This manual contains important instructions and warnings that you should
follow during the installation, operation, storage and maintenance of this
product. Failure to heed these instructions and warnings will void the warranty.
Before installation and usage, please read this User Manual thoroughly. This
helps you to use the product correctly and safely.
z
z
Install the UPS in a well-ventilated area, away from excess moisture, heat, dust,
ammable gas or explosives.
z
z
To avoid re accidents and electric shock, please install the UPS in a temperate
and humidity well-controlled indoor area free of conductive contaminants. For
the temperature and humidity specications, please refer to Appendix 1 : Tech-
nical Specications.
z
z
Leave adequate space (at least 50cm) around all sides of the UPS for proper
ventilation.
Connection Warnings
z
z
The UPS must be well grounded due to a possible risk of current leakage.
z
z
The installation of upstream and downstream protective devices is highly recommended when the UPS is connected to the mains and the loads.
z
z
The protective devices connecting to the UPS must be installed near the UPS
and must be easily accessible for operation.
z
z
If you need to move the UPS or perform re-wiring, please turn o the AC input
power and ensure that the UPS has been safely shutdown. Otherwise, the output end might still be energized, which might cause electric shock.
Usage Warnings
z
z
This is a class-A product. In a domestic environment, this product may cause radio interference, in which case, the user is required to take adequate measures.
z
z
The UPS can be used to power computers and associated peripheral devices,
such as monitors, modems, cartridge tape drives, external hard drives, etc.
1
z
z
It is strictly forbidden to connect the UPS with:
1. Any regenerative loads.
2. Any asymmetrical loads.
z
z
To ensure reliable operation of the UPS and to protect the UPS from overheating, the slits and openings in the UPS must not be blocked or covered.
z
z
Before usage, you must allow the UPS to adjust to room temperature for at least
one hour to avoid moisture condensing inside the UPS.
z
z
Do not pour and splash any liquid on the UPS. Do not insert any object into
the UPS’s slits and openings. Do not put beverage containers on or around the
UPS.
z
z
When an emergency occurs, (1) press and hold the ON/ OFF button ( ) for
3 seconds, (2) release it after you hear one beep, (3) use the Scrolling UP or
Down button (
/ ) to select
'Yes'
, and (4) press the Enter button ( ) to
conrm your selection to turn o the UPS. After that, cut o the input power to
completely shut down the UPS. Cut o the input power to completely shut down
the UPS.
z
z
Do not use any cleaning liquid or cleaning spray to clean the UPS. Before cleaning, please make sure that the UPS has been completely shut down, the UPS’s
input power has been cut o, and the batteries have been disconnected.
z
z
All maintenance services must be performed by qualied service personnel.
z
z
Forbid opening or removing the cover of the UPS yourself to avoid high voltage
electric shock.
z
z
You must contact qualied service personnel if either of the following events occurs:
1. Liquid is poured or splashed on the UPS.
2. The UPS does not run normally after this User Manual is carefully
observed.
NOTE :
If you use the UPS in an area that generates or incurs dust, you should
install two dust filters (optional) in the 5/ 6/ 8/ 10kVA UPS to ensure
normal product life and function.
Amplon RT Series
2
Chapter 1 Important Safety Instructions
100
%
100
%
Battery Warnings
z
z
Keep the batteries away from heat sources. Do not open or mutilate the batteries.
z
z
Do not dispose of batteries in a re. The batteries may explode.
z
z
The released electrolyte is harmful to the skin and eyes and may be toxic.
z
z
A battery can present a risk of electric shock and high short-circuit current.
z
z
Servicing of batteries and battery packs must be performed or supervised by
qualified service personnel knowledgeable in batteries, battery packs and the
required precautions. Keep unauthorized personnel away from batteries and
battery packs.
z
z
The risk of electric shock and short-circuit current is possible when the batteries
are connected to the UPS. Before maintenance, disconnect all batteries to cut
o the battery power.
z
z
For battery replacement, only use the same number and type of batteries.
z
z
Observe the following before replacing the batteries:
1. Remove watches, rings, or other metal objects.
2. Use tools with insulated handles.
3. Wear rubber gloves and boots.
4. Do not lay tools or metal parts on the top of batteries.
5. Disconnect charging source prior to connecting or disconnecting battery
terminals.
