Delfi DelfiScan M80 Programming Manual

Page 1
DelfiScan M80
Programming Manual
Page 2
Delfi Technologies A/S
Galoche Alle 1 DK-4600 Køge Denmark Telephone: + 45 70 222 555 Fax: + 45 70 222 666
An Unpublished Work - All rights reserved. No part of the contents of this documentation or the procedures described therein may be reproduced or transmitted in any form or by any means without prior written per-mission of Delfi Technologies A/S. Owners of Delfi products are hereby granted a non­exclusive, revocable license to reproduce and transmit this documentation for the purchaser's own internal business purposes. Purchaser shall not remove or alter any proprietary notices, including copyright notices, contained in this documentation and shall ensure that all notices appear on any reproductions of the documentation. Electronic versions may either be downloadable from the Delfi website (www.delfi.com) or provided on appropriate media.
Disclaimer
Delfi has taken reasonable measures to provide information in this manual that is complete and accurate. However, Delfi reserves the right to change any specification at any time without prior notice.
Page 3
Page 4
iii
CONTENTS
1 INTRODUCTION ........................................................................................ 1
2 INSTALLATION ......................................................................................... 3
3 CONFIGURATION ..................................................................................... 8
RS-232 PARAMETERS .............................................................................19
Baud Rate ....................................................................................................................... 20
Parity................................................................................................................................ 21
Data Bits ......................................................................................................................... 21
Stop Bits ......................................................................................................................... 21
Handshaking ................................................................................................................. 22
Ack/Nack Protocol ...................................................................................................... 22
Fifo ................................................................................................................................... 22
Inter-character Delay ................................................................................................. 23
Rx Timeout .................................................................................................................... 23
Serial Trigger Lock ...................................................................................................... 24
USB PARAMETERS ..................................................................................25
Handshaking ................................................................................................................. 26
Ack/Nack Protocol ...................................................................................................... 26
Fifo ................................................................................................................................... 26
Inter-character Delay ................................................................................................. 27
Rx Timeout .................................................................................................................... 28
Serial Trigger Lock ...................................................................................................... 28
Keyboard Nationality ................................................................................................. 29
Fifo ................................................................................................................................... 29
Inter-character Delay ................................................................................................. 30
Inter-code Delay .......................................................................................................... 31
Control Character Emulation .................................................................................. 31
USB Keyboard Speed ................................................................................................. 32
WEDGE PARAMETERS ............................................................................33
Keyboard Nationality ................................................................................................. 34
Caps Lock ....................................................................................................................... 35
Caps Lock Auto-Recognition (IBM AT compatible only) ................................. 35
Num Lock ....................................................................................................................... 36
Inter-character Delay ................................................................................................. 36
Inter-code Delay .......................................................................................................... 36
Keyboard Setting ........................................................................................................ 37
Control Character Emulation .................................................................................. 39
PEN EMULATION ....................................................................................40
Operating Mode .......................................................................................................... 41
Minimum Output Pulse ............................................................................................. 42
Conversion to Code 39 and Code 128 ................................................................. 43
Overflow ......................................................................................................................... 44
Output Level ................................................................................................................. 44
Idle Level ........................................................................................................................ 45
Inter-Block Delay ......................................................................................................... 45
Page 5
iv
DATA FORMAT .......................................................................................46
Code Identifier ............................................................................................................. 49
Custom Code Identifier ............................................................................................. 50
Header ............................................................................................................................ 51
Terminator ..................................................................................................................... 52
Special Keys ................................................................................................................... 53
Field Adjustment ......................................................................................................... 54
Field Adjustment Character..................................................................................... 55
Code Length Tx ............................................................................................................ 55
Character Replacement ............................................................................................ 56
Address Stamping....................................................................................................... 58
Address Delimiter ....................................................................................................... 58
READING PARAMETERS .........................................................................59
Hand-Held Operation ................................................................................................ 60
Stand Operation .......................................................................................................... 60
Hardware Trigger Mode ............................................................................................ 61
Trigger-off Timeout .................................................................................................... 61
Flash Mode .................................................................................................................... 62
Reads per Cycle ............................................................................................................ 62
Safety Time .................................................................................................................... 63
Beeper Intensity........................................................................................................... 63
Beeper Tone .................................................................................................................. 64
Beeper Type .................................................................................................................. 64
Beeper Length .............................................................................................................. 64
Stand Recognition Beep ........................................................................................... 65
DECODING PARAMETERS ......................................................................66
Ink Spread ...................................................................................................................... 67
Overflow Control ......................................................................................................... 67
Interdigit Control ........................................................................................................ 68
Decoding Safety .......................................................................................................... 68
Puzzle Solver™ .............................................................................................................. 69
CODE SELECTION ...................................................................................70
EAN/UPC Family .......................................................................................................... 72
2/5 Family ...................................................................................................................... 78
Code 39 Family ............................................................................................................ 79
Code 128 Family .......................................................................................................... 81
Code 93 .......................................................................................................................... 82
Codabar Family ............................................................................................................ 83
MSI .................................................................................................................................... 85
Plessey ............................................................................................................................ 85
Telepen ........................................................................................................................... 87
Delta IBM ........................................................................................................................ 88
Code 11 .......................................................................................................................... 89
Code 16K ........................................................................................................................ 90
Code 49 .......................................................................................................................... 90
GS1 DataBar™ ............................................................................................................... 91
ADVANCED FORMATTING .....................................................................92
Concatenation ............................................................................................................. 93
Advanced Formatting ............................................................................................... 96
Page 6
v
RADIO PARAMETERS .......................................................................... 109
Radio Protocol Timeout .......................................................................................... 110
Power-Off Timeout ................................................................................................... 110
Beeper Control for Radio Response .................................................................... 111
Single Store ................................................................................................................. 112
Batch Mode ................................................................................................................. 112
4 REFERENCES ........................................................................................ 114
5 TECHNICAL FEATURES ........................................................................ 136
A HOST CONFIGURATION STRINGS ...................................................... 141
B CODE IDENTIFIER TABLE .................................................................... 153
C HEX AND NUMERIC TABLE ................................................................. 156
Page 7
vi
GENERAL VIEW
DELFISCAN M80 READERS
Reading Window
Trigger
Cradle
Locking System Latch
Charge completed (yellow LED)
Charging (red LED)
Page 8
INTRODUCTION
1
1 INTRODUCTION
The DelfiScan family provides a valuable solution for users seeking an affordable handheld device without compromise in performance. The extensive range of models and options of this family can easily meet any specific challenges required by retail, and commercial data collections applications. The DelfiScan M80 is the ideal solution for retail and commercial environments where continuous and multi-tasking activities are keys to optimum productivity, lower cost of ownership and profitable business.
1.1 READING ANGLE
DelfiScan M80 readers automatically scan barcodes at a distance. Simply aim and pull the trigger. Code scanning is performed along the center of the light bar emitted from the reading window. This bar must cover the entire code.
Successful scanning is obtained by tilting the reader with respect to the barcode to avoid direct reflections, which could impair the reading performance. See the figures below.
Successful reading is obtained by an audible tone.
OK Not Advised
Good read LED
Page 9
DELFISCAN M80
2
1.2 HANDS-FREE USE
When using the DelfiScan M80 on the cradle, remember to lock the reader by pushing up the locking system as indicated in the following figure.
Page 10
INSTALLATION
3
2 INSTALLATION
2.1 USING YOUR DELFISCAN M80 READING SYSTEM
Follow the procedure below to start using your DelfiScan M80 reading system:
1. Connect a DelfiScan M80 cradle to the Host.
2. Insert the DelfiScan M80 reader into the cradle to start the battery charging. A full
charge of the Lithium battery takes 3.5 – 6 hours.
To achieve the best battery life, it is recommended to perform a full battery charge before using the reader in hand-held mode.
NOTE
In hands-free use, you can immediately start using the reader, since it is powered by the cradle.
3. Configure the DelfiScan M80 reader.
4. Configure the DelfiScan M80 cradle.
2.2 CHANGING THE BATTERIES
To change the battery of your reader, you must:
1. Unscrew the battery cover screw (Figure 1).
2. Unplug the white connector and remove the old battery (Figure 2).
3. Insert the new battery and plug in the white connector.
When inserting the new battery into the handle pay attention to position the battery and the connector just as shown in Figure 3.
