Deif PPU, PPM Installation Instructions Manual

Page 1
DEI
F
A/
S
4189340409I (UK)
Installation Instructions
Diesel generator I/O
s
Shaft generator/Shore connection I/Os Bus tie generator I/Os Wiring
DEIF A/S, Frisenborgvej 33 Tel.: +45 9614 9614, Fax: +45 9614 9615 DK-7800 Skive, Denmark E-mail: deif@deif.com, URL: www.deif.com
Page 2
PPM Installation Instructions
DEIF A/S Page 2 of 69
Table of contents
1.
ABOUT THIS DOCUMENT .................................................................................................... 3
INTENDED USERS.......................................................................................................................... 3
CONTENTS/OVERALL STRUCTURE .................................................................................................. 3
DEFINITIONS ................................................................................................................................ 3
2. WARNINGS AND LEGAL INFORMATION ........................................................................... 4
LEGAL INFORMATION AND RESPONSIBILITY ..................................................................................... 4
ELECTROSTATIC DISCHARGE AWARENESS ..................................................................................... 4
SAFETY ISSUES ............................................................................................................................ 4
3. GENERAL HARDWARE DESCRIPTION .............................................................................. 5
HARDWARE .................................................................................................................................. 5
4. DIESEL GENERATOR I/OS ................................................................................................... 6
DG UNIT WITH PMS PROCESSOR .................................................................................................. 6
DG UNIT WITHOUT PMS PROCESSOR .......................................................................................... 20
5. SHAFT GENERATOR I/OS .................................................................................................. 34
SG WITH FIXED FREQUENCY ....................................................................................................... 34
6. BUS TIE BREAKER I/OS ..................................................................................................... 45
BUS TIE BETWEEN DG AND SG ................................................................................................... 45
7. ADDITIONAL OPERATOR PANEL ..................................................................................... 54
INSTALLATION OF AOP-2 ............................................................................................................ 54
8. WIRINGS .............................................................................................................................. 57
AC CONNECTIONS (3-PHASE) ...................................................................................................... 57
INTERNAL CANBUS WIRING ......................................................................................................... 58
OPTION H2, MODBUS RTU ......................................................................................................... 58
LOAD SHARING LINES .................................................................................................................. 60
MECHANICAL SPEED GOVERNOR (STANDARD) .............................................................................. 61
AVR WITH RELAY OUTPUTS......................................................................................................... 61
ELECTRONIC SPEED GOVERNOR .................................................................................................. 62
AVR WITH ANALOGUE OUTPUTS (REQUIRES OPTION D) ................................................................ 62
BINARY INPUTS ........................................................................................................................... 63
BINARY INPUTS WITH WIRE BREAK SUPERVISION .......................................................................... 63
ANALOGUE INPUTS ..................................................................................................................... 64
OPTOCOUPLER OUTPUTS FOR EXTERNAL COUNTER ...................................................................... 64
9. GENERAL DATA ................................................................................................................. 65
TECHNICAL SPECIFICATIONS ....................................................................................................... 65
UNIT DIMENSIONS ....................................................................................................................... 68
PANEL CUTOUT (IN MM) ............................................................................................................... 69
Page 3
PPM Installation Instructions
DEIF A/S Page 3 of 69
1. About this document
This document is the Installation Instructions for DEIF’s PPU Power Management system PPM. The document mainly includes general hardware description, I/O lists for diesel, shaft and bus tie generator, wiring descriptions and FAT information.
The general purpose of these installation instructions is to give the user important information to be used in the installation of the PPM system.
Intended users
These installation instructions are mainly intended for the panel builder designer in charge. On the basis of this document, the panel builder designer will give the electrician the information he needs in order to install the PPM system, e.g. detailed electrical drawings. In some cases the electrician may use these installation instructions himself.
Contents/overall structure
This document is divided into chapters, and in order to make the structure simple and easy to use, each chapter will begin from the top of a new page.
Definitions
Throughout this document a number of notes and warnings will be presented. To ensure that these are noticed, they will be highlighted in order to separate them from the general text.
Notes
Warnings
Please make sure that you read this manual before starting to work with the PPM system. Failure to do this could result in damaging the equipment or even worse injury of personnel.
The notes provide general information which will be helpful for the reader to bear in mind.
The warnings indicate a potentially dangerous situation which could result in death, personal injury or damaged equipment, if certain guidelines are not followed.
Page 4
PPM Installation Instructions
DEIF A/S Page 4 of 69
2. Warnings and legal information
Legal information and responsibility
DEIF takes no responsibility for installation or operation of the generator sets. If there is any doubt about how to install or operate the generator sets controlled by the PPM system, the company responsible for the installation or the operation of the sets must be contacted.
Electrostatic discharge awareness
Sufficient care must be taken to protect the terminals against static discharges during the installation. Once the system is installed and connected, these precautions are no longer necessary.
Safety issues
Installing the system implies work with dangerous currents and voltages. Therefore, the installation should only be carried out by authorised personnel who understand the risks involved in working with live electrical equipment.
Be aware of the hazardous live currents and voltages. Do not touch any AC measurement inputs as this could lead to injury or death.
The system units are not to be opened by unauthorised personnel. If opened anyway,
the warranty will be lost.
Page 5
PPM Installation Instructions
DEIF A/S Page 5 of 69
3. General hardware description
Hardware
The unit housing is divided into board slot positions. This means that the unit consists of a number of printed circuit boards (PCBs) mounted in numbered slots. The green terminal blocks are then mounted in the PCBs. Some of these board slots are standard, and some are intended for options. The board slot positions are arranged as illustrated below.
Term. DG SG/SC TB Description
Slot #1 1-28 Standard Standard Standard Power supply board
Slot #2 29-36 H2 H2 H2 Option: External comm.
Slot #3 37-64 Standard Standard Standard Load sharing and
input/output board
Slot #4 65-72 Standard
Not used Not used
Outputs for governor/AVR according to choice of types
Slot #5 73-89 Standard Standard Standard AC measuring
Slot #6 90-125 F1,
M15, M16, M18
F1, M15, M16, M18
F1, M15, M16, M18
Option: F1 analogue transducer outputs, M15 (4 x 0(4)…20 mA inputs), M16 (7 x binary inputs), M18 (4 x relay outputs)
Slot #7 98-125 Standard Standard
Not used
Engine interface board
Slot #8 126-133 Standard Standard Standard Internal CANbus
Unit top side overview
An overview of the terminals is presented below. The slot positions are as follows:
Ethernet
787776757473
96 979594929190 93
89888785 8683 8482818079
727169 70686765 66
62 6359 60 615856 575553 54 645251504947464443 45 4841403837 39 42
USB Memory Service port Display
Ethernet
PMS CAN
Engine CAN
USB
Power Self check ok Alarm inhibit
SLOT # 1
SLOT # 3
SLOT # 5
SLOT # 7
SLOT # 2
SLOT # 4
SLOT # 6
SLOT # 8
Page 6
PPM Installation Instructions
DEIF A/S Page 6 of 69
4. Diesel generator I/Os
DG unit with PMS processor
Terminal strip overviews
Slots #1, #2, #5 and #6
36
SLOT # 2
external comm.
OPTION H2
363636 35353535 34343434 33333333 32323232 31313131 30303030 29292929 28282828 27272727 26262626 25252525 24242424 23232323 22222222 21212121 20202020 19191919 18181818 17171717 16161616 15151515 14141414 13131313 12121212 11111111 10101010
9999 8888 7777 6666 5555 4444 3333 2222 1111
36363636 35353535 34343434 33333333 32323232 31313131 30303030 29292929 28282828 27272727 26262626 25252525 24
242424 23232323 22222222 21212121 20202020 19191919 18181818 17171717 16161616 15151515 14141414 13131313 12121212 11111111 10101010
9999 8888 7777 6666 5555 4444 3333 2222 1111
36363636 35353535 34343434 33333333 32323232 31313131 30303030 29292929 28282828 27272727 26262626 25252525 24242424 23232323 22222222 21212121 20202020 19191919 18181818 17171717 16161616 15151515 14141414 13131313 12121212 11111111 10
101010
9999 8888 7777 6666 5555 4444 3333 2222 1111
36363636 35353535 34343434 33333333 32323232 31313131 30303030 29292929 28282828 27272727 26262626 25252525 24242424 23232323 22222222 21212121 20202020 19191919 18181818 17171717 16161616 15151515 14141414 13131313 12121212 11111111 10101010
9999 8888 7777 6666 5555 4444 3333 2222 1111
COMMON (TERM. 23-27)
PMS CONTROL
Configurable/Secured ON
Configurable/Secured OFF
Shore pos. OFF
Forced SWBD
COMMON (TERM. 20-21)
Configurable (Relay 26)
Configurable (Relay 27)
binary optocoupler
SLOT # 1
inputs
CB ON
Sync.
transistor output
relay output
CB OFF
Open breaker
RELAY 4
PMS
Alarm
RELAY 3
Configurable/Trip NEL2 RELAY 2
Configurable/Trip NEL1 RELAY 1
STATUS
relay
97979797 96969696 95959595 94949494 93939393 92929292 91919191 90909090
89898989 88888888 87878787 86868686 85858585 84848484 83838383 82828282 81818181 80808080 79797979 78787878 77777777 76767676 75757575 74747474 73737373
97979797 96969696 95959595 94949494 93939393 92929292 91919191 90909090
89898989 88888888 87878787 86868686 85858585 84848484 83838383 82828282 8181
8181 80808080 79797979 78787878 77777777 76767676 75757575 74747474 73737373
97979797 96969696 95959595 94949494 93939393 92929292 91919191 90909090
89898989 88888888 87878787 86868686 85858585 84848484 83838383 82828282 81818181 80808080 79797979 78787878 77777777 76767676 75757575 74747474 73737373
97979797 96969696 95959595 94949494 93939393 92929292 91919191 90909090
89898989 88888888 87878787 86868686 85858585 84848484 83838383 82828282 8181
8181 80808080 79797979 78787878 77777777 76767676 75757575 74747474 73737373
SLOT # 6
SLOT # 5
OPTION F1 M15, M16, M18
L2L2L2L2L2L2L2L2L2L2L2L2
L3 Neutral L2L2
L1 Neutral L3
L2
L1 S2 (l) S1 (k)
L3 AC CURRENT
S2 (l) S1 (k)
L2 AC CURRENT
S2 (l) S1 (k)
L1 AC CURRENT
GENERATOR VOLTAGE
BUSBAR VOLTAGE
various inputs/ outputs
Supply
DC Power
The functionality of the boards in slot #2 and slot #6 is optional.
Page 7
PPM Installation Instructions
DEIF A/S Page 7 of 69
Slots #3, #4, #7 and #8
The functionality of the boards in slot #4 is optional.
72
SLOT # 4
727272 71717171 70707070 69696969 68686868 67676767 66666666 65656565 64646464 63636363 62626262 61616161 60606060 59595959 58585858 57575757 56565656 55555555 54545454 53535353 52525252 51515151 50505050 49494949 48484848 47474747 46464646 45454545 44444444 43434343 42424242 41414141 40404040 39393939 38383838 37373737
72727272 71717171 70707070 69696969 68686868 67676767 66666666 65656565 64646464 63636363 62626262 61616161 60606060 59595959 58
585858 57575757 56565656 55555555 54545454 53535353 52525252 51515151 50505050 49494949 48484848 47474747 46464646 45454545 44444444 43434343 42424242 41414141 40404040 39393939 38383838 37373737
72727272 71717171 70707070 69696969 68686868 67676767 66666666 65656565 64646464 63636363 62626262 61616161 60606060 59595959 58585858 57575757 56565656 55555555 54545454 53535353 52525252 51515151 50505050 49494949 48484848 47474747 46464646 45454545 44
444444 43434343 42424242 41414141 40404040 39393939 38383838 37373737
7272 71717171 70707070 69696969 68686868 67676767 66666666 65656565 64646464 63636363 62626262 61616161 60606060 59595959 58585858 57575757 56565656 55555555 54545454 53535353 52525252 51515151 50505050 49494949 48484848 47474747 46464646 45454545 44444444 43434343 42424242 41414141 40404040 39393939 38383838 37373737
Configurable
COMMON (TERM. 43-55)
SLOT # 3
RELAY 9
RELAY 8
RELAY 7
RELAY 6
133133133133 132132132132 131131131131 130130130130 129129129129 128128128128 127127127127 126126126126
114114114114 113113113113 112112112112 111111111111 110110110110 109109109109 108108108108 107107107107 106106106106 105105105105 104104104104 103103103103 102102102102 101101101101 100100100100
99999999
133133133133 132132132132 131131131131 130130130130 129129129129 128128128128 127127127127 126126126126
114114114114 113113113113 112112112112 111111111111 110110110110 109109109109 108108108108 107107107107 106106106106 105105105105 104104104104 103103103103 102102102102 101101101101 100100100100
99999999
133
133133133 132132132132 131131131131 130130130130 129129129129 128128128128 127127127127 126126126126
114114114114 113113113113 112112112112 111111111111 110110110110 109109109109 108108108108 107107107107 106106106106 105105105105 104104104104 103103103103 102102102102 101101101101 100100100100
99999999
133133133133 132132132132 131131131131 130130130130 129129129129 128128128128 127127127127 126126126126
114114114114 113113113113 112112112112 111111111111 110110110110 109109109109 108108108108 107107107107 106106106106 105105105105 104104104104 103103103103 102102102102 101101101101 100100100100
99999999
SLOT # 8
SLOT # 7
GND 4-20 mA Configurable GND HC2 variable load/Configurable GND
internal comm.
