Delta Amplon MX Series, Amplon UPA202M2MX0B035, Amplon UPA112M2MX0B035, Amplon UPA302M2MX0B035 User Manual

The power behind competitiveness
Delta UPS - Amplon Family
MX Series, Single Phase
1.1/ 2/ 3 kVA
User Manual
www.deltapowersolutions.com
This manual contains important instructions and warnings that you should follow during the installation, operation, storage and maintenance of this product. Failure to heed these instructions and warnings will void the warranty.
Copyright © 2019 by Delta Electronics Inc. All Rights Reserved. All rights of this User Manual (“Manual”), including but not limited to the contents, information, and figures are solely owned and reserved by Delta Electronics Inc. (“Delta”). The Manual can only be applied to the operation or the use of this product. Any disposition, duplication, dissemination, reproduction, modification, translation, extraction, or usage of this Manual in whole or in part is prohibited without the prior written permission of Delta. Given that Delta will continuously improve and develop the product, changes may be made to the information in this Manual at any time without obligation to notify any person of such revision or changes. Delta will make all possible efforts to secure the accuracy and the integrity of this Manual. Delta disclaims any kinds or forms of warranty, guarantee, or undertaking, either expressly or implicitly, including but not limited to the completeness, faultlessness, accuracy,
non-infringement, merchantability or tness for a particular purpose of the Manual.
Amplon MX Series
II
Table of Contents
Table of Contents
Chapter 1 : Important Safety Warnings ------------------------------- 1
1.1 Transportation ---------------------------------------------------- 1
1.2 Preparation -------------------------------------------------------- 1
1.3 Installation --------------------------------------------------------- 1
1.4 Operation ---------------------------------------------------------- 2
1.5 Maintenance, Service and Faults --------------------------- 2
1.6 Packing List ------------------------------------------------------- 4
Chapter 2 : Installation and Setup ------------------------------------- 6
2.1 Rear Panel View ------------------------------------------------- 6
2.2 Operating principle ---------------------------------------------- 8
2.3 Install The UPS -------------------------------------------------- 8
2.4 Setup the UPS --------------------------------------------------10
2.5 Battery Replacement ------------------------------------------13
2.6 Battery Kit Assembly (option) --------------------------------15
Chapter 3 : Operation -----------------------------------------------------17
3.1 Button Operation -----------------------------------------------17
3.2 LCD Panel --------------------------------------------------------18
3.3 Audible Alarm ---------------------------------------------------- 20
3.4 LCD Display Wordings Index --------------------------------20
3.5 UPS Setting ------------------------------------------------------22
3.6 Operating Mode Description ---------------------------------27
3.7 Faults Reference Code ---------------------------------------29
3.8 Warning Indicator -----------------------------------------------29
Chapter 4 : Troubleshooting --------------------------------------------31
Chapter 5 : Storage and Maintenance -------------------------------33
Chapter 6 : Technical Specications ---------------------------------34
Chapter 7 : Warranty -------------------------------------------------------36
III
Chapter 1 : Important Safety Warnings
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully
1.1 Transportation
z
z
Please transport the UPS system only in the original package to protect against shock and impact.
1.2 Preparation
z
z
Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environ­ment.
z
z
Do not install the UPS system near water or in moist environments.
z
z
Do not install the UPS system where it would be exposed to direct sunlight or near heater.
z
z
Do not block ventilation holes in the UPS housing.
1.3 Installation
z
z
Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS output sockets.
z
z
Place cables in such a way that no one can step on or trip over them.
z
z
Do not connect domestic appliances such as hair dryers to the UPS output sockets.
z
z
The UPS can be operated by any individuals with no previous experience.
z
z
Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system.
z
z
Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your computer) to connect the UPS system to the building wiring outlet (shock­proof outlet).
Amplon MX Series
1
Chapter 1 Important Safety Warnings
z
z
Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS system.
z
z
When installing the equipment, it should ensure that the sum of the leakage cur­rent of the UPS and the connected devices does not exceed 3.5mA.
z
z
Temperature Rating - Units are considered acceptable for use in a maximum ambient of 40°C (104°F).
z
z
For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and shall be easily accessible.
z
z
Caution:The unit is heavy. Lifting the unit requires a minimum of two people.
1.4 Operation
z
z
Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.
z
z
The UPS system features its own, internal current source (batteries). The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet.
z
z
In order to fully disconnect the UPS system, rst press the OFF/ ENTER button
to disconnect the mains.
z
z
Prevent no uids or other foreign objects from inside of the UPS system.
z
z
The REPO and USB circuits are an IEC 60950-1 safety extra low voltage (SELV) circuit. This circuit must be separated from any hazardous voltage circuits by re­inforced insulation.