NOTE
Figure 1 Figure 2 Figure 3
Page 11
DELFISCAN M80
4
4. Insert the cover in the handle and screw it back into place.
Figure 4
Do not incinerate, disassemble, short terminals or expose to high temperature. Risk of fire, explosion. Use specified charger only. Risk of explosion if the battery is replaced by an incorrect type. Dispose of the batteries as required by the relevant laws in force.
WARNING
Page 12
INSTALLATION
5
2.3 SYSTEM CONNECTIONS
Connections should always be made with power OFF!
CAUTION
You can connect the DelfiScan M80 cradle to the Host through the dedicated connector, using the cable corresponding to the desired interface type.
1. Connect the appropriate interface cable to the cradle by simply plugging it into the
Host connector on the base of the cradle.
DelfiScan M80 Cradle - Bottom View
To disconnect the cable, insert a paper clip or other similar object into the hole corresponding to the connector on the base of the cradle. Push down on the clip while unplugging the cable. Refer to the following figure:
Disconnecting the Cable
Interface Cable
Page 13
DELFISCAN M80
6
2.4 RS-232 CONNECTION
2.5 USB
2.6 IBM USB POS
2.7 WEDGE CONNECTION (only for DelfiScan M80 Type:130)
CAB-413
CAB-391 or CAB-321 + CAB-431
CAB-431
POWER SUPPLY ADAPTER
Page 14
INSTALLATION
7
2.8 PEN EMULATION CONNECTION
2.9 SINGLE READER LAYOUT
Page 15
DELFISCAN M80
8
3 CONFIGURATION
3.1 CONFIGURATION METHODS
3.1.1 Reading Configuration Barcodes
This manual can be used for complete setup and configuration of your reader by following the setup procedures in this chapter.
If you wish to change the default settings, this manual provides complete configuration of your reader in an easy way.
To configure your reader:
1. Open the folded page in Appendix C
with the hex-numeric table and keep it open
during the device configuration.
2. Read the Enter Configuration code ONCE
, available at the top of each page of
configuration.
3. Modify the desired parameters in one or more sections following the procedures
given for each group.
4. Read the Exit and Save Configuration code ONCE
, available at the top of each page
of configuration.
Reference notes describing the operation of the more complex parameters are given in chapter 4.
3.1.2 Aladdin™
Aladdin™ is a multi-platform utility program that allows device configuration using a PC. It provides RS-232 interface configuration as well as configuration barcode printing.
3.1.3 Copy Command
A previously configured device (Master), can be used to send its configuration directly to other devices of the same type (Slaves). The particular procedure for each device is given.
Page 16
CONFIGURATION
9
3.1.4 Sending Configuration Strings from Host
An alternative configuration method is provided in Appendix A using the RS-232 or USB­COM interface. This method is particularly useful when many devices need to be configured with the same settings. Batch files containing the desired parameter settings can be prepared to configure devices quickly and easily.
3.2 DELFISCAN M80 STAND ALONE SETUP
Read the restore default parameters code below.
1.
Restore DelfiScan M80 Default
Ì$+$*oÎ
2.
Read the codes below to set the radio address of the DelfiScan M80 reader.
Enter configuration
Ì$+;Î
3.
Set Radio Address
ÌRA0RFHÎ
+
four digits for the DelfiScan M80 Address (from 0000 to 1999).
All readers used in the same area must have different addresses.
4.
Exit and Save configuration
Ì$-?Î
5.
Read the Bind code to pair the DelfiScan M80 to the cradle. The reader is dedicated to the cradle. Any previously bound reader will be excluded.
Bind
Ì$+RN0$-IÎ
The yellow LED on the DelfiScan M80 will blink; the reader is ready to be positioned
onto the cradle.
6.
Firmly position the reader onto the cradle within 10 seconds, a beep will be emitted, signaling that the cradle has been paired to the DelfiScan M80, and the yellow LED on the reader will go off.
Page 17
DELFISCAN M80
10
7.
Read the cradle restore default code:
Restore cradle default
Ì$+RX0$-qÎ
Go to par. 3.3 Interface Selection.
Yellow LED
Page 18
CONFIGURATION
11
3.3 INTERFACE SELECTION
Read the interface selection code for your application.
RS-232
Standard
Ì$+CP0$-$Î
POS Terminals
Nixdorf Mode A
Ì$+CM2EC0$->Î
Fujitsu
Ì$+CM1$-ÈÎ
ICL Mode
Ì$+CM0$-ÃÎ
For POS terminal default settings refer to par. 4.7.
PEN
Ì$+CP6$-BÎ
Page 19
DELFISCAN M80
12
WEDGE (only for DelfiScan M80 Type:130)
IBM AT or PS/2 PCs
Ì$+CP500$-aÎ
IBM XT
Ì$+CP503$-vÎ
PC Notebook
Ì$+CP505$-ÈÎ
IBM SURE1
Ì$+CP506$-$Î
IBM Terminal 3153
Ì$+CP504$-}Î
Page 20
CONFIGURATION
13
WEDGE (CONTINUED)
IBM Terminals 31xx, 32xx, 34xx, 37xx:
To select the interface for these IBM Terminals, read the correct KEY TRANSMISSION
code. Select the KEYBOARD TYPE if necessary (default = advanced keyboard).
KEY TRANSMISSION MODE
make-only keyboard
Ì$+CP502$-oÎ
make-break keyboard
Ì$+CP501$-hÎ
KEYBOARD TYPE
advanced keyboard
Ì$+FK1$-ÉÎ
typewriter keyboard
Ì$+FK0$-ÄÎ
Page 21
DELFISCAN M80
14
WEDGE (CONTINUED)
ALT MODE
The ALT-mode selection allows barcodes sent to the PC to be interpreted correctly independently from the Keyboard Nationality used. You do not need to make a
Keyboard Nationality selection.
(default = Num Lock Unchanged). Make sure the Num Lock key on your keyboard is ON.
IBM AT - ALT mode
Ì$+CP507$-+Î
PC Notebook - ALT mode
Ì$+CP508$-2Î
WYSE TERMINALS
ANSI Keyboard
Ì$+CP509$-9Î
PC Keyboard
Ì$+CP510$-gÎ
ASCII Keyboard
Ì$+CP511$-nÎ
VT220 style Keyboard
Ì$+CP514$-ÇÎ
Page 22
CONFIGURATION
15
WEDGE (CONTINUED)
DIGITAL TERMINALS
VT2xx/VT3xx/VT4xx
Ì$+CP512$-uÎ
Page 23
DELFISCAN M80
16
3.4 USB READER CONFIGURATION
The USB interface is compatible with:
Windows 98 (and later) IBM POS for Windows Mac OS 8.0 (and later) 4690 Operating System
USB Start-up
As with all USB devices, upon connection, the Host performs several checks by communicating with the DelfiScan M80. During this phase the yellow LED on the DelfiScan M80 reader blinks and normal operations are suspended. Two basic conditions must be met before the DelfiScan M80 is ready to read codes, the correct USB driver must be loaded and sufficient power must be supplied to the reader.
For all systems, the correct USB driver for the default USB­KBD interface is included in the Host Operating System and will either be loaded automatically or will be suggested by the O.S. and should therefore be selected from the dialog box (the first time only).
Normally the Host supplies sufficient power to the reader, the start-up phase ends correctly, the yellow LED stops blinking.
In rare cases, if the Host does not supply sufficient power to the reader, a dialog box will appear on the Host and the reader will be blocked (yellow LED continues blinking). In this case, disconnect the USB device cable at the Host (yellow LED stops blinking); and then try a different USB port as indicated by the Operating System message. You can now read codes.
At this point you can read the USB interface configuration code according to your application. Load drivers from the O.S. (if requested). When configuring the USB-COM interface, the relevant files and drivers must be installed from the USB Device Installation software, which can be downloaded from the web page http://www.delfi.com.
The reader is ready to read barcodes. Successive start-ups will automatically recognize the previously loaded drivers.
Connect De lfiScan
M80 to Host
Select desired USB
int er fac e co de
(USB-KBD is default)
Read test c odes.
Reader is READY
Loa d dr iver s
(if requested)
Loa d dr iver s
(if re
q
uested)
Yellow LED blinks
Yellow L ED o ff –
BEEP OK
Firs t Sta r t-Up
Page 24
CONFIGURATION
17
USB
USB-KBD
Ì$+UA03$-:Î
USB-KBD-ALT-MODE
Ì$+UA04$-@Î
USB-KBD-APPLE
Ì$+UA05$-FÎ
USB-COM*
Ì$+UA02$-4Î
USB-IBM-Table Top
Ì$+UA00$-(Î
USB-IBM-Hand Held
Ì$+UA01$-.Î
* When configuring USB-COM, the relevant files and drivers must be installed from the
USB Device Installation software, which can be downloaded from the web site http://www.delfi.com.
