Delta PMT Series, PMT-48V350W1AKA, PMT-48V350W1AR, PMT-48V350W1ARA, PMT-48V350W1AK Technical Data Sheet

TECHNICAL DATASHEET
PMT Panel Mount Power
Supply
48V 350W 1
Phase
1
CC Code**
□ □
R K*
□□
PMT

Highlights & Features

AC input voltage range selectable by switch
Full aluminium casing for light weight and corrosion resistant
handling
Built-in automatic fan speed control circuit
MTBF > 700,000 hrs as per Telcordia SR-332
Short Circuit / Overvoltage / Overload / Over Temperature
Protections

Safety Standards

CB Certified for worldwide use
Model Number: PMT-48V350W1A☐☐ Unit Weight: 0.83 kg (1.83 lb) Dimensions (L x W x D): 215 x 115 x 50 mm
(8.46 x 4.53 x 1.97 inch)

General Description

The new PMT series of panel mount power supplies is the latest offering from one of the world’s largest power supply manufacturers and solution providers - Delta. PMT-48V350W1A☐☐ offers a nominal output voltage of 48V with a wide operating temperature range from ­10°C to +70°C and can withstand shock and vibration (in accordance to IEC 60068-2-27 and IEC 60068-2-6 respectively). In addition to features like overvoltage and overload protections, Delta’s PMT series of panel mount power supplies is unlike many other brands in the same price level. The PMT series is designed for cost competitive markets without compromising the quality of the components and product specifications. The series of products has an expected life time of 10 years and will have no output power de-rating from 100Vac to 132Vac & 200Vac to 264Vac.

Model Information

PMT Panel Mount Power Supply
Number
Model
PMT-48V350W1A☐☐

Model Numbering

Input Voltage Range Rated Output Voltage
90-132Vac, 180-264Vac (Selectable by Switch)
48Vdc 7.30A
Rated Output Curr
ent
PM
Panel Mount Product Type
*Options **For Terminal Block Type
T – 48V
Output Voltage Output Power Single Phase No PFC Connector Type
T – Enclosed
All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (November 2018, Rev. 04)
350W 1 A
Blank – Without
R – Terminal Block K – Front Face*
connector cover A – With connector cover
TECHNICAL DATASHEET
PMT Panel Mount Power
Supply
48V 350W 1
Phase
2
PMT-48V350W1AR☐
□□

Specifications

Input Ratings / Characteristics

Nominal Input Voltage
Input Voltage Range 90-132Vac, 180-264Vac (Selectable by Switch)
Nominal Input Frequency 50-60Hz
Input Frequency Range 47-63Hz
Input Current 7.00A typ. @ 115Vac, 4.00A typ. @ 230Vac
Efficiency at 100% Load 87.5% typ. @ 230Vac
Max Inrush Current (Cold Start) 40A typ. @ 115Vac, 60A typ. @ 230Vac
Leakage Current

Output Ratings / Characteristics*

Nominal Output Voltage 48Vdc
Factory Set Point Tolerance 48Vdc ± 1%
Output Voltage Adjustment Range 43.2-52.8Vdc
Output Current 7.30A (350W max.)
Output Power 350W
Line Regulation ± 0.5% typ.
Load Regulation ± 1% typ.
PARD** (20MHz) < 240mVpp
Rise Time
Start-up Time < 1000ms @ nominal input (100% load)
Hold-up Time 16ms typ. @ 115Vac, 20ms typ. @ 230Vac (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage) ± 5% @ 10-50% load and 50-100% load
Start-up with Capacitive Loads 8,000µF Max
*For power de-rating from > 50°C to 70°C, see power de-rating on page 3. **PARD is measured with an AC coupling mode, 5cm wires, and in parallel with 0.1µF ceramic capacitor & 47µF electrolytic capacitor

Mechanical

Case Cover / Chassis
Dimensions (L x W x D) 215 x 115 x 50 mm (8.46 x 4.53 x 1.97 inch)
Unit Weight 0.83 kg (1.83 lb)
Indicator Green LED (DC OK)
Cooling System Forced Cooling
Terminal
PMT-48V350W1AK M3.5 x 9 Pins (Rated 300V/20A)
Wire
Noise (1 Meter from power supply)
Aluminium
100-120Vac, 200-240Vac (Selectable by Switch)
< 3.5mA @ 240Vac
< 50ms @ nominal input (100% load)
M3.5 x 9 Pins (Rated 300V/15A)
AWG 22-12
Sound Pressure Level (SPL) < 52dBA
.
All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (November 2018, Rev. 04)
TECHNICAL DATASHEET
PMT Panel Mount Power
Supply
48V 350W 1
Phase
3
Operating
-10°C to +70°C
< 200Vac de-rate power by 3% / V
□□

