Delta Modulon DPH series, Modulon DPH 200kVA, Modulon DPH 500kVA, Modulon DPH 300kVA, Modulon DPH 400kVA User Manual

The power behind competitiveness
Delta UPS - Modulon Family
DPH Series, Three Phase 200-500 kVA
User Manual
www.deltapowersolutions.com
This manual contains important instructions and warnings that you should follow during the installation, operation, storage and maintenance of this product. Failure to heed these instructions and warnings will void the warranty.
Copyright © 2018 by Delta Electronics Inc. All Rights Reserved. All rights of this User Manual (“Manual”), including but not limited to the contents, information, and figures are solely owned and reserved by Delta Electronics Inc. (“Delta”). The Manual can only be applied to the operation or the use of this product. Any disposition, duplication, dissemination, reproduction, modification, translation, extraction, or usage of this Manual in whole or in part is prohibited without the prior written permission of Delta. Given that Delta will continuously improve and develop the product, changes may be made to the information in this Manual at any time without obligation to notify any person of such revision or changes. Delta will make all possible efforts to secure the accuracy and the integrity of this Manual. Delta disclaims any kinds or forms of warranty, guarantee, or undertaking, either expressly or implicitly, including but not limited to the completeness, faultlessness, accuracy, non-infringement, merchantability or fitness for a particular purpose of the Manual.
Modulon DPH Series
II
Table of Contents
Table of Contents
1. Important Safety Instructions ---------------------------------------------- 1-1
1.1 Installation Warnings ---------------------------------------------------------------------- 1-2
1.2 Connection Warnings --------------------------------------------------------------------- 1-2
1.3 Usage Warnings --------------------------------------------------------------------------- 1-4
1.4 Storage Warnings ------------------------------------------------------------------------- 1-6
1.5 Standard Compliance -------------------------------------------------------------------- 1-6
2. Introduction ---------------------------------------------------------------------- 2-1
2.1 General Overview ------------------------------------------------------------------------- 2-2
2.2 Package Inspection ----------------------------------------------------------------------- 2-2
2.3 Functions & Features --------------------------------------------------------------------- 2-4
2.4 Exterior and Dimensions ----------------------------------------------------------------- 2-6
2.5 Front View ----------------------------------------------------------------------------------- 2-6
2.6 Internal View ------------------------------------------------------------------------------- 2-8
2.7 Rear View------------------------------------------------------------------------------------ 2-9
2.8 Tri-color LED Indicator & Buzzers --------------------------------------------------- 2-11
3. Operation Modes --------------------------------------------------------------- 3-1
3.1 Single Input --------------------------------------------------------------------------------- 3-4
3.1.1 Online Mode_ Single Input_ Single Unit ---------------------------------- 3-4
3.1.2 Battery Mode_ Single Input_ Single Unit---------------------------------- 3-5
3.1.3 Bypass Mode_ Single Input_ Single Unit -------------------------------- 3-6
3.1.4 Manual Bypass Mode_ Single Input_ Single Unit----------------------- 3-6
3.1.5 ECO Mode_ Single Input_ Single Unit ------------------------------------ 3-8
3.1.6 Frequency Conversion Mode_ Single Input_ Single Unit ------------ 3-8
3.1.7 Green Mode _ Single Input_ Single Unit --------------------------------- 3-9
3.1.8 Energy Recycle Mode _ Single Input_ Single Unit --------------------3-10
3.1.9 Online Mode_ Single Input_ Parallel Units -----------------------------3-11
3.1.10
3.1.11
3.1.12
3.1.13
3.1.14
3.1.15
3.2 Dual Input -----------------------------------------------------------------------------------3-19
3.2.1 Online Mode_ Dual Input_ Single Unit -----------------------------------3-19
3.2.2 Battery Mode_ Dual Input_ Single Unit ----------------------------------3-19
Battery Mode _ Single Input_ Parallel Units ----------------------------3-12
Bypass Mode_ Single Input_ Parallel Units -----------------------------3-13
Manual Bypass Mode_ Single Input_ Parallel Units ------------------3-14 ECO Mode_ Single Input_ Parallel Units --------------------------------3-16
Frequency Conversion Mode_ Single Input_ Parallel Units --------3-17
Green Mode_ Single Input_ Parallel Units-------------------------------3-18
III
3.2.3 Bypass Mode_ Dual Input_ Single Unit ----------------------------------3-20
3.2.4 Manual Bypass Mode_ Dual Input_ Single Unit ------------------------3-21
3.2.5 ECO Mode_ Dual Input_ Single Unit -------------------------------------3-22
3.2.6 Frequency Conversion Mode_ Dual Input_ Single Unit -------------3-23
3.2.7 Green Mode _ Dual Input_ Single Unit ----------------------------------3-24
3.2.8 Online Mode_ Dual Input_ Parallel Units --------------------------------3-25
3.2.9 Battery Mode _ Dual Input_ Parallel Units ------------------------------3-26
3.2.10
Bypass Mode_ Dual Input_ Parallel Units ------------------------------3-27
3.2.11
Manual Bypass Mode_ Dual Input_ Parallel Units --------------------3-28
3.2.12
ECO Mode_ Dual Input_ Parallel Units ----------------------------------3-30
3.2.13
Frequency Conversion Mode_ Single Input_ Parallel Units --------3-31
3.2.14
3.3 Hot Standby Redundancy (Only For Dual Input & At Least Two UPSs) ----3-33
3.4 Common Battery (Only for Parallel UPSs connecting to -----------------------------­the Same External Battery Cabinet(s)) ----------------------------------------------3-34