6. Remove battery grounds during installation and maintenance to reduce
likelihood of shock. Remove the connection from ground if any part of the
battery is determined to be grounded.
z
z
Do not connect the batteries in reverse; otherwise, a risk of electric shock or re
accidents might occur.
z
z
The batteries might lose their power during shipment or storage. Before you use
the UPS for the rst time, please fully charge the batteries until the battery ca-
)
(
pacity percentage shown on the UPS’s LCD is 100%
. If the UPS needs to
be stored for an extended period of time, please charge the batteries every three
months and ensure that, every time after charging, the battery capacity percent-
(
age shown on the UPS’s LCD is 100%
)
.
3
WARNING:
100
%
1. The risk of electric shock and short-circuit current is possible when
the batteries are still connected to the UPS even though the UPS
is disconnected from the mains. Do not forget to cut o the battery
source before maintenance.
2. When the UPS is connected to external battery packs, the installation
of appropriate protective devices, such as a DC fuse or a DC nonfuse breaker, is required.
1.2 Standard Compliance
z
z
z
z
CE
UL, cUL
z
z
EN 62040-1
z
z
EN 62040-2 Category C2
1.3 Storage
z
z
Prior to installation
If the UPS needs to be stored prior to installation, it should be placed in a dry
and well-ventilated area. The allowable storage temperature is between -15°C
and +50°C (5°F~122°F).
z
z
After usage
(1) Press and hold the ON/OFF button (
you hear one beep, (3) use the Scrolling UP or Down button (
‘Yes’, and (4) press the Enter button (
the UPS. Make sure the UPS is shutdown, disconnect the UPS from the utility
AC power, remove all loads/ equipment from the UPS, and store the UPS in
a dry and well-ventilated area at a temperature between -15°C and +50°C
(5°F~122°F).
Idle batteries must be recharged fully approximately every three months if the
UPS needs to be stored for an extended period of time. Ensure that, every time
after charging, the battery capacity percentage shown on the UPS’s LCD is
100%
.
(
)
) for 3 seconds, (2) release it after
/ ) to select
) to conrm your selection to turn o
Amplon RT Series
NOTE :
After storage and before start-up of the UPS, you must allow the UPS to
adjust to room temperature (20°C~25°C or 68°F~77°F) for at least one
hour to avoid moisture condensing inside the UPS.
4
Chapter 2 Introduction
Chapter 2 : Introduction
2.1 General Overview
The RT series UPS is a single-phase input, single-phase output on-line uninterruptible power supply which provides reliable and consistent sine-wave quality power
to your electronic equipment. It adopts the latest technology and the highest quality
components providing output power factor up to unity, and its eciency in on-line
mode reaches up to 96%. The UPS not only provides safe, reliable and uninterruptible power to your sensitive electronic equipment at all times, but also produces
greater electronic power efficiency at less cost. There are four different ratings,
5kVA, 6kVA, 8kVA and 10kVA, for your selection.
1. If there is any damage or anything missing, please immediately contact
the dealer from whom you purchased the unit.
2. If the UPS needs to be returned, carefully repack the UPS and all of the
accessories using the original packing material that came with the unit.
7
Chapter 3 : Operation Panel
On the front panel of the UPS, you’ll see two LED indicators, a LCD display, and
multi-function buttons.
3.3
LCD Display
ONLINE
%
100
Input
Output
ESC
232.0V50.0Hz
230.0V50.0Hz
(Figure 3-1: Operation Panel)
1
%
75
3.1 LED Indicators
No. LEDDescription
1
2
1. ON: The output is protected.
2. OFF: The output is not protected.
1. ON: The UPS detects an internal fault or an
environmental fault.
