Delfield KH, KH-NU, KCSC, KCSC-EF, KHCR-B Service Manual

...
Shelleyglas®/Shelleysteel™
CAUTION
Service฀and฀Installation฀Manual
Please฀read฀this฀manual฀completely฀before฀attempting฀to฀install฀or฀operate฀this฀equipment!฀฀
Notify฀carrier฀of฀damage!฀฀Inspect฀all฀components฀immediately.฀฀See฀page฀2.
Refrigerated,฀Heated฀and฀Non-Electrical฀Units
READ฀BEFORE฀USE
PLEASE฀SAVE฀THESE฀INSTRUCTIONS!
Effective฀March฀2003
Shelleyglas®/Shelleysteel™฀Service฀and฀Installation฀Manual
CONTENTS
RECEIVING฀&฀INSPECTING฀EQUIPMENT.................................2
SPECIFICATIONS........................................................................3
INSTALLATION฀..........................................................................4
OPERATION.............................................................................4-5
MAINTENANCE..........................................................................6
CLEANING฀LIQUITEC.................................................................7
FOOD฀WELL฀ASSEMBLY............................................................7
WIRING฀DIAGRAM.................................................................8-9
STANDARD฀LABOR฀GUIDELINES............................................10
REPLACEMENT฀PARTS฀LIST...................................................11
STANDARD฀WARRANTY..........................................................11
PARTS฀DEPOTS........................................................BACK฀PAGE
©2003฀The฀Delfield฀Company.฀All฀rights฀reserved.฀Reproduction฀without฀
written฀permission฀is฀prohibited.
“Delfield”฀is฀a฀registered฀trademarks฀of฀The฀Delfield฀Company.
SERIAL฀NUMBER฀INFORMATION
If฀your฀unit฀is฀heated,฀the฀serial฀tag฀is฀located฀above฀the฀
louvered฀panel฀near฀the฀on/off฀switch.
Refrigerated฀units฀have฀the฀serial฀tag฀located฀in฀the฀
compressor฀area฀near฀the฀on/off฀switch.
Understorage฀units฀often฀have฀the฀serial฀tag฀located฀on฀the฀
left฀inside฀the฀storage฀area.
All฀purpose฀counters,฀utility฀equipment฀or฀delivery฀carts฀do฀
not฀require฀serial฀numbers฀but฀a฀model฀tag฀is฀placed฀at฀the฀
top฀of฀the฀pylon฀on฀the฀back฀of฀the฀unit.
Always฀have฀the฀serial฀number฀of฀your฀unit฀available฀when฀
calling฀for฀parts฀or฀service.฀
This฀manual฀covers฀standard฀units฀only.฀If฀you฀have฀a฀
custom฀unit,฀consult฀the฀customer฀service฀department฀at฀the฀
number฀listed฀below.
RECEIVING฀AND฀INSPECTING฀THE฀EQUIPMENT
Even฀though฀most฀equipment฀is฀shipped฀crated,฀care฀should฀
be฀taken฀during฀unloading฀so฀the฀equipment฀is฀not฀damaged฀
while฀being฀moved฀into฀the฀building.
1.฀Visually฀inspect฀the฀exterior฀of฀the฀package฀and฀skid฀or฀฀
container.฀฀Any฀damage฀should฀be฀noted฀and฀reported฀
to฀the฀delivering฀carrier฀immediately.
2.฀If฀damaged,฀open฀and฀inspect฀the฀contents฀with฀the฀
carrier.
3.฀In฀the฀event฀that฀the฀exterior฀is฀not฀damaged,฀yet฀upon฀
opening,฀there฀is฀concealed฀damage฀to฀the฀equipment฀
notify฀the฀carrier.฀฀Notification฀should฀be฀made฀verbally฀
as฀well฀as฀in฀written฀form.
4.฀Request฀an฀inspection฀by฀the฀shipping฀company฀of฀the฀
damaged฀equipment.฀฀This฀should฀be฀done฀within฀10฀
days฀from฀receipt฀of฀the฀equipment.
5.฀Check฀the฀lower฀portion฀of฀the฀unit฀to฀be฀sure฀legs฀or฀
casters฀are฀not฀bent.
6.฀Also฀open฀the฀compressor฀compartment฀housing฀and฀
visually฀inspect฀the฀refrigeration฀package.฀฀Be฀sure฀lines฀
are฀secure฀and฀base฀is฀still฀intact.