Page 25
DELFISCAN M80
18
3.5 CHANGING DEFAULT SETTINGS
Once your reader is setup, you can change the default parameters to meet your application needs. Refer to the preceding paragraphs for initial configuration in order to set the default values and select the interface for your application.
In this manual, the configuration parameters are divided into logical groups making it easy to find the desired function based on its reference group.
The first five groups are for Standard/IBM Interface parameter configuration:
RS-232
USB
WEDGE (only for DelfiScan M80 type:130)
PEN EMULATION
The following parameter groups are common to all interface applications:
DATA FORMAT parameters regard the messages sent to the Host system for all interfaces except Pen Emulation.
READING PARAMETERS control various operating modes and indicator status functioning.
DECODING PARAMETERS maintain correct barcode decoding in certain special reading conditions.
CODE SELECTION parameters allow configuration of a personalized mix of codes, code families and their options.
ADVANCED FORMATTING PARAMETERS allow code concatenation and advanced formatting of messages towards the Host. It cannot be used with Pen Emulation connections.
RADIO PARAMETERS (Mobile series only) allow configuration of radio control parameters.
Page 26
19
RS-232 PARAMETERS
~
BAUD RATE
~
~
PARITY
~
~
DATA BITS
~
~
STOP BITS
~
~
HANDSHAKING
~
~
ACK/NACK PROTOCOL
~
~
FIFO
~
~
INTER-CHARACTER DELAY
~
~
RX TIMEOUT
~
~
SERIAL TRIGGER LOCK
~
1. Read the Enter Configuration code ONCE, available at the top of each page.
2. Read configuration codes from the desired groups.
= Read the code and follow the procedure given
= Default value
3. Read the Exit and Save Configuration code ONCE, available at the top of each
page.
Page 27
Enter Configuration Exit and Save Configuration
Ì$+;Î
RS-232
Ì$-?Î
20
BAUD RATE
300 baud
ÌCD1XÎ
600 baud
1200 baud
ÌCD2[Î
ÌCD3^Î
2400 baud
4800 baud
ÌCD4aÎ
ÌCD5dÎ
9600 baud
19200 baud
ÌCD6gÎ
ÌCD7jÎ
38400 baud
ÌCD8mÎ
Page 28
Enter Configuration
Exit and Save Configuration
Ì$+;Î
RS-232
Ì$-?Î
21
PARITY
none
ÌCC0SÎ
even parity
ÌCC1VÎ
odd parity
ÌCC2YÎ
DATA BITS
7 bits
ÌCA0OÎ
8 bits
ÌCA1RÎ
9 bits
ÌCA2UÎ
STOP BITS
1 stop bit
ÌCB0QÎ
2 stop bits
ÌCB1TÎ
Page 29
Enter Configuration Exit and Save Configuration
Ì$+;Î
RS-232
Ì$-?Î
22
HANDSHAKING
disable
ÌCE0WÎ
hardware (RTS/CTS)
ÌCE1ZÎ
software (XON/XOFF)
ÌCE2]Î
RTS always ON
ÌCE3`Î
See par. 4.1.1 for details.
ACK/NACK PROTOCOL
disable
ÌER0sÎ
enable
ÌER1vÎ
See par. 4.1.2 for details, particularly on implementing this parameter with DelfiScan M80.
FIFO
disable
ÌEC0UÎ
enable
ÌEC1XÎ
See par. 4.1.3 for details.
Page 30
Enter Configuration
Exit and Save Configuration
Ì$+;Î
RS-232
Ì$-?Î
23
INTER-CHARACTER DELAY
delay between characters transmitted to Host
ÌCK3Î
Read 2 numbers from the table where: 00 = DELAY disabled
01-99 = DELAY from 1 to 99 milliseconds
delay disabled
RX TIMEOUT
timeout control in reception from Host
ÌCL5Î
Read 2 numbers from the table where:
00 = TIMEOUT disabled 01-99 = TIMEOUT from .1 to 9.9 seconds
rx timeout 5 seconds
See par. 4.1.4 for details.
Page 31
Enter Configuration Exit and Save Configuration
Ì$+;Î
RS-232
Ì$-?Î
24
SERIAL TRIGGER LOCK
disabled
ÌCR0qÎ
enable and select characters
ÌCR1tÎ
Read 2 characters from the Hex/Numeric table in the range 00-FE where:
First Character enables device trigger
Second Character inhibits device trigger until the first character is received again.
Page 32
25
USB PARAMETERS
~
USB-COM
Handshaking, Ack/Nack protocol, FIFO, Inter-character delay, Rx
timeout, Serial trigger lock
~
~
USB-KBD
Keyboard nationality, FIFO, Inter-character delay, Inter-code delay,
Control character emulation, USB keyboard speed
~
~
USB-IBM
No parameter selection required.
~
1. Read the Enter Configuration code ONCE, available at the top of each page.
2. Read configuration codes from the desired groups.
= Read the code and follow the procedure given
= Default value
3. Read the Exit and Save Configuration code ONCE, available at the top of each
page.
Page 33
Enter Configuration Exit and Save Configuration
Ì$+;Î
USB-COM
Ì$-?Î
26
HANDSHAKING
disable
ÌCE0WÎ
hardware (RTS/CTS)
ÌCE1ZÎ
software (XON/XOFF)
ÌCE2]Î
RTS always ON
ÌCE3`Î
See par. 4.1.1 for details.
ACK/NACK PROTOCOL
disable
ÌER0sÎ
enable
ÌER1vÎ
See par. 4.1.2 for details.
FIFO
disable
ÌEC0UÎ
enable
ÌEC1XÎ
See par. 4.1.3 for details.
Page 34
Enter Configuration
Exit and Save Configuration
Ì$+;Î
USB-COM
Ì$-?Î
27
INTER-CHARACTER DELAY
delay between characters transmitted to Host
ÌCK3Î
Read 2 numbers from the table where: 00 = DELAY disabled
01-99 = DELAY from 1 to 99 milliseconds
delay disabled
Page 35
Enter Configuration Exit and Save Configuration
Ì$+;Î
USB-COM
Ì$-?Î
28
RX TIMEOUT
timeout control in reception from Host
ÌCL5Î
Read 2 numbers from the table where:
00 = TIMEOUT disabled 01-99 = TIMEOUT from .1 to 9.9 seconds
rx timeout 5 seconds
See par. 4.1.4 for details.
SERIAL TRIGGER LOCK
disabled
ÌCR0qÎ
enable and select characters
ÌCR1tÎ
Read 2 characters from the Hex/Numeric table in the range 00-FE where:
First Character enables device trigger
Second Character inhibits device trigger until the first character is received again.
Page 36
Enter Configuration
Exit and Save Configuration
Ì$+;Î
USB-KBD
Ì$-?Î
29
KEYBOARD NATIONALITY
Not Available for USB-KBD-ALT-MODE Interface
This parameter default value is restored through the Interface Selection code and not Restore Default.
Belgian
ÌFJ7yÎ
English
French
ÌFJ4pÎ
ÌFJ2jÎ
German
Italian
ÌFJ3mÎ
ÌFJ1gÎ
Japanese
Spanish
ÌFJ8|Î
ÌFJ6vÎ
Swedish
USA
ÌFJ5sÎ
ÌFJ0dÎ
FIFO
disable
ÌEC0UÎ
enable
ÌEC1XÎ
See par. 4.1.3 for details.