2. OFF: The UPS is in normal state.
3. Flashing: The UPS shows the warning message(s).
Please check the corresponding warning
message(s) in Chapter 11: Troubleshooting.
3.1
LED Indicators
3.2
Multi-function
Buttons
Amplon RT Series
8
3.2 Multi-function Buttons
Multi-
No.
function
Button
The button has multiple functions. Please refer to the following
for detailed information.
1. Turn-on
z
z
In standby/ bypass mode, press and hold the button for 3
seconds, release it after you hear one beep and the UPS
will run in on-line mode.
z
z
Cold start: When there is no AC input, press and hold the
button for 3 seconds, release it after you hear one beep
and the UPS will run in battery mode.
2. Turn-o
z
z
In on-line mode, (1) press and hold the button for 3
seconds, (2) release it after you hear one beep, (3) use
the Scrolling UP or Down button
1
ON/ OFF
Button
and (4) press the Enter button
tion. After that, the inverter will be o and the UPS will
transfer to run in standby or bypass mode.
The UPS will keep charging the batteries when the UPS
is in standby/ bypass mode. To fully turn o the UPS, it is
advised to disconnect the UPS from the AC power.
z
z
In battery mode, (1) press and hold the button for 3
seconds, (2) release it after you hear one beep, (3) use
the Scrolling UP or Down button (
and (4) press the Enter button (
tion. After that, the UPS will be turned o.
3. Fault Clear
When the UPS has a fault condition, press and hold the button for 3 seconds, release it after you hear one beep and
the UPS will try to clear the fault condition.
Description
Chapter 3 Operation Panel
(
/ )
to select 'Yes',
to conrm your selec-
)
(
/
) to select 'Yes',
) to conrm your selec-
9
No.
1
2
Multi-
function
Button
ON/ OFF
Button
(Continued)
Enter
Button
Description
NOTE :
1. When the UPS clears the fault condition, it means
that the buzzer/ warning message has been turned
off. To eliminate the fault detected, please refer
to Chapter 11: Troubleshooting for relevant solutions.
2. The function mentioned above is only applicable
to the condition when the UPS has a fault situation
and the inverter is o.
The button has multiple functions. Please refer to the following
for detailed information.
1. Entering into the setup mode
In the Main Screen (that shows the current operation
mode), press the button for 0.1 second and the UPS will enter the Main Menu (setup mode). Please refer to Chapter 9:
LCD Display & Settings.
2. Selecting and conrming the parameter in setup mode
In setup mode, press the button to choose the parameter
you want to change, and the parameter will flash. Press
the Scrolling Up or the Scrolling Down button to change
the parameter and press the button again to confirm the
change.
3
Scrolling
Up Button
Amplon RT Series
The button has multiple functions. Please refer to the following
for detailed information.
1. Scrolling Up/ Increasing Number
z
z
In the Main Screen, press the button for 0.1 second and
the UPS will directly enter the Measurement Menu’s
level 3 (see Figure 9-1: Menu Tree), which contains
related Output information.
z
z
In setup up mode, the button is used to navigate the setting items. Press the button for 0.1 second to go to the
previous setting item.
10
No.
3
4
Multi-
function
Button
Scrolling
Up Button
(Continued)
Scrolling
Down
Button
Chapter 3 Operation Panel
Description
z
z
The button is also used to navigate or set up the setting
parameter. Press the button for 0.1 second to go to the
previous display or to increase a number. If the button is
pressed for more than 2 seconds, the number will be increased single digit every 0.2 second automatically until
the button is released or the number reaches its highest
value.
2. LCD Reset
z
z
Press the Scrolling Up and the Scrolling Down buttons
together for 3 seconds to reset the LCD display.
The button has multiple functions. Please refer to the following
for detailed information.
