Delta DPT-2000 User Manual

IOM-DPT-A: FEB 2014
DELTA CONTROLS
MANUFACTURE OF PRESSURE TRANSMITTERS
AND CONTROL INSTRUMENTS
USER’S MANUAL
SMART TEMPERATURE TRANSMITTER
type: DPT-2000ALW
FEB 2014
DELTA CONTROLS LTD., Island Farm Avenue, West Molesey, Surrey, KT8 2uz tel. +44 (0) 20 8939 3570; fax +44 (0) 20 8783 1163
www.delta-controls.com, e-mail: sales@delta-controls.com
Symbol
Description
Warning to proceed strictly in accordance with the information contained in the documentation in order to ensure the safety and full functionality of the device.
i
Information particularly useful during installation and operation of the device.
Information particularly useful during installation and operation of a type Ex device.
Information on disposal of used equipment
Symbols used
BASIC REQUIREMENTS AND SAFE USE
- The manufacturer will not be liable for damage resulting from incorrect installation,
failure to maintain the device in a suitable technical condition, or use of the device other than for its intended purpose.
- Installation should be carried out by qualified staff having the required authorizations to install electrical and pressure-measuring devices. The installer is responsible for performing the installation in accordance with these instructions and with the electromagnetic compatibility and safety regulations and standards applicable to the type of installation.
- The device should be configured appropriately for the purpose for which it is to be used. Incorrect configuration may cause erroneous functioning, leading to damage to the device or an accident.
- In systems with pressure transmitters there exists, in case of leakage, a danger to staff on the side where the medium is under pressure. All safety and protection requirements must be observed during installation, operation and inspections.
- If a device is not functioning correctly, disconnect it and send it for repair to the manufacturer or to a firm authorized by the manufacturer.
In order to minimize the risk of malfunction and associated risks to staff, the device is not
to be installed or used in particularly unfavourable conditions, where the following dangers occur:
- possibility of mechanical impacts, excessive shocks and vibration;
- excessive temperature fluctuation,
- condensation of water vapour, large dust, icing.
Installation of intrinsic safety versions should be performed with particular care, in accordance with the regulations and standards applicable to that type of installation.
Changes to the products manufacturing documentation may forestall a paper user updating. Current Instruction Manual is available at Producer http on www.delta-controls.com.
1 IOM-DPT-A: FEB 2014
CONTENTS
I. APPENDIX Exd ............................................................................................................................. 2
II. APPENDIX Exi. ............................................................................................................................. 7
1. INTRODUCTION ......................................................................................................................... 11
2. USER MATERIALS ..................................................................................................................... 11
3. APPLICATIONS AND MAIN FEATURES ................................................................................... 11
4. IDENTIFYING MARKS. ORDERING PROCEDURE .................................................................... 11
5. TECHNICAL DATA ..................................................................................................................... 12
5.1. ELECTRICAL PARAMETERS .................................................................................................................12
5.2. METROLOGICAL PARAMETERS. ...........................................................................................................13
5.3. MEASUREMENT RANGES. ...................................................................................................................13
5.4. OPERATING CONDITIONS. ..................................................................................................................14
5.5. CONSTRUCTION MATERIALS ...............................................................................................................15
6. CONSTRUCTION. ....................................................................................................................... 15
6.1. MEASUREMENT PRINCIPLES. .............................................................................................................15
6.2. CONSTRUCTION ...............................................................................................................................15
6.2.1. Transmitter casing ...................................................................................................................................... 16
6.2.2. Electronic board with display .................................................................................................................... 16
6.2.3. Shields of the measuring insert ................................................................................................................ 16
7. INSTALLATION OF TRANSMITTERS ........................................................................................ 16
8. ELECTRICAL CONNECTION ..................................................................................................... 16
8.1. GENERAL RECOMMENDATIONS ...........................................................................................................16
8.2. ELECTRICAL CONNECTIONS ...............................................................................................................16