Green Mode_ Dual Input_ Parallel Units --------------------------------3-32
4. Communication Interfaces -------------------------------------------------- 4-1
4.1 Communication Interfaces on the Front of the UPS with Front Door Open 4-2
4.1.1 Display Port ---------------------------------------------------------------------- 4-3
4.1.2 REPO Dry Contacts ------------------------------------------------------------ 4-3
4.1.3 External Battery Temperature Dry Contacts ----------------------------- 4-5
4.1.4 External Switch/ Breaker Status Dry Contacts -------------------------- 4-6
4.1.5 Output Dry Contacts ------------------------------------------------------------ 4-7
4.1.6 Input Dry Contacts -------------------------------------------------------------4-10
4.1.7 Parallel Communication Cards --------------------------------------------- 4-11
4.1.8 Parallel Ports -------------------------------------------------------------------- 4-11
4.1.9 SMART Slot ---------------------------------------------------------------------4-12
4.1.10
4.1.11
4.1.12
4.2 Communication Interfaces at the Rear of the Touch Panel --------------------4-13
USB Port & RS-232 Port -----------------------------------------------------4-12
Auxiliary Power Cards --------------------------------------------------------4-12
Battery Start Buttons ----------------------------------------------------------4-13
5. Installation and Wiring -------------------------------------------------------- 5-1
5.1 Before Installation and Wiring ---------------------------------------------------------- 5-2
5.2 Installation Environment ----------------------------------------------------------------- 5-3
5.3 UPS Transportation ----------------------------------------------------------------------- 5-5
5.4 Fixing the UPS ---------------------------------------------------------------------------- 5-6
5.5 Wiring ----------------------------------------------------------------------------------------- 5-8
5.5.1 Pre-wring Warnings------------------------------------------------------------- 5-8
Modulon DPH Series
IV
Table of Contents
5.5.2 Single Input/ Dual Input Modification --------------------------------------5-10
5.5.3 Single Unit Wiring --------------------------------------------------------------5-12
5.5.4 Parallel Units Wiring ----------------------------------------------------------5-21
5.6 External Battery Cabinet Connection Warnings ---------------------------------5-25
5.7 STS Module --------------------------------------------------------------------------------5-32
5.7.1 STS Module Installation ------------------------------------------------------5-33
5.7.2 STS Module Removal -------------------------------------------------------5-35
5.7.3 STS Module’s LED Indicator ------------------------------------------------5-37
5.8 Power Module (Optional) ---------------------------------------------------------------5-37
5.8.1 Power Module Installation ---------------------------------------------------5-38
5.8.2 Power Module Removal -----------------------------------------------------5-40
5.8.3 Power Module’s LED Indicator ---------------------------------------------5-42
6. UPS Operation------------------------------------------------------------------- 6-1
6.1 Pre Start-up & Pre Turn-off Warnings for Single Unit --------------------------------­and Parallel Units -------------------------------------------------------------------------- 6-2
6.2 Start-up Procedures ---------------------------------------------------------------------- 6-4
6.2.1 Online Mode Start-up Procedures ------------------------------------------ 6-4
6.2.2 Battery Mode Start-up Procedures ----------------------------------------- 6-8
6.2.3 Bypass Mode Start-up Procedures ----------------------------------------6-10
6.2.4 Manual Bypass Mode Start-up Procedures -----------------------------6-13
6.2.5 ECO Mode Start-up Procedures -------------------------------------------6-18
6.2.6 Frequency Conversion Mode Start-up Procedures--------------------6-22
6.2.7 Green Mode Start-up Procedures -----------------------------------------6-26
6.2.8 Energy Recycle Mode Start-up Procedures -----------------------------6-30
6.3 Turn-off Procedures ----------------------------------------------------------------------6-34
6.3.1 Online Mode Turn-off Procedures -----------------------------------------6-34
6.3.2 Battery Mode Turn-off Procedures -----------------------------------------6-36
6.3.3 Bypass Mode Turn-off Procedures ----------------------------------------6-38
6.3.4 Manual Bypass Mode Turn-off Procedures ------------------------------6-39
6.3.5 ECO Mode Turn-off Procedures --------------------------------------------6-39
6.3.6 Frequency Conversion Mode Turn-off Procedures --------------------6-42
6.3.7 Green Mode Turn-off Procedures ------------------------------------------6-45
6.3.8 Energy Recycle Mode Turn-off Procedures -----------------------------6-48
7. LCD Display & Settings ------------------------------------------------------ 7-1
7.1 LCD Display Hierarchy ------------------------------------------------------------------- 7-2
7.2 Turning on the Touch Panel ------------------------------------------------------------- 7-3
7.3 ON/ OFF Button ---------------------------------------------------------------------------- 7-5
V
7.4 Introduction of Touch Panel and Function Keys ----------------------------------- 7-7
7.5 Password Entry --------------------------------------------------------------------------- 7-11
7.6 Main Screen -------------------------------------------------------------------------------7-12
7.7 Main Menu ---------------------------------------------------------------------------------7-16
7.8 Power Flow & Summary & System Status -----------------------------------------7-17
7.9 Check System Readings ---------------------------------------------------------------7-19
