Delta Amplon RT Series 5-10kVA, Amplon RT Series, Amplon RT5K, Amplon RT6K, Amplon RT10K User Manual

ii
User Manual
Save This Manual
Save This Manual
This manual contains important instructions and warnings that you should follow during the installation, operation, storage and maintenance of this on-line UPS. Failure to heed these instructions and warnings will void the warranty.
Copyright© by Delta Electronics Inc. All rights reserved. The content in this manual belongs to Delta Electronics Inc., hereafter referred to as Delta. No part of this manual can be quoted or reproduced in any form or by any means without the prior written permission of Delta. To continuously improve and develop the product, Delta will make all possible efforts to secure the accuracy and the integrity of this manual. Changes may be made periodically to the information in this manual without obligation to notify any person of such revision or changes.
User Manual
iii
Table of Contents
Chapter 1: Important Safety Instructions ------------------------------------------------- 1
Placement Warnings -----------------------------------------------------------------------------------------1 Connection Warnings ----------------------------------------------------------------------------------------1 Usage Warnings ----------------------------------------------------------------------------------------------1 Glossary of Symbols ----------------------------------------------------------------------------------------- 2 Standard Compliance ----------------------------------------------------------------------------------------2
Chapter 2: Introduction ------------------------------------------------------------------------- 3
General Overview --------------------------------------------------------------------------------------------3 Package Contents -------------------------------------------------------------------------------------------- 3 Features ---------------------------------------------------------------------------------------------------------4 Storage ----------------------------------------------------------------------------------------------------------5 Front Panel ----------------------------------------------------------------------------------------------------- 6 Rear Panel ----------------------------------------------------------------------------------------------------- 7
Chapter 3: Installation --------------------------------------------------------------------------- 8
Rack Mounting ------------------------------------------------------------------------------------------------8 Tower Mounting -----------------------------------------------------------------------------------------------8 Connection --------------------------------------------------------------------------------------------------- 10
Chapter 4: Operation ----------------------------------------------------------------------------12
UPS Start-up ------------------------------------------------------------------------------------------------- 12 UPS Turn-off ------------------------------------------------------------------------------------------------- 14 LCD Display in Different Operation Modes ----------------------------------------------------------- 14 Firmware Version Look-up ------------------------------------------------------------------------------- 15 Operation Modes ------------------------------------------------------------------------------------------- 16
Chapter 5: Communication Interface -----------------------------------------------------17
RS232 port --------------------------------------------------------------------------------------------------- 17 Remote Control Port --------------------------------------------------------------------------------------- 17 SNMP Slot ---------------------------------------------------------------------------------------------------- 18 SMART Slot -------------------------------------------------------------------------------------------------- 19 External Battery Pack Connector ----------------------------------------------------------------------- 19 Parallel Connector ------------------------------------------------------------------------------------------ 21
Table of Contents
iv
User Manual
Table of Contents
Chapter 6: Optional Accessories ----------------------------------------------------------23
Optional Accessory List ----------------------------------------------------------------------------------- 23 Optional Accessory Installation-------------------------------------------------------------------------- 24
Chapter 7: Maintenance ------------------------------------------------------------------------26
UPS ------------------------------------------------------------------------------------------------------------ 26 Battery --------------------------------------------------------------------------------------------------------- 26 Fan ------------------------------------------------------------------------------------------------------------- 26
Chapter 8: Troubleshooting ------------------------------------------------------------------27 Chapter 9: Specifi cations ---------------------------------------------------------------------28 Chapter 10: Warranty ---------------------------------------------------------------------------29
User Manual
1
Placement Warnings
Install the UPS in a well ventilated area, away from excess moisture, heat, dust, fl ammable
gas or explosives.
Leave adequate space (at least 15cm) around all sides of the UPS for proper ventilation.
Do not mount the UPS with its front or rear panel facing down at any angle.
Connection Warnings
The UPS must be well grounded due to a possible risk of current leakage.
The installation of upstream and downstream protective devices is highly recommended when
the UPS is connected to the mains and the load.
The protective devices connecting to the UPS must be installed near the UPS and must be
easily accessible for operation.
Do not use extension cords to connect the UPS to an AC outlet.
Usage Warnings
This is a class-A product. In a domestic environment, this product may cause radio interfer-
ence, in which case, the user is required to take adequate measures.