7.฀Freight฀carriers฀can฀supply฀the฀necessary฀damage฀forms฀
upon฀request.
8.฀Retain฀all฀crating฀material฀until฀an฀inspection฀has฀been฀
made฀or฀waived.
Uncrating฀the฀Equipment
First฀cut฀and฀remove฀the฀banding฀from฀around฀the฀crate.฀฀
Remove฀the฀front฀of฀the฀crate฀material,฀use฀of฀some฀tools฀will฀
be฀required.฀฀If฀the฀unit฀is฀on฀legs฀remove฀the฀top฀of฀the฀crate฀
as฀well฀and฀lift฀the฀unit฀off฀the฀skid.฀฀If฀the฀unit฀is฀on฀casters฀
it฀can฀be฀"rolled"฀off฀the฀skid.
The฀units฀with฀LiquiTec฀technology฀cold฀pans฀con-
tain฀a฀non-toxic฀eutectic฀fluid฀within฀a฀sealed฀inner฀
liner.฀฀This฀fluid฀may฀leak฀if฀the฀tank฀is฀punctured฀
so฀care฀must฀be฀taken฀when฀uncrating฀and฀setting฀
in฀place.฀฀The฀eutectic฀fluid฀is฀non-toxic฀and฀may฀be฀
flushed฀down฀a฀disposal฀drain.฀฀If฀the฀LiquiTec฀unit฀
cold฀pans฀leak,฀immediately฀call฀the฀Delfield฀service฀
department฀directly฀at฀1-800-733-8821฀not฀your฀
local฀service฀agent.
2
For฀customer฀service,฀call฀(800)฀733-8829,฀(800)฀773-8821,฀Fax฀(989)฀773-3210,฀www.deleld.com
Shelleyglas®/Shelleysteel™฀Service฀and฀Installation฀Manual
SPECIFICATIONS฀
This฀manual฀covers฀standard฀units฀only.฀If฀you฀have฀a฀custom฀unit,฀consult฀the฀customer฀service฀department฀at฀the฀number฀listed฀below.
Shelleyglas
MODEL฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀VOLTAGE/฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀NEMA฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
NUMBER฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀HERTZ/PHASE฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀PLUG฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀AMP
Heated฀Serving฀Counters
KH-2฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀14-20P฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀15.0
KH-3฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀14-30P฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀20.0
KH-4฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀14-50P฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀26.0
KH-5฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀14-50P฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀31.0
KH-6฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀14-50P฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀37.0
KH-2-NU฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀14-20P฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀11.0
KH-3-NU฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀14-20P฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀16.0
KH-4-NU฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀14-30P฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀22.0
KH-5-NU฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀14-50P฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀28.0
KH-6-NU฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀14-50P฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀33.0
MODEL฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀VOLTAGE/฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀NEMA฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
NUMBER฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀HERTZ/PHASE฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀PLUG฀฀฀฀฀฀฀฀฀AMP฀฀฀฀฀฀฀฀฀฀H.P.฀฀฀฀REFRIGERANT฀BTU
Refrigerated฀Cold฀Pan฀Serving฀Counters
KCSC-36B฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀7.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀1102
KCSC-50B฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀7.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀1240
KCSC-60B฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀7.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀1343
KCSC-74B฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀7.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀1423
KCSC-96B฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀7.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀1487
Shelleyglas฀with฀LiquiTec
KCSC-36-EF฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀7.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀1102
KCSC-50-EF฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀7.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀1240
KCSC-60-EF฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀7.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀1343
KCSC-74-EF฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀7.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀1423
KCSC-96-EF฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀7.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀1487
Heated฀and฀Refrigerated฀Combo฀Counters
KHCR-50-B฀฀฀฀฀฀฀฀฀฀฀฀120/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀5-20P฀฀฀฀฀16.0฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀1102
KHCR-60-B฀฀฀฀฀฀฀฀฀฀฀฀120/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀5-20P฀฀฀฀฀16.0฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀1102
KHCR-74-B฀฀฀฀฀฀฀฀฀฀฀฀120/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀5-20P฀฀฀฀฀16.0฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀1102
KHCR-96-B฀฀฀฀฀฀฀฀฀฀฀฀120/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀5-20P฀฀฀฀฀16.0฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀1240
KH2CR-72-B฀฀120/208-230/60/1฀฀฀฀฀14-30P฀฀฀฀18.0฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀1102
KH2CR-96-B฀฀120/208-230/60/1฀฀฀฀฀14-30P฀฀฀฀18.0฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀1343
KH3CR-96-B฀฀120/208-230/60/1฀฀฀฀฀14-30P฀฀฀฀23.0฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀1240
KH4CR-96-B฀฀120/208-230/60/1฀฀฀฀฀14-50P฀฀฀฀29.0฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀1102
Heated฀and฀Ice฀Cooled฀Combo฀Counters