8.4. EARTHING .......................................................................................................................................17
9. SETTING AND REGULATION ................................................................................................ .... 17
9.1. MEASUREMENT RANGES, DEFINITIONS ................................................................................................17
9.1.1. Nominal range ............................................................................................................................................. 17
9.1.2. Set range ...................................................................................................................................................... 17
9.1.3. Factory range............................................................................................................................................... 17
9.2. CONFIGURATION AND CALIBRATION ....................................................................................................18
9.3. CALIBRATION. ..................................................................................................................................24
10. INSPECTIONS AND SPARE PARTS .......................................................................................... 24
10.1. PERIODIC INSPECTIONS ...................................................................................................................24
10.2. UNSCHEDULED INSPECTIONS ...........................................................................................................24
10.3. SPARE PARTS. ...............................................................................................................................24
11. PACKING, STORAGE AND TRANSPORT. ................................................................................. 24
12. GUARANTEE .............................................................................................................................. 24
13. ADDITIONAL INFORMATION ..................................................................................................... 24
14. FIGURES. .................................................................................................................................... 25
Fig.1. DPT... transmitters – block diagram. ............................................................................................................ 25
ELECTRICAL CONNECTIONS FOR DPT... TRANSMITTERS ..............................................................................25
Fig.2a. The link of transmitter and communicator or modem to current line by the switch box ( in case of the
resistance in current loop is higher than 250Ω). ................................................................................................... 25
Fig.2b. The link of transmitter and communicator or modem to <SIGNAL+> <SIGNAL-> transmitter terminals in
case of the resistance in current loop is higher than 250Ω. ................................................................................. 26
Fig.2c. The link of transmitter and communicator or modem to <SIGNAL+> <TEST+> transmitter terminals in
case of the resistance in current loop is smaller than 250Ω. ................................................................................ 26
Fig.2d. The link of transmitter and communicator or modem to <SIGNAL+> <SIGNAL-> transmitter terminals in
case of the resistance in current loop is smaller than 250Ω. ................................................................................ 27
Fig.3. DPT-2000ALW smart temperature transmitter ............................................................................................. 28
Fig.4. DPT... display rotation possibility, configuration buttons. ............................................................................ 29
Fig.5. Back lighting jumper view at transmitter electric board (unit display back side) ......................................... 29
Fig.6. The types of shields of measuring insert. ..................................................................................................... 30
Fig.7. The explosion - proof joints of DPT-2000ALW transmitter. .......................................................................... 31
Fig.8. How to lead the casing of DPT-2000ALW transmitter.................................................................................. 32
2 IOM-DPT-A: FEB 2014
1180
1453
i
i
I. APPENDIX Exd
DPT–2000ALW TEMPERATURE TRANSMITTER
1. Introduction
1.1. This “Appendix Exd.01” applies to transmitters of type DPT-2000ALW in Exd versions only, marked on the rating plate as shown in 3 and denoted Exd in the Product Certificate.
1.2. The appendix contains supplementary information relating to the Exd (flame-proof) versions of mentioned transmitters. During installation and use of Exd transmitters, reference should be made to DTR.DPT.ALW.03
in conjunction with “Appendix Exd.01”.
2. Use of DPT–2000ALW transmitters in danger zones
2.1. The transmitters are produced in accordance with the requirements of the following standards: EN 60079-0:2012, EN 60079-1:2007, EN 60079-11:2012, EN 60079-26:2007, EN 60079-31:2009.
2.2. The transmitters may operate in areas where there is a risk of explosion, in accordance with the rating of the explosion protection design:
I M2 Ex d ia I Mb (steel enclosure only) II 1/2G Ex ia/d IIC T* Ga/Gb II 1/2D Ex ia/t IIIC T* Da/Db
-40°C <= Ta <= +45°C/+75°C KDB 13 ATEX
T* - temperature class for transmitter (for gases) or a maximum surface temperature (for dust) derived in
clause 5.3 and 5.4.
2.3 Transmitter category and hazard areas.
The category 1/2G, contained within the rating, means that the transmitter may be installed within a type 1 or 2 hazard zone. The process connections may connect to a 0 zone type (see the diagram below for an example).
