This manual contains important instructions and warnings that you should
follow during the installation, operation, storage and maintenance of this
product. Failure to heed these instructions and warnings will void the warranty.
Before installation and usage, please read this User Manual thoroughly. This
helps you to use the product correctly and safely.
z
z
Install the UPS in a well-ventilated area, away from excess moisture, heat, dust,
ammable gas or explosives.
z
z
To avoid re accidents and electric shock, please install the UPS in a temperate
and humidity well-controlled indoor area free of conductive contaminants. For
the temperature and humidity specications, please refer to Appendix 1 : Tech-
nical Specications.
z
z
Leave adequate space (at least 50cm) around all sides of the UPS for proper
ventilation.
Connection Warnings
z
z
The UPS must be well grounded due to a possible risk of current leakage.
z
z
The installation of upstream and downstream protective devices is highly recommended when the UPS is connected to the mains and the loads.
z
z
The protective devices connecting to the UPS must be installed near the UPS
and must be easily accessible for operation.
z
z
If you need to move the UPS or perform re-wiring, please turn o the AC input
power and ensure that the UPS has been safely shutdown. Otherwise, the output end might still be energized, which might cause electric shock.
Usage Warnings
z
z
This is a class-A product. In a domestic environment, this product may cause radio interference, in which case, the user is required to take adequate measures.
z
z
The UPS can be used to power computers and associated peripheral devices,
such as monitors, modems, cartridge tape drives, external hard drives, etc.
1
Page 6
z
z
It is strictly forbidden to connect the UPS with:
1. Any regenerative loads.
2. Any asymmetrical loads.
z
z
To ensure reliable operation of the UPS and to protect the UPS from overheating, the slits and openings in the UPS must not be blocked or covered.
z
z
Before usage, you must allow the UPS to adjust to room temperature for at least
one hour to avoid moisture condensing inside the UPS.
z
z
Do not pour and splash any liquid on the UPS. Do not insert any object into
the UPS’s slits and openings. Do not put beverage containers on or around the
UPS.
z
z
When an emergency occurs, (1) press and hold the ON/ OFF button ( ) for
3 seconds, (2) release it after you hear one beep, (3) use the Scrolling UP or
Down button (
/ ) to select
'Yes'
, and (4) press the Enter button ( ) to
conrm your selection to turn o the UPS. After that, cut o the input power to
completely shut down the UPS. Cut o the input power to completely shut down
the UPS.
z
z
Do not use any cleaning liquid or cleaning spray to clean the UPS. Before cleaning, please make sure that the UPS has been completely shut down, the UPS’s
input power has been cut o, and the batteries have been disconnected.
z
z
All maintenance services must be performed by qualied service personnel.
z
z
Forbid opening or removing the cover of the UPS yourself to avoid high voltage
electric shock.
z
z
You must contact qualied service personnel if either of the following events occurs:
1. Liquid is poured or splashed on the UPS.
2. The UPS does not run normally after this User Manual is carefully
observed.
NOTE :
If you use the UPS in an area that generates or incurs dust, you should
install two dust filters (optional) in the 5/ 6/ 8/ 10kVA UPS to ensure
normal product life and function.
Amplon RT Series
2
Page 7
Chapter 1 Important Safety Instructions
100
%
100
%
Battery Warnings
z
z
Keep the batteries away from heat sources. Do not open or mutilate the batteries.
z
z
Do not dispose of batteries in a re. The batteries may explode.
z
z
The released electrolyte is harmful to the skin and eyes and may be toxic.
z
z
A battery can present a risk of electric shock and high short-circuit current.
z
z
Servicing of batteries and battery packs must be performed or supervised by
qualified service personnel knowledgeable in batteries, battery packs and the
required precautions. Keep unauthorized personnel away from batteries and
battery packs.
z
z
The risk of electric shock and short-circuit current is possible when the batteries
are connected to the UPS. Before maintenance, disconnect all batteries to cut
o the battery power.
z
z
For battery replacement, only use the same number and type of batteries.
z
z
Observe the following before replacing the batteries:
1. Remove watches, rings, or other metal objects.
2. Use tools with insulated handles.
3. Wear rubber gloves and boots.
4. Do not lay tools or metal parts on the top of batteries.
5. Disconnect charging source prior to connecting or disconnecting battery
terminals.
6. Remove battery grounds during installation and maintenance to reduce
likelihood of shock. Remove the connection from ground if any part of the
battery is determined to be grounded.
z
z
Do not connect the batteries in reverse; otherwise, a risk of electric shock or re
accidents might occur.
z
z
The batteries might lose their power during shipment or storage. Before you use
the UPS for the rst time, please fully charge the batteries until the battery ca-
)
(
pacity percentage shown on the UPS’s LCD is 100%
. If the UPS needs to
be stored for an extended period of time, please charge the batteries every three
months and ensure that, every time after charging, the battery capacity percent-
(
age shown on the UPS’s LCD is 100%
)
.
3
Page 8
WARNING:
100
%
1. The risk of electric shock and short-circuit current is possible when
the batteries are still connected to the UPS even though the UPS
is disconnected from the mains. Do not forget to cut o the battery
source before maintenance.
2. When the UPS is connected to external battery packs, the installation
of appropriate protective devices, such as a DC fuse or a DC nonfuse breaker, is required.
1.2 Standard Compliance
z
z
z
z
CE
UL, cUL
z
z
EN 62040-1
z
z
EN 62040-2 Category C2
1.3 Storage
z
z
Prior to installation
If the UPS needs to be stored prior to installation, it should be placed in a dry
and well-ventilated area. The allowable storage temperature is between -15°C
and +50°C (5°F~122°F).
z
z
After usage
(1) Press and hold the ON/OFF button (
you hear one beep, (3) use the Scrolling UP or Down button (
‘Yes’, and (4) press the Enter button (
the UPS. Make sure the UPS is shutdown, disconnect the UPS from the utility
AC power, remove all loads/ equipment from the UPS, and store the UPS in
a dry and well-ventilated area at a temperature between -15°C and +50°C
(5°F~122°F).
Idle batteries must be recharged fully approximately every three months if the
UPS needs to be stored for an extended period of time. Ensure that, every time
after charging, the battery capacity percentage shown on the UPS’s LCD is
100%
.
(
)
) for 3 seconds, (2) release it after
/ ) to select
) to conrm your selection to turn o
Amplon RT Series
NOTE :
After storage and before start-up of the UPS, you must allow the UPS to
adjust to room temperature (20°C~25°C or 68°F~77°F) for at least one
hour to avoid moisture condensing inside the UPS.
4
Page 9
Chapter 2 Introduction
Chapter 2 : Introduction
2.1 General Overview
The RT series UPS is a single-phase input, single-phase output on-line uninterruptible power supply which provides reliable and consistent sine-wave quality power
to your electronic equipment. It adopts the latest technology and the highest quality
components providing output power factor up to unity, and its eciency in on-line
mode reaches up to 96%. The UPS not only provides safe, reliable and uninterruptible power to your sensitive electronic equipment at all times, but also produces
greater electronic power efficiency at less cost. There are four different ratings,
5kVA, 6kVA, 8kVA and 10kVA, for your selection.
1. If there is any damage or anything missing, please immediately contact
the dealer from whom you purchased the unit.
2. If the UPS needs to be returned, carefully repack the UPS and all of the
accessories using the original packing material that came with the unit.
7
Page 12
Chapter 3 : Operation Panel
On the front panel of the UPS, you’ll see two LED indicators, a LCD display, and
multi-function buttons.
3.3
LCD Display
ONLINE
%
100
Input
Output
ESC
232.0V50.0Hz
230.0V50.0Hz
(Figure 3-1: Operation Panel)
1
%
75
3.1 LED Indicators
No. LEDDescription
1
2
1. ON: The output is protected.
2. OFF: The output is not protected.
1. ON: The UPS detects an internal fault or an
environmental fault.
2. OFF: The UPS is in normal state.
3. Flashing: The UPS shows the warning message(s).
Please check the corresponding warning
message(s) in Chapter 11: Troubleshooting.
3.1
LED Indicators
3.2
Multi-function
Buttons
Amplon RT Series
8
Page 13
3.2 Multi-function Buttons
Multi-
No.
function
Button
The button has multiple functions. Please refer to the following
for detailed information.
1. Turn-on
z
z
In standby/ bypass mode, press and hold the button for 3
seconds, release it after you hear one beep and the UPS
will run in on-line mode.
z
z
Cold start: When there is no AC input, press and hold the
button for 3 seconds, release it after you hear one beep
and the UPS will run in battery mode.