7.9.1 Main Input ------------------------------------------------------------------------7-19
7.9.2 Bypass Input --------------------------------------------------------------------7-20
7.9.3 Inverter Output ------------------------------------------------------------------7-20
7.9.4 Power Module Summary -----------------------------------------------------7-21
7.9.5 UPS Output ----------------------------------------------------------------------7-21
7.9.6 Battery Status -------------------------------------------------------------------7-22
7.10 UPS Settings ------------------------------------------------------------------------------7-23
7.10.1
7.10.2
7.10.3
7.10.4 Battery & Charging Setting --------------------------------------------------7-26
7.10.5
7.10.6
7.10.7
7.10.8
7.10.9
7.11 System Maintenance --------------------------------------------------------------------7-35
7.11.1
7.11.2
7.11.3
7.11.4
7.11.5
7.11.6 Advanced Diagnosis ----------------------------------------------------------7-39
7.11.7
Bypass Setting ------------------------------------------------------------------7-23 Mode Setting --------------------------------------------------------------------7-24 Output Setting -------------------------------------------------------------------7-25
Parallel Setting ------------------------------------------------------------------7-28 Dry Contact Setting -----------------------------------------------------------7-29 General Setting -----------------------------------------------------------------7-31 IP Setting -------------------------------------------------------------------------7-33 Control ----------------------------------------------------------------------------7-34
Alarm Warning ------------------------------------------------------------------7-35 Historical Event -----------------------------------------------------------------7-36
Statistics --------------------------------------------------------------------------7-37
Test --------------------------------------------------------------------------------7-38
Clear -------------------------------------------------------------------------------7-38
Version & S/N -------------------------------------------------------------------7-40
8. Optional Accessories -------------------------------------------------------- 8-1
9. Maintenance ---------------------------------------------------------------------- 9-1
10. Troubleshooting ---------------------------------------------------------------10-1
Appendix 1: Technical Specifications ---------------------------------------- A1-1
Appendix 2: Warranty -------------------------------------------------------------- A2-1
Modulon DPH Series
VI
1
Important Safety Instructions
1
Important Safety Instructions
1.1 Installation Warnings
1.2 Connection Warnings
1.3 Usage Warnings
1.4 Storage Warnings
1.5 Standard Compliance
1-1
1.1 Installation Warnings
y This is a three-phase four-wire on-line uninterruptible power supply (hereafter referred to
as ‘UPS’). It can be used for commercial and industrial applications.
y Install the UPS in a well-ventilated indoor area, away from excess moisture, heat, dust,
flammable gas or explosives.
y Leave adequate space around all sides of the UPS for proper ventilation and maintenance.
Please refer to 5.2 Installation Environment.
y Only authorized Delta engineers or service personnel can perform installation and
maintenance. If you want to install the UPS by yourself, please install it under the supervision of authorized Delta engineers or service personnel
y Follow the IEC 60364-4-42 standard to install the UPS.
1.2 Connection Warnings
y Before applying electrical power to the UPS, make sure the UPS is grounded to avoid a
possible risk of current leakage.
y You can parallel at maximum eight UPS units.
y The UPS must be connected with an external battery cabinet (user-supplied, handled and
configured by Delta service personnel). Please refer to 5.6 External Battery Cabinet Connection Warnings for relevant information.
y The UPS must be connected with a Delta or non-Delta external maintenance bypass
cabinet. The Delta external maintenance bypass cabinet is optional, and the non-Delta external maintenance bypass cabinet is user-supplied and should be handled and configured by Delta service personnel. For the Delta or non-Delta external maintenance bypass cabinet’s information, please refer to the table below.
There are two models for selection. Please refer to the table below.
Delta External Maintenance Bypass Cabinet (Optional)
Model 3915101965-S 3915101964-S
Delta External
Maintenance
Bypass Cabinet
(Optional)
3 Switches
Switch Q’ty
Wiring Type Top & Bottom Wiring Top & Bottom Wiring
NOTE:௓)RU PRUH LQIRUPDWLRQ DERXW WKH 'HOWD H[WHUQDO
maintenance bypass cabinet (optional), please refer to its user manual.
(Input Switch/ Manual
Bypass Switch/ Output
Switch)
4 Switches
(Input Switch/ Bypass
Switch/ Manual Bypass
Switch/ Output Switch)
Modulon DPH Series
1-2
Non-Delta
External
Maintenance
Bypass
Cabinet
(User-supplied,
handled and
configured by
Delta service
personnel)
127(௓If there are switches but not breakers installed in the external
maintenance bypass cabinet, please install (1) an additional protective device between the input power and the external maintenance bypass cabinet and (2) an additional protective device between the connected critical loads and the external maintenance bypass cabinet. The protective device could be a breaker or a fuse. For the protective device’s rating current, please refer to the table below.
1
Important Safety Instructions
For configurations of the non-Delta external maintenance bypass cabinet, please refer to the following. a. Selection of three or four breakers (switches):
(1) Three breakers (switches):
An input breaker (switch), a manual bypass breaker (switch) and an output breaker (switch) should be installed.