125125125125 124124124124 123123123123 122122122122 121121121121 120120120120 119119119119 118118118118 117117117117 116116116116 115115115115
125125125125 124124124124 123123123123 122122122122 121121121121 120120120120 119119119119 118118118118 117117117117 116116116116 115115115115
125125125125 124124124124 123123123123 122122122122 121121121121 120120120120 119119119119 118118118118 117117117117 116116116116 115115115115
125125125125 124124124124 123123123123 122122122122 121121121121 120120120120 119119119119 118118118118 117117117117 116116116116 115115115115
98
relay outputs
Lower
Raise
SPEED
Configurable
Start ACKN. HC 2/Configurable
Start ACKN. HC 1/Configurable
CB CLOSED
CB OPEN
Load dependent stop block
Configurable ALARM INHIBIT 2/Configurable ALARM INHIBIT 1/Configurable
binary optocoupler inputs
NOT USED!
REACTIVE (Q) LOAD SHARING
COMMON SET POINTS
ACTIVE (P) LOAD SHARING
-10..0..10 VDC
-5....0....5 VDC
CAN-HCAN-HCAN-HCAN-H
CAN-LCAN-LCAN-LCAN-L CAN-HCAN-HCAN-HCAN-H
CAN-LCAN-LCAN-LCAN-L
EMERGENCY STOPEMERGENCY STOPEMERGENCY STOPEMERGENCY STOP ConfigurableConfigurableConfigurableConfigurable
COMMONCOMMONCOMMONCOMMON
CAN-HCAN-HCAN-HCAN-H
CAN-LCAN-LCAN-LCAN-L CAN-HCAN-HCAN-HCAN-H
CAN-LCAN-LCAN-LCAN-L
EMERGENCY STOPEMERGENCY STOPEMERGENCY STOPEMERGENCY STOP ConfigurableConfigurableConfigurableConfigurable
COMMONCOMMONCOMMONCOMMON
CAN-HCAN-HCAN-HCAN-H
CAN-LCAN-LCAN-LCAN-L CAN-HCAN-HCAN-HCAN-H
CAN-LCAN-LCAN-LCAN-L
EMERGENCY STOPEMERGENCY STOPEMERGENCY STOPEMERGENCY STOP ConfigurableConfigurableConfigurableConfigurable
COMMONCOMMONCOMMONCOMMON
CAN-HCAN-HCAN-H
CAN-LCAN-LCAN-LCAN-L CAN-HCAN-HCAN-HCAN-H
CAN-LCAN-LCAN-LCAN-L
EMERGENCY STOPEMERGENCY STOPEMERGENCY STOPEMERGENCY STOP ConfigurableConfigurableConfigurableConfigurabl e/Shaft ( or Shore) mode
RPM PICKUP
COMMONCOMMONCOMMONCOMMON (TERM. 104-106)
REMOTE STARTREMOTE STARTREMOTE STARTREMOTE START RUNNING FEEDBACKRUNNING FEEDBACKRUNNING FEEDBACKRUNNING FEEDBACK READY FOR OPERATIONREADY FOR OPERATIONREADY FOR OPERATIONREADY FOR OPERATION
REMOTE STARTREMOTE STARTREMOTE STARTREMOTE START RUNNING FEEDBACKRUNNING FEEDBACKRUNNING FEEDBACKRUNNING FEEDBACK READY FOR OPERATIONREADY FOR OPERATIONREADY FOR OPERATIONREADY FOR OPERATION
REMOTE STARTREMOTE STARTREMOTE STARTREMOTE START RUNNING FEEDBACKRUNNING FEEDBACKRUNNING FEEDBACKRUNNING FEEDBACK READY FOR OPERATIONREADY FOR OPERATIONREADY FOR OPERATIONREADY FOR OPERATION
COMMON (TERM. 114-118) REMOTE STOP REMOTE STARTREMOTE STARTREMOTE STARTREMOTE START RUNNING FEEDBACKRUNNING FEEDBACKRUNNING FEEDBACKRUNNING FEEDBACK READY FOR OPERATIONREADY FOR OPERATIONREADY FOR OPERATIONREADY FOR OPERATION
RELAY 20
RELAY 19
RELAY 18
START PREPARE
STOP
START
Configurable/Split mode Configurable/Auto mode Configurable/Semi-auto mode
Configurable Configurable Configurable
binary optocoupler inputs
0,5.....70 VAC
10...10000 Hz
with wire break supervision
analogue transducer inputs
HC1 variable load/Configurable
Configurable (Relay 13)/Lower U (option D)
Configurable (Relay 12)/Raise U (option D)
HC 2 FIXED LOAD/Configurable
HC 1 FIXED LOAD/Configurable HC 2 CONNECTED/Configurable HC 1 CONNECTED/Configurable
HC 2 REQUEST/Configurable HC 1 REQUEST/Configurable
BLACKOUT
AVR
Not used
Not used
Not used Not used
Page 8
PPM Installation Instructions
DEIF A/S Page 8 of 69
Terminal strip description
Slot #1, power supply and binary I/O
For the relay outputs the following terms will be used:
NO means Normally Open NC means Normally Closed Com. means common terminal for the relay in question
Term. Function Technical data Description
1 +12/24V DC 12/24V DC
-25/+30%
Power supply
2 0V DC 3 NC Status relay Normally closed relay, processor/power supply status
supervision
4 Com. 24 V/1A 5 NO Relay 1 Configurable/Trip NEL 1 6 Com. 250V AC/8A 7 NC 8 NO Relay 2 Configurable/Trip NEL 2 9 Com. 250V AC/8A 10 NC 11 NO Relay 3 PMS alarm 12 Com. 250V AC/8A 13 NC 14 NO Relay 4 CB OFF
Open breaker (deload)/trip
15 Com. 250V AC/8A 16 NC 17 NO Relay 5 CB ON
Close breaker (synchronising)
18 Com. 250V AC/8A 19 NC 20 Open collector 1 Transistor out configurable as standard relay output (relay number
26)
21 Open collector 2 Transistor out configurable as standard relay output (relay number
27) 22 Com. Common Common terminal for terminals 20 and 21 23 Binary input Optocoupler Configurable/Secured mode ON 24 Binary input Optocoupler Configurable/Secured mode OFF
25 Binary input Optocoupler Shore connection breaker position OFF
26 Binary input Optocoupler Forced switchboard control 27 Binary input Optocoupler PMS control 28 Com. Common Common for terminals 23-27
The power supply must be protected with a 1A fuse.
Page 9
PPM Installation Instructions
DEIF A/S Page 9 of 69
Slot #2, external communication (option)
Option H2 (RS485 Modbus RTU).
Term. Function Description
29 DATA + (A) Modbus RTU, RS485 30 Not used 31 DATA - (B) 32 Not used 33 DATA + (A) 34 Not used 35 DATA - (B) 36 Not used
The serial communication line should be terminated between DATA + and DATA - with a resistor equal to the cable impedance.
Slot #3, binary I/O
Term. Function Technical data Description
37 -5…0…5V DC Analogue I/O Active load sharing line 38 Com. Common Common for load sharing lines 39 -5…0…5V DC Analogue I/O Reactive load sharing 40 -10…0…10V DC Analogue input
NOT USED
41 Com. Common 42 -10…0…10V DC Analogue input 43 Binary input Optocoupler Blackout input from external relay (all breakers in
position OFF) 44 Binary input Optocoupler Heavy consumer 1 request/configurable 45 Binary input Optocoupler Heavy consumer 2 request/configurable 46 Binary input Optocoupler Heavy consumer 1 connected/configurable 47 Binary input Optocoupler Heavy consumer 2 connected/configurable 48 Binary input Optocoupler Heavy consumer 1 fixed load/configurable 49 Binary input Optocoupler Heavy consumer 2 fixed load/configurable 50 Binary input Optocoupler Alarm Inhibit 1/configurable 51 Binary input Optocoupler Alarm Inhibit 2/configurable 52 Binary input Optocoupler Configurable. User programmable 53 Binary input Optocoupler Load dependent stop blocking 54 Binary input Optocoupler CB open 55 Binary input Optocoupler CB closed 56 Com. Common Common for terminals 43-55 57 NO Relay 6 Start acknowledge Heavy consumer 1/configurable 58 Com. 250V AC 8A 59 NO Relay 7 Start acknowledge Heavy consumer 2/configurable 60 Com. 250V AC 8A 61 NO Relay 8 Configurable. User programmable 62 Com. 250V AC 8A 63 NO Relay 9 Configurable. User programmable 64 Com. 250V AC 8A
Page 10
PPM Installation Instructions
DEIF A/S Page 10 of 69
Slot #4, GOV/AVR (standard)
GOV/AVR relay output card (GOV standard) (voltage control option D).
Term. Function Technical data Description
65 NO Relay 10
250V AC, 8A
Generator GOV
Increase frequency 66 Com. 67 NO Relay 11
250V AC, 8A
Generator GOV
Decrease frequency 68 Com. 69 NO Relay 12
250V AC, 8A
Generator AVR (option D)
Increase voltage/configurable
70 Com. 71 NO Relay 13
250V AC, 8A
Generator AVR (option D)
Decrease voltage/configurable
72 Com.
Option E1
GOV/AVR analogue output card.
Term. Function Description
65 Not used 66 +/-20 mA out Speed governor setpoint output 67 0 68 Not used 69 Not used 70 +/-20 mA out AVR voltage setpoint output 71 0 72 Not used
If necessary the current outputs can be converted to voltage using a resistor across the terminals (250 will convert the +/-20 mA into +/-5V DC).
Voltage control setpoint to AVR is an option. If a combination of analogue signals and relay signals is needed, then option EF4 is to be used.
Page 11
PPM Installation Instructions
DEIF A/S Page 11 of 69
Option EF2
Analogue speed governor output and one transducer output.
Term. Function Description
65 Not used 66 +/-20 mA Speed governor setpoint output 67 0 68 Not used 69 Not used 70 0(4) - 20 mA out Analogue output 3 71 0 72 Not used
These outputs are active outputs, meaning that they have an internal power supply. The outputs are galvanically separated from each other and from the rest of the unit. Via the display or the PC programming software individual outputs can be selected to represent any AC measuring value and related values e.g. power, power factor, frequency etc. Outputs can be selected to be either 0…20 mA or 4…20 mA in the PC utility software. If necessary, the current outputs can be converted to voltage using a resistor across the terminals (500 will convert the 0-20 mA into 0­10V DC).
Page 12
PPM Installation Instructions
DEIF A/S Page 12 of 69
Option EF4
Combination output for governor and AVR (option EF4).
Term. Function Description
65 ANA + Analogue +/-20 mA for GOV or AVR 66 ANA ­67 Not used 68 Not used 69 GOV relay up Relay output for GOV or AVR
Raise speed or voltage
70 GOV relay up 71 GOV relay down Relay output for GOV or AVR
Lower speed or voltage
72 GOV relay down
In the menu system it is possible to set the speed governor to either binary or analogue output. With option D this selection regarding AVR control is also possible.
On the PCB there is only one set of relay outputs and one analogue output. This means that if the relay outputs are used for speed control, then the analogue output will be used for the AVR, and vice versa.