2. Turn-o
z
z
In on-line mode, (1) press and hold the button for 3
seconds, (2) release it after you hear one beep, (3) use
the Scrolling UP or Down button
1
ON/ OFF
Button
and (4) press the Enter button
tion. After that, the inverter will be o and the UPS will
transfer to run in standby or bypass mode.
The UPS will keep charging the batteries when the UPS
is in standby/ bypass mode. To fully turn o the UPS, it is
advised to disconnect the UPS from the AC power.
z
z
In battery mode, (1) press and hold the button for 3
seconds, (2) release it after you hear one beep, (3) use
the Scrolling UP or Down button (
and (4) press the Enter button (
tion. After that, the UPS will be turned o.
3. Fault Clear
When the UPS has a fault condition, press and hold the button for 3 seconds, release it after you hear one beep and
the UPS will try to clear the fault condition.
Description
Chapter 3 Operation Panel
(
/ )
to select 'Yes',
to conrm your selec-
)
(
/
) to select 'Yes',
) to conrm your selec-
9
Page 14
No.
1
2
Multi-
function
Button
ON/ OFF
Button
(Continued)
Enter
Button
Description
NOTE :
1. When the UPS clears the fault condition, it means
that the buzzer/ warning message has been turned
off. To eliminate the fault detected, please refer
to Chapter 11: Troubleshooting for relevant solutions.
2. The function mentioned above is only applicable
to the condition when the UPS has a fault situation
and the inverter is o.
The button has multiple functions. Please refer to the following
for detailed information.
1. Entering into the setup mode
In the Main Screen (that shows the current operation
mode), press the button for 0.1 second and the UPS will enter the Main Menu (setup mode). Please refer to Chapter 9:
LCD Display & Settings.
2. Selecting and conrming the parameter in setup mode
In setup mode, press the button to choose the parameter
you want to change, and the parameter will flash. Press
the Scrolling Up or the Scrolling Down button to change
the parameter and press the button again to confirm the
change.
3
Scrolling
Up Button
Amplon RT Series
The button has multiple functions. Please refer to the following
for detailed information.
1. Scrolling Up/ Increasing Number
z
z
In the Main Screen, press the button for 0.1 second and
the UPS will directly enter the Measurement Menu’s
level 3 (see Figure 9-1: Menu Tree), which contains
related Output information.
z
z
In setup up mode, the button is used to navigate the setting items. Press the button for 0.1 second to go to the
previous setting item.
10
Page 15
No.
3
4
Multi-
function
Button
Scrolling
Up Button
(Continued)
Scrolling
Down
Button
Chapter 3 Operation Panel
Description
z
z
The button is also used to navigate or set up the setting
parameter. Press the button for 0.1 second to go to the
previous display or to increase a number. If the button is
pressed for more than 2 seconds, the number will be increased single digit every 0.2 second automatically until
the button is released or the number reaches its highest
value.
2. LCD Reset
z
z
Press the Scrolling Up and the Scrolling Down buttons
together for 3 seconds to reset the LCD display.
The button has multiple functions. Please refer to the following
for detailed information.
1. Scrolling Down/ Decreasing Number
z
z
In the Main Screen, press the button for 0.1 second and
the UPS will directly enter the Measurement Menu’s
level 3 (see Figure 9-1: Menu Tree), which contains
related Output information.
z
z
In setup up mode, the button is used to navigate the setting items. Press the button for 0.1 second to go to the
next setting item.
z
z
The button is also used to navigate or set up the setting
parameter. Press the button for 0.1 second to go to the
next display or to decrease a number. If the button is
pressed for more than 2 seconds, the number will be decreased single digit every 0.2 second automatically until
the button is released or the number reaches its lowest
value.
2. LCD Reset
z
z
Press the Scrolling Up and the Scrolling Down buttons
together for 3 seconds to reset the LCD display.
11
Page 16
Multi-
No.
function
Button
5
Back/ Mute
Button
ESC
The button has multiple functions. Please refer to the following
for detailed information.
1. Back to the Previous Menu Level
z
z
In setup mode, press the button for 0.1 second to go
back to the previous menu level.
2. Mute
z
z
When the UPS has any warning of fault conditions to
trigger an audible alarm, press and hold the button for 3
seconds to turn o the audible alarm.
Description
NOTE :
If the LCD display goes dim, press any button mentioned above for 0.1
second to wake up the LCD display and enable each button function.
3.3 LCD Display
Amplon RT Series
ONLINE
Input
Output
100
232.0V
230.0V
12
%
50.0Hz
50.0Hz
1
75
%
Page 17
Chapter 3 Operation Panel
1
1
100
%
100
%
75%
3.3.1 Icon/ Display Denition
No. Icon/ DisplayDescription
1. ON: The UPS is in parallel mode.
2. OFF: The UPS is in single mode.
NOTE :
1
2
For the Master UPS, the icon will ash
during parallel mode. For the Slave UPS,
the icon will illuminate, not ash, during
parallel mode.
Indicates that the load bank status is ON.
Indicates that the load bank status is OFF.
Indicates the battery capacity level.
3
4
Input
Output
5
!
Battery disconnected
6
0x1003
X
232.0V 50.0Hz
232.0V 50.0Hz
5 seconds
Indicates that the battery is abnormal and needs
replacement. If the battery is abnormal, the bat-
tery capacity icon
(
will be o.
)
Indicates the load level (%).
When the UPS runs normally, the display will
show the input/ output voltage and frequency.
When the UPS has abnormalities or is in fault
condition, the display will show an error code
and its corresponding fault or warning message.
NOTE :
The error code and the fault/ warning
message will appear alternatively for
every 5 seconds.
Indicates that the buzzer is muted.
13
Page 18
3.3.2 Operation Mode Diagram Denition
ECO
No. DiagramDescription
1
2
3
ONLINE
Input
Output
ECO
Input
Output
BATTERY
Runtime
168
min
Input
Output
100
232.0V
230.0V
100
232.0V
232.0V
100
0.0V
230.0V
%
%
%
50.0Hz
50.0Hz
50.0Hz
50.0Hz
0.0Hz
50.0Hz
1
75
Indicates ONLINE mode.
%
Indicates ECO mode.
NOTE :
1
In ECO mode, the diagram’s
power ow will change according
to the UPS input voltage and
75
%
frequency. However, the ECO
icon (
) shown on the
upper-left corner will not change
even if the UPS transfers to online
mode or battery mode.
1
75
Indicates BATTERY mode.
%
4
Amplon RT Series
BYPASS
Input
Output
100
232.0V
232.0V
%
50.0Hz
50.0Hz
1
75
Indicates BYPASS mode.
%
14
Page 19
Chapter 3 Operation Panel
No. DiagramDescription
5
6
STANDBY
Input
Output
Freq. Conv.
Input
Output
100
232.0V
0.0V
100
232.0V
230.0V
%
%
50.0Hz
0.0Hz
50.0Hz
50.0Hz
1
Indicates AC STANDBY mode.
Indicates Frequency Conversion
mode.
NOTE :
1
In Frequency Conversion mode,
the diagram’s power ow will
change according to the UPS
75
%
input voltage and frequency.
However, the text Freq. Conv.
(
Freq. Conv.
) shown on the
upper-left corner will not change
even if the UPS transfers to
battery mode.
The rear panels of above mentioned models are similar. The dierences are the
battery voltage and DC value printed on the panels. For detailed information
about the printed battery voltage and DC value, please refer to the table below.
Here, only 5kVA UPS’s real panel (see Figure 4-1) is taken for example.
5678
123
4
9
10
PARALLELPARALLEL
MINI SLOT
DRY CONTACT
P1
NOTE :
P2 P3 P4
RS-232
RS-485
REPO
OFF
ON
INPUT
BREAKER
UPS OUTPUTUPS OUTPUT-PAC INPUT
EXTERNAL BATT.
PL2(N)PL1(PL)L2(N)L1(L)L2(N)L1(L)
192V DC 29A
CONNECTOR
Remove the terminal
cover plate and you will
see the wiring terminal
1215
blocks.
11
(Figure 4-1: 5kVA Rear Panel)
No. Item Functions
For installation of an optional card, such as Mini
1
MINI Slot
SNMP IPv6 card, Mini Relay I/O card, or Mini
MODBUS card. For more information, please
refer to Chapter 5: Communication Interfaces.
TMOV
TUPNITUPTUO
14
13
Amplon RT Series
16
Page 21
No. Item Functions
For UPS parallel communication. For more
information, please refer to Chapter 5: Communication Interfaces.
2
Parallel Ports
NOTE :
To enhance parallel reliability, please
adopt the Daisy Chain method to execute
parallel conguration.
1. Output dry contacts: Receive the UPS’s event
information to indicate the UPS status or
internal messages.