(2) Four breakers (switches):
An input breaker (switch), a bypass breaker (switch), a manual bypass breaker (switch) and an output breaker (switch) should be installed.
b. Each breaker (switch) mentioned above must be a 3-pole (R/ S/
T) device and meets the specifications defined in Table 5-3.
c. It is suggested that each breaker (switch) should be configured
with an auxiliary contactor. For relevant information, please refer
to 4.1.4 External Switch/ Breaker Status Dry Contacts.
d. Install the non-Delta external maintenance bypass cabinet next
to the UPS or align it with the UPS for convenient operation.
200kVA 300kVA 400kVA 500kVA
400A 600A 800A 1000A
y In this user manual, the meaning of Q0, Q1, Q2, Q3, Q4 and Q5 represents the following.
Code Meaning
Q0 UPS’s Bypass Switch
Q1
Q2
Q3
Q4
Q5 External Battery Cabinet’s Breaker
Delta or non-Delta External Maintenance Bypass Cabinet’s Input Breaker or Switch
Delta or non-Delta External Maintenance Bypass Cabinet’s Bypass Breaker or Switch
Delta or non-Delta External Maintenance Bypass Cabinet’s Manual Bypass Breaker or Switch
Delta or non-Delta External Maintenance Bypass Cabinet’s Output Breaker or Switch
1-3
y The installation of protective devices is highly recommended when the UPS is connected
to power sources.
y The protective devices connecting to the UPS must be installed near the UPS and easily
accessible for operation.
y Protective Devices:
1. It is suggested that you install appropriate protective devices between the UPS and input AC power. The protective devices should have the functions of over current protection, short circuit protection, insulating protection and shunt trip feature. Please refer to the table below for different UPS’s cut off current (Icc).
200kVA 300kVA 400kVA 500kVA
10kA 10kA 12.12kA 15.15kA
2. For selection of the protective devices, please take each power cable’s current
capacity and the system’s overload capacity (please refer to Appendix 1: Technical Specifications) into consideration. Besides, the short-circuit capacity of the upstream
protective devices must be equal to or higher than the capacity of the UPS’s protective devices.
3. For single input, when the UPS has abnormalities and input short current reaches 20kA, the UPS’s internal semi-conductor fast-acting fuses need 8ms ~ 10ms to be fused. Thus, the upstream protective devices’ reaction time should be more than 10ms to let the UPS’s internal protective devices block breakdown and let the UPS transfer to bypass mode.
4. For dual input, please install the protective devices between the UPS and the main AC source as well as between the UPS and the bypass AC source.
y If the UPS is supplied by a power source whose neutral is grounded, the backfeed
protective device installed as UPS input protection must be a 3-pole type. If the UPS is supplied by a power source whose neutral is not grounded, the backfeed protective device installed as UPS input protection must be a 4-pole type.
y The recommended electrical rating of the backfeed protective device is as follows.
200kVA 300kVA 400kVA 500kVA
690V/ 400A 690V/ 600A 690V/ 800A 690V/ 1000A
1.3 Usage Warnings
y Before installation, wiring and working on the UPS’s internal circuits, please completely
cut off all power supplying to the UPS, including the input power and battery power.
Modulon DPH Series
1-4
1
Important Safety Instructions
y The UPS is specifically designed for information technology equipment and used to
power computers, servers, and associated peripheral devices. If you want to connect any capacitive loads or non-linear loads (that have serious surge current) to the UPS, it needs to be de-rated according to on-site applications. For such special applications, please contact Delta service personnel for the accurate UPS sizing. The UPS is not suitable for connecting with any asymmetrical loads.
y The external slits and openings in the UPS are provided for ventilation. To ensure reliable
operation of the UPS and to protect the UPS from overheating, these slits and openings must not be blocked or covered. Do not insert any object into the slits and openings that may hinder ventilation.
y Before applying electrical power to the UPS, you must allow the UPS to adjust to room
temperature (20°C~25°C) for at least one hour to avoid moisture condensing inside the UPS.
y Do not put beverages on the UPS, external battery cabinet, Delta or non-Delta external
maintenance bypass cabinet or any other accessory associated with the UPS.
y Do not open or remove the covers or panels of the UPS to avoid high voltage electric
shock. Only authorized Delta engineers or service personnel can do so for installation or maintenance. If you want to open or remove the covers or panels, do it only under the supervision of authorized Delta engineers or service personnel.
y It is strictly forbidden to connect the UPS to any regenerative loads.
y The risk of dangerous high voltage is possible when batteries are still connected to the
UPS even though the UPS is disconnected from the power sources. Before maintenance, turn off the external battery cabinet’s circuit breaker to completely cut off the battery power from the UPS.
y Do not dispose of the battery or batteries in a fire. The batteries may explode.
y Do not open or damage the battery or batteries. The released electrolyte is harmful to the
skin and eyes and may be toxic.
y The UPS is electronic equipment that runs 24 hours continuously. To ensure its normal
lifetime, regular maintenance of the UPS and batteries is of vital importance and necessary.
y Some components like batteries, power capacitors, and fans will become worn-out due
to long-term usage, and this will increase the risk of UPS failure. To replace and maintain the components, please contact Delta service personnel.
y A battery can present a risk of electric shock and high short-circuit current. The following
precautions should be observed before replacement of batteries:
1. Remove watches, rings, or other metal objects.
2. Use tools with insulated handles.
1-5
3. Wear insulating gloves and boots.
4. Do not lay tools or metal parts on the top of batteries.
5. Disconnect the charging source prior to connecting or disconnecting the batteries’ terminals.
y You must contact Delta customer service if either of the following events occur:
1. Liquid is poured or splashed on the UPS.
2. The UPS does not run normally after carefully following the instructions in this User Manual.
1.4 Storage Warnings
y Use the original packing material to pack the UPS to prevent any possible damage from
rodents.
y If the UPS needs to be stored prior to installation, it should be placed in a dry indoor area.