1. Scrolling Down/ Decreasing Number
z
z
In the Main Screen, press the button for 0.1 second and
the UPS will directly enter the Measurement Menu’s
level 3 (see Figure 9-1: Menu Tree), which contains
related Output information.
z
z
In setup up mode, the button is used to navigate the setting items. Press the button for 0.1 second to go to the
next setting item.
z
z
The button is also used to navigate or set up the setting
parameter. Press the button for 0.1 second to go to the
next display or to decrease a number. If the button is
pressed for more than 2 seconds, the number will be decreased single digit every 0.2 second automatically until
the button is released or the number reaches its lowest
value.
2. LCD Reset
z
z
Press the Scrolling Up and the Scrolling Down buttons
together for 3 seconds to reset the LCD display.
11
Multi-
No.
function
Button
5
Back/ Mute
Button
ESC
The button has multiple functions. Please refer to the following
for detailed information.
1. Back to the Previous Menu Level
z
z
In setup mode, press the button for 0.1 second to go
back to the previous menu level.
2. Mute
z
z
When the UPS has any warning of fault conditions to
trigger an audible alarm, press and hold the button for 3
seconds to turn o the audible alarm.
Description
NOTE :
If the LCD display goes dim, press any button mentioned above for 0.1
second to wake up the LCD display and enable each button function.
3.3 LCD Display
Amplon RT Series
ONLINE
Input
Output
100
232.0V
230.0V
12
%
50.0Hz
50.0Hz
1
75
%
Chapter 3 Operation Panel
1
1
100
%
100
%
75%
3.3.1 Icon/ Display Denition
No. Icon/ DisplayDescription
1. ON: The UPS is in parallel mode.
2. OFF: The UPS is in single mode.
NOTE :
1
2
For the Master UPS, the icon will ash
during parallel mode. For the Slave UPS,
the icon will illuminate, not ash, during
parallel mode.
Indicates that the load bank status is ON.
Indicates that the load bank status is OFF.
Indicates the battery capacity level.
3
4
Input
Output
5
!
Battery disconnected
6
0x1003
X
232.0V 50.0Hz
232.0V 50.0Hz
5 seconds
Indicates that the battery is abnormal and needs
replacement. If the battery is abnormal, the bat-
tery capacity icon
(
will be o.
)
Indicates the load level (%).
When the UPS runs normally, the display will
show the input/ output voltage and frequency.
When the UPS has abnormalities or is in fault
condition, the display will show an error code
and its corresponding fault or warning message.
NOTE :
The error code and the fault/ warning
message will appear alternatively for
every 5 seconds.
Indicates that the buzzer is muted.
13
3.3.2 Operation Mode Diagram Denition
ECO
No. DiagramDescription
1
2
3
ONLINE
Input
Output
ECO
Input
Output
BATTERY
Runtime
168
min
Input
Output
100
232.0V
230.0V
100
232.0V
232.0V
100
0.0V
230.0V
%
%
%
50.0Hz
50.0Hz
50.0Hz
50.0Hz
0.0Hz
50.0Hz
1
75
Indicates ONLINE mode.
%
Indicates ECO mode.
NOTE :
1
In ECO mode, the diagram’s
power ow will change according
to the UPS input voltage and
75
%
frequency. However, the ECO
icon (
) shown on the
upper-left corner will not change
even if the UPS transfers to online
mode or battery mode.
1
75
Indicates BATTERY mode.
%
4
Amplon RT Series
BYPASS
Input
Output
100
232.0V
232.0V
%
50.0Hz
50.0Hz
1
75
Indicates BYPASS mode.
%
14
Chapter 3 Operation Panel
No. DiagramDescription
5
6
STANDBY
Input
Output
Freq. Conv.
Input
Output
100
232.0V
0.0V
100
232.0V
230.0V
%
%
50.0Hz
0.0Hz
50.0Hz
50.0Hz
1
Indicates AC STANDBY mode.