Slot #5, AC measuring
Term. Function Technical data Description
73 I L1 s1 Generator current L1 1/5 A AC input 74 I L1 s2 75 I L2 s1 Generator current L2 1/5 A AC input 76 I L2 s2 77 I L3 s1 Generator current L3 1/5 A AC input 78 I L3 s2 79 U L1 Generator voltage L1 Max. 690V AC phase - phase value 80
Not used
81 U L2 Generator voltage L2 Max. 690V AC phase - phase value 82
Not used
83 U L3 Generator voltage L3 Max. 690V AC phase - phase value 84 U neutral Generator voltage
neutral
For land-based applications only
85 U L1 Bus voltage L1 Max. 690V AC phase - phase value 86
Not used
87 U L2 Bus voltage L2 Max. 690V AC phase - phase value 88 U neutral Bus voltage neutral For land-based applications only 89 U L3 Bus voltage L3 Max. 690V AC phase - phase value
Current inputs are galvanically separated. Max. 0.3 VA per phase. Voltage measurements are available (phase to phase) from 100V AC to 690V AC.
Page 13
PPM Installation Instructions
DEIF A/S Page 13 of 69
Slot #6, inputs/outputs (I/Os)
Option F1
Analogue transducer output.
Term. Function Description
90 Not used 91 0 Analogue output 1, selectable 92 0(4) - 20 mA out 93 Not used 94 Not used 95 0 Analogue output 2, selectable 96 0(4) - 20 mA out 97 Not used
These outputs are active outputs, meaning that they have an internal power supply. The outputs are galvanically separated from each other and from the rest of the unit. Via the display or the PC programming software individual outputs can be selected to represent any AC measuring value and related values e.g. power, power factor, frequency etc. Outputs can be selected to be either 0…20 mA or 4…20 mA in the PC utility software. If necessary, the current outputs can be converted to voltage using a resistor across the terminals (500 will convert the 0-20 mA into 0­10V DC).
Option M15
4 x analogue 4-20 mA inputs.
Term. Function Description
90 Input 90 common Common 91 Analogue input 91+ 4-20 mA in 92 Input 92 common Common 93 Analogue input 93+ 4-20 mA in 94 Input 94 common Common 95 Analogue input 95+ 4-20 mA in 96 Input 96 common Common 97 Analogue input 97+ 4-20 mA in
Option M16
7 x binary inputs.
Term. Function Description
90 Common Common 91 Digital input Configurable 92 Digital input Configurable 93 Digital input Configurable 94 Digital input Configurable 95 Digital input Configurable 96 Digital input Configurable 97 Digital input Configurable
Page 14
PPM Installation Instructions
DEIF A/S Page 14 of 69
Option M18
4 x relay outputs.
Term. Function Description
90 Relay output 14
250V AC, 8A max.
Configurable 91 92 Relay output 15
250V AC, 8A max.
Configurable 93 94 Relay output 16
250V AC, 8A max.
Configurable 95 96 Relay output 17
250V AC, 8A max.
Configurable 97
Slot #7, engine interface board
Term. Function Technical data Description/preconfiguration
98 Analogue input 1 + +4…20 mA in Heavy consumer 1 variable load/configurable 99 Analogue input 1 - GND 100 Analogue input 2 + +4…20 mA in Heavy consumer 2 variable load/configurable 101 Analogue input 2 - GND 102 Analogue input 3 + +4…20 mA in Configurable. User-programmable 103 Analogue input 3 - GND 104 Binary input With wire break
supervision Wire break resistor: 100
Configurable. User-programmable 105 Binary input Configurable. User-programmable 106 Binary input Configurable. User-programmable 107 Common Common terminals for 104-106 108 Tacho input 0.5…70V AC
10…10.000 Hz
RPM/magnetic pick-up/overspeed 109 Tacho input 110 Binary input Optocoupler Configurable/Semi-auto mode 111 Binary input Optocoupler Configurable/Auto mode 112 Binary input Optocoupler Configurable/Split mode 113 Binary input Optocoupler Configurable/Shaft (or Shore) mode 114 Binary input Optocoupler External emergency stop activated 115 Binary input Optocoupler Ready for operation (ON = ready, OFF = blocked) 116 Binary input Optocoupler Running feedback 117 Binary input Optocoupler Remote start (only active in SEMI-AUTO plant
mode) 118 Binary input Optocoupler Remote stop (only active in SEMI-AUTO plant
mode) 119 Com. Common Common for terminals 114-118 120 NO Relay 18
250V AC/8A
Start 121 Com. 122 NO Relay 19
250V AC/8A
Stop coil/running coil (selectable) 123 Com. 124 NO Relay 20
250V AC/8A
Start prepare 125 Com.
Page 15
PPM Installation Instructions
DEIF A/S Page 15 of 69
The engine interface board consists of configurable inputs and outputs. The configuration is performed via the PC utility software, and the default settings can be changed to the relevant settings. For input configuration, upload the parameter list from the unit and select the input in question. Then a configuration dialog box will appear, and the settings can be changed. The standard title (e.g. 4-20 mA in no. 1) can be changed, and the new title will also be shown in the display. The minimum and maximum values of the 4-20 mA input can be adjusted:
Value: Nominal heavy consumer power (e.g. 400 kW) Min.: Value corresponding to 4 mA (e.g. 0 kW) Max.: Value corresponding to 20 mA (e.g. 400 kW)
The inputs can be used as high or low alarms. As a ‘high alarm’ the alarm will appear, when the measured value is higher than the alarm limit, and as a ‘low alarm’ the alarm will appear, when the measured value is lower than the alarm limit.
Slot #8, internal communication
Term. Function Description
126 Not used CANbus communication line between the units
For internal use only!
127 Not used 128 Can-L 129 Not used 130 Can-H 131 Can-L 132 Not used 133 Can-H
Page 16
PPM Installation Instructions
DEIF A/S Page 16 of 69
Binary inputs
Term. Name Function
23 Configurable/Secured mode ON This input is programmable from the PC utility
software/Input for activating the secured mode (pulse signal)
24 Configurable/Secured mode OFF This input is programmable from the PC utility
software/Input for deactivating the secured mode (pulse signal)
25 Shore connection breaker position
OFF
The shore connection breaker is in position OFF. When the shore connection breaker is connected, the generator breaker ON sequence is blocked.
26 Forced switchboard control If the input is set, the entire system will be forced into
switchboard control. (Regulation is deactivated).
27 PMS control The unit is set to be in power management control or in
switchboard control.
43 Blackout Signal from an external relay. All generator breakers
are in position OFF. This signal is used for the blackout start sequence in case of missing power management.
44 HC 1 request/configurable
When this input is active, the heavy consumer has been requested for operation. The power management is calculating the power demand and starts the necessary number of diesel generators (not in SEMI­AUTO mode). The HC request information is also indicated at the AOP-2/Configurable. User-programmable.
45 HC 2 request/configurable
46 HC 1 connected/configurable The heavy consumer in question is in operation and
connected to the busbar/Configurable. User-programmable.
47 HC 2 connected/configurable
48 HC 1 fixed load/configurable
When this input is activated (ON), then the heavy consumer in question is using 100% of its load and 0% is reserved. A deactivated input (OFF) means that 0% of the load is used and 100% is reserved/ Configurable. User-programmable.
49 HC 2 fixed load/configurable
50 Alarm inhibit 1/configurable External input for inhibit of selected alarms/ Configur-
able. User-programmable.
51 Alarm inhibit 2/configurable External input for inhibit of selected alarms/ Configur-
able. User-programmable. 52 Configurable. User-programmable This input is programmable from the PC utility software. 53 Load dependent stop block The load dependent stop function is blocked when the
binary input is set. This will also be indicated at the
AOP-2. 54 CB open Breaker feedback signal. The connection breaker is in
position ON. 55 CB closed Breaker feedback signal. The connection breaker is in
position OFF. 104 Configurable. User-programmable This input is programmable from the PC utility software.
This input has wire break supervision and therefore
needs a potentially free contact. The wire break
resistor is 100 .
105 Configurable. User-programmable This input is programmable from the PC utility software.
This input has wire break supervision and therefore
needs a potentially free contact. The wire break
resistor is 100 .
Page 17
PPM Installation Instructions
DEIF A/S Page 17 of 69
106 Configurable. User-programmable This input is programmable from the PC utility software.
This input has wire break supervision and therefore
needs a potentially free contact. The wire break
resistor is 100 .
110 Configurable/Semi-auto mode This input is programmable from the PC utility
software/Input for activating the semi-auto mode (pulse
signal). 111 Configurable/Auto mode This input is programmable from the PC utility
software/Input for activating the auto mode (pulse
signal). 112 Configurable/Split mode This input is programmable from the PC utility
software/Input for activating the split mode (pulse
signal). 113 Configurable/Shaft (or shore) mode This input is programmable from the PC utility
software/Input for activating the shaft (or shore) mode
(pulse signal). 114 Emergency stop The emergency stop input has been activated.
The engine is shutting down. 115 Ready for operation The diesel engine is ready for operation. When this
input is OFF, the diesel engine is blocked for start/CB
ON. 116 Running feedback The diesel engine has achieved the running status =
ON. 117 Remote start Remote input for start + CB ON. (Only available in
SEMI-AUTO mode). 118 Remote stop Remote input for CB OFF + stop. (Only available in
SEMI-AUTO mode).
Analogue transducer inputs
Term. Name Function
98 HC 1 power feedback/configurable Analogue power feedback for heavy consumer no. 1
regarding the adjustable setpoint. 4..20 mA (0 kW…HC 1 max. kW)/Configurable. User-programmable.
100 HC 2 power feedback/configurable Analogue power feedback for heavy consumer no. 2
regarding to the adjustable setpoint. 4..20 mA (0 kW…HC 2 max. kW)/Configurable. User-programmable.
102 Configurable. User programmable Configurable analogue alarm input.
Adjustable setpoint (4..20 mA).
Page 18
PPM Installation Instructions
DEIF A/S Page 18 of 69
Relay outputs
Term. Name Function
3 Status relay The status relay on the power supply board is a normally closed
relay with the purpose of processor and power supply supervision.
4 5 Configurable/
Trip NEL 1/(RELAY 1)
Configurable. User-programmable/Trip of the NEL (Non Essential Load) group no. 1 due to measured underfrequency, overcurrent or push load on the busbar. The output can be selected to be normally open (NO, terminal 5-6) or normally closed (NC, terminal 6-7).
6 7
8 Configurable/
Trip NEL 2/(RELAY 2)
Configurable. User-programmable/Trip of the NEL (Non Essential Load) group no. 2 due to measured underfrequency, overcurrent or push load on the busbar. The output can be selected to be normally open (NO, terminal 8-9) or normally closed (NC, terminal 9-10).
9 10
11 PMS alarm
(RELAY 3)
A PMS alarm has been activated. All alarms in the system activate the PMS alarm output. The output will be reset when the alarm condition disappears The output can be selected to be normally open (NO, terminal 11-12) or normally closed (NC, terminal 12-13).
12 13
14 CB OFF
(RELAY 4)
Connection breaker OFF signal. When this output is active, the generator breaker will open. The output can be selected to be normally open (NO, terminal 14-15) or normally closed (NC, terminal 15-16).
15 16
17 CB ON
(RELAY 5)
Connection breaker ON signal. When this output is active, the generator breaker will close. The output can be selected to be normally open (NO, terminal 17-18) or normally closed (NC, terminal 18-19).
18 19
20 Configurable (RELAY
26)
Configurable digital output (transistor output type)
21 Configurable (RELAY
27)
Configurable digital output (transistor output type)
57 START ACKN. HC
1/configurable (RELAY 6)
The heavy consumer is ready for operation as long as this output is active. The available power on the busbar is above max. HC power Configurable. User-programmable.
58
59 START ACKN. HC
2/configurable (RELAY 7)
60
61 Configurable
(RELAY 8)
This output is user-programmable. 62 63 Configurable
(RELAY 9)
This output is user-programmable. 64 65 Increase of speed
(RELAY 10)
Increase of speed. The signal is connected to the speed governor. A
speed droop of 4% (+/-2%) has to be adjusted in the speed
governor.
66
67 Decrease of speed
(RELAY 11)
Decrease of speed. The signal is connected to the speed governor.
A speed droop of 4% (+/-2%) has to be adjusted in the speed
governor.
68
69 Increase of voltage
(Option D)/configurable (RELAY 12)
Increase of voltage. The signal is connected to the AVR. A voltage
droop of 4% (+/-2%) has to be adjusted in the AVR/Configurable.
User-programmable.
70
71 Decrease of voltage
(Option D)/configurable (RELAY 13)
Decrease of voltage. The signal is connected to the AVR. A voltage
droop of 4% (+/-2%) has to be adjusted in the AVR/Configurable.
User-programmable.
72
120 START
(RELAY 18)
Start output to the diesel engine is activated = ON. 121
122 STOP Stop output to the diesel engine is activated. Stop coil or running
Page 19
PPM Installation Instructions
DEIF A/S Page 19 of 69
123 (RELAY 19)
coil can be selected.