The allowable storage temperature is below 70°C and relative humidity is below 95%.
1.5 Standard Compliance
y EN 62040-1
y EN 61000-6-4
y EN 62040-2 Category C3
y EN 61000-4-2
y EN 61000-4-3
y EN 61000-4-4
y EN 61000-4-5
y EN 61000-4-6
y EN 61000-4-8
y EN 61000-2-2
y YD/ T 2165-2010
y YD 5083-2005
y YD/ T 5096-2016
Modulon DPH Series
1-6
2
Introduction
2
Introduction
2.1 General Overview
2.2 Package Inspection
2.3 Functions & Features
2.4 Exterior and Dimensions
2.5 Front View
2.6 Internal View
2.7 Rear View
2.8 Tri-color LED Indicator & Buzzers
2-1
2.1 General Overview
The DPH series UPS, a three-phase four-wire online uninterruptible power supply, is a dedicated design for data centers, factory facilities and large scale power systems. The unit not only adopts advanced IGBT technology to provide high quality, low noise, pure and uninterruptible output power to the connected loads, but also applies the latest design of DSP digital control technology and highest quality components.
The UPS supports high efficient operation modes and its modular and hot-swappable design makes maintenance easy and quick. You can add power modules (optional) according to on-site applications to expand overall system capacity, which realizes a highly cost-effective solution to your power requirements and produces greater electric power efficiency at less cost.
The unit provides diversified communication interfaces and has built-in SNMP and MODBUS cards for the user to facilitate remote control and management. You can parallel at maximum eight UPS units to increase the system capacity and redundancy and enhance the unit’s availability and reliability.
2.2 Package Inspection
y External
During UPS transportation, some unpredictable situations might occur. It is recommended that you inspect the UPS exterior packaging. If you notice any damage, please immediately contact the dealer from whom you purchased the unit.
y Internal
1. Check the rating label attached to the UPS and make sure the device No. and capacity match what you ordered.
2. Examine if any parts are loose or damaged.
3. The UPS package contains the following items. Please check if any items are missing.
Modulon DPH Series
1
2
6 7 8 9
11
3
×35
12 13 14 15
2-2
4
×35
×2
5
10
×10×35
×2
2
Introduction
No. Item Q’ty
UPS (two pieces of 50ppi dust filters have been installed on the inner
1
side of the UPS front door before shipment)
User Manual 1 PC
2
RS-232 Cable (1.8 meters) 1 PC
3
Parallel Cable (3 meters) 1 PC
4
Test Report 1 PC
5
Key
6
1 PC
1 PC (two copies placed inside the UPS cabinet)
M12 Screw (used for input/ output/ battery/ grounding wiring) 35 PCS
7
Washer (used for input/ output/ battery/ grounding wiring) 35 PCS
8
Washer Spring (used for input/ output/ battery/ grounding
9
wiring)
M4 Screw (used to fix the parallel fasteners) 10 PCS
10
USB Cable 1 PC
11
4-Pin Dry Contact Terminal Block
12
(used for REPO dry contacts; please refer to Figure 4-3)
6-Pin Dry Contact Terminal Block (used for MODBUS and BMS ports located at the rear of the
13
touch panel; please refer to Figure 4-15)
8-Pin Dry Contact Terminal Block (used for (1) external battery temperature dry contacts and (2)
14
external switch/ breaker status dry contacts; please refer to
Figure 4-3)
10-Pin Dry Contact Terminal Block (used for input and output
15
dry contacts; please refer to Figure 4-3)
35 PCS
1 PC
1 PC
2 PCS
2 PCS
4. If there is any damage or anything missing, please immediately contact the dealer from whom you purchased the unit.
2-3
5. If the UPS needs to be returned, carefully repack the UPS and all of the accessories using the original packing material that came with the unit.
2.3 Functions & Features
y Hot swappable STS module, communication interfaces and power modules (optional)
realize on-line maintenance, reduce the MTTR (Mean Time to Repair) and expand system capacity flexibly (200 ~ 500kVA).
y Input power factor > 0.99 and input THDi < 3% save on installation cost and diminish
power contamination.
y Output power factor= 1 (for 500kVA, output power factor is 0.9).
y Efficiency > 96% saves on operation cost.
y Automatic input frequency detection enables operation at 50Hz or 60Hz.
y Automatic restart:
1. The UPS will restart in normal mode automatically right after the AC line resumes following a low battery shutdown.
2. The UPS returns automatically to normal mode from bypass mode after an overload condition is cleared.
y Automatically detects whether bypass voltage is out of rating voltage (default: voltage
±15% & frequency ±3Hz). If yes, the UPS will stop supplying power to the critical loads to protect your electronic equipment.
y Supports ECO mode: when input voltage and frequency are within the range of rating
voltage ±10% and rating frequency ±3Hz, the UPS will transfer to bypass mode; otherwise, the UPS will transfer to normal mode to reach higher efficiency.
y Both auxiliary power and control circuit adopt redundancy design, which doubly enhances
UPS reliability.
y Suitable for top and bottom wiring by use of the Delta external maintenance bypass
cabinet (optional).
y Generator compatible
y Surge protection and EMI filter functions.
y Remote emergency power off.
y Single input and dual input functions.
y Supports external switch/ breaker status detection.