KHC-50-NU฀฀฀฀฀฀฀฀฀฀฀฀120/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀9.0฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
KHC-60-NU฀฀฀฀฀฀฀฀฀฀฀฀120/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀9.0฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
KHC-74-NU฀฀฀฀฀฀฀฀฀฀฀฀120/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀9.0฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
KHC-96-NU฀฀฀฀฀฀฀฀฀฀฀฀120/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀9.0฀฀฀฀฀฀฀฀฀฀฀฀
KH2C-74-NU฀฀120/208-230/60/1฀฀฀฀฀14-20P฀฀฀฀11.0฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
KH2C-96-NU฀฀120/208-230/60/1฀฀฀฀฀14-20P฀฀฀฀11.0฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
KH3C-74-NU฀฀120/208-230/60/1฀฀฀฀฀14-20P฀฀฀฀16.0฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
KH3C-96-NU฀฀120/208-230/60/1฀฀฀฀฀14-20P฀฀฀฀16.0฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
KH4C-96-NU฀฀120/208-230/60/1฀฀฀฀฀14-30P฀฀฀฀22.0฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
Frost฀Top฀Serving฀Counters
KCFT-36-NU฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀7.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀435
KCFT-50-NU฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀7.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀595
KCFT-60-NU฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀7.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀717
KCFT-74-NU฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀7.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀827
KCFT-96-NU฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀7.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404a฀921
Milk฀Counters
KCM-36฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀5.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀134a฀1114
KCM-50฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀5.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀134a฀1190
KCM-60฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀5.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀134a฀1329
KCM-74฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀5.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀134a฀1535
Ice฀Cream฀Counters
KCF-36฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀7.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404A฀915
KCF-50฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀7.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404A฀1350
KCF-60฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀8.0฀฀฀฀฀฀฀฀฀1/3฀฀฀฀฀฀฀฀฀404A฀1456
KCF-74฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀8.0฀฀฀฀฀฀฀฀฀1/3฀฀฀฀฀฀฀฀฀404A฀1609
Milk฀and฀Ice฀Cream฀Counters฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀REF/FRZ
KCFM-50฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀4.0฀฀฀฀฀฀฀฀฀1/4฀฀฀฀฀฀฀฀฀404A฀789/1580
KCFM-74฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀8.0฀฀฀฀฀฀฀฀฀1/3฀฀฀฀฀฀฀฀฀404A฀1199/2040
Carving฀Counter
KRB฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀5.0฀฀฀฀฀฀฀฀฀฀฀฀
®
For฀customer฀service,฀call฀(800)฀733-8829,฀(800)฀773-8821,฀Fax฀(989)฀773-3210,฀www.deleld.com
Shelleysteel™
MODEL฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀VOLTAGE/฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀NEMA฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
NUMBER฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀HERTZ/PHASE฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀PLUG฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀AMP
Heated฀Serving฀Counters
SH-2฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀14-20P฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀15.0
SH-3฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀14-30P฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀20.0
SH-4฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀14-50P฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀26.0
SH-5฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀14-50P฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀31.0
SH-6฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀14-50P฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀37.0
SH-2-NU฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀14-20P฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀11.0
SH-3-NU฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀14-20P฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀16.0
SH-4-NU฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀14-30P฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀22.0
SH-5-NU฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀14-50P฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀28.0
SH-6-NU฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀14-50P฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀33.0
MODEL฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀VOLTAGE/฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀NEMA฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
NUMBER฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀HERTZ/PHASE฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀PLUG฀฀฀฀฀฀฀฀฀฀AMP฀฀฀฀H.P.฀฀฀฀฀฀REFRIGERANT฀BTU
Refrigerated฀Cold฀Pan฀Serving฀Counters
SCSC-36B฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀7.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀1102
SCSC-50B฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀7.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀1240
SCSC-60B฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀7.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀1343
SCSC-74B฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀7.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀1423
SCSC-96B฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀7.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀1487