3
Dry Contacts
2. Input dry contacts: Let the UPS to receive
external control signals.
3. For more information, please refer to Chapter 5: Communication Interfaces.
When emergency events occur, it can shut
4
REPO Port
down the UPS safely and immediately. Please
refer to Chapter 5: Communication Interfaces
for details.
Chapter 4 Rear Panel
Connects to a computer so you can monitor the
5
RS-485 Port
UPS status or let the UPS communicate with
lithium ion batteries.
Connects to a computer so you can build up
RS-232 communication, congure the UPS
6
RS-232 Port
and upgrade the UPS rmware. Please refer
to Chapter 5: Communication Interfaces for
more information.
Connects to a computer to monitor the state of
the UPS, congure the UPS parameters and
7
(USB Port)
update the management software. Please refer
to Chapter 5: Communication Interfaces for
more information.
17
Page 22
No. Item Functions
8
9
10
11
12
13
14
15
Input Breaker
External Batt.
Connector
UPS Output
Terminal Block
Terminal Block
UPS Output
Terminal Block – P
Controls the UPS’s input switch and for safety
protection.
Connects to the external battery pack (optional).
5K: 192V DC 29A
6K: 192V DC 35A
8K: 240V DC 37A
10K: 240V DC 46A
TMOV For UPS internal TMOV's grounding.
For loads’ grounding.
1. Uncontrollable.
2. Without load-bank function.
3. Connects to the loads (L1 & L2 for sux B8
model; L & N for sux 35/ B0 model).
For UPS grounding.
AC Input
Connects to the mains.
(L1 & L2 for sux B8 model; L & N for sux 35/
B0 model)
1. Controllable.
2. With load-bank function.
3. Connects to the loads (PL1 & PL2 for sux
B8 model; PL & N for sux 35/ B0 model).
NOTE :
1. Please note that, for parallel application, the output loads can only be
connected to this output terminal
block.
2. When the UPS is working in singleunit mode, the output terminal block
has load bank function. The load bank
function will be disabled when the
UPS is running in parallel mode.
Amplon RT Series
18
Page 23
Chapter 5 Communication Interfaces
Chapter 5 : Communication Interfaces
NOTE :
1. The UPS can still function properly without making the connections below.
2. For the location of the following communication interfaces, please refer to
Figure 4-1~Figure 4-2.
5.1 MINI Slot
The MINI slot is for mini-size cards. You can install the Mini SNMP IPv6, Mini
Relay I/O, or Mini MODBUS card in this slot to let the system have network
communication, dry contact function, and MODBUS communication respectively.
5.2 Parallel Ports
The two parallel ports are for UPS parallel communication. UPSs (at maximum 4)
with the same capacity, voltage and frequency can be coupled via the provided
parallel cable to run in parallel mode.
5.3 Dry Contacts
The RT UPS provides one input dry contact for you to receive external control
signals. You can set up relevant items in the Dry Contact Setting screen, which
includes Disable/ ROO/ RPO/ Remote shutdown/ Forced bypass/ On generator.
Besides, there are three congurable output dry contacts for you to receive UPS
events. The output dry contacts are normally open (NO). You can set up relevant
items in the Dry Contact Setting screen, which includes Disable/ On bat/ Low
bat/ Bat fault/ Bypass/ UPS OK/ Load protected/ Load powered/ General alarm/
Overload alarm. Please refer to 9.2.2 Setting Menu and 9.2.4 Maintenance Menu
for relevant information.
5.4 REPO Port
The REPO port can be connected to an external switch. After the external switch
is turned to the ‘CLOSED’ position, the UPS will switch o the inverter immediately
and cut o the UPS output without transferring to bypass mode.
19
Page 24
NOTE :
1. You can use the management software to configure the REPO port as
normally open (NO) or normally closed (NC). The factory default setting is
normally open (NO).
2. The REPO port can also be used for ROO application, which allows you
remotely turn on/ o the inverter. If you need detailed ROO information or
ROO setup service, please contact your local dealer or customer service.
Please note that this port can only be modified by qualified service
personnel.
5.5 RS-232 Port
You can use a RS-232 cable (user supplied) to connect the UPS with a computer
and install the UPSentry 2012 software*
z
z
The RS-232 port provides the following functions
1
to check and monitor the UPS status.
1. RS-232 communication (baud rate: 2400/ 9600)
2. UPS conguration
3. Firmware upgrade (baud rate: 9600)
z
z
Pin Assignment
1. PIN 2: TXD <Transmitting Data>
2. PIN 3: RXD <Receiving Data>
3. PIN 5: GND <Signal Ground>
z
z
Hardware
1. Baud Rate: 2400/ 9600bps
2. Data Length: 8 bit
3. Stop Bit: 1 bit
4. Parity: None
NOTE :
1. *1 You can download the software from the following link:
http://www.deltapowersolutions.com/en/mcis/ups-software.php.
2. Do not use the USB port and the RS-232 port simultaneously. If you
connect the USB cable (user-supplied) to the USB port, the RS-232
port will be disabled right away.
Amplon RT Series
20
Page 25
5.6 USB Port
Chapter 5 Communication Interfaces
Please use the provided USB cable to connect the UPS with a computer and install
the UPSentry 2012 software*
1
to check and monitor the UPS status. The USB port
has the following functions:
1. HID USB communication
2. UPS conguration with EEPROM programming
3. UPS rmware upgrade
4. Event logs download
5. Dry contacts setup
NOTE :
1. *1 You can download the software from the following link:
http://www.deltapowersolutions.com/en/mcis/ups-software.php.
2. Do not use the USB port and the RS-232 port simultaneously. If you
connect the USB cable (user-supplied) to the USB port, the RS-232
port will be disabled right away.
5.7 RS-485 Port
You can use the RS-485 port to check and monitor the UPS status.
z
z
The RS-485 port provides the following functions
1. Lithium-ion battery communication
2. RS-485 communication (baud rate: 9600)*
z
z
Pin Assignment
1
1. PIN 7: RS485 D+
2. PIN 8: RS485 D-
z
z
Hardware
1. Baud Rate: 9600bps
2. Data Length: 8 bit
3. Stop Bit: 1 bit
4. Parity: None
21
Page 26
NOTE :
1
*
: The RS-485 port is mainly designed for lithium-ion battery
communication. If you don’t use the lithium-ion batteries and would like to
check and monitor the UPS via the MODBUS protocol, the RS-485 port
(PIN 7 & PIN 8) is supportive.
5.8 External Battery Connector
To increase the battery backup time, you can connect several external battery packs
to the UPS. The connector is for connection to the external battery pack(s). Please
see below for relevant information.
z
z
Battery
UPS
Charge
Voltage
5kVA/ 6kVA219.2Vdc1A (default)*
8kVA/ 10kVA274Vdc1.5A (default)*
Charge
Current
Low Battery
Shutdown
1
168V±3%12V × 16 PCS
1
210V±3%12V × 20 PCS
The Number
Of Batteries
NOTE :
1
*
: For sux B0 model, its charge current default setting is 4A.
WARNING:
1. Please refer to the table below to select the charge current for 5kVA/
6kVA/ 8kVA/ 10kVA UPS.
2. If you need to modify the charge current default setting, please
contact your local dealer or customer service.
5kVA/ 6kVA UPSLevel 1Level 2Level 3Level 4
Total Battery
Capacity
5~9Ah9~17Ah18~30Ah27~40Ah
Charge Current1A2A3A4A
Amplon RT Series
22
Page 27
Chapter 5 Communication Interfaces
8kVA/ 10kVA UPSLevel 1Level 2Level 3Level 4
Total Battery
Capacity
9~17Ah17~20Ah20~30Ah27~40Ah
Charge Current1.5A2A3A4A
z
z
External Battery Pack
1. Delta external battery pack is optional. Please refer to the Quick Guide,
User Manual or Installation & Operation Guide included in the package of
the external battery pack.
2. When connecting the external battery pack with the UPS, you must install
an appropriate non-fuse DC breaker or the fast-acting fuse that meets the
safety certication. Do not use an AC breaker.
3. The breaker must be a 2-pole non-fuse DC breaker with characteristics of
1-pole 250Vdc, 2-pole 500Vdc and 35kA (or above) DC breaking capacity.
z
z
Battery/ Battery Pack Connection Warnings
1. Only use the same type of batteries from the same supplier. Never use old,
new and dierent Ah batteries at the same time.
2. The number of batteries must meet UPS requirements.
3. Do not connect the batteries in reverse.
4. Use the voltage meter to measure whether the total voltage, after battery
pack connection, is around 12.5Vdc × the total number of batteries.