124 START PREPARE
(RELAY 20)
The start prepare output is activated, before the start output is
activated. This could be preglow or preheating of the engine.
125
Page 20
PPM Installation Instructions
DEIF A/S Page 20 of 69
DG unit without PMS processor
Terminal strip overviews
Slots #1, #2, #5 and #6
The functionality of the boards in slot #2 and slot #6 is optional.
36
SLOT # 2
external comm.
OPTION H2
363636 35353535 34343434 33333333 32323232 31313131 30303030 29292929 28282828 27272727 26262626 25252525 24242424 23232323 22222222 21212121 20202020 19191919 18181818 17171717 16161616 15151515 14141414 13131313 12121212 11111111 10101010
9999 8888 7777 6666 5555 4444 3333 2222 1111
36363636 35353535 34343434 33333333 32323232 31313131 30303030 29292929 28282828 27272727 26262626 25252525 24
242424 23232323 22222222 21212121 20202020 19191919 18181818 17171717 16161616 15151515 14141414 13131313 12121212 11111111 10101010
9999 8888 7777 6666 5555 4444 3333 2222 1111
36363636 35353535 34343434 33333333 32323232 31313131 30303030 29292929 28282828 27272727 26262626 25252525 24242424 23232323 22222222 21212121 20202020 19191919 18181818 17171717 16161616 15151515 14141414 13131313 12121212 11111111 10
101010
9999 8888 7777 6666 5555 4444 3333 2222 1111
36363636 35353535 34343434 33333333 32323232 31313131 30303030 29292929 28282828 27272727 26262626 25252525 24242424 23232323 22222222 21212121 20202020 19191919 18181818 17171717 16161616 15151515 14141414 13131313 12121212 11111111 10101010
9999 8888 7777 6666 5555 4444 3333 2222 1111
COMMON (TERM. 23-27)
PMS CONTROL
Configurable
Configurable
Configurable
Configurable
COMMON (TERM. 20-21)
Configurable (Relay 26)
Configurable (Relay 27)
binary optocoupler
SLOT # 1
inputs
CB ON
Sync.
transistor output
relay output
CB OFF
Open breaker
RELAY 4
PMS
Alarm
RELAY 3
RELAY 2
RELAY 1
STATUS
relay
97979797 96969696 95959595 94949494 93939393 92929292 91919191 90909090
89898989 88888888 87878787 86868686 85858585 84848484 83838383 82828282 81818181 80808080 79797979 78787878 77777777 76767676 75757575 74747474 73737373
97979797 96969696 95959595 94949494 93939393 92929292 91919191 90909090
89898989 88888888 87878787 86868686 85858585 84848484 83838383 82828282 8181
8181 80808080 79797979 78787878 77777777 76767676 75757575 74747474 73737373
97979797 96969696 95959595 94949494 93939393 92929292 91919191 90909090
89898989 88888888 87878787 86868686 85858585 84848484 83838383 82828282 81818181 80808080 79797979 78787878 77777777 76767676 75757575 74747474 73737373
97979797 96969696 95959595 94949494 93939393 92929292 91919191 90909090
89898989 88888888 87878787 86868686 85858585 84848484 83838383 82828282 8181
8181 80808080 79797979 78787878 77777777 76767676 75757575 74747474 73737373
SLOT # 6
SLOT # 5
OPTION F1 M15, M16, M18
L2L2L2L2L2L2L2L2L2L2L2L2
L3 Neutral L2L2
L1 Neutral L3
L2
L1 S2 (l) S1 (k)
L3 AC CURRENT
S2 (l) S1 (k)
L2 AC CURRENT
S2 (l) S1 (k)
L1 AC CURRENT
GENERATOR VOLTAGE
BUSBAR VOLTAGE
various inputs/ outputs
Supply
DC Power
Configurable/Trip NEL2
Configurable/Trip NEL1
Page 21
PPM Installation Instructions
DEIF A/S Page 21 of 69
Slots #3, #4, #7 and #8
The functionality of the boards in slot #4 is optional.
Page 22
PPM Installation Instructions
DEIF A/S Page 22 of 69
Terminal strip description
Slot #1, power supply and binary I/O
For the relay outputs the following terms will be used:
NO means Normally Open NC means Normally Closed Com. means common terminal for the relay in question
Term. Function Technical data Description
1 +12/24V DC 12/24V DC
-25/+30%
Power supply
2 0V DC 3 NC Status relay Normally closed relay, processor/power supply status
supervision
4 Com. 24 V/1A 5 NO Relay 1 Configurable/Trip NEL 1 6 Com. 250V AC/8A 7 NC 8 NO Relay 2 Configurable/Trip NEL 2 9 Com. 250V AC/8A 10 NC 11 NO Relay 3 PMS alarm 12 Com. 250V AC/8A 13 NC 14 NO Relay 4 CB OFF
Open breaker (deload)/trip
15 Com. 250V AC/8A 16 NC 17 NO Relay 5 CB ON
Close breaker (synchronising)
18 Com. 250V AC/8A 19 NC 20 Open collector 1 Transistor out Configurable as standard relay output (relay number
26)
21 Open collector 2 Transistor out Configurable as standard relay output (relay number
27) 22 Com. Common Common terminal for terminals 20 and 21 23 Binary input Optocoupler Configurable. User-programmable 24 Binary input Optocoupler Configurable. User-programmable
25 Binary input Optocoupler Configurable. User-programmable 26 Binary input Optocoupler Configurable. User-programmable
27 Binary input Optocoupler PMS control 28 Com. Common Common for terminals 23-27
The power supply must be protected with a 1A fuse.
Page 23
PPM Installation Instructions
DEIF A/S Page 23 of 69
Slot #2, external communication (option)
Option H2 (RS485 Modbus RTU)
Term. Function Description
29 DATA + (A) Modbus RTU, RS485 30 Not used 31 DATA - (B) 32 Not used 33 DATA + (A) 34 Not used 35 DATA - (B) 36 Not used
The serial communication line should be terminated between DATA + and DATA - with a resistor equal to the cable impedance.
Slot #3, binary I/O
Term. Function Technical data Description
37 -5…0…5V DC Analogue I/O Active load sharing line 38 Com. Common Common for load sharing lines 39 -5…0…5V DC Analogue I/O Reactive load sharing 40 -10…0…10V DC Analogue input
NOT USED
41 Com. Common 42 -10…0…10V DC Analogue input 43 Binary input Optocoupler Blackout input from external relay. (All breakers in
position OFF) 44 Binary input Optocoupler Heavy consumer 1 request/configurable 45 Binary input Optocoupler Heavy consumer 2 request/configurable 46 Binary input Optocoupler Heavy consumer 1 connected/configurable 47 Binary input Optocoupler Heavy consumer 2 connected/configurable 48 Binary input Optocoupler Heavy consumer 1 fixed load/configurable 49 Binary input Optocoupler Heavy consumer 2 fixed load/configurable 50 Binary input Optocoupler Alarm inhibit 1, external input for inhibit of selected
alarms/configurable 51 Binary input Optocoupler Alarm inhibit 2, external input for inhibit of selected
alarms/configurable 52 Binary input Optocoupler Configurable. User-programmable 53 Binary input Optocoupler Configurable. User-programmable 54 Binary input Optocoupler CB open 55 Binary input Optocoupler CB closed 56 Com. Common Common for terminals 43-55 57 NO Relay 6 Start acknowledge heavy consumer 1/configurable 58 Com. 250V AC 8A 59 NO Relay 7 Start acknowledge heavy consumer 2/configurable 60 Com. 250V AC 8A 61 NO Relay 8 The relay is user configurable and can be used as
both alarm and limit relay
62 Com. 250V AC 8A 63 NO Relay 9 The relay is user configurable and can be used as
both alarm and limit relay
64 Com. 250V AC 8A
Page 24
PPM Installation Instructions
DEIF A/S Page 24 of 69
Slot #4, GOV/AVR (standard)
GOV/AVR relay output card (GOV standard) (voltage control option D).
Term. Function Technical data Description
65 NO Relay 10
250V AC, 8A
Generator GOV
Increase frequency 66 Com. 67 NO Relay 11
250V AC, 8A
Generator GOV
Decrease frequency 68 Com. 69 NO Relay 12
250V AC, 8A
Generator AVR (option D)
Increase voltage/configurable
70 Com. 71 NO Relay 13
250V AC, 8A
Generator AVR (option D)
Decrease voltage/configurable
72 Com.
Option E1
GOV/AVR analogue output card.
Term. Function Description
65 Not used 66 +/-20 mA out Speed governor setpoint output 67 0 68 Not used 69 Not used 70 +/-20 mA out AVR voltage setpoint output 71 0 72 Not used
If necessary the current outputs can be converted to voltage using a resistor across the terminals (250 will convert the +/-20 mA into +/-5V DC).
Voltage control setpoint to AVR is an option. If a combination of analogue signals and relay signals is needed, then option EF4 is to be used.
Page 25
PPM Installation Instructions
DEIF A/S Page 25 of 69
Option EF2
Analogue speed governor output and one transducer output.
Term. Function Description
65 Not used 66 +/-20 mA Speed governor setpoint output 67 0 68 Not used 69 Not used 70 0(4) - 20 mA out Analogue output 3 71 0 72 Not used
These outputs are active outputs, meaning that they have an internal power supply. The outputs are galvanically separated from each other and from the rest of the unit. Via the display or the PC programming software individual outputs can be selected to represent any AC measuring value and related values, e.g. power, power factor, frequency etc. Outputs can be selected to be either 0…20 mA or 4…20 mA in the PC utility software. If necessary the current outputs can be converted to voltage using a resistor across the terminals (500 will convert the 0-20 mA into 0­10V DC).
Option EF4
Combination output for governor and AVR (option EF4).
Term. Function Description
65 ANA + Analogue +/-20 mA for GOV or AVR 66 ANA ­67 Not used 68 Not used 69 GOV relay up Relay output for GOV or AVR.
Raise speed or voltage
70 GOV relay up 71 GOV relay down Relay output for GOV or AVR.
Lower speed or voltage
72 GOV relay down
In the menu system it is possible to set the speed governor to either binary or analogue output. With option D this selection regarding AVR control is also possible.
On the PCB there is only one set of relay outputs and one analogue output. This means that if the relay outputs are used for speed control, then the analogue output will be used for the AVR, and vice versa.
Page 26
PPM Installation Instructions
DEIF A/S Page 26 of 69
Slot #5, AC measuring
Term. Function Technical data Description
73 I L1 s1 Generator current L1 1/5 A AC input 74 I L1 s2 75 I L2 s1 Generator current L2 1/5 A AC input 76 I L2 s2 77 I L3 s1 Generator current L3 1/5 A AC input 78 I L3 s2 79 U L1 Generator voltage L1 Max. 690V AC phase - phase value 80
Not used
81 U L2 Generator voltage L2 Max. 690V AC phase - phase value 82
Not used
83 U L3 Generator voltage L3 Max. 690V AC phase - phase value 84 U neutral Generator voltage
neutral
For land-based applications only
85 U L1 Bus voltage L1 Max. 690V AC phase - phase value 86
Not used
87 U L2 Bus voltage L2 Max. 690V AC phase - phase value 88 U neutral Bus voltage neutral For land-based applications only 89 U L3 Bus voltage L3 Max. 690V AC phase - phase value
Current inputs are galvanically separated. Max. 0.3 VA per phase. Voltage measurements are available (phase to phase) from 100V AC to 690V AC.
Page 27
PPM Installation Instructions
DEIF A/S Page 27 of 69
Slot #6, optional I/Os
Option F1
Analogue transducer output.
Term. Function Description
90 Not used 91 0 Analogue output 1, selectable 92 0(4) - 20 mA out 93 Not used 94 Not used 95 0 Analogue output 2, selectable 96 0(4) - 20 mA out 97 Not used
These outputs are active outputs, meaning that they have an internal power supply. The outputs are galvanically separated from each other and from the rest of the unit. Via the display or the PC programming software individual outputs can be selected to represent any AC measuring value and related values, e.g. power, power factor, frequency etc. Outputs can be selected to be either 0…20 mA or 4…20 mA in the PC utility software. If necessary the current outputs can be converted to voltage using a resistor across the terminals (500 will convert the 0-20 mA into 0­10V DC).
Option M15
4 x analogue 4-20 mA inputs.
Term. Function Description
90 Input 90 common Common 91 Analogue input 91+ 4-20 mA in 92 Input 92 common Common 93 Analogue input 93+ 4-20 mA in 94 Input 94 common Common 95 Analogue input 95+ 4-20 mA in 96 Input 96 common Common 97 Analogue input 97+ 4-20 mA in
Option M16
7 x binary inputs.