Page 37
Enter Configuration Exit and Save Configuration
Ì$+;Î
USB-KBD
Ì$-?Î
30
INTER-CHARACTER DELAY
delay between characters transmitted to Host
ÌCK3Î
Read 2 numbers from the table where: 00 = DELAY disabled
01-99 = DELAY from 1 to 99 milliseconds
delay disabled
Page 38
Enter Configuration
Exit and Save Configuration
Ì$+;Î
USB-KBD
Ì$-?Î
31
INTER-CODE DELAY
delay between codes transmitted to Host
ÌFG.Î
Read 2 numbers from the table where:
00 = DELAY disabled 01-99 = DELAY from 1 to 99 seconds
delay disabled
CONTROL CHARACTER EMULATION
CTRL + Shift + Key
ÌFO0nÎ
CTRL + Key
ÌFO1qÎ
Page 39
Enter Configuration Exit and Save Configuration
Ì$+;Î
USB-KBD
Ì$-?Î
32
USB KEYBOARD SPEED
Normal
ÌUT10cÎ
Fast
ÌUT01dÎ
Page 40
33
WEDGE PARAMETERS
~
KEYBOARD NATIONALITY
~
~
CAPS LOCK
~
~
CAPS LOCK
A
UTO-RECOGNITION
~
~
NUM LOCK
~
~
INTER-CHARACTER DELAY
~
~
INTER-CODE DELAY
~
~
KEYBOARD SETTING
~
~
CONTROL CHARACTER
EMULATION
~
1. Read the Enter Configuration code ONCE, available at the top of each page.
2. Read configuration codes from the desired groups.
= Read the code and follow the procedure given
= Default value
3. Read the Exit and Save Configuration code ONCE, available at the top of each
page.
.
Page 41
Enter Configuration Exit and Save Configuration
Ì$+;Î
WEDGE
Ì$-?Î
34
KEYBOARD NATIONALITY
Belgian
ÌFJ7yÎ
English
French
ÌFJ4pÎ
ÌFJ2jÎ
German
Italian
ÌFJ3mÎ
ÌFJ1gÎ
Spanish
Swedish
ÌFJ6vÎ
ÌFJ5sÎ
USA
ÌFJ0dÎ
The Japanese Keyboard Nationality selection is valid only for IBM AT compatible PCs.
Japanese
ÌFJ8|Î
Page 42
Enter Configuration Exit and Save Configuration
Ì$+;Î
WEDGE
Ì$-?Î
35
CAPS LOCK
caps lock OFF
ÌFE0ZÎ
caps lock ON
ÌFE1]Î
Select the appropriate code to match your keyboard caps lock status.
Note: Caps lock manual configuration is ignored when Caps Lock Auto-Recognition is enabled.
For PC Notebook interface selections, the caps lock status is automatically recognized; therefore this command is not necessary.
CAPS LOCK AUTO-RECOGNITION (IBM AT COMPATIBLE ONLY)
disable
ÌFP0pÎ
enable
ÌFP1sÎ
Page 43
Enter Configuration Exit and Save Configuration
Ì$+;Î
WEDGE
Ì$-?Î
36
NUM LOCK
toggle num lock
ÌFL1kÎ
num lock unchanged
ÌFL0hÎ
This selection is used together with the Alt Mode interface selection for AT or Notebook PCs.
It changes the way the Alt Mode procedure is executed; therefore it should be set as follows:
if your keyboard Num Lock is normally on
use num lock unchanged
if your keyboard Num Lock is normally off
use toggle num lock
In this way the device will execute the Alt Mode procedure correctly for your application.
INTER-CHARACTER DELAY
delay between characters transmitted to Host
ÌCK3Î
Read 2 numbers from the table where: 00 = DELAY disabled
01-99 = DELAY from 1 to 99 milliseconds
delay disabled
INTER-CODE DELAY
delay between codes transmitted to Host
ÌFG.Î
Read 2 numbers from the table where:
00 = DELAY disabled 01-99 = DELAY from 1 to 99 seconds
delay disabled
Page 44
Enter Configuration Exit and Save Configuration
Ì$+;Î
WEDGE
Ì$-?Î
37
KEYBOARD SETTING
ALPHANUMERIC KEYBOARD SETTING
The reader can be used with terminals or PCs with various keyboard types and nationalities through a simple keyboard setting procedure.
The type of computer or terminal must be selected before activating the keyboard setting command.
Keyboard setting consists of communicating to the reader how to send data corresponding to the keyboard used in the application. The keys must be set in a specific order.
Press and release a key to set it.
Some characters may require more than one key pressed simultaneously during normal use (refer to the manual of your PC or terminal for keyboard use). The exact sequence must be indicated to the reader in this case pressing and releasing the different keys.
Example:
If one has to press the "Shift" and "4" keys simultaneously on the keyboard to transmit the character "$" to the video, to set the "$", press and release "Shift" then press and release "4".
Each pressed and released key must generate an acoustic signal on the reader, otherwise repress the key. Never press more than one key at the same time, even if this corresponds to the normal use of your keyboard.
Press "Backspace" to correct a wrong key entry. In this case the reader emits 2 beeps. Note: "CAPS LOCK" and "NUM LOCK" must be off before starting the keyboard setting procedure. "SHIFT" must be repressed for each character and cannot be substituted by "CAPS LOCK".
setting the alphanumeric keyboard
ÌFB0TÎ
Read the code above. Press the keys shown in the following table according to their numerical order.
Some ASCII characters may be missing as this depends on the type of keyboard: these are generally particular characters relative to the various national symbologies. In this case:
The first 4 characters (Shift, Alt, Ctrl, and Backspace) can only be substituted with keys not
used, or substituted with each other.
characters can be substituted with other single symbols (e.g. "SPACE") even if not included in the
barcode set used.
characters can be substituted with others corresponding to your keyboard.
The reader signals the end of the procedure with 2 beeps indicating the keys have been registered.
Page 45
Enter Configuration Exit and Save Configuration
Ì$+;Î
WEDGE
Ì$-?Î
38
01 : Shift 02 : Alt 03 : Ctrl 04 : Backspace 05 : SPACE 28 : 7 51 : N 06 : ! 29 : 8 52 : O 07 : " 30 : 9 53 : P 08 : # 31 : : 54 : Q 09 : $ 32 : ; 55 : R 10 : % 33 : < 56 : S 11 : & 34 : = 57 : T 12 : ' 35 : > 58 : U 13 : ( 36 : ? 59 : V 14 : ) 37 : @ 60 : W 15 : * 38 : A 61 : X 16 : + 39 : B 62 : Y 17 : , 40 : C 63 : Z 18 : - 41 : D 64 : [ 19 : . 42 : E 65 : \ 20 : / 43 : F 66 : ] 21 : 0 44 : G 67 : ^ 22 : 1 45 : H 68 : _ (underscore) 23 : 2 46 : I 69 : ` 24 : 3 47 : J 70 : { 25 : 4 48 : K 71 : | 26 : 5 49 : L 72 : } 27 : 6 50 : M 73 : ~
74 : DEL
The keyboard setup functioning is signaled by the LEDs on the cradle. Each key stroke corresponds to a double blinking of the yellow LED.
By pressing the Backspace key the red LED on the cradle blinks, while the yellow LED stays on.
Do not place the reader onto the cradle during this procedure. Otherwise, the battery charging will occur modifying the LEDs functioning.
CAUTION
Once the procedure has been completed, the yellow LED turns off.
Page 46
Enter Configuration Exit and Save Configuration
Ì$+;Î
WEDGE
Ì$-?Î
39
CONTROL CHARACTER EMULATION
CTRL + Shift + Key
ÌFO0nÎ
CTRL + Key
ÌFO1qÎ
Page 47
40
PEN EMULATION
~
OPERATING MODE
~
~
MINIMUM OUTPUT PULSE
~
~
CONVERSION TO CODE 39
~
~
OVERFLOW
~
~
OUTPUT LEVEL
~
~
IDLE LEVEL
~
~
INTER-BLOCK DELAY
~
1. Read the Enter Configuration code ONCE, available at the top of each page.
2. Read configuration codes from the desired groups.
= Default value
3. Read the Exit and Save Configuration code ONCE, available at the top of each
page.
Page 48
PEN EMULATION
41
The operating mode parameters are complete commands and do not require reading the Enter and Exit configuration codes.
OPERATING MODE
interpret mode
Ì$]8Î
Interprets commands without sending them to the decoder.
transparent mode
Ì$[4Î
Sends commands to the decoder without interpreting them.
Page 49
Enter Configuration Exit and Save Configuration
Ì$+;Î
PEN EMULATION
Ì$-?Î
42
MINIMUM OUTPUT PULSE
200 μs
low resolu tion code
emulation
hi gh r eso lution code
emulation
ÌDG0\Î
400 μs
600 μs
ÌDG1_Î
ÌDG2bÎ
800 μs
1 ms
ÌDG3eÎ
ÌDG4hÎ
1.2 ms
ÌDG5kÎ
See par. 4.2.1 for details.