Modulon DPH Series
2-4
2
Introduction
y Wide AC input voltage range (140Vac~276Vac) reduces frequent transfer from normal
mode to battery mode to save battery consumption and prolong battery life.
y AC start-up function even when the UPS is not connected to the batteries.
WARNING:
Please note that when the UPS is not connected to the batteries, it will not protect your equipment if the utility power is lost.
y Connects at maximum four external battery cabinets to extend backup time.
y Schedulable battery test and battery replacement alarm.
y Battery temperature monitoring and compensation.
y Battery monitoring system allows measurement of per battery cell’s voltage and current.
y Smart battery charger design allows auto-charging or manual charging to shorten
charging time.
y Provides communication interfaces and a smart slot (where you can install the optional
Relay I/O card for dry contact expansion). Please refer to 4. Communication Interfaces.
y Built-in RS-232 port and USB port located on the communication interfaces allow
monitoring and management of the UPS. For relevant location and information, please
refer to Figure 4-3 and Page 4-11.
y Built-in SNMP card and MODBUS card located at the rear of the touch panel provide
network communication and MODBUS communication respectively. For relevant location
and information, please refer to Page 4-12 and Page 4-13.
y Built-in SNMP card located at the rear of the touch panel allows remote monitoring,
management and event log download of the UPS. For relevant location and information,
please refer to Page 4-12 and Page 4-13.
y Built-in USB ports ( ) located at the rear of the touch panel allow upgrade of the UPS,
touch panel, power modules, system control card and parallel communication cards’ firmware and event log download. For relevant location and information, please refer to
Page 4-12 and Page 4-13.
y Built-in SRAM records at maximum 10000 event logs.
y 10-inch graphic and color touch panel enables the user to easily operate the UPS and
understand the UPS status.
y Fan speed auto adjustment prolongs fan life and reduces noise when the critical loads
decrease. Moreover, fan failure detection circuit is established.
y State-of-the-art microprocessor technology performs self-detection and monitors fan
speed in real time, which provides complete and detailed operating status of the UPS.
2-5
2.4 Exterior and Dimensions
600 mm
2000
mm
1100
mm
2.5 Front View
On the front of the UPS, there are a 10” color touch panel, a tri-color LED indictor, a door
switch, six casters and four leveling feet. Please see Figure 2-2.
1. For information about the 10” color touch panel, please refer to 7. LCD Display & Settings.
2. For information about the tri-color LED indicator, please refer to 2.8 Tri-color LED Indicator & Buzzers.
3. The casters at the bottom of the UPS can be used to move over short distances, and
the leveling feet fix and stabilize the UPS on the ground. Please refer to 5.3 UPS Transportation for relevant information.
4. Please refer to Figure 2-3 for how to open the UPS front door.
(Figure 2-1: Exterior & Dimensions)
Modulon DPH Series
2-6
10” Color Touch Panel
Tri-color LED Indictor
Levelling Feet
(Figure 2-2: UPS Front View)
Door Switch
Casters
2
Introduction
Pull Up
(Figure 2-3: How to Open the UPS Front Door)
2-7
90°90°
2.6 Internal View
WARNING:
Only authorized Delta engineers or service personnel can perform installation, wiring, panel & cover removal, maintenance and operation. If you want to execute any action mentioned above by yourself, the action must be under the supervision of authorized Delta engineers or service personnel.
After you open the UPS’s front door, you will see the internal mechanisms including communication interfaces, a bypass switch (Q0), an STS module, and nine power module
slots. Please refer to Figure 2-4.
Communication Interfaces
Internal View
(Front View with Door Open)
DISPLAY
I/P DRY
O/P DRY
EXT.SWITCH
EXT. BATT
CONTACT
CONTACT
STATUS
TEMP.
P1P2
S1S2
P1P2 P3
BT1BT2
REPO NCNO
BT4
BT3
P4
P5P6
S3S4
P3
P4
N
G
D A
G
N
D
B
A B
RESET
M
OD
B
US
BM
S
Y A L
ISP D
LE O
EMS ONS C I
PARALLEL
PARALLEL
BYPASS SWITCH
O OFF
BATT. START
BATT. START
USB RS-232
ON I
Bypass Switch (Q0)
STS Module
1. For information about the communication interfaces, please refer to 4. Communication Interfaces.
2. For how to turn on/ off the bypass switch (Q0), please refer to Figure 2-5.
Modulon DPH Series
Power Module Slots
(Figure 2-4: UPS Internal View (Front View with Door Open))
2-8
Turn on the Bypass Switch (Q0) Turn off the Bypass Switch (Q0)
2
Introduction
(ON) (OFF)
ON I
O OFF
3. For STS module information, please refer to 5.7 STS Module.
4. For the power module slots, please follow on-site requirements to install appropriate
number of power modules (optional) into the slots. Please refer to 5.8 Power Module (Optional) for relevant information.