NOTE :
1. Turn off the UPS and cut off the AC source before performing
battery/ battery pack replacement.
2. A battery can present a risk of electric shock and high short-circuit
current.
3. Servicing of batteries and battery packs must be performed
or supervised by qualified service personnel knowledgeable
in batteries, battery packs and the required precautions. Keep
unauthorized personnel away from batteries and battery packs.
23
Page 28
z
Maintenance
z
Alarm
When any external battery pack connected to the UPS has the following
problems, the UPS system will sound an alarm. Please see the table below.
No.
External Battery
Pack Status
Description
1Battery ModeThe alarm beeps once every 2 seconds.
2Battery Low WarningThe alarm beeps once every 0.5 second.
Battery Missing/
3
Weak Battery/ Battery
The alarm beeps once every 2 seconds.
Replacement
1. Overload_105%~125%: The alarm beeps
4Overload
once every 2 seconds.
2. Overload_125%~150%: The alarm beeps
once every 0.5 second.
The alarm beeps continuously for 5 seconds
5Fault
when the UPS detects an internal fault. After
the 5-seconds long beep, the alarm beeps
once every 2 seconds.
NOTE :
1
*
: After reconnecting or replacing the batteries, it might take a while for
the UPS to switch o the alarm automatically. If, after a period of time, the
audible alarm still exists, please manually initiate a battery test. Please
follow the route below to execute the manual battery test in order to clear
the alarm.
Route: press the button
for 0.1 second → select
Test → select Start Battery Test. Fore relevant information, please refer
to 9.2 Main Menu.
→ select
Amplon RT Series
24
Page 29
Chapter 6 Installation
Chapter 6 : Installation
Please refer to the system block diagram and related information below for correct
installation.
Bypass
Aux
Power
Inverter relay
Communication
Output
Board
Control
Board
LCD
Board
EMI
Output relay
To A2D/D2D
To inverter
To charger
Output load 1
Output load 2
A2D&D2D
External
Battery
Pack
Input relay
Input
I/P
EMI
Inverter
CHG
6.1 Rack Mounting
Use the included bracket ears and screws to mount the UPS in a rack by following
the procedures below.
1
Attach the included bracket ears to the lateral mounting holes of the UPS. See
Figure 6-1.
ESC
(Figure 6-1: UPS Bracket Ear Installation)
25
Page 30
2
Follow steps 1 to 4 to install the UPS in Delta’s rail kit (optional). See Figure
6-2.
1
Step
Step
Step
Step
3
If you want to use a non-Delta rail kit, please only follow step 4 .
: Adjust the length of the rail according to the rack.
2
: Tighten the nuts.
3
: Fix the rail on the rack.
4
: Insert the UPS in the rack and tighten the screws.
1
4
ESC
3
2
NOTE :
Amplon RT Series
(Figure 6-2: Rack Mounting)
If you need the optional rail kit, please contact your local dealer.
26
Page 31
Chapter 6 Installation
6.2 Tower Mounting
Use the included tower stands to mount the UPS in an upright tower position by
following the steps below.
1
Assemble the tower stands (see Figure 6-3).
Tower Stand
× 4 PCS
(Figure 6-3: Assemble the Tower Stands for 5/ 6/ 8/ 10kVA UPS)
2
Pull out the control panel 1, rotate the panel and the Delta logo nameplate
90° clockwise
and re-insert the control panel 3 (see Figure 6-4).
2
2
Delta Logo
Nameplate
Panel
(Figure 6-4: Rotate the Control Panel and the Delta Logo Nameplate)
3
Carefully lift the whole unit upright 4 with the Delta logo nameplates and the
2
3
ESC
1
icons shown on the panels facing up.
27
Page 32
Panel
ESC
4
Lift Up 90˚
(Figure 6-5: Place the Whole Unit Upright)
4
Place the whole unit inside the tower stands 5.
ESC
5
ESC
Delta Logo
Nameplate
ESC
Facing Up
Facing Up
(Figure 6-6: Place the Whole Unit inside the Tower Stands)
Leave adequate space (at least 50cm) around all sides of the unit for good
ventilation.
NOTE :
Amplon RT Series
A minimum of two people are required to execute 3 and 4.
28
Page 33
Chapter 7 Connection and Wiring
Chapter 7 : Connection and Wiring
7.1 UPS Connection Warnings
1
When connecting the UPS to the mains and the loads, it is highly recom-
mended that you install the protective devices. Please refer to the table below
and Figure 7-3.
UPS Power RatingSuggested Protective Device
Suggested
Supplier
5/ 6kVAD curve-50A circuit breakerDELIXI
8/ 10kVAD curve-80A circuit breakerDELIXI
2
The protective devices must use approved components that meet safety
certications.
3
The power supplying to the UPS must be single-phase in accordance with the
unit's rating label, and the UPS must be properly grounded.
7.2 Input/ Output Connection
1
Please see the gures below for input/ output connection.
2
Cable Selection:
UPS OUTPUTUPS OUTPUT-PAC INPUT
(Figure 7-1: Input/ Output Wiring Terminal Block)
PL2(N)PL1(PL)L2(N)L1(L)L2(N)L1(L)
29
Page 34
For the specications of input/ output cables, please refer to Table 7-1.
In accordance with National Electrical Codes (NEC), please install the
suitable conduits and cable sleeves.
3
When connecting the input/ output power cords, please observe the following
rules.
1. Turn o the UPS and cut o both AC source and the battery source before
connection.
2. Calculate the power consumption of the loads to avoid an overload
condition.
3. Ensure that the screws are tightly fixed after connection. Please refer to
Table 7-1.
4
Backfeed Protection:
When the UPS runs in battery mode or during AC power failure, the UPS’s
inner voltage or energy might be fed back to the input terminals, either directly
or via a leakage loop. To avoid the risk of electric shock resulted from the
backfeed, installation of a backfeed protection device between the AC input
and the UPS is highly recommended.
Amplon RT Series
30
Page 35
Chapter 7 Connection and Wiring
NOTE :
1. The UPS doesn’t have any built-in backfeed protection device.
Installation of the backfeed protection device between the AC input
and the UPS is highly recommended.
2. If there is no backfeed protection device installed between the AC
input and the UPS, please (1) attach a warning label on the switch
or breaker that controls the AC power supplying to the UPS, and (2)
check if any hazardous voltage exists on any terminals connected to
the AC power. The warning label shall carry the following wording or
equivalent.
Before Working on This Circuit
-Isolate Uninterruptible Power System (UPS)
-Then check for Hazardous Voltage between all terminals
Please refer to the diagram below to install the backfeed protection device
between the AC input and the UPS.
31
Page 36
Contactor
L (L1)
N (L2)
Coil
Control Relay
DC 12V
(Figure 7-2: Backfeed Protection Wiring Diagram)
L (L1)
N (L2)
UPS
Dry
Contact
7.3 Single Unit Wiring
1
Remove the terminal cover plate and you will see the wiring terminal block
shown in Figure 7-1.
2
Conrm the input breaker is in the OFF position.
3
According to the capacity and the model of your UPS, select proper input and
output cables.
4
Connect the main AC source/ output/ external battery pack cables to the wiring
terminal block. Please refer to Figure 7-3.
5
Ground the UPS.
Amplon RT Series
32
Page 37
Output
Protective
Devices
P
A
MINI SLOT
For Grounding
Chapter 7 Connection and Wiring
R
A
L
L
E
L
P
A
R
A
L
L
E
L
D
R
Y
C
P
O
1
N
T
P
A
2
C
T
P
3
P
4
R
E
P
O
R
S
4
8
5
R
S
2
3
2
U
L1(L)
PS
CONNECTOR
O
EXTERNAL BATT.
240V DC 46A
U
T
P
U
T
L2(N)
U
PL1(PL)
P
S
O
U
T
P
U
T
P
PL2(N)
T
M
O
V
L1(L)
A
C
I
N
P
U
T
L2(N)
For Grounding
Loads
For Grounding
Loads
Utility AC
Power
Input
Protective
Device
(Figure 7-3: Single Unit Wiring Diagram)
7.4 Parallel Units Wiring
NOTE :
1. You can parallel at maximum four UPS units. To enhance parallel
reliability, please adopt the Daisy Chain method to execute parallel
conguration. Please refer to Figure 7-4.
2. Please ensure that each parallel UPS’s wiring is correct, and all external
output protective devices are in the 'OFF' position. For the location of
output protective devices, please refer to Figure 7-3.
3. When UPSs are paralleled, the diameter and the length of each parallel
UPS’s input cables and output cables must be equal. This ensures that
the parallel UPSs can equally share the equipment loads in bypass mode.