Page 50
Enter Configuration Exit and Save Configuration
Ì$+;Î
PEN EMULATION
Ì$-?Î
43
CONVERSION TO CODE 39 AND CODE 128
disable conversion to Code 39
ÌDA0PÎ
Transmits codes in their original format.
enable conversion to Code 39
ÌDA1SÎ
Converts codes read into Code 39 format.
enable conversion to Code 128
ÌDA2VÎ
Converts codes read into Code 128 format.
See par. 4.2.2 for details.
Page 51
Enter Configuration Exit and Save Configuration
Ì$+;Î
PEN EMULATION
Ì$-?Î
44
OVERFLOW
narrow
ÌDH0^Î
medium
ÌDH1aÎ
wide
ÌDH2dÎ
See par. 4.2.3 for details.
OUTPUT LEVEL
normal
(white = logic level 0)
ÌDD0VÎ
inverted
(white = logic level 1)
ÌDD1YÎ
See par. 4.2.4 for details.
Page 52
Enter Configuration Exit and Save Configuration
Ì$+;Î
PEN EMULATION
Ì$-?Î
45
IDLE LEVEL
normal
(black level)
ÌDE0XÎ
inverted
(white level)
ÌDE1[Î
See par. 4.2.4 for details.
INTER-BLOCK DELAY
delay between character blocks transmitted to Host
ÌCK3Î
Read 2 numbers from the table where: 00 = DELAY disabled
01-99 = DELAY from .1 to 9.9 seconds
delay disabled
See par. 4.2.5 for details.
Page 53
46
DATA FORMAT
NOT FOR PEN INTERFACES
~
CODE IDENTIFIER
~
~
CUSTOM CODE IDENTIFIER
~
~
HEADER
~
~
TERMINATOR
~
~
SPECIAL KEYS
~
~
FIELD ADJUSTMENT
~
~
FIELD ADJ. CHARACTER
~
~
CODE LENGTH TX
~
~
CHARACTER REPLACEMENT
~
~
ADDRESS STAMPING
~
~
ADDRESS DELIMITER
~
1. Read the Enter Configuration code ONCE, available at the top of each page.
2. Read configuration codes from the desired groups.
= Read the code and follow the procedure given
= Default value
3. Read the Exit and Save Configuration code ONCE, available at the top of each
page.
Page 54
DATA FORMAT
47
CODE IDENTIFIER TABLE
CODE AIM STANDARD DATALOGIC STANDARD Custom
2/5 interleaved ] I y N 2/5 industrial ] X y P 2/5 normal 5 bars ] S y O 2/5 matrix 3 bars ] X y Q EAN 8 ] E 4 A EAN 13 ] E 0 B UPC A ] X y C UPC E ] X y D EAN 8 with 2 ADD ON ] E 5 J EAN 8 with 5 ADD ON ] E 6 K EAN 13 with 2 ADD ON ] E 1 L EAN 13 with 5 ADD ON ] E 2 M UPC A with 2 ADD ON ] X y F UPC A with 5 ADD ON ] X y G UPC E with 2 ADD ON ] X y H UPC E with 5 ADD ON ] X y I Code 39 ] A y V Code 39 Full ASCII ] A y W CODABAR ] F y R ABC CODABAR ] X y S Code 128 ] C y T EAN 128 ] C y k
ISBT 128
] C4 f
Code 93 ] G y U CIP/39 ] X y Y CIP/HR ] X y e Code 32 ] X y X MSI ] M y Z Plessey Standard ] P 0 a Plessey Anker ] P 1 o Telepen ] X 0 d Delta IBM ] X 0 c Code 11 ] H y b Code 16K ] K 0 p Code 49 ] T y q RSS Expanded Linear and Stacked ] e 0 t RSS Limited ] e 0 v RSS 14 Linear and Stacked ] e 0 u
Page 55
DATA FORMAT
48
AIM standard identifiers are not defined for all codes: the X identifier is assigned to the code for
which the standard is not defined. The y value depends on the selected options (check digit tested or not, check digit tx or not, etc.).
When customizing the Datalogic Standard code identifiers, 1 or 2 identifier characters can be
defined for each code type. If only 1 identifier character is required, the second character must be selected as FF (disabled).
The code identifier can be singly disabled for any code by simply selecting FF as the first
identifier character.
Write in the Custom character identifiers in the table above for your records.
Page 56
Enter Configuration Exit and Save Configuration
Ì$+;Î
DATA FORMAT
Ì$-?Î
49
CODE IDENTIFIER
disable
ÌEB0SÎ
Datalogic standard
ÌEB1VÎ
AIM standard
ÌEB2YÎ
custom
ÌEB3\Î
Page 57
Enter Configuration Exit and Save Configuration
Ì$+;Î
DATA FORMAT
Ì$-?Î
50
CUSTOM CODE IDENTIFIER
define custom code identifier(s)
ÌEH/Î
c Read the above code.
(Code Identifiers default to Datalogic standard, see table on previous page).
d Select the code type from the code table in Appendix
B for the identifier you want to change.
e You can define 1 or 2 identifier characters for each code type. If only 1 identifier character is
required, the second character must be selected as FF (disabled). Read the hexadecimal value corresponding to the character(s) you want to define as identifiers for the code selected in step d: valid characters are in the range 00-FD. For Wedge and USB-KBD interfaces, it is also possible to read the Special Key(s) on page 53.
Example
: To define Code 39 Code Identifier = @
define custom code identifier(s)
Code 39
Read
ÌEH/Î
+
ÌVWÎ
+
40
+
FF
Page 58
Enter Configuration Exit and Save Configuration
Ì$+;Î
DATA FORMAT
Ì$-?Î
51
HEADER
no header
ÌEA00*Î
one character header
two character header
ÌEA01.Î
ÌEA022Î
three character header
four character header
ÌEA036Î
ÌEA04:Î
five character header
six character header
ÌEA05>Î
ÌEA06BÎ
seven character header
eight character header
ÌEA07FÎ
ÌEA08JÎ
After selecting one of the desired Header codes, read the character(s) from the HEX table. Valid characters are in the range 00-FE. For Wedge and USB-KBD interfaces, it is also possible to read the Special Key(s) on page 53.
Example
:
four character header
+ 41 + 42 + 43 + 44 = Header ABCD
For more details see par. 4.2.6.
Page 59
Enter Configuration Exit and Save Configuration
Ì$+;Î
DATA FORMAT
Ì$-?Î
52
TERMINATOR
no terminator
ÌEA10-Î
one character terminator
two character terminator
ÌEA111Î
ÌEA125Î
three character terminator
four character terminator
ÌEA139Î
ÌEA14=Î
five character terminator
six character terminator
ÌEA15AÎ
ÌEA16EÎ
seven character terminator
eight character
terminator
ÌEA17IÎ
ÌEA18MÎ
After selecting one of the desired Header codes, read the character(s) from the HEX table. Valid characters are in the range 00-FE. For Wedge and USB-KBD interfaces, it is also possible to read the Special Key(s) on page 53.
Example:
two character terminator
+ 0D + 0A = Terminator CR LF
For more details see par. 4.2.6.
Page 60
Enter Configuration Exit and Save Configuration
Ì$+;Î
DATA FORMAT
Ì$-?Î
53
SPECIAL KEYS
Available only for Wedge IBM AT-PS/2 and USB-KBD Interfaces
It is necessary to define each Special Key by following the procedure given in par. 4.2.7.
NOTE
Select one or more of the following Special Keys according to your needs.
Special Key 1
Ì9CÄÎ
Special Key 2
Special Key 3
Ì9DÆÎ
Ì9EÈÎ
Special Key 4
Special Key 5
Ì9FÊÎ
ÌA0bÎ
Page 61
Enter Configuration Exit and Save Configuration
Ì$+;Î
DATA FORMAT
Ì$-?Î
54
FIELD ADJUSTMENT
disable field adjustment
ÌEF0[Î
Field adjustment allows a number of characters n, to be added to or subtracted from the barcode read. The adjustment can be different for each enabled code type. To define
the field adjustment:
c Read the enable field adjustment code:
enable field adjustment
ÌEF+Î
d Select the code type from the Code Identifier Table in Appendix B.
e Select the type of adjustment to perform:
right addition
Ì01Î
left addition
right deletion
Ì12Î
Ì23Î
left deletion
Ì34Î
f Read a number in the range 01 - 32 from the Hex/Numeric Table to define how many characters
to add or delete:
Conditions:
Adjustment is only performed on the barcode data; the Code Identifier and Code Length
Transmission fields are not modified by the field adjustment parameter.