Term. Function Description
90 Common Common 91 Digital input Configurable 92 Digital input Configurable 93 Digital input Configurable 94 Digital input Configurable 95 Digital input Configurable 96 Digital input Configurable 97 Digital input Configurable
Page 28
PPM Installation Instructions
DEIF A/S Page 28 of 69
Option M18
4 x relay outputs.
Term. Function Description
90 Relay output 14
250V AC, 8A max.
Configurable 91 92 Relay output 15
250V AC, 8A max.
Configurable 93 94 Relay output 16
250V AC, 8A max.
Configurable 95 96 Relay output 17
250V AC, 8A max.
Configurable 97
Slot #7, engine interface board
Term. Function Technical data Description/preconfiguration
98 Analogue input 1 + +4…20 mA in Heavy consumer 1 variable load/configurable 99 Analogue input 1 - GND 100 Analogue input 2 + +4…20 mA in Heavy consumer 2 variable load/configurable 101 Analogue input 2 - GND 102 Analogue input 3 + +4…20 mA in Configurable. User-programmable 103 Analogue input 3 - GND 104 Binary input With wire break
supervision Wire break resistor: 100
Configurable. User-programmable 105 Binary input Configurable. User-programmable 106 Binary input Configurable. User-programmable 107 Common Common terminals for 104-106 108 Tacho input 0.5…70V AC
10…10.000 Hz
RPM/magnetic pick-up/overspeed 109 Tacho input 110 Binary input Optocoupler Configurable. User-programmable 111 Binary input Optocoupler Configurable. User-programmable 112 Binary input Optocoupler Configurable. User-programmable 113 Binary input Optocoupler Configurable. User-programmable 114 Binary input Optocoupler External emergency stop activated 115 Binary input Optocoupler Ready for operation (ON = ready, OFF = blocked) 116 Binary input Optocoupler Running feedback 117 Binary input Optocoupler Remote start (only active in SEMI-AUTO plant
mode) 118 Binary input Optocoupler Remote stop (only active in SEMI-AUTO plant
mode) 119 Com. Common Common for terminals 114-118 120 NO Relay 18
250V AC/8A
Start 121 Com. 122 NO Relay 19
250V AC/8A
Stop coil/running coil (selectable) 123 Com. 124 NO Relay 20
250V AC/8A
Start prepare 125 Com.
Page 29
PPM Installation Instructions
DEIF A/S Page 29 of 69
The engine interface board consists of configurable inputs and outputs. The configuration is performed via the PC utility software, and the default settings can be changed to the relevant settings. For input configuration, upload the parameter list from the unit and select the input in question. Then a configuration dialog box will appear, and the settings can be changed. The standard title (e.g. 4-20 mA in no. 1) can be changed, and the new title will also be shown in the display. The minimum and maximum values of the 4-20 mA input can be adjusted:
Value: Nominal heavy consumer power (e.g. 400 kW) Min.: Value corresponding to 4 mA (e.g. 0 kW) Max.: Value corresponding to 20 mA (e.g. 400 kW)
The inputs can be used as high or low alarms. As a ‘high alarm’ the alarm will appear, when the measured value is higher than the alarm limit, and as a ‘low alarm’ the alarm will appear, when the measured value is lower than the alarm limit.
Slot #8, internal communication
Term. Function Description
126 Not used CANbus communication line between the units
For internal use only!
127 Not used 128 Can-L 129 Not used 130 Can-H 131 Can-L 132 Not used 133 Can-H
Page 30
PPM Installation Instructions
DEIF A/S Page 30 of 69
Binary inputs
Term. Name Function
23 Configurable. User-programmable This input is programmable from the PC utility software. 24 Configurable. User-programmable This input is programmable from the PC utility software. 25 Configurable. User-programmable This input is programmable from the PC utility software. 26 Configurable. User-programmable This input is programmable from the PC utility software. 27 PMS control The unit is set to be in power management control or in
switchboard control.
43 Blackout Signal from an external relay. All generator breakers
are in position OFF. This signal is used for the blackout start sequence in case of missing power management.
44 HC 1 request/configurable
When this input is active, the heavy consumer has been requested for operation. The power management is calculating the power demand and starts the necessary number of diesel generators (not in SEMI­AUTO mode). The HC request information is also indicated at the AOP.
45 HC 2 request/configurable
46 HC 1 connected/configurable The heavy consumer in question is in operation and
connected to the busbar/Configurable. User­programmable.
47 HC 2 connected/configurable
48 HC 1 fixed load/configurable
When this input is activated (ON), then the heavy consumer in question is using 100% of its load and 0% is reserved. A deactivated input (OFF) means that 0% of the load is used and 100% is reserved/Configurable. User-programmable.
49 HC 2 fixed load/configurable
50 Alarm inhibit 1/configurable External input for inhibit of selected
alarms/Configurable. User-programmable.
51 Alarm inhibit 2/configurable External input for inhibit of selected
alarms/Configurable. User-programmable. 52 Configurable. User-programmable This input is programmable from the PC utility software. 53 Configurable. User-programmable This input is programmable from the PC utility software. 54 CB open Breaker feedback signal. The connection breaker is in
position ON. 55 CB closed Breaker feedback signal. The connection breaker is in
position OFF. 104 Configurable. User-programmable This input is programmable from the PC utility software.
This input has wire break supervision and therefore
needs a potentially free contact. The wire break
resistor is 100 .
105 Configurable. User-programmable This input is programmable from the PC utility software.
This input has wire break supervision and therefore
needs a potentially free contact. The wire break
resistor is 100 .
106 Configurable. User-programmable This input is programmable from the PC utility software.
This input has wire break supervision and therefore
needs a potentially free contact. The wire break
resistor is 100 .
110 Configurable. User-programmable This input is programmable from the PC utility software. 111 Configurable. User-programmable This input is programmable from the PC utility software. 112 Configurable. User-programmable This input is programmable from the PC utility software. 113 Configurable. User-programmable This input is programmable from the PC utility software.
Page 31
PPM Installation Instructions
DEIF A/S Page 31 of 69
114 Emergency stop The emergency stop input has been activated.
The engine is shutting down. 115 Ready for operation The diesel engine is ready for operation. When this
input is OFF, the diesel engine is blocked for start/CB
ON. 116 Running feedback The diesel engine has achieved the running status =
ON. 117 Remote start Remote input for start + CB ON. (Only available in
SEMI-AUTO mode). 118 Remote stop Remote input for CB OFF + stop. (Only available in
SEMI-AUTO mode).
Analogue transducer inputs
Term. Name Function
98 HC 1 power feedback/configurable Analogue power feedback for heavy consumer no. 1
regarding the adjustable setpoint. 4..20 mA (0 kW…HC 1 max. kW/Configurable. User-programmable.
100 HC 2 power feedback/configurable Analogue power feedback for heavy consumer no. 2
regarding the adjustable setpoint. 4..20 mA (0 kW…HC 2 max. kW)/Configurable. User-programmable.
102 Configurable. User-programmable Configurable analogue alarm input.
Adjustable setpoint (4..20 mA).
Page 32
PPM Installation Instructions
DEIF A/S Page 32 of 69
Relay outputs
Term. Name Function
3 Status relay The status relay on the power supply board is a normally closed
relay with the purpose of processor and power supply supervision.
4 5 Configurable/
Trip NEL 1/(RELAY 1)
Configurable. User-programmable/Trip of the NEL (Non Essential Load) group no. 1 due to measured underfrequency, overcurrent or push load on the busbar. The output can be selected to be normally open (NO, terminal 5-6) or normally closed (NC, terminal 6-7).
6 7
8 Configurable/
Trip NEL 2/(RELAY 2)
Configurable. User-programmable/Trip of the NEL (Non Essential Load) group no. 2 due to measured underfrequency, overcurrent or push load on the busbar. The output can be selected to be normally open (NO, terminal 8-9) or normally closed (NC, terminal 9-10).
9 10
11 PMS alarm
(RELAY 3)
A PMS alarm has been activated. All alarms in the system activate the PMS alarm output. The output will be reset when the alarm condition disappears The output can be selected to be normally open (NO, terminal 11-12) or normally closed (NC, terminal 12-13).
12 13
14 CB OFF
(RELAY 4)
Connection breaker OFF signal. When this output is active, the generator breaker will open. The output can be selected to be normally open (NO, terminal 14-15) or normally closed (NC, terminal 15-16).
15 16
17 CB ON
(RELAY 5)
Connection breaker ON signal. When this output is active, the generator breaker will close. The output can be selected to be normally open (NO, terminal 17-18) or normally closed (NC, terminal 18-19).
18 19
20 Configurable (RELAY
26)
Configurable digital output (transistor output type)
21 Configurable (RELAY
27)
Configurable digital output (transistor output type)
57 START ACKN. HC 1/
configurable (RELAY 6)
The heavy consumer is ready for operation as long as this output is active. The available power on the busbar is above max. HC power/Configurable. User-programmable.
58
59 START ACKN. HC 2/
configurable (RELAY 7)
60
61 Configurable
(RELAY 8)
This output is user-programmable. 62 63 Configurable
(RELAY 9)
This output is user-programmable. 64 65 Increase of speed
(RELAY 10)
Increase of speed. The signal is connected to the speed governor. A
speed droop of 4% (+/-2%) has to be adjusted in the speed
governor.
66
67 Decrease of speed
(RELAY 11)
Decrease of speed. The signal is connected to the speed governor.
A speed droop of 4% (+/-2%) has to be adjusted in the speed
governor.
68
69 Increase of voltage
(Option D)/configurable (RELAY 12)
Increase of voltage. The signal is connected to the AVR. A voltage
droop of 4% (+/-2%) has to be adjusted in the AVR/Configurable.
User-programmable.
70
71 Decrease of voltage
(Option D)/configurable (RELAY 13)
Decrease of voltage. The signal is connected to the AVR. A voltage
droop of 4% (+/-2%) has to be adjusted in the AVR/Configurable.
User-programmable.
72
120 START
(RELAY 18)
Start output to the diesel engine is activated = ON. 121
122 STOP Stop output to the diesel engine is activated. Stop coil or running
Page 33
PPM Installation Instructions
DEIF A/S Page 33 of 69
123 (RELAY 19)
coil can be selected.
124 START PREPARE
(RELAY 20)
The start prepare output is activated, before the start output is
activated. This could be preglow or preheating of the engine.
125
Page 34
PPM Installation Instructions
DEIF A/S Page 34 of 69
5. Shaft generator I/Os
SG with fixed frequency
Terminal strip overviews
Slots #1, #2, #5 and #6
36
SLOT # 2
external comm.
OPTION H2
363636 35353535 34343434 33333333 32323232 31313131 30303030 29292929 28282828 27272727 26262626 25252525 24242424 23232323 22222222 21212121 20202020 19191919 18181818 17171717 16161616 15151515 14141414 13131313 12121212 11111111 10101010
9999 8888 7777 6666 5555 4444 3333 2222 1111
36363636 35353535 34343434 33333333 32323232 31313131 30303030 29292929 28282828 27272727 26262626 25252525 24
242424 23232323 22222222 21212121 20202020 19191919 18181818 17171717 16161616 15151515 14141414 13131313 12121212 11111111 10101010
9999 8888 7777 6666 5555 4444 3333 2222 1111
36363636 35353535 34343434 33333333 32323232 31313131 30303030 29292929 28282828 27272727 26262626 25252525 24242424 23232323 22222222 21212121 20202020 19191919 18181818 17171717 16161616 15151515 14141414 13131313 12121212 11111111 10
101010
9999 8888 7777 6666 5555 4444 3333 2222 1111
36363636 35353535 34343434 33333333 32323232 31313131 30303030 29292929 28282828 27272727 26262626 25252525 24242424 23232323 22222222 21212121 20202020 19191919 18181818 17171717 16161616 15151515 14141414 13131313 12121212 11111111 10101010
9999 8888 7777 6666 5555 4444 3333 2222 1111
COMMON (TERM. 23-27)
PMS CONTROL
Configurable
Configurable
Configurable
Configurable
COMMON (TERM. 20-21)
Configurable (Relay 26)
Configurable (Relay 27)
binary optocoupler
SLOT # 1
inputs
CB ON
Sync.
transistor output
relay output
CB OFF
Open breaker
RELAY 4
PMS
Alarm
RELAY 3
RELAY 2
RELAY 1
STATUS
relay
97979797 96969696 95959595 94949494 93939393 92929292 91919191 90909090
89898989 88888888 87878787 86868686 85858585 84848484 83838383 82828282 81818181 80808080 79797979 78787878 77777777 76767676 75757575 74747474 73737373
97979797 96969696 95959595 94949494 93939393 92929292 91919191 90909090
89898989 88888888 87878787 86868686 85858585 84848484 83838383 82828282 8181
8181 80808080 79797979 78787878 77777777 76767676 75757575 74747474 73737373
97979797 96969696 95959595 94949494 93939393 92929292 91919191 90909090
89898989 88888888 87878787 86868686 85858585 84848484 83838383 82828282 81818181 80808080 79797979 78787878 77777777 76767676 75757575 74747474 73737373
97979797 96969696 95959595 94949494 93939393 92929292 91919191 90909090
89898989 88888888 87878787 86868686 85858585 84848484 83838383 82828282 8181
8181 80808080 79797979 78787878 77777777 76767676 75757575 74747474 73737373
SLOT # 6
SLOT # 5
OPTION F1 M15, M16, M18
L2L2L2L2L2L2L2L2L2L2L2L2
L3 Neutral L2L2
L1 Neutral L3
L2
L1 S2 (l) S1 (k)
L3 AC CURREN T
S2 (l) S1 (k)
L2 AC CURREN T
S2 (l) S1 (k)
L1 AC CURREN T
GENERATOR VOLTAGE
BUSBAR VOLTAGE
various inputs/ outputs
Supply
DC Power
Configurable/Trip NEL2
Configurable/Trip NEL1
The functionality of the boards in slot #2 and slot #6 is optional.
