, with the lid in place and within the parameters set for mechanical and electrical performance, will not cause danger or hazard to life or limb.
HEALTH AND SAFETY AT WORK ACT 1974 WARNINGS
1. THE USERS ATTENTION IS DRAWN TO THE FACT THAT, WHEN THE UNIT IS ‘LIVE’ WITH RESPECT TO ELECTRICAL OR PRESSURE SUPPLIES, A HAZARD MAY EXIST IF THE UNIT IS OPENED OR DISMANTLED.
2. UNITS MUST BE SELECTED AND INSTALLED BY SUITABLY TRAINED AND QUALIFIED PERSONNEL IN ACCORDANCE WITH APPROPRIATE CODES OF PRACTICE SO THAT THE POSSIBILITY OF FAILURE RESULTING IN INJURY OR DAMAGE CAUSED BY MISUSE OR MISAPPLICATION IS AVOIDED.
OPERATING PRINCIPLES A diaphragm is used to sense the difference between two pressures applied to either side of the diaphragm. The force is opposed by a control spring, which, at the point of equilibrium permits movement of an operating rod that actuates a switch or switches.
INSTALLATION
The instruments are designed to be mounted to a wall or panel vertically as shown in figs 4, 5, 6, 7, 8, 9 using the backplates provided. However, mounting up to 45° from the vertical in any plane is acceptable, although a small calibration shift may occur. Select the mounting point so as to avoid excessive shock, vibration or temperature fluctuation. Instruments should be mounted to avoid excessive heat transfer from the process lines or adjacent plant. To avoid undue stresses being imparted to the instrument when wall / panel mounted, it is recommended that a short length of flexible line be installed between the instrument and process line.
If sudden changes of pressure (pulsations) are likely then we recommend that snubbers are fitted between the process line and switch.
Use a spanner to support the process connection when fitting the instrument. DO NOT OVER­TIGHTEN. When fitting the instrument lid, make sure gaskets or ‘O’ rings are in good condition and fitted correctly.
WARNING: CHECK THE CONNECTION THREAD SIZE AND SPECIFICATION ON THE UNIT TO AVOID MIS-MATCHING WITH THE PROCESS CONNECTION ADAPTOR. SEE DIGIT 11 OF PRODUCT CODE.
SET POINT ADJUSTER
FIG 2
SPDT
REAR FRONT
2 x SPDT
NC = NORMALLY CLOSED COM = COMMON NO = NORMALLY OPEN
NC
RED
NC = NORMALLY CLOSED
COM = COMMON
NO = NORMALLY OPEN
MA
SET POINT LOCK
NC
REAR
SWITCH
RED
2 x
SWITCH
EARTH / GROUND
NC
BLUE
FIG 1A
BLUE
FIG 1B
INSTALLATION, OPERATING AND
MAINTENANCE INSTRUCTIONS FOR
DIAPHRAGM ACTUATED SERIES
S30 SOVEREIGN PRESSURE DIFFERENCE
SWITCHES (MODELS S31 & S34)
ISSUE F 02/10
PRODUCT CODE
ENCLOSURE
MODEL
CERTIFIED ENCLOSURES
All series S30 pressure switches can be supplied with enclosures for use in hazardous areas to the following standards:
Zone 1 (Div 1) IEC 79-1
BS 5501: Parts 1 and 5: EN50 014 and EN50 018 CENELEC. Codes ‘H’ for aluminium EEx d IIC T6, and ‘R’ for stainless steel EExd IIC T6.
DIV 1 (NEC 500)
Class I Groups C and D, Class II Groups E, F and G. Codes ‘T’ for aluminium and ‘U’ for stainless steel.
The above-mentioned enclosures are suitable for outdoor use rated IP 66 / NEMA 4. Only operation, maintenance or repair procedures either contained herein or approved by Delta Controls may be used, to avoid rendering the equipment unsafe in operation and / or nullifying the Certification. NO MODIFICATIONS ARE PERMITTED.
Japanese Zone 1.
Same as CENELEC Zone 1 IEC 79 with additional label and alternative terminal arrangement. Code ‘B’ for aluminium IIC T6. Refer to appropriate Japanese standards for guidance on installation and use.
Electrical Adaptors
Use only certified adaptors for Zone 1/Div 1. WARNING: IT IS A REQUIREMENT OF SAFETY
THAT AT LEAST 5 FULL THREADS ARE ENGAGED BETWEEN THE ADAPTOR AND CONDUIT ENTRY.