4. Before start-up of the parallel system, make sure that each UPS’s ID is
correctly set up and each unit’s major parameters are set the same. For
the major parameters’ information, please contact service personnel.
5. Ensure that each parallel UPS is completely turned on before starting
up the loads. To prevent the UPS from activating the overload protection
mechanism during start-up process, please turn on the high-power loads
rst and then low-power loads.
6. The parallel UPSs cannot connect with common batteries.
7. The parallel UPSs cannot run in ECO mode.
33
Page 38
AC Input
Terminal
Block
UPS 1
UPS Output
Terminal
Block
Parallel Port
Parallel Port
Daisy Chain
Method
Parallel Cable
UPS Output
Terminal
Block
Parallel Port
Parallel Port
UPS Output
Terminal
Block
Parallel Port
Parallel Port
1Ø2W
Parallel Cable
Parallel Cable
Loads
Main AC
Source
1Ø3W
AC Input
Terminal
Block
UPS 2
AC Input
Terminal
Block
UPS 4
(Figure 7-4: Parallel Units Wiring Diagram)
1
Please follow steps 1 ~ 4 stated in 7.3 Single Unit Wiring.
2
Use the provided parallel cable to connect the parallel ports on the parallel
units.
3
Ground the parallel UPSs.
7.5 External Battery Pack Connection
To increase the battery backup time, you can connect several external battery
packs to the UPS. Please follow the steps below (Figure 7-5 & Figure 7-6) and
information in 5.7 External Battery Connector to complete the connection.
NOTE :
1. When connecting the external battery pack with the UPS, you must install
an appropriate non-fuse DC breaker or the fast-acting fuse that meets the
safety certication. Do not use an AC breaker.
2. The breaker must be a 2-pole non-fuse DC breaker with characteristics of
1-pole 250Vdc, 2-pole 500Vdc and 35kA (or above) DC breaking capacity.
Amplon RT Series
34
Page 39
Chapter 7 Connection and Wiring
1
Remove the two screws from the external battery connector’s panel shown
Insert the provided battery cable into the external battery connector 1 and use
the provided two screws and two standos to rmly x the battery cable
2
1
After Removal of
the External Battery
Connector’s Panel
2
.
StandoffsScrews
(Figure 7-6: Battery Cable Connection)
35
Page 40
Chapter 8 : Operation
100
%
8.1 Single Unit Start-up
NOTE :
1. Before start-up, ensure that the batteries are fully charged. Before
using the UPS for the first time, please check the battery capacity and
the charging settings. Make sure that you charge the batteries until the
battery capacity percentage shown on the UPS’s LCD is 100%
2. The congurable battery Q’ty is 12, or 16 ~ 22. Please make sure that the
actual battery Q’ty is the same as that is congured on the LCD. Set up
the corresponding charge current based on the total battery amp-hour.
3. If the UPS connects to an inductive load, the inrush current (initial surge
current) may restart the inverter. To avoid this situation, please turn on the
inductive load in bypass mode before starting up the inverter.
8.1.1 Start-up with AC Input (Single Unit)
1
Verify if the UPS’s input cord meets with N, L & G of the wall socket and the
utility AC power works normally.
2
Switch on the input protective device (see Figure 7-3) installed between the
UPS and the utility AC power and switch on the input breaker. After that, the
UPS will enter the Initial Setting Screen (please refer to 9.1 Initial Setting Screen for more information).
(
.
)
Amplon RT Series
Press and hold
3
the ON/ OFF button (
for 3 seconds to start up the UPS.
)
Release the button after you hear one beep and the UPS will start up. After the
UPS performs self-diagnosis, the UPS will run in ON-LINE mode.
36
Page 41
Chapter 8 Operation
Press and hold the button
BYPASS
%
100
Input
Output
232.0V
232.0V
50.0Hz
50.0Hz
for 3 seconds and release it
after you hear one beep.
Self Diagnosis
In Progress...
ONLINE
X
1
75
75%
%
0x1012
4
Once the UPS runs normally, switch on the output protective devices (see
!
Battery Test Fail
Figure 7-3) installed between the UPS and the loads.
8.1.2 Start-up with Batteries (Single Unit)
1
Please check the '+' and '-' poles of the batteries and ensure that wiring is
correct.
2
Turn on the UPS’s external battery pack’s breaker.
When there is no AC input, press and hold the ON/ OFF button
3
seconds to start up the UPS. Release the button after you hear one beep and
the UPS will start up. After the UPS performs self-diagnosis, the UPS will run in
BATTERY mode.
37
(
)
for 3
Page 42
Press and hold the button
for 3 seconds and release it
after you hear one beep.
Self Diagnosis
In Progress...
BATTERY
Runtime
168
min
Input
Output
4
Once the UPS runs normally, switch on the output protective device (see
100
0.0V
230.0V
%
0.0Hz
50.0Hz
1
75
%
Figure 7-3) installed between the UPS and the loads.
NOTE :
To prevent the UPS from activating the overload protection mechanism
during start-up process, please turn on the high-power loads rst and
then low-power loads.
8.2 Single Unit Turn-o
1
Make sure all of the loads connected to the UPS are o.
2
(1) Press and hold the ON/ OFF button (
you hear one beep, (3) use the Scrolling UP or Down button (
lect 'Yes', and (4) press the Enter button (
) for 3 seconds, (2) release it after
/ ) to se-
) to conrm your selection.
Amplon RT Series
38
Page 43
Chapter 8 Operation
3
Switch off the input breaker, input protective device (see Figure 7-3) and
output protective devices (see Figure 7-3).
4
After the LCD backlight goes dim and the fans stop completely, switch o the
battery breaker to ensure that there is no remaining battery power.
8.3 Parallel Units Start-up
NOTE :
1. You can parallel at maximum four UPS units. To enhance parallel
reliability, please adopt the Daisy Chain method to execute parallel
conguration. Please refer to Figure 7-4.
2. Please ensure that each parallel UPS’s wiring is correct, and all external
output protective devices are in the 'OFF' position. For the location of
output protective devices, please refer to Figure 7-3.
3. When UPSs are paralleled, the diameter and the length of each parallel
UPS’s input cables and output cables must be equal. This ensures that
the parallel UPSs can equally share the equipment loads in bypass mode.
4. Before start-up of the parallel system, make sure that each UPS’s ID is
correctly set up and each unit’s major parameters are set the same. For
the major parameters’ information, please contact service personnel.
5. Ensure that each parallel UPS is completely turned on before starting
up the loads. To prevent the UPS from activating the overload protection
mechanism during start-up process, please turn on the high-power loads
rst and then low-power loads.
6. The parallel UPSs cannot connect with common batteries.
7. The parallel UPSs cannot run in ECO mode.
8.3.1 Start-up with AC Input (Parallel Units)
1
Ensure that input and output connection is correct for the parallel system.
2
Turn on each UPS’s external battery pack’s breaker.
3
Turn on each UPS’s input protective device and input breaker. For the location
of input protective device, please refer to Figure 7-3.
Press and hold each parallel UPS’s ON/ OFF button () for 3 seconds to start
4
up the UPS. Release the button after you hear one beep and the UPS will start
up. After each UPS performs self-diagnosis, each parallel UPS will run in ON-
39
Page 44
LINE mode.
5
Turn on each UPS’s output protective devices. For the location of output
protective devices, please refer to Figure 7-3.
6
Once the parallel system runs normally, please turn on the high-power loads
rst and then low-power loads.
8.3.2 Start-up with Batteries (Parallel Units)
1
Please check the '+' and '-' poles of the batteries and ensure that wiring is
correct.
2
Turn on each UPS’s external battery pack’s breaker.
Press and hold each parallel UPS’s ON/ OFF button () for 3 seconds to
3
start up the UPS. Release the button after you hear one beep and the UPS will
start up. After each UPS performs self-diagnosis, each parallel UPS will run in
Battery mode.
4
Turn on each UPS’s output protective devices. For the output protective
devices’ location, please refer to Figure 7-3.
5
Once the parallel system runs normally, please turn on the high-power loads
rst and then low-power loads.
8.4 Parallel Units Turn-o
1
Make sure all of the loads connected to each Parallel UPS are o.
(1) Press and hold each parallel UPS’s ON/ OFF button () for 3 seconds,
2
(2) release it after you hear one beep, (3) use the Scrolling UP or Down button
/ ) to select 'Yes', and (4) press the Enter button () to conrm your
(
selection. After that, the parallel system will transfer to bypass mode if bypass
power runs normally.
3
Turn o each UPS’s input breaker, input protective device and output protective
devices. For the input and output protective devices’ location, please refer to
Figure 7-3. After the LCD backlight goes dim and the fans stop completely, the
parallel system will completely shut down.