3. Identifying marks.
Flame-proof transmitters must have a rating plate containing the information specified in paragraph 4.1 of DTR.DPT.ALW.03 and also at least the following:
- CE mark and number of notified unit: mark,
- Designation of explosion protection design, certificate number,
- Power supply,
- Process connection,
- Year of manufacture,
- Temperature use range,
4. User information.
Together with the ordered transmitters, the user will receive:
a) Product Certificate b) Declaration of conformity c) Copy of certificate – on request d) User’s Manual numbered: DTR.DPT.ALW.03 with Appendix Exd0.1.
User can find them b), c), d) at www.delta-controls.com
5. Power supply and exploitation of transmitters
5.1. The transmitter connecting should be made after introduction with present instruction content. Electrically transmitter should be connected according to scheme at p.6 Appendix Exd.01. Transmitter
electrical installation should be realised with engineering standard requirements.Electrical connections of transmitters in danger zone should be made by people who have indispensable knowledge and experience in this branch.
5.2. Earth clamps must be used with earth transmitters. In the event that transmitters come in contact with structural metal parts or pipes which are connected to the equipotential bonding system, transmitters do not require to be earthed. Transmitters should be supplied from DC electrical source with voltage max.45V from transformer feeders or other devices which have at least a strengthened isolation among
Exd VERSION
3 IOM-DPT-A: FEB 2014
Temperature transmitter
Tp
Thermal shield
Safe area
Safe area
Zone 0
Zone 0
Temperature transmitter
measuring insert
Shield of the
Zone 1 or 2
Tap
Thermal shield
Tp
Zone 1 or 2
Shield of the measuring insert
Tap
Thermal isolation
Thermal isolation
Tp[C]
Temperature class and ambient temperature Ta[C]
Tp75C
T6 and Ta=45C T5 and Ta=75C
Tp>75C
T4 and T5 Ta=70C T3 and T2 Ta=65C T1 Ta=60C
i
primary and secondary windings in which don’t appear voltage higher than 250V. The duty of power supply installation with above mentioned requirements rests on user.
Appendix Exd.01
5.3. Measurements of operating temperature of transmitter
5.3.1. After installing the DPT-2000ALW transmitter for the medium maximum expected temperature and
expected the maximum ambient temperature measure out Tp temperature of the most hot place on the surface of transmitter and determine the temperature transmitter class or a maximum surface temperature according to p. 5.4.
When measuring the warmed media, above ambient, is recommended to determine the temperature of the stub while is screwed into the transmitter or at the wall of the pipe or tank as shown below.
5.3.2. When medium is heated above ambient temperature it is allowed to determine the temperature class of the transmitter or the maximum surface temperature Tp through the adoption of a maximum temperature of the medium which provides the technological process. Measurement of Tp isn’t then necessary. If during the measurement of Tp for maximum temperature expected for the medium is not possible to ensure the maximum expected ambient temperature after the measurement of Tp one can estimate the potential growth in temperature Tp due to the increase of ambient temperature.
5.3.3. If the other elements of the plant have or may have a temperature higher than the highest temperature Tp on the transmitter, security conditions must be ensured in accordance with accepted principles in such cases
5.4. Determination of the transmitter temperature class T * for gas and the maximum surface temperature
1. Determine the temperature class of the transmitter for the gas or the maximum temperature for
combustible dust depending on the temperature Tp from the formula:
T*Tp+0,1Tp+5K for class T3..T6
T*Tp+0,1Tp+10K for class T1, T2
2. Determine the maximum surface temperature transmitter for combustible dust from the formula: T*Tp+0,1Tp
3. The following table contains the values of permissible ambient temperature depending on the
temperature Tp and temperature class of the transmitter.
Tp- transmitter temperature measured in clause 5.3
4 IOM-DPT-A: FEB 2014
Ex power supply
see p.5..
_
+
TEST
short-circuit( jumper)
Fuse: In = 0,05A, Un = 250V
according to EN 60127
RD
Communicator

Safe area
_

TEST
SIGNAL
_
+
.