If the field setting would subtract more characters than exist in the barcode, the subtraction will
take place only to code length 0.
You can set up to a maximum of 10 different field adjustments on the same barcode family or on
different barcode families.
Example:
To add 4 characters to the right of Standard Code 39 Codes:
enable field adjustment
Code 39
right addition
Read
ÌEF+Î
+
ÌVWÎ
+
Ì01Î
+
04
Page 62
Enter Configuration Exit and Save Configuration
Ì$+;Î
DATA FORMAT
Ì$-?Î
55
FIELD ADJUSTMENT CHARACTER
c
Read the field adjustment character code:
field adjustment character
ÌEG-Î
d
Read the hexadecimal value corresponding to the character you want to use for field adjustment.
Valid characters are in the range 00-FE. For Wedge and USB-KBD interfaces, it is also possible to read the Special Key(s) on page 53.
Example:
To define the field adjustment character = A:
field adjustment character
CODE LENGTH TX
code length not transmitted
ÌEE0YÎ
code length transmitted in variable-digit format
ÌEE1\Î
code length transmitted in fixed 4-digit format
ÌEE2_Î
The code length is transmitted in the message after the Headers and Code Identifier characters. The code length is calculated after performing any field adjustment operations.
Page 63
Enter Configuration Exit and Save Configuration
Ì$+;Î
DATA FORMAT
Ì$-?Î
56
CHARACTER REPLACEMENT
disable character replacement
ÌEO0mÎ
This parameter allows up to three characters to be replaced from the barcode read. These substitutions are stored in memory. To define each
character replacement:
c
Read one of the following character replacement codes:
first character replacement
ÌEO1pÎ
second character replacement
ÌEO2sÎ
third character replacement
ÌEO3vÎ
d From the Code Identifier Table in Appendix B, read the Code Identifier for the desired code
family. 0 = character replacement will be effective for all code families.
e From the Hex/Numeric Table read two characters corresponding to the Hex value (00-FE) which
identifies the character to be replaced.
For Wedge and USB-KBD interfaces, it is also possible to
read the Special Key(s) on page 53.
f From the Hex/Numeric Table read two characters corresponding to the Hex value (00-FE) which
identifies the new character to replace. For Wedge and USB-KBD interfaces, it is also possible to read the Special Key(s) on page 53. FF = the character to be replaced will be substituted with no character, that is, it will be removed from the code.
Page 64
Enter Configuration Exit and Save Configuration
Ì$+;Î
DATA FORMAT
Ì$-?Î
57
Example:
The following strings define:
1. First Character Replacement: substitution in Code 39 barcodes of all occurrences of the
0 character with the 1 character.
2. Second Character Replacement: substitution in Code 39 barcodes of all occurrences of the A
character with the B character.
first character replacement
Code 39
ASCII characters corresponding to the HEX value for character 0
ASCII characters corresponding to the HEX value for character 1
ÌEO1pÎ
+
ÌVWÎ
+
30
+
31
For Code 39 codes containing the string "0123", the contents transmitted will be "1123".
second character
replacement
Code 39
ASCII characters corresponding to the HEX value for character A
ASCII characters corresponding to the HEX value for character B
ÌEO2sÎ
+
ÌVWÎ
+
41
+
42
For Code 39 codes containing the string "ABCD", the contents transmitted will be "BBCD".
Page 65
58
ADDRESS STAMPING
disable reader address stamping
ÌRU0ÊÎ
enable reader address stamping
ÌRU1"Î
See par. 4.2.8 for details.
ADDRESS DELIMITER
disable reader address delimiter
ÌRV0!Î
enable reader address delimiter and select characters
ÌRV1$Î
Read 2 HEX characters in the range 00-FE.
See par. 4.2.9 for details.
Page 66
59
READING PARAMETERS
~
HAND-HELD OPERATION
~
~
STAND OPERATION
~
~
HARDWARE TRIGGER MODE
~
~
TRIGGER-OFF TIMEOUT
~
~
FLASH MODE
~
~
READS PER CYCLE
~
~
SAFETY TIME
~
~
BEEPER INTENSITY
~
~
BEEPER TONE
~
~
BEEPER TYPE
~
~
BEEPER LENGTH
~
~
STAND RECOGNITION BEEP
~
1. Read the Enter Configuration code ONCE, available at the top of each page.
2. Read configuration codes from the desired groups.
= Read the code and follow the procedure given
= Default value
3. Read the Exit and Save Configuration code ONCE, available at the top of each
page.
Page 67
Enter Configuration Exit and Save Configuration
Ì$+;Î
READING PARAMETERS
Ì$-?Î
60
HAND-HELD OPERATION
hardware trigger
ÌBK1eÎ
software trigger
* always on
ÌBK0bÎ
ÌBK3kÎ
automatic
* not available for Mobile series readers
hardware trigger ready
ÌBK2hÎ
ÌBK4nÎ
STAND OPERATION
ONLY Devices with Stand Recognition Beep
hardware trigger
ÌBU3ÃÎ
software trigger
* always on
ÌBU1yÎ
ÌBU2|Î
automatic
* not available for Mobile series readers
ÌBU0vÎ
Page 68
Enter Configuration Exit and Save Configuration
Ì$+;Î
READING PARAMETERS
Ì$-?Î
61
HARDWARE TRIGGER MODE
trigger active level
ÌBA0NÎ
trigger active pulse
ÌBA1QÎ
See par. 4.3.1 for details
TRIGGER-OFF TIMEOUT
trigger-off timeout
ÌBD$Î
Read 2 numbers in the range 00-99:
00 = disables the trigger-off timeout 01-99 = corresponds to a max. 99-sec. delay after the trigger press to
allow the reader to turn off automatically.
trigger-off timeout disabled
See par. 4.3.2 for details.
Page 69
Enter Configuration Exit and Save Configuration
Ì$+;Î
READING PARAMETERS
Ì$-?Î
62
FLASH MODE
"FLASH" ON duration
ÌBB0PÎ
"FLASH" OFF duration
ÌBB1SÎ
Read 2 numbers in the range 01-99:
01 to 99 = from .1 to 9.9 seconds.
Flash-ON = 1 sec. Flash-OFF = 0.6 sec
READS PER CYCLE
one read per cycle
ÌBC0RÎ
multiple reads per cycle
ÌBC1UÎ
See par. 4.3.3 for details.
Page 70
Enter Configuration Exit and Save Configuration
Ì$+;Î
READING PARAMETERS
Ì$-?Î
63
SAFETY TIME
safety time
ÌBE&Î
Limits same
code consecutive reading.
Read 2 numbers in the range 00-99:
00 = no same code consecutive reading until reader is removed
(no decoding) for at least 400 ms.
01-99 = timeout from .1 to 9.9 seconds before a consecutive read on
same code.
safety time = 0.5 sec
See par. 4.3.4 for details.
BEEPER INTENSITY
* very low intensity
ÌBG0ZÎ
low intensity
medium intensity
ÌBG1]Î
ÌBG2`Î
high intensity
ÌBG3cÎ
* This sets the beeper OFF for data entry, while for all other beeper signals it has the meaning “very
low intensity”. The Beeper Intensity parameter is effective for all operating conditions described in par. 5.2.
Page 71
Enter Configuration Exit and Save Configuration
Ì$+;Î
READING PARAMETERS
Ì$-?Î
64
BEEPER TONE
tone 1
ÌBH0\Î
tone 2
tone 3
ÌBH1_Î
ÌBH2bÎ
tone 4
ÌBH3eÎ
BEEPER TYPE
monotone
ÌBJ0`Î
bitonal
ÌBJ1cÎ
BEEPER LENGTH
long
ÌBI0^Î
short
ÌBI1aÎ
Page 72
Enter Configuration Exit and Save Configuration
Ì$+;Î
READING PARAMETERS
Ì$-?Î
65
STAND RECOGNITION BEEP
ONLY Devices with Stand Recognition
disable
ÌBV0xÎ
enable
ÌBV1{Î
Page 73
66
DECODING PARAMETERS
~
INK SPREAD
~
~
OVERFLOW CONTROL
~
~
INTERDIGIT CONTROL
~
~
DECODING SAFETY
~
~
PUZZLE SOLVER
~
Before changing these parameter values read the descriptions in par. 4.4.
CAUTION
1. Read the Enter Configuration code ONCE, available at the top of each page.
2. Read configuration codes from the desired groups.
= Default value
3. Read the Exit and Save Configuration code ONCE, available at the top of each
page.