The UPS can be used to power computers and associated peripheral devices, such as
monitors, modems, cartridge tape drives, external hard drives, etc.
The external slits and openings in the UPS are provided for ventilation. To ensure reliable operation of the UPS and to protect the UPS from overheating, these slits and openings must not be blocked or covered. Do not insert any object into the slits and openings that may hinder ventilation.
Before usage, you must allow the UPS to adjust to room temperature (20°C~25°C or 68°F~77°F) for at least one hour to avoid moisture condensing inside the UPS.
Do not put beverage containers on the UPS, battery pack, cabinet or any other accessory associated with the UPS.
The risk of dangerous high voltage is possible when the batteries are still connected to the
UPS even though the UPS is disconnected from the mains. Do not forget to pull out the battery cable to completely cut off the battery source.
Do not open or mutilate the battery or batteries. The released electrolyte is harmful to the skin
Chapter 1: Important Safety Instructions
Important Safety Instructions
2
User Manual
and eyes and may be toxic.
Do not dispose of the battery or batteries in a fi re. The batteries may explode.
All maintenance services must be performed by qualifi ed service personnel.
Forbid open
ing or
removing the cover of the UPS to avoid high voltage electric shock.
You must contact qualifi ed service personnel if either of the following events occur:
1. Liquid is poured or splashed on the UPS.
2. The UPS does not run normally after this User Manual is carefully observed.
NOTE:
If you use the UPS in an area that generates or incurs dust, you should install a dust fi lter
in the UPS to ensure normal product life and function.
Glossary of Symbols
Standard Compliance
CE
IEC62040-1-1
IEC62040-2 C2
IEC61000-4-2 (ESD) Level 4
IEC61000-4-3 (Radiated Field) Level 3
IEC61000-4-4 (EFT) Level 4
IEC61000-4-5 (Surge) Level 4
Symbol Description Symbol Description
The UPS is in on-line mode. Protective earthing conductor
The UPS is in battery mode. Bonded to ground
The UPS is in bypass mode. Positive battery terminal
The UPS has an internal fault. Negative battery terminal
UP button Phase
DOWN button Warning
Do not connect any computer to the charger detection port.
Note
DC voltage
Important Safety Instructions
User Manual
3
Chapter 2: Introduction
Item Quantity
Introduction
General Overview
This RT series UPS, available in 5kVA, 6kVA, and 10kVA, is a true on-line double-conversion UPS pro­viding reliable and consistent sine-wave quality power to your sensitive electronic equipment. It adopts the latest technology and the highest quality components providing output power factor up to 0.9, and its effi ciency in on-line mode and in economy mode can reach at maximum 92% and 96% respectively. With its outstanding features, the UPS not only provides safe, reliable and uninterrupted power to your
sensi-
tive electronic equipment at all times, but also produces greater electric power effi ciency at less cost.
Package Contents
The UPS package contains the following items. Please carefully inspect the UPS and check the included accessories. If there is any damage or anything missing, please immediately contact the dealer from whom you purchased the unit. If the UPS needs to be returned, carefully repack the UPS and all of the accessories using the original packing material that came with the unit.
UPS 1 PCS
User Manual 1 PCS
Software CD –SMART2000 1 PCS
Battery Cable 1 PCS
RS232 Cable 1 PCS
Parallel Cable 1 PCS
Tower Stand 1 SET (4 PCS)
Bracket Ear 1 SET (2 PCS)
Terminal 5/6kVA: 8 PCS
10kVA: 6 PCS
4
User Manual
Features
True on-line design UPS protects your sensitive electronic equipment from power interruption.
Wide AC input voltage range (100Vac~300Vac) reduces frequent transfer
from AC mode
to DC
mode to save battery consumption and prolong battery life.
Smart battery charger design performs auto-charging and reduces the charging time.
Automatic input frequency detection enables operation at 50Hz or 60Hz.
The input power factor correction and the high frequency pulse-width-modulated inverter give the UPS excellent performance characteristics in this compact design.
Battery-Start switch powers on the UPS to provide stable AC power when there is no AC line available.
Remote Control Port: Use this port to either shut down the UPS completely (REPO) or switch off the inverter only (ROO).
Built-in RS232 communication port allows the monitoring and management of the UPS via SMART2000 software.
Optional accessories include
Mini SNMP, Mini Relay I/O, Mini USB, Mini ModBus
and
Mini
TVSS
cards for
network communication
, dry contact, USB communication, ModBus com-
munication and surge protection.