32
VWX
MNO
DEF
YZ#
5 6
PQR*+/
9
GHI
8 0
@%&
1
4
JKL
7
STU
ABC
REF2PV F4
F3 F4PFF1
+
Ro
Hazardous area
i
i
i
In the case of significant increase in medium temperature measurement of Tp must be executed again and again must be specified the temperature class for the gas or the maximum surface temperature combustible dust.
5.5. With regard on kind of casing material (light alloy with large aluminium content), the user is obliged to assure, that possibility of hitting casing does not step out in place of transmitter installation.
5.6. In transmitter casing are two holes to assembly of cable intakes from thread M20x1,5 or 1/2 NPT.
5.7. Normally transmitters are delivered without installed glands but with blank plugs (corks) in the second hole. They are at table 1 and table 2 at list of packing glands and plugs agreeable with production documentation and accepted by certificate station. Customer should install packing glands according to tables 1 and plugs according to tables 2 (if plugs aren’t installed) or other accordance with flame-proof standards.
5.8. It is necessary apply a shield cable or without shield cable with round cross-section in protection from elastomer, not moisture absorbing, for example: YKSLY 2 * 1, YnTKSYekw 1 * 2 * 1, LIYCY 2 * In case of need of use cable about different building customer should co-ordinate this with transmitters manufacturer to choose intakes with cable diameter.
5.9. The general principles of connecting and the exploitation of transmitter in Exd realization should be
compatible with principles and relating standards for Exd casing devices how in p.2.1, in this including also : EN600079-14, EN60079-17.
5.10. During service must be made a check of the tight fastening of covers and the packing glands and the fastening of the cable in the glands. The casing and supply line must be inspected for mechanical damage, and the transmitter rating plate for legibility. Periodic checks should also be made of the diaphragm, which should not carry signs of damage. During maintenance it is recommended that the threads of the covers be lubricated with non-acid vaseline.
Because of the transmitter damage possibility, the ambient temperature should not be allowed to become higher than 80C, even when there is no explosion risk.
6. How to connect Exd transmitter DPT-2000ALW
5 IOM-DPT-A: FEB 2014
Type of packing glands
Producer
Screw
Feature
Other marking
No of certificate
Note
501/423
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A
Baseefa 06 ATEX 0056X
501/421
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A
Baseefa 06 ATEX 0056X
ICG 623
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A
Baseefa 06 ATEX 0058X
501/453
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A
Baseefa 06 ATEX 0056X
*
501/453/RAC
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A
Baseefa 06 ATEX 0056X
*
501/453/Universal
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A
Baseefa 06 ATEX 0057X
*
ICG 653
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A
Baseefa 06 ATEX 0058X
* 8163/2-A2F
STAHL
M20x1.5
EXd IIC
SIRA06ATEX1188X
A2F, A2FRC, SS2K
CMP­Products
M20x1,5
Exd IIC
SIRA06ATEX1097X
E1FW, E1FX/Z, E2FW, E2FX/Z
CMP­Products
M20x1,5
Exd IIC
SIRA06ATEX1097X
*
T3CDS, T3CDSPB
CMP­Products
M20x1,5
Exd IIC
SIRA06ATEX1283X
*
PX2K, PXSS2K, PX2KX, PXB2KX
CMP­Products
M20x1,5
Exd IIC
SIRA06ATEX1097X
*
Type of plug
Producer
Screw
Feature
Other marking
No of certificate
Note
AGRO AG
M20x1,5
Exd IIC
Nr kat.
475
HAWKE
M20x1,5
Exd IIC
477
HAWKE
M20x1,5
Exd IIC
i i
i
Appendix Exd.01
In danger zone don’t unscrew transmitter covers and don’t change the display position or
its back lighting.
In case of transmitter calibration outside danger zone is possible communicator connecting to <SIGNAL+> and <TEST+> terminals. Transmitter is furnished in communication resistor (RD = 240Ω), closed with jumper at <SIGNAL-> and <TEST-> terminals installed by manufacturer. RD resistor can be use then, when it is necessary to communicate with transmitter from its terminals and the load resistance (Ro) in current loop is lover then 250Ω. Than <SIGNAL-> and <TEST-> terminals have to be open.
Permissible gap of joint is smaller than this was defined in norm EN 60079-1:2008 and can not be greater than passed value on fig. 7.