4
Switch off each UPS’s external battery breaker or disconnect all external
battery cables from the parallel UPSs to ensure that there is no remaining
Amplon RT Series
40
Page 45
Chapter 8 Operation
battery power.
8.5 Operation Mode
z
z
Standby Mode
After the UPS is connected to the utility AC power, it will supply power to the
UPS and the batteries will be charged.
z
z
Online Mode
In on-line mode, the connected loads are supplied by the inverter, which derives
its power from the utility AC power, and the UPS charges the batteries and
provides power protection to its connected loads.
z
z
Bypass Mode
In bypass mode, the critical loads are directly supplied by the utility AC power
and the batteries are charged. The default setting of the UPS is set in BYPASS
mode.
z
z
Battery Mode
When the UPS is operating during a power outage, the batteries provide DC
power, which maintains inverter operation to supply power to the critical loads.
You can install the UPSentry 2012 software (please download from http://www.
deltapowersolutions.com/en/mcis/software-center.php) or install the Mini SNMP
IPv6 card (optional) or the Mini MODBUS card (optional) to monitor and estimate
the battery remaining capacity. For more information about the Mini SNMP IPv6
card (optional) or the Mini MODBUS card (optional), please refer to its user
manual.
z
z
ECO Mode
In ECO mode, when the utility input voltage and frequency are within the range
of rating voltage ±10% and rating frequency ±3Hz, the loads are supplied by the
utility AC power; if out of the range, the loads are supplied by the inverter.
z
z
Frequency Conversion Mode
In Frequency Conversion mode, the UPS output frequency is manually set up.
The system will disable the bypass function and there is no bypass output.
41
Page 46
Chapter 9 : LCD Display & Settings
NOTE :
1. Please refer to Chapter 3: Operation Panel to learn how to use the
operation panel and understand every icon/ diagram denition.
2. Each of the display diagrams shown in this chapter is for reference only.
Actual display depends on the operation of the UPS.
9.1 Initial Setting Screen
When the UPS is powered on for the rst time, the LCD display will show the Initial
Setting Screen and you can modify language, output voltage, battery parameters
based on actual needs during initial setup. The default settings of language, output
voltage, and battery parameters may vary according to dierent models. Press the
button to continue if there is no special requirement. After you configure the
Language, Date & Time, Output Setting, External Battery Type and External
Battery Capacity settings, the LCD display will move to the Main Screen that
shows the current operation mode.
The following ow chart helps you to navigate the LCD screen.
Amplon RT Series
42
Page 47
Welcome
Page
Chapter 9 LCD Display & Settings
Output Setting
Prev.
Output Phase:
Voltage:
Frequency:
External Battery Type
Standard Battery Pack
P/N:
GES161B105700
Qty:
1-Phase
100 V
Auto
Next
Prev.
0
Next
Initial Setting
Screen
Date:
Time:
Language
Prev.
English
Next
Date & Time
Prev.
2017 / 10 / 06
18 : 04 : 25
Next
External Battery Capacity
Prev.
Customer Own Battery Cabinet
Battery Voltage:
Battery Capacity:
STANDBY
Input
Output
Next
100
232.0V
0.0V
%
192 Vdc
9 9 9
50.0Hz
0.0Hz
1
Main Screen
(showing
the current
operation mode)
The Initial Setting Screen will no longer appear after initial conguration. Next time,
when the UPS is powered on, the LCD display will show DELTA welcome page for
3 seconds and then directly go to the Main Screen that shows the current operation
mode.
43
Page 48
Welcome Page
BYPASS
1
Main Screen
%
75
50.0Hz
50.0Hz
Input
Output
100
232.0V
232.0V
%
9.2 Main Menu
In the Main Screen, press the button
You can set up relevant items here.
Main Menu
Measurement
NOTE :
Please note that only qualied service personnel can perform setup actions.
Control
for 0.1 second to enter the Main Menu.
Setting
Maintenance
Amplon RT Series
44
Page 49
Chapter 9 LCD Display & Settings
For setup procedures, please refer to the following:
1
In the Main Menu, select the item you want to configure, press the ENTER
button
Press the button
2
for 0.1 second and the UPS will enter the setup mode.
for 0.1 second or press the button
for 0.1 second to
navigate the setting items.
Press the button
3
for 0.1 second to choose the parameter that you want to
change, and the parameter will ash.
Press the button
4
for 0.1 second or press the button
for 0.1 second to
increase or decrease the parameter value. If either of the buttons is pressed
for over 2 seconds, the LCD will automatically switch between the selectable
values every 0.2 second until either of the buttons is released or the number
reaches its highest or lowest value.
Press the button
5
to conrm your parameter setup or press the button
to go back to the previous status.
After that, press the button
6
for 0.1 second or press the button
for 0.1
second to move to the previous or the next setting item.
ESC
In setup mode, press the
7
button and the LCD will exit from the setup
mode.
8
In setup mode, if you don’t press any button for more than 5 minutes, the LCD
will exit from the setup mode and go back to the original display automatically.
Please refer to the Menu Tree below for all setting options.
ESC
45
Page 50
(Level 1)(Level 1)(Level 1)(Level 1)
Measurement
(Level 2)
Output
Voltage/ Frequency/
(Level 3)(Level 3)(Level 3)
Current/ Watts/
Load/ VA/
Cumulated/ Power
(Level 2)
Input
Voltage/ Frequency
(Level 2)
Bypass Input
Voltage
Frequency
(Level 2)
Battery
Voltage/ Capacity/
Last Battery Test Runtime/
Charge Mode/
Charge Stage/
Total Capacity
Start Battery Test
Deep Discharge Test
Local Output Dry Contact Test
(Level 2)
Battery Aging
Create Discharging Reference
Battery Discharging History
(Level 2)
Reset
Reset Power Usage Calculator
Restore Factory Setting
(Level 2)
Log
Event List
Clear Log
(Level 2)
About
Model Name/ UPS Part No./
UPS Serial No./
UPS Manufacture Date/
UPS Firmware Version/
Battery Summary - Installed/
Battery Summary - Replaced
Amplon RT Series
(Figure 9-1: Menu Tree)
46
Page 51
9.2.1 Measurement Menu
Measurement
Setting
Chapter 9 LCD Display & Settings
In Main Menu, after selecting
, press the button
to enter the
Measurement Menu. The Measurement Menu displays the UPS’s status readings,
such as Output, Input, Bypass and Battery information.
Measurement
Control
Setting
Maintenance
Output
Input
Bypass
Battery
9.2.2 Setting Menu
In Main Menu, after selecting
Measurement
Control
Setting
Maintenance
, press the button
to enter the Setting Menu.
Output
Input
ECO Mode
Parallel
On/Off Settings
Battery
General
Outlet Control
1 /3
2 /3
3 /3
Dry Contact Setting
Component Life Prediction
47
Page 52
You can choose the setup items such as Output, Input, ECO Mode, Parallel,
On/ Off Settings, Battery, General, Outlet Control, Dry Contact Setting and
Component Life Prediction to set up relevant settings. For more information about
the Setting Menu, please refer to the tables below for each setup item’s relevant
default value and selectable value.
z
z
Output
Setup ItemsSelectable ValueDefault
Output Phase1-phase1-phase
208V for sux B8 model
230V for sux 35 & B0
models
Auto
Output Voltage
Output Frequency
Output Sync.
Freq. Range
Output Freq.
Slew Rate
200V, 208V, 220V,
230V, 240V
1
Auto*
/ Converter-50Hz*2 /
Converter-60Hz*
2
±0.5/ 1/ 3/ 5Hz±3Hz
0.5/ 1/ 2/ 3/ 4 Hz/ sec.1 Hz/sec.
Output ModeIndustrial/ ITIT
Standby ModeNo output/ Bypass outputBypass output
Overload Alarm30-105% (per step: 5%)105%
NOTE :
1. *1: When the Output Frequency is set as Auto, the output frequency
will vary according to the bypass frequency. If the bypass frequency
is ≥ 55Hz, the Free_Run_Frequency/ Cold_Start_Frequency will be
set as 60Hz.
If the bypass frequency is < 55Hz, the Free_Run_Frequency/ Cold_
Start_Frequency will be set as 50Hz.
2. When the Output Frequency is set as Auto and the Bypass Output
under the Standby Mode item is set as Enable, the bypass output
range will be the same as the Output Sync. Freq. Range.
2
3. *
: When the Output Frequency is set as Converter-50Hz/
Converter-60Hz, the UPS will enter the Frequency Conversion
mode and the bypass output will become Disable.