Environment

Surrounding Air Temperature
Storage -25°C to +85°C
Power De-rating > 50°C de-rate power by 2.5% / °C
< 100Vac de-rate power by 3% / V
Operating Humidity 5 to 95% RH (Non-Condensing)
Operating Altitude 0 to 5,000 Meters (16,400 ft.)
Shock Test Non-Operating IEC 60068-2-27, Half Sine: 50G for a duration of 11ms, 3
times per direction, 18 times in total
Vibration Operating IEC 60068-2-6, Sine Wave: 10Hz to 150Hz @ 25m/S² (2.5G
peak); 90 min per axis for all X, Y, Z direction
Non-Operating IEC 60068-2-6, Random: 5Hz to 500Hz @ 2.09Grms peak;
20 min per axis for all X, Y, Z direction
Over Voltage Category II
Pollution Degree 2

Protections

Overvoltage
Overload / Overcurrent 105%~150% of rated load current, Hiccup Mode,
Over Temperature Hiccup Mode, Non-Latching
Short Circuit Hiccup Mode, Non-Latching
Internal Fuse at L pin T10AH
Protection Against Shock Class I with PE* connection
*PE: Primary Earth

Reliability Data

MTBF > 700,000 hrs as per Telcordia SR-332
Expected Cap Life Time 10 years (115Vac & 230Vac, 50% load @ 40°C)
57.6V~67.2V, Latch Mode
Non-Latching (Auto-Recovery)
(Auto-Recovery when the fault is removed)
(Auto-Recovery when the fault is removed)
I/P: 100Vac, O/P: 100% load, Ta: 35°C
All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (November 2018, Rev. 04)
TECHNICAL DATASHEET
PMT Panel Mount Power
Supply
48V 350W 1
Phase
4
Safety Entry Low Voltage
SELV (EN 60950-1)
CB scheme
IEC 60950-1
Emissions
Contact Discharge: 8kV
Differential Mode3): 1kV
Differential Mode3): 1kV

Safety Standards / Directives

□□
Electrical Safety
CE In conformance with EMC Directive 2014/30/EU and Low
Material and Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input to Output 3.0KVac
Input to Ground 1.5KVac
Output to Ground 0.5KVac
TUV Bauart
UL/cUL recognized
EN 60950-1 UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E131881)
Voltage Directive 2014/35/EU
EMC
(CE & RE)
Immunity EN 55024
Electrostatic Discharge IEC 61000-4-2 Level 4 Criteria A1)
Radiated Field IEC 61000-4-3 Level 3 Criteria A1)
Electrical Fast Transient / Burst IEC 61000-4-4 Level 3 Criteria A1)
Surge IEC 61000-4-5 Level 3 Criteria A1)
CISPR 32, EN 55032, EN 55011, FCC Title 47: Class B
Air Discharge: 15kV
80MHz-1GHz, 10V/M with 1kHz tone / 80% modulation
2kV
Common Mode2): 2kV
Conducted IEC 61000-4-6 Level 3 Criteria A1)
150kHz-80MHz, 10Vrms
Power Frequency Magnetic Fields IEC 61000-4-8 Criteria A1)
10A/Meter
Voltage Dips and Interruptions IEC 61000-4-11 100% dip; 1 cycle (20ms); Self Recoverable
Low Energy Pulse Test (Ring Wave) IEC 61000-4-12 Level 3 Criteria A1)
Common Mode
Harmonic Current Emission NA
Voltage Fluctuation and Flicker* IEC/EN 61000-3-3
*Fulfills tested conditions
1) Criteria A: Normal performance within the specification limits
2) Asymmetrical: Common mode (Line to earth)
3) Symmetrical: Differential mode (Line to line)
2)
: 2kV
All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (November 2018, Rev. 04)
TECHNICAL DATASHEET
PMT Panel Mount Power
Supply
48V 350W 1
Phase
5
PMT-48V350W1AR: Terminal Block
PMT-48V350W1AK: Front Face

Block Diagram

□□

Device Description

1) Input & Output terminal block connector
2) DC voltage adjustment potentiometer
3) DC OK control LED (Green)
4) AC selectable switch
All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (November 2018, Rev. 04)
Loading...
+ 10 hidden pages