Blocking cover method before unscrewing and plumbing possibility is shoved at fig 8.
It is not permitted to repair or otherwise interfere with the transmitter’s electrical circuits
in any way. Damage estimation and repair possibility may be assessed by the manufacturer or another authorized party only.
Table 1 Permitted packing glands.
Table 2. permitted plugs
*) for special cable only.
6 IOM-DPT-A: FEB 2014
i
i
Specific conditions of use:
Permissible gap of flameproof joint marked L4 is less than defined in norm EN 60079-1:2007 and cannot be greater than passed value on fig. 7.
Temperature class (T* for gases) or maximum surface temperature (T* for dust ) depends mainly on the temperature of the process (temperature of the controlled medium), and the method of installation on site. Therefore, to determine the temperature Tp hottest places on the surface of the transducer housing (practically cover the sensor) in contact with explosive atmosphere in conditions of installation on site and proceed in accordance with p.5.3 Appendix Exd.01.
7 IOM-DPT-A: FEB 2014
1180
1453
Shield of the measuring insert
Temperature transmitter
Zone 0 Zone 1 or 2 Safe area
i
Appendix Exi
II. APPENDIX Exi.
DPT–2000ALW TEMPERATURE TRANSMITTER
1. Introduction
1.1. This “Appendix Exi” applies to transmitters of type DPT-2000ALW in Ex versions only, marked on
the rating plate as shown in 2 and 3 and denoted Ex in the Product Certificate.
1.2. The appendix contains supplementary information relating to the Ex versions of these transmitters.
During installation and use of Ex transmitters, reference should be made to DTR.DPT.ALW.02(ENG) in
conjunction with “Appendix Exi”.
2. Use of DPT–2000ALW transmitters in danger zones.
2.1. The transmitters are produced in accordance with the requirements of the following standards:
EN 60079-0:2012, EN 60079-11:2012, EN 60079-26:2007, EN 50303:2000
2.2. The transmitters may operate in areas where there is a risk of explosion, in accordance with the rating of
the explosion protection design:
COMING SOON!
(the temperature class of transmitter depends from medium temperature)
2.3. Transmitter category and hazard areas
The category 1/2G, contained within the rating, means that the transmitter may be installed within a type
1 or 2 hazard zone. Shield of the measuring insert DPT-2000ALW, may connect to a 0 zone type (see the diagram below for an example).
Exi VERSION
3. Identifying marks..
Intrinsically safe transmitters must have a rating plate containing the information specified in paragraph 4.1 of.
DTR.DPT.ALW.03 and also at least the following:
CE mark and number of notified unit  designation of explosion protection design, certificate number  values of parameters such as. Ui, Ii, Ci, Li,  year of manufacture
8 IOM-DPT-A: FEB 2014
Rw
Uo
I DIi
Io
Io
Ui
Uo
Q
I
Rw
U
Q
Ii
transmitter
U
Q
2
U
Q
I
0
U0(UQ –U0) Rw
transmitter
4P
0
I
0
Appendix Exi
4. User information.
Together with the ordered transmitters, the user will receive:
a) Product Certificate, b) Declaration of conformity c) Copy of certificate – on request d) „User’s Manual numbered: „DTR.DPT.ALW.03” with Appendix Exi..
User can find them at www.delta-controls.com
5. Permitted input parameters (based on data from the FTZÚ 14 ATEX
certificate, and certification documentation).
The transmitters should be powered via the associated power feeding and measurement devices provided with the relevant intrinsic-safe certificates. The parameters of their outputs to the danger zone should not exceed the limit power supply parameters for the below specified transmitters.
Temperature classes T4, T5, or T6 depend on the input power and maximum ambient temperature – see p.
5.1, 5.2, 5.3.The ambient temperature range is reduced to Ta = -20ºC to +60ºC if the devices is installed as group I M1 equipment. External connections are made via integral terminals and cable glands which must be of certified type if they are mounted on the version f or combustible dust hazard application.