Shelleysteel฀with฀LiquiTec
SCSC-36-EF฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀7.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀1102
SCSC-50-EF฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀7.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀1240
SCSC-60-EF฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀7.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀1343
SCSC-74-EF฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀7.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀1423
SCSC-96-EF฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀7.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀1487
Heated฀and฀Refrigerated฀Combo฀Counters
SHCR-50-B฀฀฀฀฀฀฀฀฀฀฀฀฀120/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-20P฀฀฀฀฀฀16.0฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀1102
SHCR-60-B฀฀฀฀฀฀฀฀฀฀฀฀฀120/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-20P฀฀฀฀฀฀16.0฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀1102
SHCR-74-B฀฀฀฀฀฀฀฀฀฀฀฀฀120/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-20P฀฀฀฀฀฀16.0฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀1102
SHCR-96-B฀฀฀฀฀฀฀฀฀฀฀฀฀120/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-20P฀฀฀฀฀฀16.0฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀1240
SH2CR-62-B฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀14-20P฀฀฀฀฀16.0฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀1423
SH2CR-72-B฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀14-30P฀฀฀฀฀18.0฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀1102
SH2CR-96-B฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀14-30P฀฀฀฀฀18.0฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀1343
SH3CR-96-B฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀14-30P฀฀฀฀฀23.0฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀1240
SH4CR-96-B฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀14-50P฀฀฀฀฀29.0฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀1102
Heated฀and฀Ice฀Cooled฀Combo฀Counters
SHC-50-NU฀฀฀฀฀฀฀฀฀฀฀฀฀120/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀9.0฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
SHC-60-NU฀฀฀฀฀฀฀฀฀฀฀฀฀120/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀9.0฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
SHC-74-NU฀฀฀฀฀฀฀฀฀฀฀฀฀120/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀9.0฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
SHC-96-NU฀฀฀฀฀฀฀฀฀฀฀฀฀120/60/1฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀9.0
SHC2-62-NU฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀14-20P฀฀฀฀฀11.0฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
SH2C-74-NU฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀14-20P฀฀฀฀฀11.0฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
SH2C-96-NU฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀14-20P฀฀฀฀฀11.0฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
SH3C-74-NU฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀14-20P฀฀฀฀฀16.0฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
SH3C-96-NU฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀14-20P฀฀฀฀฀16.0฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
SH4C-96-NU฀฀฀฀120/208-230/60/1฀฀฀฀฀฀฀14-30P฀฀฀฀฀22.0฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
Frost฀Top฀Serving฀Counters
SCFT-36-NU฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀7.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀435
SCFT-50-NU฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀7.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀595
SCFT-60-NU฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀7.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀717
SCFT-74-NU฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀7.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀827
SCFT-96-NU฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀7.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404a฀921
Milk฀Counters
SCM-36฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀5.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀134a฀1114
SCM-50฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀5.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀134a฀1190
SCM-60฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀5.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀134a฀1328
SCM-74฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀5.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀134a฀1535
Ice฀Cream฀Counters
SCF-36฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀7.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404A฀915
SCF-50฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀7.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404A฀1350
SCF-60฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀8.0฀฀฀฀1/3฀฀฀฀฀฀฀฀฀฀404A฀1456
SCF-74฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀8.0฀฀฀฀1/3฀฀฀฀฀฀฀฀฀฀404A฀1609
Milk฀and฀Ice฀Cream฀Counters฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀REF/FRZ
SCFM-50฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀7.0฀฀฀฀1/4฀฀฀฀฀฀฀฀฀฀404A฀789/1580
SCFM-74฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀8.0฀฀฀฀1/3฀฀฀฀฀฀฀฀฀฀404A฀1199/2040
Carving฀Counter
SRB฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀115฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀5-15P฀฀฀฀฀฀฀5.0฀฀฀฀฀฀฀
Trimline฀L-shaped฀Heated฀Serving฀Counter
SLT4฀(-L฀OR฀-R)฀฀208-230/60/1฀฀฀฀฀฀฀฀฀฀14-30P฀฀฀฀฀20.0฀฀฀฀฀฀
3
Shelleyglas®/Shelleysteel™฀Service฀and฀Installation฀Manual
INSTALLATION:฀HEATED฀UNITS
Location
Do฀not฀install฀the฀unit฀near฀combustible฀objects฀or฀surfaces฀
affected฀by฀heat฀or฀moisture.
