Delta HEX150PC, HEX260PA-A Instruction Manual

HEX150PC Heat Exchanger
Instruction Manual
USA 46101 Fremont Blvd, Fremont, CA 94538, U.S.A. TEL : 1-510-668-5100 FAX : 1-510-668-0680 Cabinet-Thermal-Solutions@deltaww.com Taiwan Delta Electronics, Inc. 252, Shang Ying Road, Kuei San District TEL : 886-(0)3-3591968 Taoyuan City 33341, Taiwan, R. O. C. FAX : 886-(0)3-3591991
Table of contents
1. Version ......................................................................................................... 1
2. Description ................................................................................................... 1
2-1. General ................................................................................................ 1
2-2. Specification ....................................................................................... 1
2-3. Environmental condition ................................................................... 2
3. Installation ................................................................................................... 2
3-1. Outline drawing .................................................................................. 2
3-2. Mounting panel cutout and waterproof foam sticking .................... 3
4. Electrical specification ................................................................................ 3
4-1. Connection and LED indicator (on HEX panel) ................................ 3
4-2. Standalone control mode ................................................................... 5
5. Mechanical feature ...................................................................................... 6
5-1. Thermal path and Airflow baffle ....................................................... 6
5-2. Configuration ..................................................................................... 6
6. Maintenance and Replacement .................................................................. 7
6-1. Maintenance ....................................................................................... 7
6-2. Replacement ...................................................................................... 8
7. MTBF and Reliability ................................................................................... 8
7-1. MTBF................................................................................................... 8
7-2. Relibability ......................................................................................... 8
8. Safety ............................................................................................................ 9
9. Accessory .................................................................................................... 9
9-1. Power cable ........................................................................................ 9
9-2. Function cable ................................................................................... 9
10. General Safety and Warnings ................................................................... 9
HEX150PC Heat Exchanger Instruction Manual
Page 1
1. Version
Rev. Description Drawn Approved Issue date
00 Issue spec. Nick Wang Adam Chen 2016/1/25 01 Add sectioni 10 Nick Wang Adam Chen 2016/6/10
2. Description
2-1 . General
Delta Heat Exchanger (HEX) is designed for direct air to air heat
exchange to remove heat from the cabinet.
The internal and the external air circulation loops of the HEX are separated to prevent the introduction of dust, humidity and dirt. The fan on the external air loop conforms to IP55 protection rating.
2-2 . Specification
Main feature Unit
Model Number
HEX150PC
Outline Dimension (H x W x D)
mm
(in)
690 x 550 x 242
(27 x 22 x 10)
Cooling Capacity (*Note 1)
W/K (W/)
100 (56) 135 (75) Rated Voltage VDC 48 Rated Current (*Note 2) A 6.3 Operating Voltage Range VDC 40 - 60 Operating Current A 2.6 5.8 Operating Power Consumption W 125 279 Acoustic Noise at 1.5M (SPL) dB-A 65.0 73.0 Weight Kg (Lb) 20 (44)
* Note1 : The cooling capacity (W/K , W/°C or W/) is defined as Q/ (TI-TA)
Q : Heat dissipation (W) from inside of cabinet TI : Return temperature of internal air circuit (K , °C or ) TA : Ambient temperature of external air circuit (K , °C or )
*Note 2 : Rated current is announcement of safety
HEX150PC Heat Exchanger Instruction Manual
Page 2
2-3 . Environmental condition
Description Specification
Operating
-10°C ~ +65°C (-14°F ~ 149°F)
Storage
-40°C ~ +70°C (-40°F ~ 158°F)
Humidity
External air circuit: 0 ~ 100% RH
Ingress protection (on external side)l
IEC60529 IP55 (NEMA 3) GR-487 720hrs salt spray
3. Installation
3-1 . Outline drawing
(1) Material : Aluminum sheet t=1.5mm (2) Finish : Power paint , Color RAL7032 (3) Dimensional tolerance : ± 1mm [0.04”]