5.1. - for power supply with a “linear“ characteristic Ui = 30V Ii = 0,1A Pi = 0,75W Ta ≤ 80ºC and T4, Ta 70C and T5, Pi = 0,45W Ta ≤ 40ºC and T6 Power supply with a “linear” characteristic may be e.g. a typical barrier with parameters
Uo = 28V Io = 0.093A Rw = 300.
Fig.1. Power supply from a source with “linear” characteristic
5.2.for power supply with a “trapezial” characteristic
Ui = 24V Ii = 50mA Pi = 0,6W Ta 80°C and T5 and Pi = 0,45W Ta 40°C and T6
Example of power supply from a source with “trapezial” characteristic (see Fig. 2).
Fig. 2. Power supply from a source with “trapezial” characteristic
If Uo < then parameters Uq, Io, Po are interrelated as follows:
UQ = , Rw = , P0 = for U0 ≤ 1/2U
5.3. - for power supply with “rectangular” characteristic Ui = 24V Ii = 25mA Pi = 0,6W Ta 80C and T5
The supply of power from a source with a “rectangular” characteristic means that the voltage of the Ex power
supply remains constant until current limitation activates.
The protection level of power supplies with a “rectangular” characteristic is normally “ib”. The transmitter powered from such a supply is also a Ex device with protection level “ib”.
Example of practical provision of power supply.
use a stabilized power supply with Uo=24V with protection level „ib” and current limited to Io=25mA.
Q
9 IOM-DPT-A: FEB 2014
In hazardous areas, connections to the control terminals must be made using only instruments which are permitted to be used in such areas.
mA
Ex-Milliammeter
TEST
To measure the current in the transmitter without disconnecting the signalling circuit, connect a milliammeter to control sockets <TEST+>, <TEST->.
Hazardous area Safe area
Aplisens KAP-03Ex Communicator
_
_
+
TEST
SIGNAL
+

RD
.
32
VWX
MNO
DEF
YZ#
5 6
PQR*+/
9
GHI
8 0
@%&
1
4
JKL
7
STU
ABC
REF2PV F4
F3 F4PFF1
Jumper
a Ex power supply see p.5.
+
Ro
_

28V – 13.5V** – (300Ω* * 0,02A)
0,023A
Uzas. – 13.5V** 0,023A
i
Delta Controls KAP-03Ex Communicator
Appendix Exi
5.4. Input inductance and capacity: Ci = 20nF, Li = 1,1mH
5.5. Supply voltage min.: 13.5VDC **
5.6. Load resistance:
from 28V linear supply
Ro max [Ω] = for transmitter without display back lighting from a source with “trapezial” or “rectangular” characteristic supply
Ro max [Ω] = *) barrier resistance
**) 16,5V for transmitter with display back lighting
5.7. Temperature
Temperature of transmitter’s surface from regard temperature of shield part as on figure in point 2.3. can't
surpass the admissible values of temperatures for temperature class of steam and gases according with standard PN-EN 60079-0. Simultaneously the casing temperature should not surpass max. temperature value Ta definite for conditions power supply in Certificate Exi and p.5 of Appendix Exi.
6. How to connect Ex transmitters DPT-2000ALW.
The transmitter and other devices in the measuring loop should be connected in accordance with the intrinsic-safety and explosion-safety regulations and the conditions for use in dangerous areas.
Failure to observe the intrinsic-safety regulations can cause explosion and the resulting hazard to people.
The transmitter is equipped in additional communication resistor RD = 240 Ω. During normal operation terminals <Signal –> and <Test –> are shorted. RD resistor is used when you wish to communicate with the transmitter locally (from its terminals) and Ro < 250. Terminals <Signal –> and <Test –> must be opened.
Transmitter electrical installation should be realised with engineering standard requirements.
It is not allowed to repair or otherwise interfere with the transmitter’s electrical circuits in any
way. Damage and possible repair may be assessed only by the manufacturer or another authorized party.
10 IOM-DPT-A: FEB 2014
i
i
Specific conditions of use
Allowed operating temperature range specified in point 5 Appendix Exi Operating temperature range is restricted in the range of Ta = -20°C to 60°C if the device is
operating in a Group I M1.
Loading...
+ 25 hidden pages