1.5 Maintenance, Service and Faults
z
z
The UPS system operates with hazardous voltages. Repairs may be carried out
only by qualied maintenance personnel.
z
z
Caution - risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still con­nected to the battery and electrically live and dangerous. Before carrying out
any kind of service and/ or maintenance, disconnect the batteries and verify that
no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
2
z
z
To avoid electrical shock, turn off the unit and unplug it form the AC power source before servicing the battery
z
z
Only persons are adequately familiar with batteries and with the required pre­cautionary measures may replace batteries and supervise operations. Unauthor­ized persons must be kept well away from the batteries.
z
z
Caution - risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present!
z
z
Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary measures specied below and any other measures nec­essary when working with batteries:
- remove wristwatches, rings and other metal objects
- use only tools with insulated grips and handles.
z
z
When changing batteries, install the same number and same type of batteries.
z
z
Do not attempt to dispose of batteries by burning them. This could cause battery explosion.
z
z
Do not open or destroy batteries. Escaping electrolyte can cause injury to the
skin and eyes. It may be toxic.
z
z
A battery can may cause a risk of electrical shock and high short-circuit current. The following precautions should be observed when working on batteries:
a)Remove watches, rings, or other metal objects. b)Use tools with insulated
handles.c)Wear rubber gloves and boots. d)Do not lay tools or metal parts on top of batteries. e)Disconnect charging source prior to connecting or disconnecting battery
terminals. f)Determine if battery is inadvertently grounded. If inadvertently grounded,
remove source from ground. Contact with any part of a grounded battery can
result in electrical shock. The likelihood of such shock can be reduced if such
grounds are removed during installation and maintenance.
z
z
When replacing batteries, use the same type and number of batteries or battery packs.
z
z
Do not dismantle the UPS system.
z
z
This is a category C1 UPS product.
Amplon MX Series
3
Chapter 1 Important Safety Warnings
1.6 Packing List
For models UPA112M2MX0B035(1.1 kVA), UPA202M2MX0B035(2kVA),
UPA302M2MX0B035(3kVA)
1
2
4
3
5
7
Test report
6
No. Item Q’ty
1
2
UPS 1 PC
Input cable (Schuko) 1 PC
3
4
5
6
7
USB cable 1 PC
User manual 1 PC
Tower stand with screws 4 PCS
Ear kit with screws 2 PCS
Test report 1 PC
4
For models UPA112M2MX0B0BB(1.1 kVA), UPA202M2MX0B0BB(2kVA) ,
UPA302M2MX0B0BB(3kVA)
1
2
4
3
5
7
Test report
6
No. Item Q’ty
1
2
3
4
5
6
7
Amplon MX Series
UPS 1 PC
Input cable (AU) 1 PC
USB cable 1 PC
User manual 1 PC
Tower stand with screws 4 PCS
Ear kit with screws 2 PCS
Test report 1 PC
5
MX-1.1K
MX-2K
MX-3K
65
65
65
8
7
4
311 10
8
7
4
3
1
2
1
2
11
9
9
8
7
4
3
1
11
2
Chapter 2 : Installation and Setup
2.1 Rear Panel View
z
z
Standard Runtime Model
Chapter 2 Installation and Setup
6
No. Item
10
11
1
2
3
4
5
6
7
8
9
Programmable outlets: connect to non-critical loads.
Output receptacles: connect to mission-critical loads.
AC input
Network/Fax/Modem surge protection
Emergency power off function connector (REPO)
USB communication port
RS-232 communication port
Mini Slot
Input circuit breaker
Fuse
Ground screw
Amplon MX Series
7
Chapter 2 Installation and Setup
EMI/ RFI
Filters
Battery
Charger
Battery
DC- to- DC
Converter
Inverter
AVR
TX
Output
2.2 Operating principle
The operating principle of the UPS is shown as below
The UPS is composed of
mains input, EMI/RFI Filters,
Inverter, Battery charger, DC-to-DC converter, battery, AVR TX and UPS output
2.3 Install The UPS
For safety consideration, the UPS is shipped out from factory without connecting battery wires. Before install the UPS, please follow below steps to re-connect bat-
tery wires rst.
Step 1 Step 2 Step 3
Remove front panel. Disconnect battery wires. Pull out the battery box
by removing two screws
8
on the front panel.
Rack-mount Installation
CAUTION :
Do NOT use the mounting brackets to lift the unit. The mounting brackets
are only for securing the unit to the rack.
Tower Installation
Step 1
Step 2 Step 3
Amplon MX Series
9
Loading...