2.7 Rear View
WARNING:
Only authorized Delta engineers or service personnel can perform installation, wiring, panel & cover removal, maintenance and operation. If you want to execute any action mentioned above by yourself, the action must be under the supervision of authorized Delta engineers or service personnel.
The rear view of the UPS is shown in Figure 2-6. Please remove the rear panel (there are eight screws (see Figure 2-7) to see the wiring terminals shown in Figure 2-8 ~ Figure 2-10.
(ON) (OFF)
ON I
O OFF
ON I
O OFF
90°
(Figure 2-5: Turn On/ Off the Bypass Switch (Q0))
ON I
O OFF
90°
(Rear) (Rear)
M5 Screw X 8
Rear Panel
(Figure 2-6: UPS Rear View) (Figure 2-7: UPS Rear Panel and Screw Location)
2-9
32
32
32
32
32
32
35
T
S
R
N
N
BYPASS I/P
BYPASS I/P BYPASS I/P MAIN I/P
T
MAIN I/P
R
MAIN I/P
(Rear View after Rear Panel Removal)
42
42
42
41
Bypass Input T erminals AC Input Terminals
32
32
323232
32
35
BYPASS I/P BYPASS I/P BYPASS I/P MAIN I/PTMAIN I/PRMAIN I/P
BYPASS I/P
TSRNN
22 22 2221 21 21
(Figure 2-8: Wiring Terminals_ AC Input & Bypass Input)
UPS Output Terminals
N
T
S
R
T T
BYPASS I/P
R R
S S
N N
(Rear View after Rear Panel Removal)
Modulon DPH Series
41
42
42
42
(Figure 2-9: Wiring Terminals_ UPS Output)
2-10
2
Introduction
(Rear View after Rear Panel Removal)
(Figure 2-10: Wiring Terminals_ Battery Input & Grounding)
Grounding Terminals
( & )
Battery Input Terminals
N
2.8 Tri-color LED Indicator & Buzzers
Please see Figure 2-11 for the location of the tri-color LED indictor. For information about the tri-color LED indicator, please refer to Table 2-1. For information about the 10” color touch panel, please refer to 7. LCD Display and Settings.
MEASUREMENT
UPS-1.1 SETUP MAINTENANCE
Power Flow
POWER FLOW
Maintenance
Power Flow
Bypass
Bypass
Summary
Mains
System Status
90 %
5 mins
(Figure 2-11: Tri-color LED Indictor Location)
LOG IN
EVENT LOG
User
Load 30 %
10:15
May 25,2018
Bypass
Tri-color LED Indicator
2-11
Open the UPS front door and find the buzzers at the rear of the UPS front door. Please see
Figure 2-12.
(UPS Front View with Door Open)
Buzzer
BYPASS SWITCH
A
B D N G
A B D N
G
T
SE
E
BMS
R
US
MODB
DISPLAY
EMS ICONSOLE
A B
D N G A
B D N G
S
BM S DBU O M
ET RES
DISPLAY
EMS ICONSOLE
ON I
Buzzer
(Figure 2-12: Buzzers Location)
Please refer to the table below for the status of the tri-color LED indicator and buzzers.
Table 2-1: Tri-color LED Indicator & Buzzers
Tri-color LED
Indicator
Status Meaning
1. The UPS is running in online mode and the text ‘On­Line’ appears in the upper right corner of the screen.
2. The UPS is running in ECO mode and the text ‘ECO’ appears in the upper right corner of the screen.
Green ON
3. The UPS is running in frequency conversion mode and the text ‘Frequency Conversion’ appears in the upper right corner of the screen.
4. The UPS is running in green mode and the text ‘Green’ appears in the upper right corner of the screen.
Modulon DPH Series
2-12
2
Introduction
Tri-color LED
Indicator
Yellow ON
Status Meaning
1. The UPS is running in bypass mode and the text ‘Bypass’ appears in the upper right corner of the screen.
2. The UPS is running in battery mode and the text ‘Battery’ appears in the upper right corner of the screen.
3. The UPS is running in standby mode and the text ‘Standby’ appears in the upper right corner of the screen.
4. The UPS is in the soft start status and the text ‘Softstart’ appears in the upper right corner of the screen.
5. The UPS is in the energy recycle status and the text ‘Energy Recycle’ appears in the upper right corner of the screen.
6. There is a minor or medium warning and the buzzers sound.
Warning Level Buzzer Frequency
Minor
Medium
The buzzers beep 0.5 second for
every three seconds.
The buzzers beep 0.5 second for
every second.
Red ON
To clear the warning, please refer to 10. Troubleshooting.
There is a major warning and the buzzers sound.
Warning Level Buzzer Frequency
Major Long beep
To clear the warning, please refer to 10. Troubleshooting.
2-13
Modulon DPH Series
2-14
3
Operation Modes
3
Operation Modes
3.1 Single Input
3.2 Dual Input
3.3 Hot Standby Redundancy (Only For Dual Input & At Least Two UPSs)
3.4 Common Battery (Only For At Least Two Parallel UPSs)
3-1
The UPS runs in eight basic operation modes, which are online mode, battery mode, bypass mode, manual bypass mode, ECO mode, frequency conversion mode, green mode and energy recycle mode. Besides these eight operation modes, the UPS is also designed for common battery application and hot standby redundancy. Please see the following sections for relevant information.