Indicates Frequency Conversion
mode.
NOTE :
1
In Frequency Conversion mode,
the diagram’s power ow will
change according to the UPS
75
%
input voltage and frequency.
However, the text Freq. Conv.
(
Freq. Conv.
) shown on the
upper-left corner will not change
even if the UPS transfers to
battery mode.
The rear panels of above mentioned models are similar. The dierences are the
battery voltage and DC value printed on the panels. For detailed information
about the printed battery voltage and DC value, please refer to the table below.
Here, only 5kVA UPS’s real panel (see Figure 4-1) is taken for example.
5678
123
4
9
10
PARALLELPARALLEL
MINI SLOT
DRY CONTACT
P1
NOTE :
P2 P3 P4
RS-232
RS-485
REPO
OFF
ON
INPUT
BREAKER
UPS OUTPUTUPS OUTPUT-PAC INPUT
EXTERNAL BATT.
PL2(N)PL1(PL)L2(N)L1(L)L2(N)L1(L)
192V DC 29A
CONNECTOR
Remove the terminal
cover plate and you will
see the wiring terminal
1215
blocks.
11
(Figure 4-1: 5kVA Rear Panel)
No. Item Functions
For installation of an optional card, such as Mini
1
MINI Slot
SNMP IPv6 card, Mini Relay I/O card, or Mini
MODBUS card. For more information, please
refer to Chapter 5: Communication Interfaces.
TMOV
TUPNITUPTUO
14
13
Amplon RT Series
16
No. Item Functions
For UPS parallel communication. For more
information, please refer to Chapter 5: Communication Interfaces.
2
Parallel Ports
NOTE :
To enhance parallel reliability, please
adopt the Daisy Chain method to execute
parallel conguration.
1. Output dry contacts: Receive the UPS’s event
information to indicate the UPS status or
internal messages.
3
Dry Contacts
2. Input dry contacts: Let the UPS to receive
external control signals.
3. For more information, please refer to Chapter 5: Communication Interfaces.
When emergency events occur, it can shut
4
REPO Port
down the UPS safely and immediately. Please
refer to Chapter 5: Communication Interfaces
for details.
Chapter 4 Rear Panel
Connects to a computer so you can monitor the
5
RS-485 Port
UPS status or let the UPS communicate with
lithium ion batteries.
Connects to a computer so you can build up
RS-232 communication, congure the UPS
6
RS-232 Port
and upgrade the UPS rmware. Please refer
to Chapter 5: Communication Interfaces for
more information.
Connects to a computer to monitor the state of
the UPS, congure the UPS parameters and
7
(USB Port)
update the management software. Please refer
to Chapter 5: Communication Interfaces for
more information.
17
No. Item Functions
8
9
10
11
12
13
14
15
Input Breaker
External Batt.
Connector
UPS Output
Terminal Block
Terminal Block
UPS Output
Terminal Block – P
Controls the UPS’s input switch and for safety
protection.
Connects to the external battery pack (optional).
5K: 192V DC 29A
6K: 192V DC 35A
8K: 240V DC 37A
10K: 240V DC 46A
TMOV For UPS internal TMOV's grounding.
For loads’ grounding.
1. Uncontrollable.
2. Without load-bank function.
3. Connects to the loads (L1 & L2 for sux B8
model; L & N for sux 35/ B0 model).
For UPS grounding.
AC Input
Connects to the mains.
(L1 & L2 for sux B8 model; L & N for sux 35/
B0 model)
1. Controllable.
2. With load-bank function.
3. Connects to the loads (PL1 & PL2 for sux
B8 model; PL & N for sux 35/ B0 model).
NOTE :
1. Please note that, for parallel application, the output loads can only be
connected to this output terminal
block.
2. When the UPS is working in singleunit mode, the output terminal block
has load bank function. The load bank
function will be disabled when the
UPS is running in parallel mode.
Amplon RT Series
18
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.