Page 35
PPM Installation Instructions
DEIF A/S Page 35 of 69
Slots #3, #4, #7 and #8
Page 36
PPM Installation Instructions
DEIF A/S Page 36 of 69
Terminal strip description
Slot #1, power supply and binary I/O
For the relay outputs the following terms will be used:
NO means Normally Open NC means Normally Closed Com. means common terminal for the relay in question
Term. Function Technical data Description
1 +12/24V DC 12/24V DC (-25/+30%) Power supply 2 0V DC 3 NC Status relay Normally closed relay, processor/power supply
status supervision
4 Com. 24 V/1A 5 NO Relay 1 Configurable/Trip NEL 1 6 Com. 250V AC/8A 7 NC 8 NO Relay 2 Configurable/Trip NEL 2 9 Com. 250V AC/8A 10 NC 11 NO Relay 3 PMS alarm 12 Com. 250V AC/8A 13 NC 14 NO Relay 4 CB OFF
Open breaker (deload)/trip
15 Com. 250V AC/8A 16 NC 17 NO Relay 5 CB ON
Close breaker (synchronising)
18 Com. 250V AC/8A 19 NC 20 Open collector 1 Transistor out Relay 26, configurable 21 Open collector 2 Transistor out Relay 27, configurable 22 Com. Common Common terminal for terminals 20 and 21 23 Binary input Optocoupler Configurable. User-programmable 24 Binary input Optocoupler Configurable. User-programmable 25 Binary input Optocoupler Configurable. User-programmable 26 Binary input Optocoupler Configurable. User-programmable 27 Binary input Optocoupler PMS control 28 Com. Common Common for terminals 23-27
The power supply must be protected with a 1A fuse.
Page 37
PPM Installation Instructions
DEIF A/S Page 37 of 69
Slot #2, external communication (option)
Option H2 (RS485 Modbus RTU).
Term. Function Description
29 DATA + (A) Modbus RTU, RS485 30 Not used 31 DATA - (B) 32 Not used 33 DATA + (A) 34 Not used 35 DATA - (B) 36 Not used
The serial communication line should be terminated between DATA + and DATA - with a resistor equal to the cable impedance.
Slot #3, binary I/O
Term. Function Technical data Description
37 -5…0…5V DC Analogue I/O Active load sharing line 38 Com. Common Common for load sharing lines 39 -5…0…5V DC Analogue I/O Reactive load sharing
40 -10…0…10V DC Analogue input
Not used
41 Com. Common 42 -10…0…10V DC Analogue input 43 Binary input Optocoupler Configurable. User-programmable 44 Binary input Optocoupler Heavy consumer 1 request/configurable 45 Binary input Optocoupler Heavy consumer 2 request/configurable 46 Binary input Optocoupler Heavy consumer 1 connected/configurable 47 Binary input Optocoupler Heavy consumer 2 connected/configurable 48 Binary input Optocoupler Heavy consumer 1 fixed load/configurable 49 Binary input Optocoupler Heavy consumer 2 fixed load/configurable 50 Binary input Optocoupler Alarm inhibit 1, external input for inhibit of selected
alarms/configurable 51 Binary input Optocoupler Selection of PTH mode/Alarm Inhibit 2 52 Binary input Optocoupler Configurable. User-programmable 53 Binary input Optocoupler Configurable. User-programmable 54 Binary input Optocoupler CB open 55 Binary input Optocoupler CB closed 56 Com. Common Common for terminals 43-55
57 NO Relay 6 Start acknowledge heavy consumer 1/configurable 58 Com. 250V AC 8A 59 NO Relay 7 Start acknowledge heavy consumer 2/configurable 60 Com. 250V AC 8A 61 NO Relay 8 Configurable. User-programmable 62 Com. 250V AC 8A 63 NO Relay 9 Configurable. User-programmable 64 Com. 250V AC 8A
Page 38
PPM Installation Instructions
DEIF A/S Page 38 of 69
Slot #4, not used
Slot #5, AC measuring
Term. Function Technical data Description
73 I L1 s1 Generator current L1 1/5 A AC input 74 I L1 s2 75 I L2 s1 Generator current L2 1/5 A AC input 76 I L2 s2 77 I L3 s1 Generator current L3 1/5 A AC input 78 I L3 s2 79 U L1 Generator voltage L1 Max. 690V AC phase - phase value 80 Not used 81 U L2 Generator voltage L2 Max. 690V AC phase - phase value 82 Not used 83 U L3 Generator voltage L3 Max. 690V AC phase - phase value 84 U neutral Generator voltage
neutral
For land based applications only
85 U L1 Bus voltage L1 Max. 690V AC phase - phase value 86 Not used 87 U L2 Bus voltage L2 Max. 690V AC phase - phase value 88 U neutral Bus voltage neutral For land based applications only 89 U L3 Bus voltage L3 Max. 690V AC phase - phase value
Current inputs are galvanically separated. Max. 0.3 VA per phase. Voltage measurements are available (phase to phase) from 100V AC to 690V AC.
Page 39
PPM Installation Instructions
DEIF A/S Page 39 of 69
Slot #6, optional I/Os
Option F1
Analogue transducer output.
Term. Function Description
90 Not used 91 0 Analogue output 1, selectable 92 0(4) - 20 mA out 93 Not used 94 Not used 95 0 Analogue output 2, selectable 96 0(4) - 20 mA out 97 Not used
These outputs are active outputs, meaning that they have an internal power supply. The outputs are galvanically separated from each other and from the rest of the unit. Via the display or the PC programming software individual outputs can be selected to represent any AC measuring value and related values, e.g. power, power factor, frequency etc. Outputs can be selected to be either 0…20 mA or 4…20 mA in the PC utility software. If necessary the current outputs can be converted to voltage using a resistor across the terminals (500 will convert the 0-20 mA into 0­10V DC).
Option M15
4 x analogue 4-20 mA inputs.
Term. Function Description
90 Input 90 common Common 91 Analogue input 91+ 4-20 mA in 92 Input 92 common Common 93 Analogue input 93+ 4-20 mA in 94 Input 94 common Common 95 Analogue input 95+ 4-20 mA in 96 Input 96 common Common 97 Analogue input 97+ 4-20 mA in
Option M16
7 x binary inputs.
Term. Function Description
90 Common Common 91 Digital input Configurable 92 Digital input Configurable 93 Digital input Configurable 94 Digital input Configurable 95 Digital input Configurable 96 Digital input Configurable 97 Digital input Configurable
Page 40
PPM Installation Instructions
DEIF A/S Page 40 of 69
Option M18
4 x relay outputs.
Term. Function Description
90 Relay output 14
250V AC, 8A max.
Configurable 91 92 Relay output 15
250V AC, 8A max.
Configurable 93 94 Relay output 16
250V AC, 8A max.
Configurable 95 96 Relay output 17
250V AC, 8A max.
Configurable 97
Slot #7, engine interface board
Term. Function Technical data Description/preconfiguration
98 Analogue input 1 + +4…20 mA in Heavy consumer 1 variable load/configurable 99 Analogue input 1 - GND 100 Analogue input 2 + +4…20 mA in Heavy consumer 2 variable load/configurable 101 Analogue input 2 - GND 102 Analogue input 3 + +4…20 mA in Configurable. User-programmable 103 Analogue input 3 - GND 104 Binary input With wire break
supervision Wire break
resistor: 100
Configurable. User-programmable This input will need a potential free contact
105 Binary input Configurable. User-programmable
This input will need a potential free contact
106 Binary input Configurable. User-programmable
This input will need a potential free contact 107 Common Common terminals for 104-106 108 Tacho input 0.5…70V AC
10…10.000 Hz
RPM/magnetic pick-up/overspeed 109 Tacho input 110 Binary input Optocoupler Configurable. User-programmable 111 Binary input Optocoupler Configurable. User-programmable 112 Binary input Optocoupler Configurable. User-programmable 113 Binary input Optocoupler Configurable. User-programmable 114 Binary input Optocoupler External emergency stop activated 115 Binary input Optocoupler Ready for operation (ON = ready, OFF = blocked) 116 Binary input Optocoupler Running feedback 117 Binary input Optocoupler Configurable. User-programmable 118 Binary input Optocoupler Configurable. User-programmable 119 Com. Common Common for terminals 114-118 120 NO Relay no. 18
250V AC/8A
Not used 121 Com. 122 NO Relay no. 19
250V AC/8A
Not used 123 Com. 124 NO Relay no. 20
250V AC/8A
Not used 125 Com.
Page 41
PPM Installation Instructions
DEIF A/S Page 41 of 69
The engine interface board consists of configurable inputs and outputs. The configuration is performed via the PC utility software, and the default settings can be changed to the relevant settings. For input configuration, upload the parameter list from the unit and select the input in question. Then a configuration dialog box will appear, and the settings can be changed. The standard title (e.g. 4-20 mA in no. 1) can be changed, and the new title will also be shown in the display. The minimum and maximum values of the 4-20 mA input can be adjusted:
Value: Nominal heavy consumer power (e.g. 400 kW) Min.: Value corresponding to 4 mA (e.g. 0 kW) Max.: Value corresponding to 20 mA (e.g. 400 kW)
The inputs can be used as high or low alarms. As a ‘high alarm’ the alarm will appear, when the measured value is higher than the alarm limit, and as a ‘low alarm’ the alarm will appear, when the measured value is lower than the alarm limit.
Slot #8, internal communication
Term. Function Description
126 Not used CANbus communication line between the units
For internal use only!
127 Not used 128 Can-L 129 Not used 130 Can-H 131 Can-L 132 Not used 133 Can-H
Page 42
PPM Installation Instructions
DEIF A/S Page 42 of 69
Binary inputs
Term. Name Function
23 Configurable. User-programmable This input is programmable from the PC utility
software.
24 Configurable. User-programmable This input is programmable from the PC utility
software.
25 Configurable. User-programmable This input is programmable from the PC utility
software.
26 Configurable. User-programmable This input is programmable from the PC utility
software.
27 PMS/SWBD control The unit is set to be in power management control or
in switchboard control.
43 Configurable This input is programmable from the PC utility
software.
44 HC 1 request/configurable
When this input is active, the heavy consumer has been requested for operation. The power manage­ment is calculating the power demand and starts the necessary number of diesel generators (not in SEMI­AUTO mode). The HC request information is also shown at the AOP/Configurable. User-programmable.
45 HC 2 request/configurable
46 HC 1 connected/configurable The heavy consumer in question is in operation and
connected to the busbar/Configurable. User­programmable.
47 HC 2 connected/configurable
48 HC 1 fixed load/configurable
When this input is activated (ON), then the heavy consumer in question is using 100% of its load and 0% is reserved. A deactivated input (OFF) means that 0% of the load is used and 100% is reserved/ Configurable. User-programmable.
49 HC 2 fixed load/configurable
50 Alarm inhibit 1/configurable External input for inhibit of selected
alarms/Configurable. User-programmable.
51 PTH/Alarm inhibit 2 PTH (Power Take Home) mode activation in-
put/External input for inhibit of selected alarms.
52 Configurable. User-programmable This input is programmable from the PC utility
software.