References for Selection and Installation
BS 5345 Part 3 for Enclosure Codes H and R. BS 5501 Part 1 for Enclosure Codes H and R. BS 5490 IEC 529 IP RATING (Ingress Protection) NEC ARTICLE 500 for Enclosure Code T and U.
MAINTENANCE
Inspections should be carried out at quarterly to yearly intervals depending upon operating conditions. Isolate the unit from process and power and remove the lid. Check all terminals for tightness. Check that
ELECTRICAL ENTRY
MATERIAL OF WETTED PARTS
RANGE
SWITCHING OPTIONS
PROCESS CONNECTION
OPTIONS AND TREATMENTS SPECIAL ENGINEERING
WIRING Fig 1A Enclosures H, R, T, U, B WIRING Fig 1B Enclosures A, W
Wire in accordance with local and National codes. Use cables no larger than 2.5 mm2 (14 AWG). Deliver electrical connection through a suitable cable gland, which will maintain the IP rating of the instrument. Insert bare wires fully into the terminal block and tighten securely. Keep wiring tails to a minimum and check that wires do not interfere with the operating mechanism. Use the earthing points provided.
SET POINT LOCK
FIG 3
ELECTRICAL ENTRY
MODEL S31/S34
RANGE
DIM A
BD, CB, CE
115 (4.52) 57 (2.24)
DC, DD, EA
103 (4.05)
spanner to open.
11 (0.43)
25 (1)
5.5 (0.21)R
In the interest of development and improvement Delta Controls Ltd, reserve the right to amend without notice,
details contained in this publication. No legal liability will be accepted by Delta Controls Ltd, for any errors,
DELTA CONTROLS LIMITED, ISLAND FARM AVENUE, WEST MOLESEY, SURREY KT8 2UZ
T +44 (0) 208 939 3511 F +44 (0) 208 783 1163 E sales@delta-controls.com W www.delta-controls.com
MIN
MAX
174 (6.85) 154 (6.06)
FIXING CE NTRES
DIM B
45 (1.77)
YOUR TRUSTED PARTNER IN PROCESS INSTRUMENTATION
EARTH / GROUND
COM
COM
IN
SET POINT ADJUSTER
DIM A
DIM B
SCREW
W ENCLOSURE
DIMENSIO NS FOR G UIDANCE ONLY mm (i nches)
MIN.
350 (13.8)
Fig. 4A
FIG 4
omissions or amendments.
cable tails are not fouled or chafed. Check for internal condensation. Rectify as necessary. It is recommended that instruments used to provide an alarm are operated periodically to ensure they are functioning correctly. If further maintenance is required seek advice from DELTA CONTROLS before attempting repair or replacement of parts.
CAUTION
Moving parts have been treated with a water repelling lubricant before leaving the factory. Occasional inspection and the application of a water repelling lubricant is recommended to ensure moving parts remain free under all conditions.
WARNING: DOES NOT APPLY TO OXYGEN SERVICE.
On enclosures H, R, T, U and B, remove the lid using an appropriate tool. If tight use edge of a spanner or a metal rod (fig 4A).
RANGE
BD, CB, CE
DC, DD, EA
RANGE
BD, CB, CE
DC, DD, EA
FIXING C ENTR ES
MODEL S3 1/S 34
DIM A
115 (4.52) 57 (2.24)
103 (4.05)
140 (5.51)
100 (3.93)
FIXING CENTRES
MODEL S31/ S34
DIM A
149 (5.86)
136 (5.35) 67 (2.63)
174 (6.85) 154 (6.06)
SCREW
DIM B
45 (1.77)
DIME NSIO NS FO R GUI DAN CE ONL Y m m (in che s)
ROT AT E TO R EM OVE
ENT RY
8 mm D IA
LO OSE N TO R EMO VE LID
DIM B
80 (3.14)
H, R, T, U ENCLO SURE
DIM EN SI ON S F OR G UIDA NC E ON LY
DIM A
WH EN APPLICABLE)
A ENCLOSURE
FAC ILIT Y
WH EN APP LIC AB LE)
mm (inch es )
DIM B
DIM B
FIG 5
FIG 6
Registered Office Registered in England No 5369683
Zone 1 Enclosure (H, R, T, U, B)
Thread seal and contact surfaces must be lightly lubricated using a non-setting non-corrosive grease compatible with the lid seal. Do not use copper bearing grease. Screw on lid hand tight making sure that mating surfaces of the lid and enclosure are in contact. Re-tighten the lid lock screw.