Amplon RT Series
48
Page 53
Chapter 9 LCD Display & Settings
z
z
Input
Setup ItemSelectable ValueDefault Value
Bypass Max. Voltage+10/ 15/ 20%+15%
Bypass Min. Voltage-10/ 15/ 20/ 25/ 30/ 35/ 40%-20%
z
z
ECO Mode
Setup ItemSelectable ValueDefault Value
ECO ModeDisable/ EnableDisable
ECO Max. Voltage5-15% (per step: 1%)+10%
ECO Min. Voltage5-15% (per step: 1%)-10%
NOTE :
The setup items ECO Max. Voltage and ECO Min. Voltage will only be
shown on the display when ECO Mode is enabled.
z
z
Parallel
NOTE :
The following function is not applicable to the Standard Runtime Model.
In Setting Menu, the sub item Option 1 under the item Energy Saving
cannot be changed.
z
z
Battery
Setup ItemSelectable ValueDefault Value
Automatic Battery Test
No test/ Daily/ Weekly/
Biweekly/ Monthly
No test
Deep Discharge Test20-90% (per step: 10%)90%
Low Battery
Warning Capacity
Warning of
Remaining Time
Runtime Limitation
Disable/ 1/ 2/ 3…./ 240mins
0-95%
(per step: 5%)
0-60mins
(per step: 1min)
(per step: 1min)
2mins
Disable
Charge Mode2-stage/ 3-stage2-stage
Float Charging
Voltage
Internal Charging
Current
External Battery Type *
For 5K/ 6K: 1/ 2/ 3/ 4/ 5/ 6/ 7/ 8A*
3
Auto/ Customize
(2.20 - 2.35 V/ cell,
per step: 0.01V)
For 8K/ 10K: 1.5/ 2/ 3/ 4/ 5/ 6A
Standard battery pack/
Customer own batt. pack
1
1A (5K/ 6K)*2
1.5A (8K/ 10K)*
10%
Auto
2
Amplon RT Series
50
Page 55
Chapter 9 LCD Display & Settings
Setup ItemSelectable ValueDefault Value
Standard battery pack:
External Battery
Capacity
Part Number Quantity
Customer own batt. pack:
Battery Voltage Capacity
Install dateYYYY/ MM/ DD
NOTE :
1
*
: Under the condition of rated battery voltage ≤ 192Vdc.
2
: For sux B0 model, its charge current default setting is 4A.
*
3
: When the External Battery Type is set as Standard battery pack,
*
you need to congure the Part Number and the Quantity of the standard
battery pack(s).
- Battery
Internal Charging Current
1.5 A
External Battery Type
Standard Battery Pack
Part Number
GES161B151XXX
3 /4
- Battery
Quantity
0
Install Date
2017/11/11
When the External Battery Type is set as Customer own batt. pack,
the Part Number and Quantity will be changed accordingly to Battery Voltage and Total Capacity.
z
z
General
Setup ItemSelectable ValueDefault Value
Language
English/ 简体中文 / 繁體中文 /….
Audible AlarmEnable/ DisableEnable
LCD Back LightAlways On/ Auto OAuto o
DateYYYY/MM/DD
TimeHH:MM:SS
4 /4
English
51
Page 56
z
z
Outlet Control
Setup
Item
Outlets -
Group 1
z
z
Dry Contact Setting
Setup
items
Dry Contact
1 - Input
Dry Contact
2 - Output
Dry Contact
3 - Output
Selectable Values-
Level 2
Output Reboot
Duration
Load Bank
Runtime Limitation
Selectable Values-
Level 3
Disable/ 5/ 6/
…/ 300
seconds
(per step: 1sec)
Disable/ 1/ 2/…/ 240mins
(per step: 1min)
Selectable
value
1
Option 1
*
: Disable/ ROO/ RPO/ Remote
shutdown/ Forced bypass/ On generator
Option 2: 0-999s (per step: 1 sec)
Option 3: Normal open/Normal close
Disable/ On bat/ Low bat/ Bat fault/ Bypass/ UPS
OK/ Load protected/ Load powered/ General alarm/
Overload alarm
Disable/ On bat/ Low bat/ Bat fault/ Bypass/ UPS
OK/ Load protected/ Load powered/ General alarm/
Overload alarm
Default
Value
Disable
Disable
Default
value
Disable
On batt.
Low batt.
Dry Contact
4 - Output
Remote
Control
Amplon RT Series
Disable/ On bat/ Low bat/ Bat fault/ Bypass/ UPS
OK/ Load protected/ Load powered/ General alarm/
Overload alarm
The Maintenance Menu provides commands for enabling UPS maintenance
functions. It also provides event logs and UPS identification. Please refer to the
table below for the setup items and selectable values.
LEVEL 1LEVEL 2LEVEL 3LEVEL 4LEVEL 5
Test Result: Pass
Maintenance
Test
Battery
Aging
Start Battery Test
Deep Discharge Test
Local Output Dry
Contact Test
Create Discharging
Reference
Battery Discharging
History
Test in
Progress…
Test in
Progress…
Dry Contact 2
Dry Contact 3
Dry Contact 4
Yes/ Cancel
Item, Output
power, Total
discharging time
Test Result: Fail
Test Result: Not
Finished
Test Result: Pass
Test Result: Fail
Test Result: Not
Finished
Dry Contact 2
In Progress…
Dry Contact 3
In Progress…
Dry Contact 4
In Progress…
Date/ Time,
Average load (W),
Actual discharging
time,
Estimated remaining
time,
Total discharging time
Amplon RT Series
Reset
Reset Power Usage
Calculator
Restore Factory
Setting
56
Yes/ Cancel
Yes/ Cancel
Page 61
Chapter 9 LCD Display & Settings
LEVEL 1LEVEL 2LEVEL 3LEVEL 4LEVEL 5
Description,
Event code
YYYY/MM/DD
HH:MM:SS
Error Description
Maintenance
Log
About
Event List
Clear Log Yes/Cancel
Model Name: RT-5K
UPS - Part No.
UPS502R2RT0B035
UPS - Serial No.
1BA0150001
UPS - Manufacture
Date
YYYY-MM
PS Firmware –
Version
06AR004
Battery Summary:
Installed YYYY/MM/
DD
Replace YYYY/MM/
DD
57
Page 62
For example, if you need to execute a battery test, please go to Test → Start
Battery Test → Test In Progress… → Test Result: Pass (or Fail).
Test
Battery Aging
Reset
Log
1 /2
- Test
Start Battery Test
Deep Discharge Test
Local Dry Contact test
Battery Test
Test In Progress...
Battery
Press ESC key to abort test
Battery Test
272.0V
85%
Test In Progress...
Battery
Press ESC key to abort test
272.0V
85%
ESC
ESC
Amplon RT Series
Battery Test
Test In Progress...
Battery
Press ESC key to abort test
272.0V
85%
Test Completed
58
ESC
Page 63
Chapter 9 LCD Display & Settings
A.B.
Once the test is completed, the test result will be shown as follows.
A. Test Result_ Fail: The alarm icon will show in the left bottom of the LCD display.
B. Tests Result_ Pass: No alarm icon occurs, and the UPS runs normally.
Alarm
Icon
Battery Test
Battery Test
Test In Progress...
Test Result: FAIL
Battery
Battery
72.0V85%
272.0V
0%
Press ESC key to Escape
ONLINE
0X1012 01
!
X
1
75%
Battery disconnect or need replaced.
Battery Test
Battery Test
Test In Progress...
Test Result: Pass
Battery
Battery
72.0V85%
272.0V
Press ESC key to Escape
ONLINE
%
100
Input
Output
232.0V
230.0V
50.0Hz
50.0Hz
80%
1
75
%
59
Page 64
Chapter 10 : Optional Accessories
There are several optional accessories available for this RT series UPS. Please
refer to the table below for the optional accessories and their functions.
No. Item Function
1Dust Filter(s)
2Mini SNMP IPv6 Card
3Mini Relay I/O CardIncreases the quantity of dry contacts.
4Mini MODBUS Card
External Battery Pack
Cable Extension Kit
5
(includes 2 annular
terminals and 2 butt
joint connectors)
Delta Lead-acid
6
Battery Pack
Delta Lithium-ion
7
Battery Pack
Maintenance Bypass
8
Box (Single/ Parallel)
Prevent(s) dust from entering into the UPS to
ensure UPS reliability and to prolong product life.
Monitors and controls the status of the UPS via a
network system.
Lets the UPS have MODBUS communication
function.
Use the external battery pack cable extension kit
to extend its range.
Provides lead-acid batteries to let the UPS
continue supplying power to its connected loads
when a power outage occurs.
Provides lithium-ion batteries to let the UPS
continue supplying power to its connected loads
when a power outage occurs.