53 Configurable. User-programmable This input is programmable from the PC utility
software.
54 CB open Breaker feedback signal. The connection breaker is in
position ON.
55 CB closed Breaker feedback signal. The connection breaker is in
position OFF.
104 Configurable. User-programmable Configurable.
This input has wire break supervision and therefore needs a potentially free contact. The wire break resistor is 100 .
105 Configurable. User-programmable Configurable.
This input has wire break supervision and therefore needs a potentially free contact. The wire break resistor is 100 .
106 Configurable. User-programmable Configurable.
This input has wire break supervision and therefore needs a potentially free contact. The wire break resistor is 100 .
110 Configurable. User-programmable This input is programmable from the PC utility
software.
111 Configurable. User-programmable This input is programmable from the PC utility
software.
112 Configurable. User-programmable This input is programmable from the PC utility
Page 43
PPM Installation Instructions
DEIF A/S Page 43 of 69
software.
113 Configurable. User-programmable This input is programmable from the PC utility
software.
114 Emergency stop The emergency stop input has been activated. If
running on the SG, the CB for the SG will be tripped. If the TB is opened due to a blackout, then the mode will change to AUTO, and the generators will perform a blackout start.
115 Ready for operation The SG is ready for operation. When this input is
OFF, the SG is blocked for start/CB ON. 116 Running feedback The SG has achieved the running status = ON. 117 Configurable. User-programmable This input is programmable from the PC utility
software 118 Configurable. User-programmable This input is programmable from the PC utility
software
Analogue transducer inputs
Term. Name Function
98 HC 1 power feedback/configurable Analogue power feedback for heavy consumer no. 1
regarding the adjustable setpoint. 4..20 mA (0 kW…HC 1 max. kW)/Configurable. User-programmable.
100 HC 2 power feedback/configurable Analogue power feedback for heavy consumer no. 2
regarding the adjustable setpoint. 4..20 mA (0 kW…HC 2 max. kW)/Configurable. User-programmable.
102 Configurable Configurable analogue alarm input.
Adjustable setpoint. 4..20 mA.
Page 44
PPM Installation Instructions
DEIF A/S Page 44 of 69
Relay outputs
Term. Name Function
3 Status relay The status relay on the power supply board is a normally closed
relay with the purpose of processor and power supply supervision.
4 5 Configurable/
Trip NEL 1/(RELAY 1)
Configurable. User-programmable. Trip of the NEL (Non Essential Load) group no. 1 due to measured underfrequency, overcurrent or push load on the busbar. The output can be selected to be normally open (NO, terminal 5-6) or normally closed (NC, terminal 6-7).
6 7
8 Configurable/
Trip NEL 2 (RELAY 2)
Configurable. User-programmable. Trip of the NEL (Non Essential Load) group no. 2 due to measured underfrequency, overcurrent or push load on the busbar. The output can be selected to be normally open (NO, terminal 5-6) or normally closed (NC, terminal 6-7).
9 10
11 PMS alarm
(RELAY 3)
A PMS alarm has been activated. All alarms in the system activate the PMS alarm output. The output will be reset when the alarm condition disappears. The output can be selected to be normally open (NO, terminal 5-6) or normally closed (NC, terminal 6-7).
12 13
14 CB OFF
(RELAY 4)
Connection breaker OFF signal. When this output is active the generator breaker will open. The output can be selected to be normally open (NO, terminal 5-6) or normally closed (NC, terminal 6-
7).
15 16
17 CB ON
(RELAY 5)
Connection breaker ON signal. When this output is active, the generator breaker will close. The output can be selected to be normally open (NO, terminal 5-6) or normally closed (NC, terminal 6-
7).
18 19
20 Configurable (RELAY
26)
Configurable digital output (transistor output type)
21 Configurable (RELAY
27)
Configurable digital output (transistor output type)
57 START ACKN. HC 1/
configurable (RELAY 6)
The heavy consumer is ready for operation as long as this output is active. The available power on the busbar is above max. HC power/Configurable. User-programmable.
58
59 START ACKN. HC 2/
configurable (RELAY 7)
60
61 Configurable
(Relay 8)
The relay is user-configurable and can be used as both alarm and limit relay.
62 63 Configurable
(Relay 9)
The relay is user-configurable and can be used as both alarm and limit relay.
64 120 Configurable
(Relay 18)
The relay is user-configurable and can be used as both alarm and limit relay.
121 122 Configurable
(Relay 19)
The relay is user-configurable and can be used as both alarm and limit relay.
123 124 Configurable
(Relay 20)
The relay is user-configurable and can be used as both alarm and limit relay.
125
Page 45
PPM Installation Instructions
DEIF A/S Page 45 of 69
6. Bus tie breaker I/Os
Bus tie between DG and SG
Terminal strip overviews
Slots #1, #2, #5 and #6
36
SLOT # 2
external comm.
OPTION H2
363636 35353535 34343434 33333333 32323232 31313131 30303030 29292929 28282828 27272727 26262626 25252525 24242424 23232323 22222222 21212121 20202020 19191919 18181818 17171717 16161616 15151515 14141414 13131313 12121212 11111111 10101010
9999 8888 7777 6666 5555 4444 3333 2222 1111
36363636 35353535 34343434 33333333 32323232 31313131 30303030 29292929 28282828 27272727 26262626 25252525 24
242424 23232323 22222222 21212121 20202020 19191919 18181818 17171717 16161616 15151515 14141414 13131313 12121212 11111111 10101010
9999 8888 7777 6666 5555 4444 3333 2222 1111
36363636 35353535 34343434 33333333 32323232 31313131 30303030 29292929 28282828 27272727 26262626 25252525 24242424 23232323 22222222 21212121 20202020 19191919 18181818 17171717 16161616 15151515 14141414 13131313 12121212 11111111 10
101010
9999 8888 7777 6666 5555 4444 3333 2222 1111
36363636 35353535 34343434 33333333 32323232 31313131 30303030 29292929 28282828 27272727 26262626 25252525 24242424 23232323 22222222 21212121 20202020 19191919 18181818 17171717 16161616 15151515 14141414 13131313 12121212 11111111 10101010
9999 8888 7777 6666 5555 4444 3333 2222 1111
COMMON (TERM. 23-27)
PMS CONTROL
Configurable
Configurable
Configurable
Configurable
COMMON (TERM. 20-21)
Configurable (Relay 26)
Configurable (Relay 27)
binary optocouple
r
SLOT # 1
inputs
CB ON
Sync.
transisto
r
output
relay output
CB OFF
Open breake
r
RELAY 4
PMS
A
larm
RELAY 3
RELAY 2
RELAY 1
STATUS
relay
97979797 96969696 95959595 94949494 93939393 92929292 91919191 90909090
89898989 88888888 87878787 86868686 85858585 84848484 83838383 82828282 81818181 80808080 79797979 78787878 77777777 76767676 75757575 74747474 73737373
97979797 96969696 95959595 94949494 93939393 92929292 91919191 90909090
89898989 88888888 87878787 86868686 85858585 84848484 83838383 82828282 81818181 80808080 79797979 78787878 77777777 76767676 75
75
7575 74747474 73737373
97979797 96969696 95959595 94949494 93939393 92929292 91919191 90909090
89898989 88888888 87878787 86868686 85858585 84848484 83838383 82828282 81818181 80808080 79797979 78787878 77777777 76767676 75757575 74747474 73737373
97979797 96969696 95959595 94949494 93939393 92929292 91919191 90909090
89898989 88888888 87878787 86868686 85858585 84848484 83838383 82828282 81818181 80808080 79797979 78787878 77777777 76767676 7575
7575 74747474 73737373
SLOT # 6
SLOT # 5
OPTION F1 M15, M16, M18
L2L2L2L2L2L2L2L2L2L2L2L2
L3 Neutral L2L2
L1 Neutral L3
L2
L1 S2 (l) S1 (k)
L3 AC CURRENT
S2 (l) S1 (k)
L2 AC CURRENT
S2 (l) S1 (k)
L1 AC CURRENT
BUSBAR 2 VOLTAGE
BUSBAR 1 VOLTAGE
variou inputs/ outputs
Supply
DC Powe
r
Configurable
Configurable
The functionality of the boards in slot #2 and slot #6 is optional.
Page 46
PPM Installation Instructions
DEIF A/S Page 46 of 69
Slots #3, #4, #7 and #8
Page 47
PPM Installation Instructions
DEIF A/S Page 47 of 69
Terminal strip description
Slot #1, power supply and binary I/O
For the relay outputs the following terms will be used:
NO means Normally Open NC means Normally Closed Com. means common terminal for the relay in question
Term. Function Technical data Description
1 +12/24V DC 12/24V DC -25/+30% Power supply 2 0V DC 3 NC Status relay Normally closed relay, processor/power supply
status supervision
4 Com. 24 V/1A 5 NO Relay 1 Configurable. User-programmable 6 Com. 250V AC/8A 7 NC 8 NO Relay 2 Configurable. User-programmable 9 Com. 250V AC/8A 10 NC 11 NO Relay 3 PMS alarm 12 Com. 250V AC/8A 13 NC 14 NO Relay 4 CB OFF
Open breaker (deload)/trip
15 Com. 250V AC/8A 16 NC 17 NO Relay 5 CB ON
Close breaker (synchronising)
18 Com. 250V AC/8A 19 NC 20 Open collector 1 Transistor out Relay 26, configurable
Relay 27, configurable Common terminal for terminals 20 and 21
21 Open collector 2 Transistor out 22 Com. Common 23 Binary input Optocoupler Configurable. User-programmable 24 Binary input Optocoupler Configurable. User-programmable
25 Binary input Optocoupler Configurable. User-programmable 26 Binary input Optocoupler Configurable. User-programmable
27 Binary input Optocoupler PMS control 28 Com. Common Common for terminals 23-27
The power supply must be protected with a 1A fuse.
Page 48
PPM Installation Instructions
DEIF A/S Page 48 of 69
Slot #2, external communication (option)
Option H2 (RS485 Modbus RTU).
Term. Function Description
29 DATA + (A) Modbus RTU, RS485 30 Not used 31 DATA - (B) 32 Not used 33 DATA + (A) 34 Not used 35 DATA - (B) 36 Not used
The serial communication line should be terminated between DATA + and DATA - with a resistor equal to the cable impedance.
Slot #3, binary I/O
Term. Function Technical data Description
37 -5…0…5V DC Analogue I/O
Not used
38 Com. Common 39 -5…0…5V DC Analogue I/O 40 -10…0…10V DC Analogue input
Not used
41 Com. Common 42 -10…0…10V DC Analogue input 43 Binary input Optocoupler Configurable. User-programmable 44 Binary input Optocoupler Configurable. User-programmable 45 Binary input Optocoupler Configurable. User-programmable 46 Binary input Optocoupler Configurable. User-programmable 47 Binary input Optocoupler Configurable. User-programmable 48 Binary input Optocoupler Configurable. User-programmable 49 Binary input Optocoupler Configurable. User-programmable 50 Binary input Optocoupler Alarm inhibit 1, external input for inhibit of selected
alarms
51 Binary input Optocoupler Alarm inhibit 2, external input for inhibit of selected
alarms/configurable. 52 Binary input Optocoupler Configurable. User-programmable 53 Binary input Optocoupler Configurable. User-programmable 54 Binary input Optocoupler CB open 55 Binary input Optocoupler CB closed 56 Com. Common Common for terminals 43-55 57 NO Relay 6 User-configurable 58 Com. 250V AC 8A 59 NO Relay 7 User-configurable 60 Com. 250V AC 8A 61 NO Relay 8 User-configurable 62 Com. 250V AC 8A 63 NO Relay 9 User-configurable 64 Com. 250V AC 8A
Page 49
PPM Installation Instructions
DEIF A/S Page 49 of 69
Slot #4, not used
Slot #5, AC measuring
Term. Function Technical data Description
73 I L1 s1 Busbar current L1 1/5 A AC input 74 I L1 s2 75 I L2 s1 Busbar current L2 1/5 A AC input 76 I L2 s2 77 I L3 s1 Busbar current L3 1/5 A AC input 78 I L3 s2 79 U L1 Bus 1 voltage L1 Max. 690V AC phase - phase value 80 Not used 81 U L2 Bus 1 voltage L2 Max. 690V AC phase - phase value 82 Not used 83 U L3 Bus 1 voltage L3 Max. 690V AC phase - phase value 84 U neutral Not used 85 U L1 Bus voltage L1 Max. 690V AC phase - phase value 86 Not used 87 U L2 Bus voltage L2 Max. 690V AC phase - phase value 88 U neutral Not used 89 U L3 Bus voltage L3 Max. 690V AC phase - phase value
Current inputs are galvanically separated. Max. 0.3 VA per phase. Voltage measurements are available (phase to phase) from 100V AC to 690V AC.