Leveling
The฀unit฀must฀be฀level,฀both฀front฀and฀back฀and฀left฀to฀
right,฀in฀order฀to฀maintain฀an฀equal฀water฀depth฀through-
out฀the฀wells.
OPERATION:฀HEATED฀UNITS
After฀plugging฀in฀the฀power฀supply฀cord,฀select฀desired฀
temperature฀by฀rotating฀the฀knob฀on฀the฀temperature฀control฀
panel.฀Indicator฀light฀will฀come฀on฀when฀the฀switch฀is฀
activated.฀Individual฀temperature฀control฀knobs฀and฀indicator฀
lights฀are฀provided฀for฀each฀heated฀food฀well.
If฀the฀same฀temperature฀settings฀for฀each฀well฀are฀used฀
every฀day,฀the฀temperature฀knobs฀can฀be฀left฀in฀their฀set฀
position฀and฀the฀wells฀can฀be฀turned฀off฀using฀the฀ON/OFF฀
switch฀at฀the฀end฀of฀the฀control฀panel.
Before฀the฀unit฀is฀used฀the฀first฀time฀for฀serving,฀turn฀the฀
temperature฀knob฀to฀“10”฀and฀heat฀the฀well฀for฀15฀minutes.฀
Do฀not฀be฀alarmed฀if฀smoke฀appears;฀this฀preheat฀should฀
burn฀off฀any฀residue฀or฀dust฀that฀has฀adhered฀to฀the฀food฀well฀
element.
When฀serving฀thick฀sauces฀always฀use฀the฀hot฀food฀well฀in฀
“wet”฀operation.฀This฀provides฀more฀uniform฀temperature฀for฀
the฀sauce.฀฀Product฀temperature฀should฀range฀from฀140˚F฀to฀
160˚F
฀Never฀place฀food฀directly฀in฀well.฀฀Always฀use฀
pans.
For฀most฀efficient฀operation,฀keep฀covered฀insets฀
empty฀in฀each฀well฀during฀preheating฀and฀when฀the฀well฀is฀not฀
in฀use.
Always฀place฀covers฀on฀pans฀when฀not฀serving฀to฀prevent฀
food฀from฀drying฀out฀and฀to฀reduce฀your฀operating฀costs.
Wet฀operation
Fill฀the฀food฀well฀with฀about฀two฀inches฀of฀water฀and฀cover฀
with฀lid฀or฀empty฀pan.฀To฀preheat฀water,฀set฀temperature฀
Electrical฀Connections
฀Connections฀must฀be฀made฀in฀accordance฀with฀
all฀applicable฀local฀codes฀and/or฀the฀National฀
Electrical฀Code.฀Refer฀to฀the฀amperage฀data฀on฀
page฀3฀and฀the฀wiring฀diagrams฀on฀pages฀8฀and฀9.฀
A฀standard฀unit฀is฀provided฀with฀a฀power฀cord฀and฀
3-prong฀grounded฀plug.฀All฀units฀should฀be฀plugged฀
into฀a฀grounded฀receptacle฀with฀its฀own฀circuit฀pro-
tection฀that฀matches฀the฀amperage฀of฀the฀plug.
control฀at฀“High”.฀With฀pans฀in฀place,฀wells฀will฀boil฀water.฀
Food฀temperature฀will฀vary฀depending฀on฀type฀and฀amount฀of฀
product.฀To฀minimize฀steam฀and฀water฀usage,฀set฀control฀to฀
lowest฀setting฀that฀will฀maintain฀proper฀food฀temperature.
To฀reduce฀preheating฀time,฀use฀hot฀water฀to฀fill฀the฀well.
฀Steam฀can฀cause฀serious฀burns.฀Always฀wear฀
some฀type฀of฀protective฀covering฀on฀your฀hands฀
and฀arms฀when฀removing฀lids฀from฀the฀unit.฀
Lift฀the฀lid฀in฀a฀way฀that฀will฀direct฀escaping฀
steam฀away฀from฀your฀face฀and฀body.฀฀Water฀
temperature฀will฀average฀180˚F.