WARNING: IT IS A SAFETY REQUIREMENT THAT AT LEAST 5 FULL THREADS ARE ENGAGED WHEN THE UNIT IS IN OPERATION. NEVER OPERATE THE UNIT UNLESS THIS CONDITION IS MET. DO NOT USE GREASES OR LUBRICANTS NOT COMPATIBLE WITH THE ENVIRONMENT OR PROCESS.
Weather-proof Enclosure (W)
If lid gasket is dried out or damaged, replace with new greased gasket. Make sure gasket aligns correctly with sealing faces.
Stainless Steel Weather-proof Enclosure (A) Check gasket. If damaged, replace.
OPERATION
Pressure difference switches are supplied calibrated against falling pressure unless otherwise specified. Set Point adjustment refers to falling pressure. Switching differential is the difference between the set point and the operating value on rising pressure. For opening details see Figs 4, 5, 6.
Set Point Adjustment: Models S31, S34 (Figs 2, 3)
1. Isolate the instrument from process and power.
2. Remove the instrument lid.
3. Slacken the set point lock screw.
4. Rotate the set point adjuster screw as required. Rotate clockwise to increase the set point and counter­clockwise to decrease the set point.
5. Tighten the set point lock screw.
6. Replace the instrument lid (see maintenance). Note: For accurate setting, a suitable pressure gauge
must be used in conjunction with the above procedure. Do not attempt to set the switch outside the scale limits. Though the unit may be set anywhere within its operation range, for optimum performance, it is good practice to have a set point value between 25% and 75% of span.
LP
MO D EL S 31
RAN GE
BD , CB , CE
LP
51 (2)
MOD EL S3 4
RANGE
BD, CB , CE
DC, DD , EA
LP
FIX ING CE N TRE S
FIXIN G C EN TRE S
MOD E L S31
HP
7 (0 .27 )
75 (2.9 5)
DIA A DIM B
DIM A
113 (4 .44 )
88 (3.4 6)
DIM EN SI ON S F OR G UID A NC E O NL Y m m (i nc hes )
179 (7 .04 )
154 (6 .06 )
170 (6 .69 )
DIM B
COD E H CO DE J
COD E H COD E J
CON NE C TIO N
COD E A & F
COD E A & F
MODE L S34
HP
7 (0.27)
75 (2.95 )
DIA A
DIM B
DIM A
126 ( 4.96)
100 ( 3.93)
DIME NS ION S FO R G UID AN CE ONL Y m m (inch es)
MODEL S31 RANGE BC
7 (0.27)
75 (2.95)
PRO CESS CON NEC TIO N
DIM B
192 ( 7.55)
CODE A & F
CODE H
218 (8. 58) 208 (8. 18)
CODE J
CODE A & F
166 (6. 35)
CODE H
192 (7. 55)
CODE J
182 (7. 16)
HP
PROCESS CONNECTION
DIMENSIONS FOR GUIDANCE ONLY mm (inches)
DIM C
52 (2.0 4)
DIM C
63 (2 .48)
166 (6.53)
DIM D
DIM D
126 (4.96)
103 (4.05)
DIM C
DIM D
121 (4 .76 )
96 (3.7 7)
DIM C
DIM D
102 (4.01)
FIG 8
Stock No: 002522/S31
Machinery Safety Directive MSD
– 2006/42/EC
WIRING
Pollution degree
TAB L E A
– MICROSWI TC H R A T I N G S
C O D E
U L / C S A
IEC 9 4 7
-5-
1 / EN 60 9 4 7
-5-
1 RATING
D e s i g n a t i o n
VA
R A T I N G
0 . 6 / 0 . 3 A @
A C 1 4 /
AC 4 3 2
7 2
0 . 8 k V
2 5 0
0 . 2 2 / 0 . 1 A @
D C 1 3 /
D C
2 8 2 8
0 . 6 / 0 . 3 A @
A C 1 4 /
A C
4 3 2 7 2
0 . 8 k V
2 5 0 V
0 . 2 2 / 0 . 1 A @
D C 1 3 /
D C
2 8 2 8
0 4
1 A @ 1
2 5 V A C R E S I S T I V E ( I E C 1 0 5 8
-
1 / E N 6 1 0 5 8
-
1 )
0 . 6 / 0 . 3 A @
A C 1 4 /
A C
4 3 2 7 2
0 . 5 k V
2 5 0 V
0 . 2 2 / 0 . 1 A @
D C 1 3 /
D C
2 8 2 8
0 G
A C 1 4 /
A C
2
1 6 3 6
0 . 5 k V
1 2 5 V
0 . 3 A @ 1 2 0
V A C
0 C
0 . 8 k V
2 5 0 V
0 . 6 / 0 . 3 A @
A C 1 4 /
A C
4 3 2 7 2
0 . 6 / 0 . 3 A @
A C 1 4 /
A C
4 3 2 7 2
0 . 8 k V
2 5 0 V
0 . 2 2 / 0 . 1 A @
D C 1 3 /
D C
2 8 2 8