State-of-the-art microprocessor technology performs self-detection and displays the UPS status on LCD.
Surge protection and EMI fi lter functions.
Automatic restart:
1) The UPS will restart in on-line mode automatically right after the AC line resumes
following a low battery shutdown.
2) The UPS returns automatically to on-line mode from bypass mode after the overload
condition is cleared.
External battery pack connector is provided to connect an external battery pack to extend the backup time.
Optional ECO Mode: When the utility input voltage and frequency are
within the range of rating voltage ±10% and rating frequency ±6%, the UPS will transfer to bypass mode; otherwise, the UPS will transfer to on-line mode to reach higher effi ciency.
Auto-detect the bypass mode voltage: Automatically detects whether the bypass voltage is out of rating voltage (240Vac output: 156~276Vac; 200/ 208/ 220/ 230Vac output: 156~264Vac). If yes, the UPS will stop the supply to the load to protect your electronic equipment.
Automatically detects and shows whether the fan(s) is operating normally.
Introduction
User Manual
5
Normal start-up function even when the UPS is not connected to the batteries.
WARNING:
Please note that when the UPS is not connected to the batteries, it will not protect your equipment if the utility power is lost.
Enables set up of “1+1” parallel redundant system (with optional manual bypass box) to increase the system availability and reliability.
The fan(s) automatically adjusts the fan speed to prolong fan life.
Storage
Prior to installation:
If the UPS needs to be stored prior to installation, it should be placed in a dry area. The allow-
able storage temperature is between -15°C and +50°C (5°F~122°F).
After usage:
Press the ‘OFF’ button, make sure the UPS is shutdown, disconnect the UPS from the utility
power, remove all equipment from the UPS, and store the UPS in a dry and well-ventilated
area at a temperature between -15°C and +50°C (5°F~122°F). Idle batteries must be re-
charged fully approximately every three months if the UPS needs to be stored for an extended
period of time. The charging time must not be less than 24 hours each time.
NOTE: After storage and before start-up of the UPS, you must allow the UPS to adjust to
room temperature (20°C~25°C or 68°F~77°F) for at least one hour to avoid moisture con­densing inside the UPS.
Introduction
6
User Manual
Front Panel
(Figure 2-a) Front Panel
Introduction
No. Item Description
On-line LED Indicates that the UPS is in on-line mode. Battery LED Indicates that the UPS is currently in battery mode and the exter-
nal battery is discharging now.
Fault LED
Indicates that the UPS has an internal fault.
Bypass LED
Indicates that the UPS is in bypass mode.
Backlight LCD Display The LCD display shows the status of the UPS and relevant infor-
mation.
ON Button Press this button for 3~5 seconds to start up the UPS. In on-line
mode with utility power available, press this button for 3 seconds to execute the 10-second battery discharge test.
OFF Button Press this button for over 3 seconds to shut down the inverter of
the UPS.
and Buttons
Use these two buttons to set up the output frequency, voltage, op­eration mode and the LCD. Press either
or button for more
than 3 seconds to disable ‘BEEP’.
1 2
3 4 5
6
7
8
User Manual
7
Rear Panel
(Figure 2-b) 5kVA/ 6kVA Rear Panel
(Figure 2-c) 10kVA Rear Panel
Introduction
No. Item Description
Input Breaker
Protects the utility power from further damage when the UPS fails.
Input Terminal Block
Connects the UPS to the mains.
Output Terminal Block
Connects to the load.
Fan
Cools and ventilates the UPS.
Parallel Connector
For UPS parallel communication, please see Chapter 5 for de­tailed information.
Remote Control Port
Shuts down the UPS completely or switches off the inverter only. Please see Chapter 5 for detailed information.
Charger Detection
Connects to the charger box and detects the charger status.
SNMP Slot Accepts SNMP/ Relay I/O/ ModBus card. Please see Chapter 5
for detailed information.
RS232 Port Communication interface port. Please see Chapter 5 for detailed
information.
Smart Slot Accepts Mini SNMP/ Mini Relay I/O/ Mini USB/ Mini ModBus/ Mini
TVSS card. Please see Chapter 5 for detailed information.
External Battery Pack Connector
Connects to the external battery pack. Please see Chapter 5 for detailed information.
1 2
3 4 5
6
10
11
7 8
9