Page 74
Enter Configuration Exit and Save Configuration
Ì$+;Î
DECODING PARAMETERS
Ì$-?Î
67
INK SPREAD
disable
ÌAX0{Î
enable
ÌAX1~Î
See par. 4.4.1 for details.
OVERFLOW CONTROL
disable
ÌAW1|Î
enable
ÌAW0yÎ
See par. 4.4.2 for details.
Page 75
Enter Configuration Exit and Save Configuration
Ì$+;Î
DECODING PARAMETERS
Ì$-?Î
68
INTERDIGIT CONTROL
disable
ÌAV0wÎ
enable
ÌAV1zÎ
See par. 4.4.3 for details.
DECODING SAFETY
one read
ÌED0WÎ
(decoding safety disabled)
two reads
three reads
ÌED1ZÎ
ÌED2]Î
four reads
ÌED3`Î
Required number of good reads before accepting code.
Page 76
Enter Configuration Exit and Save Configuration
Ì$+;Î
DECODING PARAMETERS
Ì$-?Î
69
PUZZLE SOLVER
disable
ÌAU0uÎ
enable
ÌAU1xÎ
In the case of damaged or poorly printed codes, this parameter allows reading multiple parts of the single code to reconstruct it.
To read codes using this technology, simply move the illuminated bar over the code so that each line of the code is scanned. During this process a series of brief “ticks” indicates that reading is proceeding correctly.
Conditions:
This parameter is only valid for the following codes:
EAN 8
without Add-on
EAN 13
without Add-on
UPC A
without Add-on
Code 128 Code 39
For Code 39, Check digit control is forced.
PuzzleSolver is not valid for ISBT 128 code.
Page 77
70
CODE SELECTION
~
EAN/UPC FAMILY
~
~
2/5 FAMILY
~
~
CODE 39 FAMILY
~
~
CODE 128 FAMILY
~
~
CODABAR FAMILY
~
~
CODE 93
~
~
MSI
~
~
PLESSEY
~
~
TELEPEN
~
~
DELTA IBM
~
~
CODE 11
~
~
CODE 16K
~
~
CODE 49
~
~
GS1 DATABAR
~
1. Read the Enter Configuration code ONCE, available at the top of each page.
2. Read configuration codes from the desired groups.
= Read the code and follow the procedure given
= Default value
3. Read the Exit and Save Configuration code ONCE, available at the top of each
page.
Page 78
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
71
DISABLE ALL CODE FAMILIES
ÌAZ0ÃÎ
The reader allows up to 5 code selections. This does not limit the number of
CODES enabled to 5, as it depends on the code family.
NOTE
SINGLE
SELECTIONS =
Example
5 code selections: 1. 2/5 Interleaved
2. 2/5 Industrial
3. Code 128 + EAN 128
4. Code 39 Full ASCII + Code 32
5. UPC A/UPC E
In this section all SINGLE code selections are underlined and in bold.
ONE combination code from the EAN family
ONE code
from the 2/5 family
Page 79
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
72
EAN/UPC FAMILY
disable the family
ÌAA0MÎ
c Read the desired family code
Note:
Since the EAN/UPC without ADD ON code selection is enabled by default, to correctly enable another selection, first disable the family.
WITHOUT ADD ON
EAN 8/EAN 13/UPC A/UPC E
ÌAA1PÎ
EAN 8/EAN 13
ÌAA3VÎ
UPC A/UPC E
ÌAA4YÎ
Page 80
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
73
WITH ADD ON 2 AND 5
EAN 8/EAN 13/UPC A/UPC E
ÌAA5\Î
EAN 8/EAN 13
ÌAA6_Î
UPC A/UPC E
ÌAA7bÎ
WITH ADD ON 2 ONLY
EAN 8/EAN 13
ÌAAK7Î
UPC A/UPC E
ÌAAM=Î
WITH ADD ON 5 ONLY
EAN 8/EAN 13
ÌAAL:Î
UPC A/UPC E
ÌAAN@Î
Page 81
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
74
WITH AND WITHOUT ADD ON
EAN/UPC with and without ADD ON no
Autodiscrimination
ÌAA8Ad03Î
EAN/UPC Autodiscrimination ADD ON by
Prefix
ÌAA8Ad19Î
By setting the EAN/UPC Autodiscrimination ADD ON by Prefix, the desired prefixes must be selected by reading the corresponding codes given in the following section, since no prefix is configured by default.
Page 82
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
75
SELECT EAN/UPC PREFIXES
When scanning the following codes, barcodes starting with the selected prefixes will be read and transmitted only if the ADD ON is present. If no ADD ON is found, the barcode will not be read. Barcodes starting with different characters are read regardless of ADD ON presence and transmitted always without ADD ON.
NOTE
Cancel All Selections
ÌET0wÎ
OR
select one or more of the following prefixes:
378/379
ÌET1378ET2379PÎ
434/439
ÌET3434ET4439ÉÎ
414/419
ÌET5414ET6419}Î
977
ÌET7977QÎ
978
ÌET8978ZÎ
979
ÌET9979cÎ
The commands above are not mutually exclusive. They can be used to configure more than one set of prefixes simultaneously.
Page 83
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
76
Example:
The following string allows reading and transmitting with ADD ON all EAN/UPC starting with the 434/439, 977 and 978 prefixes:
1. EAN/UPC Autodiscrimination ADD ON by Prefix.
2. 434/439: enables reading and transmission with ADD ON of all EAN/UPC barcodes starting with
434/439 prefixes.
3. 977: enables reading and transmission with ADD ON of all EAN/UPC barcodes starting with 977
prefix.
4. 978: enables reading and transmission with ADD ON of all EAN/UPC barcodes starting with 978
prefix.
EAN/UPC Autodiscrimination ADD ON by Prefix 434/439
ÌAA8Ad19Î
+
ÌET3434ET4439ÉÎ
+
977 978
+
ÌET7977QÎ
+
ÌET8978ZÎ
To clear the current prefix selections:
1. Cancel all Selections
Cancel All Selections
ÌET0wÎ
Page 84
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
77
EAN/UPC CHECK DIGIT TX SELECTIONS
For each code type in this family you can choose to transmit the check digit or not
CHECK DIGIT TRANSMISSION
EAN 8
NO CHECK DIGIT TRANSMISSION
ÌAAG1oÎ
EAN 8
ÌAAG0kÎ
EAN 13
ÌAAH1rÎ
EAN 13
ÌAAH0nÎ
UPC A
ÌAAI1uÎ
UPC A
ÌAAI0qÎ
UPC E
ÌAAJ1xÎ
UPC E
ÌAAJ0tÎ
Page 85
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
78
CONVERSION OPTIONS
UPC E to UPC A conversion
ÌAAAÄÎ
UPC E to EAN 13 conversion
ÌAABÇÎ
UPC A to EAN 13 conversion
ÌAACÊÎ
EAN 8 to EAN 13 conversion
ÌAAD"Î
Enable only ISBN conversion
ÌAP1nÎ
Enable only ISSN conversion
ÌAP2qÎ
Enable both ISBN and ISSN conversion
ÌAP3tÎ
Disable both ISBN and ISSN conversion
ÌAP0kÎ
2/5 FAMILY
disable the family
ÌAC0QÎ
c Read the desired family code
d Read a check digit selection
 Interleaved 2/5
ÌAC1TÎ
CHECK DIGIT TABLE
no check digit control
Page 86
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
79
Normal 2/5 (5 Bars)
Ì12Î
ÌAC2WÎ
check digit control and transmission
Industrial 2/5 (IATA)
Ì23Î
ÌAC3ZÎ
check digit control without transmission
Matrix 2/5 (3 Bars)
Ì34Î
ÌAC4]Î
e Read 4 numbers for the code length
where:
First 2 digits = minimum code length.
Second 2 digits = maximum code
length.
The pharmaceutical code below is part of the 2/5 family but has no check digit or code length selections.
The maximum code length is 99 characters.
The minimum code length must always be less than or equal to the maximum.
Code CIP/HR
ÌAC5`Î
Examples: 0199 = variable from 1 to 99 digits in the
code. 1010 = 10 digit code length only.