Dry฀operation
Wet฀operation฀is฀usually฀much฀more฀efficient฀and฀is฀usually฀
preferred.฀However,฀these฀units฀may฀be฀operated฀without฀
water฀with฀no฀damage฀to฀the฀unit.
The฀dry฀well฀should฀never฀be฀preheated฀longer฀
than฀15฀minutes.฀Only฀6”฀deep฀pans฀should฀be฀
used฀with฀dry฀food฀wells.
฀When฀operated฀dry,฀the฀well฀bottoms฀become฀very฀
hot.฀Do฀not฀allow฀unprotected฀skin฀to฀contact฀any฀
well฀surface.
When฀operated฀dry,฀the฀bottom฀of฀the฀well฀will฀
discolor.฀To฀clean,฀use฀a฀stainless฀steel฀cleaner฀or฀mild฀
abrasive.
Operation฀of฀optional฀heated฀understorage
If฀necessary,฀preheat฀the฀heated฀understorage฀to฀desired฀
temperature.฀Temperature฀range฀of฀understorage฀is฀100°F฀
to฀300°F.฀The฀temperature฀control฀knob฀is฀always฀the฀far฀left฀
knob฀on฀the฀panel.฀Indicator฀light฀is฀also฀at฀the฀far฀left.
4
For฀customer฀service,฀call฀(800)฀733-8829,฀(800)฀773-8821,฀Fax฀(989)฀773-3210,฀www.deleld.com
Shelleyglas®/Shelleysteel™฀Service฀and฀Installation฀Manual
CAUTION
INSTALLATION:฀REFRIGERATED฀UNITS
Location
Be฀sure฀the฀location฀chosen฀has฀a฀floor฀strong฀enough฀to฀
support฀the฀total฀weight฀of฀the฀cabinet฀and฀contents.฀Reinforce฀
the฀floor฀as฀necessary฀to฀provide฀for฀maximum฀loading.
For฀the฀most฀efficient฀refrigeration,฀be฀sure฀to฀provide฀good฀
air฀circulation฀inside฀and฀out.
Inside฀cabinet:฀Do฀not฀pack฀unit฀so฀full฀that฀air฀cannot฀
circulate.฀Take฀care฀not฀to฀block฀air฀flow฀to฀the฀fans฀and฀
allow฀space฀along฀the฀sides.
Outside฀cabinet:฀Be฀sure฀the฀unit฀has฀access฀to฀ample฀air;฀
avoid฀hot฀corners฀and฀locations฀near฀stoves฀and฀ovens.฀It฀
is฀suggested฀the฀rear฀of฀the฀unit฀be฀no฀less฀than฀two฀inches฀
from฀any฀wall,฀partition฀or฀any฀other฀object฀which฀will฀
restrict฀exhaust฀air฀flow.
Leveling
A฀level฀cabinet฀looks฀better฀and฀will฀perform฀better฀because฀
the฀doors฀will฀line฀up฀with฀the฀door฀frames฀properly,฀and฀the฀
cabinet฀will฀not฀be฀subject฀to฀unnecessary฀strain.
Stabilizing
Some฀models฀are฀supplied฀on฀casters฀for฀your฀convenience,฀
for฀ease฀of฀cleaning฀underneath฀and฀mobility.
The฀unit฀must฀be฀installed฀in฀a฀stable฀condition฀
with฀the฀front฀wheels฀locked,฀locking฀the฀front฀
casters฀after฀installation฀is฀the฀owner’s฀and฀
operator’s฀responsibility.
Plumbing
Refrigerated฀units฀have฀a฀drain฀that฀exits฀the฀unit฀on฀the฀
bottom,฀and฀is฀located฀on฀the฀operator’s฀left฀side.฀Standard฀
units฀on฀casters฀or฀legs฀will฀have฀a฀bronze฀faucet฀that฀fits฀a฀
standard฀garden฀hose.฀Units฀on฀legs฀with฀optional฀remote฀drain฀
valve฀handle฀will฀have฀1”฀threaded฀pipe฀extending฀from฀bottom฀
of฀unit.฀On฀standard฀units,฀a฀stainless฀steel฀access฀panel฀or฀
hinged฀louver฀will฀be฀provided฀for฀access฀to฀drain฀connections.
฀Moisture฀collecting฀from฀improper฀drainage฀
can฀create฀a฀slippery฀surface฀on฀the฀floor฀and฀
a฀hazard฀to฀employees.฀It฀is฀the฀owner’s฀and฀
operator’s฀responsibility฀to฀provide฀a฀container฀or฀
outlet฀for฀drainage.
