This manual contains important instructions and warnings that you should
follow during the installation, operation, storage and maintenance of this
product. Failure to heed these instructions and warnings will void the warranty.
Please comply with all warnings and operating instructions in this manual strictly.
Save this manual properly and read carefully the following instructions before installing the unit. Do not operate the unit before reading through all safety information
and operating instructions carefully.
z
z
Do not try to repair the unit yourself, contact your local supplier or your warranty
will be void.
z
z
To eliminate any overheating of the battery box, keep all ventilation openings
free from obstruction and do not place any foreign objects on top of the battery
bank. Keep the battery box 20 cm away from the wall.
z
z
Make sure the battery box is installed within the proper environment as specied
(0-40°C and 30-90% non-condensing humidity).
z
z
Do not install the battery box under direct sunlight. Your warranty will be void if
the batteries fail due to overheating.
z
z
This battery box is not designed for use in dusty, corrosive and salty environment.
z
z
The warranty for this battery bank will be void if water or other liquid is spilt or
poured directly onto the battery box. Similarly we do not warrant any damage to
the battery box if foreign objects are deliberately or accidentally inserted into the
battery box enclosure.
z
z
The battery will discharge naturally if the system is unused for a period of time.
z
z
It should be recharged every 2-3 months if unused. If this is not done, then the
warranty will be null and void. During normal operation, the batteries will be automatically remained in charged condition.
z
z
Servicing of batteries should be performed or supervised by trained personnel
with knowledge of batteries and the required precautions.
z
z
When replacing batteries, it is necessary to replace ALL batteries with the same
quantity, type & capacity.
z
z
CAUTION – Do not dispose of battery or batteries in a re. The battery may explode.
Amplon RX Series
1
Page 5
Chapter 1 Important Safety Warnings
z
z
CAUTION – Do not open or mutilate the batteries. The electrolyte from the batteries is toxic and harmful to the skin and eyes.
z
z
CAUTION – Risk of Electric Shock – Hazardous voltage may exist between battery terminals and ground. Test before touching with bare hands.
z
z
CAUTION – A battery can present a risk of electrical shock and high short circuit
current. The following precaution should be observed when working on batteries:
1. Remove watches, rings, or other metal objects.
2. Use tools with insulated handles.
3. Wear rubber gloves and boots.
4. Do not lay tools or metal parts on top of batteries.
5. Disconnect charging source prior to connecting or disconnecting battery terminals.
z
z
Do not plug or unplug the battery connector if UPS works in DC (discharging)
mode.
2
Page 6
Chapter 2 : Product Overview and Setup
NOTE :
Before installation, please inspect the unit. Be sure that nothing
inside the package is damaged. Please keep the original package in a safe
place for future use.
2.1 Rear Panel View
21
EXTERNAL BATT. CONNECTOR
72Vdc,50A max.
1
External battery connector: connects to either UPS or the 2nd battery box.
The battery box is very heavy, be cautious when unpacking
2. Check the inside package:
Amplon RX Series
3
Page 7
Chapter 2 Product Overview and Setup
12
The power behind competitiveness
Delta UPS - Amplon Family
External Battery Box
for RX 3 kVA
User Manual
B TTERY
PACK
www.deltapowersolutions.com
4
PACK
B TTERY
B TTERY
PACK
56
3
No.ItemQuantity
1
2
3
4
5
6
External battery box 1 PC
User manual1 PC
Ear2 PCS
Battery connection cable 1 PC
Screw 8 PCS
Extended stand2 PC
z
z
Selecting Installation Position
It is necessary to select a proper environment to install the unit, in order to
minimize the possibility of damage to the battery box and extend the life of the
batteries. Please follow the instructions below:
1. Keep at least 20cm (8 inches) clearance from the rear panel of the unit from
the wall or other obstructions.
2. Do not block the air-ow to the ventilation openings of the unit.
3. Please ensure the installation site environmental conditions are in accord-
ance with the unit’s working specications to avoid overheat and excessive
moisture.
4. Do not place the unit in a dusty or corrosive environment or near any am-
mable objects.