French pharmaceutical code
CODE 39 FAMILY
disables the family
ÌAB0OÎ
c Read the desired family code
d
Read a check digit selection
Standard Code 39
CHECK DIGIT TABLE
no check digit control
ÌAB1RÎ
Ì12Î
Full ASCII Code 39
check digit control
and transmission
ÌAB2UÎ
Ì23Î
Page 87
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
80
check digit control
without transmission
Ì34Î
The pharmaceutical codes below are part of the Code 39 family but have no check digit selections.
Code CIP39
ÌAB3XÎ
French pharmaceutical code
Code 32
ÌAB4[Î
Italian pharmaceutical code
CODE LENGTH (optional)
The code length selection is valid for the entire Code 39 family
Read the code + 4 numbers for the code length where:
set code length
First 2 digits = minimum code length. Second 2 digits = maximum code length.
ÌAB*=Î
The maximum code length is 99 characters.
The minimum code length must always be less than or equal to the maximum.
Examples: 0199 = variable from 1 to 99 digits in the code. 1010 = 10 digit code length only.
Page 88
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
81
CODE 128 FAMILY
disables the family
ÌAI0]Î
c
Read the desired family code
Code 128
ÌAI11=Î
control without transmission
of check digit
EAN 128
ÌAI21@Î
control without transmission
of check digit
Transmit GS Before Code
Code EAN 128 uses the ASCII <GS> character to separate a variable length code field from the next code field. This character can also be transmitted before the code.
disable
ÌEQ0qÎ
enable
ÌEQ1tÎ
If the <GS> character has been modified in the Character Replacement parameter, the new character is affected by this command.
ISBT 128
ÌAI31CÎ
Enabling ISBT 128 automatically disables Puzzle Solver™.
CODE LENGTH (optional)
The code length selection is valid for the entire Code 128 family.
Read the code + 4 numbers for the code length where: First 2 digits = minimum code length
set code length
Page 89
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
82
Second 2 digits = maximum code length
ÌAILJÎ
The maximum code length is 99 characters. The minimum code length must always be less than or equal to the maximum.
Examples: 0199 = variable from 1 to 99 digits in the code. 1010= 10 digit code length only.
The length is calculated on the output string.
CODE 93
disables the code
ÌAK0aÎ
Code 93
ÌAK1dÎ
control without transmission
of check digit
Page 90
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
83
CODABAR FAMILY
disable the family
ÌAD0SÎ
c
Read the desired equality control code
d Read a start/stop transmission
selection
START/STOP CHARACTER
TRANSMISSION
Standard Codabar
ÌAD113Î
no start/stop character equality
control
no transmission
Ì12Î
Standard Codabar
ÌAD127Î
start/stop character equality
control
transmission
Ì23Î
The Codabar ABC code below uses a fixed start/stop character transmission selection.
Codabar ABC
ÌAD212)Î
no start/stop character equality control but transmission.
Page 91
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
84
Codabar ABC Forced Concatenation
enable Codabar ABC with forced concatenation
ÌAD2321Î
non start/stop character equality control but transmission
CODE LENGTH (optional)
The code length selection is valid for the entire Codabar family
Read the code + 4 numbers for the code length where:
set code length
First 2 digits = minimum code length. Second 2 digits = maximum code length.
ÌAD*AÎ
The maximum code length is 99 characters.
The minimum code length must always be less than or equal to the maximum.
Examples: 0199 = variable from 1 to 99 digits in the code. 1010 = 10 digit code length only.
START/STOP CHARACTER CASE IN TRANSMISSION
The start/stop character case selections below are valid for the entire Codabar family:
transmit start/stop characters in lower case
ÌADA0_Î
transmit start/stop characters in upper case
ÌADA1cÎ
Page 92
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
85
MSI
disable the family
ÌAE0UÎ
Enable the code by selecting one of the check digit selections.
no check digit control
ÌAE1XÎ
MOD10 check digit control no check digit transmission
ÌAE2[Î
MOD10 check digit control
check digit transmission
ÌAE3^Î
MOD11 - MOD10 check digit control
no check digit transmission
ÌAE4aÎ
MOD11 - MOD10 check digit control
check digit transmission
ÌAE5dÎ
MOD10 - MOD10 check digit control
no check digit transmission
ÌAE6gÎ
MOD10 - MOD10 check digit control
check digit transmission
ÌAE7jÎ
PLESSEY
disable the family
ÌAF0WÎ
Enable the code by selecting one of the check digit selections.
Standard Plessey
no check digit control
ÌAF117Î
Page 93
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
86
check digit control
check digit transmitted
ÌAF12;Î
check digit control
check digit not transmitted
ÌAF13?Î
Anker Plessey
no check digit control
ÌAF21:Î
check digit control
check digit transmitted
ÌAF22>Î
check digit control
check digit not transmitted
ÌAF23BÎ
Page 94
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
87
TELEPEN
disable the family
ÌAL0cÎ
Enable the code by selecting one of the check digit selections.
Numeric Telepen
no check digit control
ÌAL11CÎ
check digit control
check digit transmitted
ÌAL12GÎ
check digit control
check digit not transmitted
ÌAL13KÎ
Alphanumeric Telepen
no check digit control
ÌAL21FÎ
check digit control
check digit transmitted
ÌAL22JÎ
check digit control
check digit not transmitted
ÌAL23NÎ
Page 95
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
88
DELTA IBM
disable the family
ÌAH0[Î
Enable the code by selecting one of the check digit selections.
no check digit control
ÌAH1^Î
Type 1 check digit control
ÌAH2aÎ
Type 2 check digit control
ÌAH3dÎ
Page 96
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
89
CODE 11
disable the family
ÌAG0YÎ
Enable the code by selecting one of the check digit selections.
no check digit control
ÌAG1\Î
Type C check digit control
check digit transmitted
ÌAG21<Î
Type C check digit control
check digit not transmitted
ÌAG22@Î
Type K check digit control
check digit transmitted
ÌAG31?Î
Type K check digit control
check digit not transmitted
ÌAG32CÎ
Type C and Type K check digit control
check digits transmitted
ÌAG41BÎ
Type C and Type K check digit control
check digits not transmitted
ÌAG42FÎ
Page 97
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
90
CODE 16K
disable the code
ÌAJ0_Î
Code 16K
ÌAJ1bÎ
To read stacked codes, simply move the reader over the code so that each line of the code is scanned. During this process a series of brief “ticks” indicates that reading is proceeding correctly.
CODE 49
disable the code
ÌAM0eÎ
Code 49
ÌAM1hÎ
To read stacked codes, simply move the reader over the code so that each line of the code is scanned. During this process a series of brief “ticks” indicates that reading is proceeding correctly.
Page 98
Enter Configuration Exit and Save Configuration
Ì$+;Î
CODE SELECTION
Ì$-?Î
91
GS1 DATABAR
disable the family
ÌAQ0mÎ
DISABLE CODE
disable RSS Expanded Linear and Stacked
ENABLE CODE
ÌAQ10IÎ
enable RSS Expanded Linear and Stacked
disable RSS Limited
ÌAQ11MÎ
ÌAQ20LÎ
enable RSS Limited
disable RSS 14 Linear and Stacked
ÌAQ21PÎ
ÌAQ30OÎ
enable RSS 14 Linear and Stacked
ÌAQ31SÎ
To read stacked codes, simply move the reader over the code so that each line of the code is scanned. During this process a series of brief “ticks” indicates that reading is proceeding correctly.
Page 99
92
ADVANCED FORMATTING
NOT FOR PEN INTERFACES
~
C
ONCATENATION
~
~
A
DVANCED FORMATTING
~
Please follow the setup procedure carefully for these parameters.
NOTE
The Advanced Formatting parameters may not be compatible with the IBM USB POS interface selection.
NOTE
1. Read the Enter Configuration code ONCE, available at the top of page .
2. Read configuration codes precisely following the numbered procedure given.
= Read the code and follow the procedure given
= Default value
3. Read the Exit and Save Configuration code ONCE, available at the top of page.
Page 100
Enter Configuration Exit and Save Configuration
Ì$
+;Î
ADVANCED FORMATTING
Ì$-?Î
93
CONCATENATION
disable
ÌEI0aÎ
enable
ÌEI1dÎ
Permits the concatenation of two codes defined by code type and length. It is possible to set a timeout for the second code reading and to define code transmission if the timeout expires.
The order of transmission is CODE 1-CODE 2.
Define Concatenation
1
Code 1
code ID
ÌEK0eÎ
Read the code type from the Code Identifier Table beginning in Appendix B.
code length
ÌEL0gÎ
Read a number in the range 01-99 from the Hex/Numeric Table.
Loading...