0 . 6 / 0 . 3 A @
A C 1 4 /
A C
4 3 2 7 2
0 . 5 k V
2 5 0 V
0 . 2 2 / 0 . 1 A @
D C 1 3 /
D C
2 8 2 8
Low Voltage Directive (LVD) – 2006/95/AC. Switch products with enclosure codes ‘W’ and ‘A’ supplied CE-marked must be installed and used in accordance with the main instructions and this addendum supplied with each product. Products rated lower than 50V ac and 75 V dc are outside the scope of the LVD, and therefore, do not require CE-marking under this directive. The LVD does not apply to products with enclosure codes ‘H’, ‘K’, ‘R’, ‘M’, ‘N’ for use in hazardous areas. Switch products with enclosure codes ‘H’, ‘K’, ‘R’, ‘M’, ‘N’, are covered by the Explosive Atmospheres Directive ATEX – 94/9/EC and when CE-marked will indicate compliance with this directive alone. The following directives do not apply to switch products manufactured by Delta Controls: Electromagnetic Compatibility EMC – 2004/08/EC
ENCLOSURE ‘W’ Cable Glands and adaptors – If enclosure ‘W’ is supplied with a through hole of 22 mm
blanked with a blind grommet. Discard the grommet and fit a suitable proprietary brass or nylon M20 cable gland with thread length of 10 mm and locknut. Fit the nylon reducer provided to the inside and a fibre washer to the outside. See diagram 1. Alternately, the enclosure may be supplied from the factory with a threaded adaptor ready to accept the customer’s gland or conduit system. Alternatives: i) a metal or nylon adaptor may be used to accommodate other sizes of gland eg NPT, or conduit system. See diagram 2. ii) an elbow kit may be supplied to enable the entry to be rotated axially through 90° and radially through 360°. See diagram 3.
Earthing / grounding – The user must make suitable local earthing arrangements, if required, to ensure that metal glands are earthed. An earthing point is provided inside the enclosure. If this is disturbed in any way it must be reassembled correctly to be an effective earth and prevent ingress. See diagram 4. When removing the lid slacken the M4 nut first and ensure it is re tightened whenever the lid is replaced. See diagram 4.1.
ENCLOSURE ‘A’ Cable Glands and adaptors – Enclosure ‘A’ is supplied with an M20 x 1.5 tapped hole. Use a
suitable stainless steel cable gland and sealing washer. Alternately the enclosure may be supplied with a threaded adaptor fitted at the factory ready to accept the customer’s gland or conduit system. See diagram 5.
Earthing / grounding – Bonding between the enclosure and gland / adaptor will be achieved when both parts are screwed together. An earthing point is provided inside the enclosure. If this is disturbed in any way it must be reassembled correctly to be an effective earth and prevent ingress. See diagram 4.
EARTHING / GROUNDING OF PROCESS CONNECTION AND BACK PLATES – All the internal dead metal work is bonded to the enclosure earthing point. Due to requirements of sealing, the process connection and back plates may be isolated from the earthing point. Do not, therefore, rely on either for earthing, instead always use the earthing point provided. If required, the process connection and back plates may be bonded locally. Never use the process connection or inlet pipe for locally grounding welding equipment unless it is separately earth bonded.