5. This unit is not designed for outdoor use.
4
Page 8
This unit can either be mounted or placed vertically on the desk.
z
z
Rack Installation
B TTERY
PACK
z
z
Tower Installation
z
z
Connecting with UPS and Other Battery Box
B TTERY
PACK
ON/MUTE
SELECT
OFF/ENTER
PACK
B TTERY
Follow below installation chart to connect with UPS and other battery box with
included cable.
st
1 battery box
UPS
Amplon RX Series
nd
2 battery box
5
Page 9
Chapter 3 Type of Battery Required
Chapter 3 : Type of Battery Required
This battery box has been designed to operate with the following types of batteries:
1. 72V/ 9Ah Version: 6 pieces of 12V 9Ah batteries.
If your battery box is not installed with batteries, please follow proper procedure to
put batteries inside of the unit.
NOTE :
Make sure that the battery box is disconnected from the UPS before
performing the following sequence of operations.
z
z
Battery Box 72V
1
Open the package and place the battery box on a horizontal plane.
2
Remove the removable left-hand front panel by pulling it from the lower
extremity.
Left-hand front panel
3
Remove the 2 screws present and remove the right-hand front panel.
Amplon RX Series
Right-hand front panel
7
Page 11
Chapter 4 Battery Installation
4
Remove the metal top cover of the battery box by unscrewing the 8 screws
present on the two sides (4 on the right side and 4 on the left side), 3
screws on the top and 4 screws on the back side.
5
Once the battery box is opened, remove the two battery xing plates pre-
sent on the left side of the battery box by unscrewing the 4 screws present.
NOTE :
To install the second branch of batteries, repeat the same
procedure on the two battery fixing plates on the right side of the
battery box.
6
Now, it is possible to put the batteries inside following below picture (in the
following drawing is indicated the fasten positions for the correct batteries
placing).
8
Page 12
NOTE :
To install the second branch of batteries, repeat the same
procedure on the right side of the battery box.
7
Connecting all batteries following the wiring diagram shown in Chapter 5:
Wiring Diagram.
8
Put all batteries inside and re-install the battery xing plates.
9
Put metal top cover back to the unit. Reinstall the right-hand front panel and
secure it with the original 2 screws. After that, replace the left-hand front
panel.
10
Connect the battery box to the UPS.
Amplon RX Series
NOTE :
To install the second branch of batteries, repeat the same
procedure on the right side of the battery box.
9
Page 13
z
z
Battery Box 72V
Chapter 5 Wiring Diagram
Chapter 5 : Wiring Diagram
1 baery bench
st
Ba Link PCBA +
Breaker
Ba Link PCBA -
BLACK
RED
BLACK
RED
nd
2 baery bench
10
Page 14
Picture example as below:
+
-
-
+
+ - -
+
+
-
-
+
+
-
-
+
+
-
-
+
+
-
+
-
240mm
380mm
280mm
380mm
NOTE :
already present inside the battery box. All the other cable connection should
be followed by wiring diagram.
Amplon RX Series
The cable connection from external battery connector to PCB is
11
Page 15
Chapter 6 Storage & Maintenance
Chapter 6 : Storage & Maintenance
The unit contains no user-serviceable parts. If the battery service life (3~5 years at
25°C ambient temperature) has been exceeded, the batteries must be replaced. In
this case, please contact your dealer.
Be sure to deliver the spent battery to a recycling facility or ship it
to your dealer in the replacement battery packing material.
z
z
Storage
Before storing, charge the unit 4 hours. Store the unit covered and upright in a
cool, dry location. During storage, recharge the battery in accordance with the
following table:
Seller warrants this product, if used in accordance with all applicable instructions,
to be free from original defects in material and workmanship within the warranty
period. If the product has any failure problem within the warranty period, Seller will
repair or replace the product at its sole discretion according to the failure situation.
This warranty does not apply to normal wear or to damage resulting from improper
installation, operation, usage, maintenance or irresistible force (i.e. war, fire,
natural disaster, etc.), and this warranty also expressly excludes all incidental and
consequential damages.
Maintenance service for a fee is provided for any damage out of the warranty
period. If any maintenance is required, please directly contact the supplier or Seller.
WARNING:
The individual user should take care to determine prior to use whether the
environment and the load characteristic are suitable, adequate or safe for
the installation and the usage of this product. The User Manual must be
carefully followed. Seller makes no representation or warranty as to the
suitability or tness of this product for any specic application.
Amplon M Series
Version Date : 2016_12_19
13
Page 17
Page 18
Page 19
Page 20
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.