Lets the UPS continue supplying power to
its connected loads when the UPS is under
maintenance.
9Rail KitFixes the UPS in a rack cabinet rmly.
NOTE :
1. For detailed installation and operation of any accessory mentioned above,
please refer to the Quick Guide, User Guide, or Installation & Operation Guide included in the package of the relevant optional accessory.
2. If you want to buy any accessory mentioned above, please contact your
local dealer or customer service.
Amplon RT Series
60
Page 65
Chapter 11 Troubleshooting
Chapter 11 : Troubleshooting
1. When a problem occurs, please check if following situations exist before
contacting Delta service personnel:
z
z
Is the main input voltage present?
2. Please have the following information ready if you would like to contact the Delta
service personnel:
z
z
Unit information including model, serial number, etc.
z
z
An exact description of the problem. The more detailed description of the
problem, the better.
3. When you see the following problems occur, please refer to the solutions shown
below.
Error
Code
Alarm
Message
0X61C1 Input Fuse Open
0X60C0 PFC Soft Start Fail
0X6221
0X6241
0X62A0
0X62C0
DC Bus Over
Shutdown
DC Bus Under
Shutdown
0X1200 INV Volt Abnormal
Possible
Cause
The input fuse is
melted or the input
relay is open.
The UPS has an
internal fault.
1. The output has
capacitive or
inductive loads.
2. The UPS has an
internal fault.
The UPS has an
internal fault.
The UPS has an
internal fault.
Solution
Please contact
service personnel.
Please contact
service personnel.
1. Remove the
capacitive or
inductive loads.
2. Please contact
service personnel.
Please contact
service personnel.
Please contact
service personnel.
61
Page 66
Error
Code
0X1101
Alarm
Message
Output Overload
Shutdown
Possible
Cause
The UPS is overloaded.
Solution
Check the power
consumption of the
loads, and remove
the unnecessary
loads.
0XA000 Charger Fault
0X8106
0X6100
0X1003
INV IGBT Over
Heat Shutdown
PFC Over Heat
Shutdown
Battery
Disconnected
The UPS has an
internal fault.
1. The vents are
blocked.
2. The UPS has an
internal fault.
1. The vents are
blocked.
2. The UPS has an
internal fault.
1. The UPS is
not properly
connected to the
external battery
pack(s).
2. The battery/
batteries is (are)
damaged.
Please contact
service personnel.
1. Check whether the
vents are blocked.
2 Contact service
personnel.
1. Check whether the
vents are blocked.
2. Contact service
personnel.
1. Check whether the
UPS is properly
connected to the
external battery
pack(s).
2. Contact service
personnel.
NOTE :
If all possible causes are eliminated but the alarm still appears, please
contact your local dealer or customer service.
Amplon RT Series
62
Page 67
Chapter 12 Maintenance
100
%
Chapter 12 : Maintenance
12.1 UPS
z
z
UPS Cleaning
Regularly clean the UPS, especially the slits and openings, to ensure that the
air freely ows into the UPS to avoid overheating. If necessary, use an air-gun
to clean the slits and openings to prevent any object from blocking or covering
these areas.
z
z
UPS Regular Inspection
Regularly check the UPS every half year and inspect:
1. Whether the UPS, LEDs, and alarm function are operating normally.
2. Whether battery voltage is normal. If battery voltage is too high or too low,
nd the root cause.
12.2 Batteries
The RT series UPS uses lead-acid or lithium-ion batteries. Though the typical
battery life cycle is 3~5 years, the battery life depends on the temperature, usage,
and charging/ discharging frequency. High temperature environments and high
charging/ discharging frequency will quickly shorten the battery life. The batteries do
not require user maintenance; however, they should be checked periodically. Please
follow the suggestions below to ensure a normal battery lifetime.
z
z
Keep the usage temperature at 20°C ~ 25°C.
z
z
Idle batteries must be fully recharged every three months if the UPS needs to be
stored for an extended period of time. Please fully charge the batteries until the
battery capacity percentage shown on the UPS’s LCD is 100%
.
)
(
NOTE :
If the UPS’s batteries need to be replaced, please contact qualified
service personnel. During battery replacement, the loads connected to
the UPS will not be protected if input power fails.
63
Page 68
12.3 Fans
Higher temperatures shorten fan life. When the UPS is running, please periodically
check if each fan works normally and make sure if the ventilation air can move freely
around and through the UPS. If not, contact service personnel to replace the fans.
NOTE :
Please ask your local dealer or customer service for more maintenance
information. Do not perform maintenance if you are not trained for it.
Amplon RT Series
64
Page 69
Appendix 1 Technical Specications
Appendix 1 : Technical Specications
ModelRT-5K RT-6KRT-8KRT-10K
Power Rating5kVA/5kW 6kVA/6kW8kVA/8kW10kVA/10kW
WaveformPure Sinewave
Input
Output
Battery &
Charger
Nominal
Voltage
Voltage
Range
Frequency50/60 Hz ± 10 Hz
Power Factor0.99 (full load)
iTHD< 3% (linear load)
ConnectionTerminal Block
Power FactorUnity
Voltage200/208/220/230/240 Vac
Voltage
Regulation
Frequency50/60 Hz ± 0.05 Hz
vTHD<2% (linear load)
Overload
Capacity
Cress
Factor
ConnectionTerminal Block × 2
Battery Voltage
Battery Type
Charging
Current
< 105%: continuous; 105% ~ 125%: 2 minutes;
125% ~ 150%: 30 seconds; >150%, 500 ms
1
144
*
Default: 192 Vdc
200/208/220/230/240 Vac
175 ~ 280Vac (100% load);
100 ~ 175Vac (50% ~ 100% load)
± 1% (linear load)
3:1
, 192 ~ 264 Vdc
adjustable
Lead-acid battery or
Lithium-ion battery
Up to 8A
1
144
,192 ~ 264 Vdc
*
adjustable
Default: 240 Vdc
65
Page 70
ModelRT-5K RT-6KRT-8KRT-10K
Eciency
Online ModeUp to 95.5%
ECO ModeUp to 99%
Audible Noise48 dBA50 dBA
DisplayLED indicators and LCD display
Communication
Interfaces
Physical
Environ-
ment
Dimensions
(W × D × H)
Weight
Operating
Altitude
Operating
Temperature
Storage
Temperature
Relative
Humidity
MINI Slot × 1, RS-232 Port × 1, USB Port × 1,
Parallel Port x 2, REPO/ROO × 1,
RS-485 Port × 1, Dry Contact × 4
440 × 430/ 508
2
× 88.2 mm
*
(17.3 × 16.9/ 20 × 3.5 inch)
10.9 kg
(24.03 lb)
10.9 kg
(24.03 lb)
440 × 565/ 643
(17.3 × 22.2/ 25.3 × 3.5 inch)
15.2 kg
(33.51 lb)
0 ~ 3000 m (0 ~ 10000 ft);
0 ~ 1000 m (0 ~ 3300 ft) (without derating)
0°C ~ 55°C
3
(32 ~ 131°F)
*
-15°C ~ 55°C (-59 ~ 131°F)
5% ~ 95% (non-condensing)
NOTE :
1. *1: The UPS needs to be de-rated to 70% of its capacity.
2
2. *
: The latter value of UPS’s depth is measured including its terminal
block.
3
3. *
: When the operating temperature is at 40 ~ 55°C (104 ~ 131°F), the
UPS will be de-rated to 75% of its capacity.
4. Please refer to the rating label for the safety rating.
5. All specications are subject to change without prior notice.
2
× 88.2 mm
*
15.2 kg
(33.51 lb)
Amplon RT Series
66
Page 71
Appendix 2 Warranty
Appendix 2 : Warranty
Seller warrants this product, if used in accordance with all applicable instructions,
to be free from original defects in material and workmanship within the warranty
period. If the product has any failure problem within the warranty period, Seller will
repair or replace the product at its sole discretion according to the failure situation.
This warranty does not apply to normal wear or to damage resulting from improper
installation, operation, usage, maintenance or irresistible force (i.e. war, fire,
natural disaster, etc.), and this warranty also expressly excludes all incidental and
consequential damages.
Maintenance service for a fee is provided for any damage out of the warranty
period. If any maintenance is required, please directly contact the supplier or Seller.
WARNING:
The individual user should take care to determine prior to use whether the
environment and the load characteristic are suitable, adequate or safe for
the installation and the usage of this product. The User Manual must be
carefully followed. Seller makes no representation or warranty as to the
suitability or tness of this product for any specic application.
No. 501327240102
Version : V 1.2
Release Date :2019_07_02
67
Page 72
5013272401
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.