DELTA CME-PD01 User Manual

2007-10-12
5011650001-PDS1
Profibus Communication Module (CME-PD01) Instruction Sheet
Profibus is a registered trademark of Profibus International. Please thoroughly read and understand the following contents to ensure correct use before operation. The content of this instruction sheet may be revised without prior notice. Please consult our distributors or
A. Panel Appearance
NET LEDAddress Switches
SP LED
C. Parameters Setting in VFD-E
Baud Rate 9600 Pr.09.01=1
ADDH
ADDL
SPNET
CME-PD01
RTU 8, N, 2 Pr.09.04=3
Freq. Source Pr.02.00=3
Command Source Pr.02.01=3
D. Power Supply
The power of CME-PD01 is supplied from VFD-E. Please connect VFD-E to CME-PD01 by using 8 pins RJ-45 cable,
RS-485 (RJ45)
1: Reserv ed 2: EV 3: GND 4: SG- 5: SG+ 6: Reserved 7: Reserv ed 8: Reserved
which is packed together with CME-PD01. After connection is completed, CME-PD01 is powered whenever power is applied to VFD-E.
E. PROFIBUS Address
VFD-E
Profibus-DP Interface (DB9)
1. SP LED: Indicating the connection status between VFD-E and CME-PD01.
2. NET LED: Indicating the connection status between CME-PD01 and PROFIBUS-DP.
3. Address Switches: Setting the address of CME-PD01 on PROFIBUS-DP network.
4. RS-485 Interface (RJ45): Connecting to VFD-E, and supply power to CME-PD01.
5. PROFIBUS-DP Interface (DB9): 9-PIN connector that connects to PROFIBUS-DP network.
6. Extended Socket: 4-PIN socket that connects to PROFIBUS-DP network.
B. Dimensions
72.2 [2.84]
]
]
5
4
ADDH ADDL
3
.
1
.
2
[
0
[
7
.
6
.
9
3
5
CME-PB01
]
SPNET
6 2
. 2
[ 3
. 7 5
3.5 [0.14]34.8 [1.37]
CME-PD01 has two rotary s select the PROFIBUS address. The set value via 2 address switches, ADDH and ADDL, is in HEX format. ADDH sets the upper 4 bits, and ADDL sets the lower 4 bits of the PROFIBUS address.
Address Meaning
1..0x7D Valid PROFIBUS address
0 or 0x7E..0xFE Invalid PROFIBUS address
NOTE
Please download the GSD file and user manual at http://www.delta.com.tw/industrialautomation/
Profibus 通讯模块(CME-PD01)说明书
Profibus 为 Profibus international 注册商标。 请详细阅读下列说明后才使用本产品,以确保使用安全。 由于产品精益求精,当内容规格有所修正时,请洽询代理商或至台达网站
(http://www.delta.com.tw/ch/product/em/em_main.asp)下载最新版本。
A. 面板外观
NET LEDAddress Switches
SP LED
C. VFD-E 通讯参数的设定
ADDL
ADDH
Profibus-DP Interface (DB9)
SPNET
CME-PD01
RS-485 (RJ45)
1: Reser ved 2: EV 3: GND 4: SG- 5: SG+ 6: Reser ved 7: Reser ved 8: Reser ved
1. SP LED:变频器与 CME-PD01 连接状态指示
2. NET LED:CME-PD01 PROFIBUS-DP 连接状态 指示
3. 地址设定钮:设定 CME-PD01 PROFIBUS-DP
网络上的通信地址
4. RS-485 通讯口 (RJ-45):与 VFD-E 系列变频器连 接并经由此 port 提供电源给 CME-PD01
5. PROFIBUS-DP 接口 (DB9):用于连接 PROFIBUS-DP 网络
6. 并连插座:使用 4-PIN socket 连接 PROFIBUS-DP
网络
VFD-E
Baud Rate 9600 Pr.09.01=1
RTU 8, N, 2 Pr.09.04=3
Freq. Source Pr.02.00=3
Command Source Pr.02.01=3
D. 电源供应
CME-PD01 电源由所连接之变频器所供给,使用标准通讯传 输线(附于包装盒内,连接 RJ-45,8pins) 连接变频器和 CME-PD01,当变频器上电后,电源即可输入 CME-PD01。
E. 地址设定钮
CME-PD01 提供两个可旋转之地址设定钮来设定,其在 PROFIBUS-DP 网络上的通信地址。两个旋钮包括:ADDH
ADDLADDH 用来设定高 4 位的通信地址,ADDL 用来 设定低 4 位的通信地址,并采用 16 进制。
通信地址 说明
1..0x7D
0 0x7E..0xFE 无效的 PROFIBUS 地址
有效的 PROFIBUS 地址
B. 外观尺寸
ADDH AD DL
3.6 [0.14]
59.7 [2.35]
72.2 [2.84]
CME-PB01
NOTE
请至台达网站下载 GSD 档案及其使用手册 http://www.delta.com.tw/ch/product/em/em_main.asp
SPNET
57.3 [2.26]
34.8 [1.37]
UNIT: mm(inch)