127(௓
1. The UPS must be connected with a Delta or non-Delta external maintenance bypass cabinet. The Delta external maintenance bypass cabinet is optional, and the non-Delta external maintenance bypass cabinet is user-supplied and should be handled and configured by Delta service personnel. For the Delta or non-Delta external maintenance bypass cabinet’s information, please refer to the table below.
There are two models for selection. Please refer to the table below.
Delta External Maintenance Bypass Cabinet (Optional)
Model 3915101965-S 3915101964-S
Delta External
Maintenance
Bypass Cabinet
(Optional)
Non-Delta
External
Maintenance
Bypass Cabinet
(User-supplied,
handled and
configured by
Delta service
personnel)
3 Switches (Input
Switch Q’ty
Wiring Type Top & Bottom Wiring Top & Bottom Wiring
NOTE:௓)RU PRUH LQIRUPDWLRQ DERXW WKH 'HOWD H[WHUQDO
maintenance bypass cabinet (optional), please refer to its user manual.
For configurations of the non-Delta external maintenance bypass cabinet, please refer to the following. a. Selection of three or four breakers (switches):
(1) Three breakers (switches):
An input breaker (switch), a manual bypass breaker (switch) and an output breaker (switch) should be installed.
(2) Four breakers (switches):
An input breaker (switch), a bypass breaker (switch), a manual bypass breaker (switch) and an output breaker (switch) should be installed.
c. Each breaker (switch) mentioned above must be a 3-pole (R/ S/
T) device and meets the specifications defined in Table 5-3.
d. It is suggested that each breaker (switch) should be configured
with an auxiliary contactor. For relevant information, please refer
to 4.1.4 External Switch/ Breaker Status Dry Contacts.
e. Install the non-Delta external maintenance bypass cabinet next
to the UPS or align it with the UPS for convenient operation.
Switch/ Manual Bypass
Switch/ Output Switch)
4 Switches (Input Switch/ Bypass Switch/ Manual Bypass Switch/
Output Switch)
Modulon DPH Series
3-2
3
Operation Modes
127(௓If there are switches but not breakers installed in the external
maintenance bypass cabinet, please install (1) an additional protective device between the input power and the external maintenance bypass cabinet and (2) an additional protective device between the connected critical loads and the external maintenance bypass cabinet. The protective device could be a breaker or a fuse. For the protective device’s rating current, please refer to the table below.
200kVA 300kVA 400kVA 500kVA
400A 600A 800A 1000A
2. In this user manual, the meaning of Q0, Q1, Q2, Q3, Q4 and Q5 represents the following.
Code Meaning
Q0 UPS’s Bypass Switch
Q1
Q2
Q3
Q4
Delta or non-Delta External Maintenance Bypass Cabinet’s Input Breaker or Switch
Delta or non-Delta External Maintenance Bypass Cabinet’s Bypass Breaker or Switch
Delta or non-Delta External Maintenance Bypass Cabinet’s Manual Bypass Breaker or Switch
Delta or non-Delta External Maintenance Bypass Cabinet’s Output Breaker or Switch
Q5 External Battery Cabinet’s Breaker
3. The structure of the UPS and the Delta or non-Delta external maintenance bypass cabinet
is shown in Figure 3-1 (single input application) and Figure 3-2 (dual input application).
Delta or non-Delta External Maintenance Bypass Cabinet
Q3
UPS
MAIN LOAD
Q1 Q0 Q4
Static Switch
Rectifier Inverter
Batteries
(Figure 3-1: Single Input Application_ UPS and Delta or non-Delta
Q5
External Maintenance Bypass Cabinet Structure)
3-3
Delta or non-Delta External Maintenance Bypass Cabinet
Q3
UPS
BYPA.
Q0Q2
MAIN LOAD
Q1 Q4
Q5
Batteries
(Figure 3-2: Dual Input Application_ UPS and Delta or non-Delta
External Maintenance Bypass Cabinet Structure)
Static Switch
Rectifier Inverter
4. Up to eight UPS units can be paralleled for redundancy and capacity expansion. Only UPSs with the same capacity, voltage and frequency can be paralleled. Please only use the provided parallel cable to parallel the UPS units. Otherwise, parallel functions will fail.
3.1 Single Input
3.1.1 Online Mode_ Single Input_ Single Unit
In online mode, the main AC source supplies AC power via the Delta or non-Delta external maintenance bypass cabinet’s Input Breaker or Switch (Q1) and the UPS’s Bypass Switch (Q0) to the rectifier, and the rectifier converts the AC power to DC power and supplies the DC power to the inverter. In the meantime, the rectifier provides charging power to the batteries. After receiving the DC power, the inverter converts it into clean and stable AC power to the connected critical loads via the Delta or non-Delta external maintenance bypass cabinet’s
Output Breaker or Switch (Q4). Please refer to Figure 3-3. During online mode, the UPS’s
tri-color LED illuminates green and the text ‘On-Line’ appears in the upper right corner of the screen.
Modulon DPH Series
3-4
Loading...
+ 202 hidden pages