Electrical฀connection
A฀standard฀refrigerated฀unit฀is฀provided฀with฀a฀power฀cord฀
and฀3-prong฀grounded฀plug.
The฀unit฀should฀be฀plugged฀into฀a฀receptacle฀with฀its฀own฀
circuit฀protection฀that฀matches฀the฀amperage฀of฀the฀plug.
฀Refer฀to฀the฀amperage฀data฀on฀page฀3฀or฀the฀
serial฀tag฀data฀and฀your฀local฀code฀or฀the฀National฀
Electrical฀Code฀to฀be฀sure฀the฀unit฀is฀connected฀
to฀the฀proper฀power฀source.฀A฀protected฀circuit฀
of฀the฀correct฀voltage฀and฀amperage฀must฀be฀run฀
for฀connection฀of฀the฀supply฀cord฀or฀permanent฀
connection฀to฀the฀unit.
฀On฀cord-connected฀units,฀an฀ON/OFF฀switch฀is฀
located฀directly฀on฀the฀face฀of฀the฀compressor฀
section.฀The฀switch฀must฀be฀turned฀to฀its฀OFF฀position฀and฀
power฀supply฀disconnected฀whenever฀doing฀the฀following:
฀฀฀1.฀Performing฀maintenance฀functions.
฀฀฀2.฀Cleaning฀the฀refrigerated฀cabinet฀area.
฀฀฀3.฀Performing฀service฀or฀repair฀functions.
฀Under฀no฀circumstances฀should฀the฀unit฀be฀operated฀
without฀the฀louvered฀panel฀in฀place.
OPERATION฀LIQUITEC฀UNITS
LiquiTec฀Series฀cold฀pans฀are฀adjusted฀at฀the฀factory฀to฀provide฀
satisfactory฀operation฀without฀any฀further฀adjustments.฀฀
However,฀if฀it฀is฀necessary฀to฀adjust฀the฀temperature,฀the฀
control฀is฀located฀in฀the฀machine฀compartment.฀฀Turn฀the฀knob฀
clockwise฀as฀indicated฀on฀the฀control.฀฀Settings฀are฀from฀1฀
through฀7;฀7฀being฀the฀coldest.฀฀Adjustments฀should฀be฀made฀
gradually.฀฀Several฀small฀adjustments฀will฀be฀more฀effective฀
than฀one฀large฀adjustment.฀฀It฀may฀take฀an฀hour฀or฀longer฀to฀
realize฀the฀temperature฀change฀depending฀on฀the฀application฀
and฀location฀of฀the฀unit.
These฀units฀are฀not฀designed฀to฀cool฀warm฀food฀products.฀฀
Items฀should฀be฀placed฀in฀the฀unit฀pre-cooled฀at฀least฀to฀the฀
desired฀holding฀temperature,฀if฀not฀slightly฀colder.฀฀In฀some฀
applications,฀a฀gradual฀warming฀of฀product฀may฀occur,฀particu-
For฀customer฀service,฀call฀(800)฀733-8829,฀(800)฀773-8821,฀Fax฀(989)฀773-3210,฀www.deleld.com
larly฀at฀the฀exposed฀top฀of฀the฀products.฀฀Stirring฀or฀rotation฀of฀
the฀product฀may฀be฀necessary฀to฀maintain฀overall฀temperature.฀฀
Warming฀of฀food฀product฀can฀occur฀very฀quickly฀outside฀of฀
the฀unit.฀฀When฀loading฀or฀rotating฀the฀product,฀avoid฀leaving฀
food฀items฀in฀a฀non-refrigerated฀location฀for฀any฀length฀of฀time฀
to฀prevent฀warming฀or฀spoilage.
The฀temperature฀control฀is฀used฀to฀turn฀the฀unit฀on฀and฀off฀as฀
well฀as฀control฀the฀temperature฀of฀the฀cold฀pan.฀฀The฀settings฀
range฀from฀1฀to฀7;฀7฀being฀the฀coldest.฀฀To฀turn฀the฀cold฀pan฀
off,฀turn฀the฀knob฀to฀the฀off฀position.฀฀
The฀cold฀pan฀is฀not฀intended฀to฀be฀used฀with฀ice.
5
Loading...
+ 11 hidden pages