Declaration of Conformity
We: Delta Controls Ltd Island Farm Avenue West Molesey Surrey, UK KT8 2UZ
As the manufacturers of the apparatus listed, declare under our sole responsibility that the products listed below:
Pressure, Pressure Difference, Temperature & Flow switches series “W” or “A”: 201, 202, 203, 281, 204, 207, 208, 209, 231, 232, 233, 234, S21, S22, S24, GR2, GR4, VM2, VM4. 301, 303, 304, 381, 384, 306, 386, 310, 316, S31, S34, GR3, GR6. 721, 731, 771, 722, 732, 772, 723, 733, 773, 781, 734, 774, 741, 742, 743, 744, S71, GR7.
131. To which this declaration relates are in conformity with the following relevant standards or parts thereof: EN 60947-1 :1992 Low voltage switch gear and control-gear-general rules.
EN 60947-5-1:1992 Low voltage switch gear and control-gear-control circuit devices and switching elements. EN 60529: 1991 Specification for classification of degrees of protection provided by enclosures. EN 60950:1992 Safety of information technology equipment including electrical business equipment: section 2.5. BS 6134:1991 Specification for pressure and vacuum switches.
And thereby conforms to the requirements of the Low Voltage Directive 73/23/EC amended by 93/68/EEC.
…………………. R. Harrison Managing Director
Original dated 22nd June 2000 Rev. B dated 12
th
August 2009
Signed:
conditions where condensation may readily form, then sealed contacts should be used. See Table A codes 08/09, 0G/0H, H2/H3/H6.
Electrical isolation – These products are not suitable for electrical isolation. Always isolate circuit separately to carry out any electrical work.
M I C R O S W I T C H
( R E S I S T I V E )
* S E E N O T E
S W I T C H
5 A @ 1 1 0 / 2 5 0
0 0
&
0 1
5 A @ 1 1 0 / 2 5 0
0 2
&
0 3
2 A @ 3 0 V D C
1 A @ 1 2 5 V A C
&
0 5
* 1 0 0 m A @ 3 0
0 8 0 9
0 H
0 D
H 2 H 3 H 6
1 1 0 / 2 5 0 V A C
&
5 A @ 3 0 V D C
* 1 A @ 3 0 V A C
&
5 A @ 1 1 0 / 2 5 0
5 A @ 1 1 0 / 2 5 0
2 A @ 3 0 V D C
5 A @ 1 1 0 / 2 5 0
&
2 A @ 3 0 V D C
&
The el e c t r i c a l rat i n g is depe nd e n t on th e mi c roswitch fi t t e d to th e instrume nt. T h e electric al ra t i ng is de f i n e d by each ap p r o v a l t hat the mic r o s w i t c h c om plies wi t h a n d is shown o n t h e pr o duct nameplate, i e U L / CSA, or IE C. It s h o u l d b e n o t e d t ha t t he s wi tch must b e u s ed wit hi n t h e elect r i c a l rating s p e c i f i e d from t h e approv al you r e q u i r e . Tabl e A lists t h e ac t ua l IE C r a t i ngs aga i nst t he Designati on & Utilis at i o n Cat egory m a r k e d on t h e nameplate. In t he absence of a n y v e r i f i c a t ion by UL / CSA t h e m i c r o s wi t c h *m anufactu r e r ’ s rating i s s pecified i n b o ld i t a l i c s . If i n d o ubt, seek guidance f r o m f a c t o r y.
– all products are suitable for use in pollution degree 3. For extreme
R A T I N G
V A C
V A C
V D C
* 5 A @
& 3 0 V D C
V A C
V A C
V A C
( I e I U e )
Uimp
Ui
V
1 2 0 / 2 4 0 V A C
1 2 5 / 2 5 0 V D C
1 2 0 / 2 4 0 V A C
1 2 5 / 2 5 0 V D C
1 2 0 / 2 4 0 V A C
1 2 5 / 2 5 0 V D C
1 2 0 / 2 4 0
V A C
1 2 0 / 2 4 0 V A C
1 2 5 / 2 5 0 V D C
1 2 0 / 2 4 0 V A C
1 2 5 / 2 5 0 V D C
&
U t i l i s a t i o n
C a t e g o r y
D 3 0 0
R 3 0 0
D 3 0 0
R 3 0 0
D 3 0 0
R 3 0 0
E 1 5 0
D 3 0 0
D 3 0 0
R 3 0 0
D 3 0 0
R 3 0 0
Make
Break
Loading...