Page 50
PPM Installation Instructions
DEIF A/S Page 50 of 69
Slot #6, optional I/Os
Option F1
Analogue transducer output.
Term. Function Description
90 Not used 91 0 Analogue output 1, selectable 92 0(4) - 20 mA out 93 Not used 94 Not used 95 0 Analogue output 2, selectable 96 0(4) - 20 mA out 97 Not used
These outputs are active outputs, meaning that they have an internal power supply. The outputs are galvanically separated from each other and from the rest of the unit. Via the display or the PC programming software individual outputs can be selected to represent any AC measuring value and related values, e.g. power, power factor, frequency etc. Outputs can be selected to be either 0…20 mA or 4…20 mA in the PC utility software. If necessary the current outputs can be converted to voltage using a resistor across the terminals (500 will convert the 0-20 mA into 0­10V DC).
Option M15
4 x analogue 4-20 mA inputs.
Term. Function Description
90 Input 90 common Common 91 Analogue input 91+ 4-20 mA in 92 Input 92 common Common 93 Analogue input 93+ 4-20 mA in 94 Input 94 common Common 95 Analogue input 95+ 4-20 mA in 96 Input 96 common Common 97 Analogue input 97+ 4-20 mA in
Option M16
7 x binary inputs.
Term. Function Description
90 Common Common 91 Digital input Configurable 92 Digital input Configurable 93 Digital input Configurable 94 Digital input Configurable 95 Digital input Configurable 96 Digital input Configurable 97 Digital input Configurable
Page 51
PPM Installation Instructions
DEIF A/S Page 51 of 69
Option M18
4 x relay outputs.
Term. Function Description
90 Relay output 14
250V AC, 8A max.
Configurable 91 92 Relay output 15
250V AC, 8A max.
Configurable 93 94 Relay output 16
250V AC, 8A max.
Configurable 95 96 Relay output 17
250V AC, 8A max.
Configurable 97
Slot #7, not used
Slot #8, internal communication
Term. Function Description
126 Not used CANbus communication line between the units
For internal use only!
127 Not used 128 Can-L 129 Not used 130 Can-H 131 Can-L 132 Not used 133 Can-H
Page 52
PPM Installation Instructions
DEIF A/S Page 52 of 69
Binary inputs
Term. Name Function
23 Configurable. User-programmable This input is programmable from the PC utility software. 24 Configurable. User-programmable Trip of breaker due to short circuit protection from
external device. 25 Configurable. User-programmable This input is programmable from the PC utility software. 26 Configurable. User-programmable This input is programmable from the PC utility software. 27 PMS control The unit is selected to be in power management control
or in switchboard control. 43 Configurable. User-programmable These inputs are programmable from the PC utility
software.
44 Configurable. User-programmable 45 Configurable. User-programmable 46 Configurable. User-programmable 47 Configurable. User-programmable 48 Configurable. User-programmable 49 Configurable. User-programmable 50 Alarm Inhibit 1/configurable External input for inhibit of selected alarms/configurable. 51 Alarm Inhibit 2/configurable External input for inhibit of selected alarms/configurable 52 Configurable. User-programmable These inputs are programmable from the PC utility
software.
53 Configurable. User-programmable
54 CB open Breaker feedback signal. The connection breaker is in
position ON. 55 CB closed Breaker feedback signal. The connection breaker is in
position OFF.
Page 53
PPM Installation Instructions
DEIF A/S Page 53 of 69
Relay outputs
Term. Name Function
3 Status relay The status relay on the power supply board is a normally closed
relay with the purpose of processor and power supply supervision.
4 5 Configurable
(RELAY 1)
The relay is user configurable and can be used as both alarm and limit relay.
6 7 8 Configurable
(RELAY 2)
9 10 11 PMS alarm
(RELAY 3)
A PMS alarm has been activated. All alarms in the system activate the PMS alarm output. The output will be reset when the alarm condition disappears. The output can be selected to be normally open (NO, terminal 5-6) or normally closed (NC, terminal 6-7).
12 13
14 CB OFF
(RELAY 4)
Connection breaker OFF signal. When this output is active, the generator breaker will open. The output can be selected to be normally open (NO, terminal 5-6) or normally closed (NC, terminal 6-7).
15 16
17 CB ON
(RELAY 5)
Connection breaker ON signal. When this output is active, the generator breaker will close. The output can be selected to be normally open (NO, terminal 5-6) or normally closed (NC, terminal 6-7).
18 19
20 Configurable (RELAY 26) Configurable digital output (transistor output type) 21 Configurable (RELAY 27) Configurable digital output (transistor output type) 57 Configurable
(Relay 6)
These relays are user-configurable and can be used as both alarm and limit relays.
58 59 Configurable
(Relay 7)
60 61 Configurable
(Relay 8)
62 63 Configurable
(Relay 9)
64
Page 54
PPM Installation Instructions
DEIF A/S Page 54 of 69
7. Additional operator panel
Installation of AOP-2
Display CANbus cable connection
The cable between the terminal blocks should be shielded twisted pair.
The maximum length of the CANbus line is 200 m.
A DC/DC converter for the DC supply voltage and 2 x 3 m cable with an RJ12 plug in one end and stripped wires in the other end is included in the AOP-2 delivery.
Page 55
PPM Installation Instructions
DEIF A/S Page 55 of 69
CAN ID configuration on AOP-2
The CAN ID for the AOP-2 can be changed by the following procedure:
1. Push button no. 7 and no. 8 at the same time to activate the CAN ID change menu, this will activate the LED for the present CAN ID number, and LED no. 16 will be flashing.
2. Use button no. 7 (increase) and button no. 8 (decrease) to change the CAN ID accord­ing to the table below.
3. Press button no. 6 to save the CAN ID and return to normal operation.
Selection of CAN ID:
CAN ID Indication of CAN ID selection
0 CANbus OFF: LED 16 flashes 1 LED 1 light steady + LED 16 flashes (default value)
2 LED 2 light steady + LED 16 flashes 3 LED 3 light steady + LED 16 flashes
4 LED 4 light steady + LED 16 flashes
5 LED 5 light steady + LED 16 flashes
Status relay
The status relay will activate approximately five seconds after power-up.
Page 56
PPM Installation Instructions
DEIF A/S Page 56 of 69
CAN ID configuration on display unit
The CANbus ID no. for the display unit of generator 1 (Master) has to be changed from ID no. 0 (default) to ID no. 1. To do this, press the three buttons left, up and right at the same time.
Then press the up button to change the ID no. from 0 to 1.
Acknowledge by pressing 'ENTER'. The display will then automatically reset.
Page 57
PPM Installation Instructions
DEIF A/S Page 57 of 69
8. Wirings
AC connections (3-phase)
The neutral line (N) connection is not necessary for correct measurement. 3­phase without neutral is also possible. The current transformer ground connection can be on s1 or s2 connection, whichever is preferred. Fuses: 2A slow-blow.
Page 58
PPM Installation Instructions
DEIF A/S Page 58 of 69
Internal CANbus wiring
The wiring for the internal CANbus communication between units is indicated in the illustration below.
Option H2, Modbus RTU
Connection with 2-wire screened cable (recommended):
Connect shield to ground at one end only. Shield ends must be insulated with tape or insulation tubing.
Use shielded twisted cable.
Not used
DATA -
(
B
)
COM
DATA +
(
A
)
Multi-line
29 30 31 32 33 34 35 36
Not used
Not used
DATA +
(
A
)
DATA -
(
B
)
Not used
DATA -
(
B
)
COM
DATA +
(
A
)
Multi-line
29 30 31 32 33 34 35 36
Not used
Not used
DATA +
(
A
)
DATA -
(
B
)
Not used
DATA -
(
B
)
COM
DATA +
(
A
)
Multi-line
29 30 31 32 33 34 35 36
Not used
Not used
DATA +
(
A
)
DATA -
(
B
)
PLC or other device
DATA -
(
B
)
COM
DATA +
(
A
)
133
120
131 130 128 133 131 130 128 133 131 130 128
120
Page 59
PPM Installation Instructions
DEIF A/S Page 59 of 69
Connection with 3-wire shielded cable:
This solution is only feasible if the COM line is insulated. Check PLC/other device before connecting. Non-insulated COM line may result in damage to the equipment.
Connect shield to ground at one end only. Shield ends must be insulated with tape or insulation tubing.
Use shielded twisted cable.
Normally, the Modbus does not need bias resistors (end terminators). These are only needed in case of very long lines and/or many nodes (>32) on the Modbus network. If bias resistors are needed, the calculation should be based on the following data:
- A line internal pull-up bias resistor: 22 k
- B line internal pull-down bias resistor: 22 k
- Receiver input sensitivity: +/-200 mV
- Receiver input impedance: 12 k
Cable: Belden 3105A or equivalent. 22 AWG (0.6 mm2) twisted pair, shielded, <40 m/m, min. 95% shield coverage.
PLC or other device
DATA -
(
B
)
COM
DATA +
(
A
)
Not used
DATA -
(
B
)
COM
DATA +
(
A
)
Multi-line
29 30 31 32 33 34 35 36
Not used
Not used
DATA +
(
A
)
DATA -
(
B
)
Not used
DATA -
(
B
)
COM
DATA +
(
A
)
Multi-line
29 30 31 32 33 34 35 36
Not used
Not used
DATA +
(
A
)
DATA -
(
B
)
Not used
DATA -
(
B
)
COM
DATA +
(
A
)
Multi-line
29 30 31 32 33 34 35 36
Not used
Not used
DATA +
(
A
)
DATA -
(
B
)
Page 60
PPM Installation Instructions
DEIF A/S Page 60 of 69
Load sharing lines
Screened, twisted cable is recommended to prevent disturbances on the load sharing lines.
Max. distance between units: 3 m.
Page 61
PPM Installation Instructions
DEIF A/S Page 61 of 69
Mechanical speed governor (standard)
The illustration below shows the necessary connections to carry out speed control using relay outputs.
In order to extend the lifetime of the internal relays and prevent unwanted switching noise, it is recommended to use free wheel diodes (1N4007), if a DC voltage is used for the regulation. If an AC voltage is used for the regulation, it is recommended to use a varistor. This applies to both pilot motors and external regulation relays.
AVR with relay outputs
Page 62
PPM Installation Instructions
DEIF A/S Page 62 of 69
Electronic speed governor
If necessary, the current outputs can be converted to voltage using a resistor across the terminals (250 will convert the +/-20 mA into +/-5V DC).
AVR with analogue outputs (requires option D)
If necessary, the current outputs can be converted to voltage using a resistor across the terminals (250 will convert the +/-20 mA into +/-5V DC).
For further information on how to connect the analogue output to the most common speed governors please refer to:
Application Notes, Interfacing DEIF equipment to governors and AVRs, document number 4189340149
at www.deif.com.
For further information on how to connect the analogue output to the most common AVRs please refer to:
Application Notes, Interfacing DEIF equipment to governors and AVRs, document number 4189340149
at www.deif.com.
Page 63
PPM Installation Instructions
DEIF A/S Page 63 of 69
Binary inputs
All binary inputs are 12/24V DC bi-directional optocoupler. Typical input is:
12/24V DC
Binary inputs with wire break supervision
The binary inputs with wire break supervision only need potential free contacts.
The binary inputs use fixed signals - they do not use pulse signals.
Page 64
PPM Installation Instructions
DEIF A/S Page 64 of 69
Analogue inputs
The analogue 0(4)...20 mA inputs are passive and require an external power supply:
or
Optocoupler outputs for external counter
+
-
- Transmitter
Inputs
24V DC supply
+
-
+
-
+ Transmitter _
Inputs
24V DC supply
+
-
PPU
+12/24V DC
OV DC
22 (COMMON)
20(kWh)
EXTERNAL COUNTER
0.5 uF
100V
Page 65
PPM Installation Instructions
DEIF A/S Page 65 of 69
9. General data
Technical specifications
Accuracy: Class 1.0, to IEC/EN 60688
Operating temperature: -25…70°C (-13...158°F)
(UL/cUL Listed: Max. surrounding air temp.: 55°C/131°F)
Storage temperature: -40…70°C (-40...158°F)
Climate: 97% RH to IEC 60068-2-30
Measuring voltage: 100-690V AC +/-20%
(UL/cUL Listed: 110-480V AC phase-phase)
Consumption: Max. 0.25 VA/phase
Measuring current: -/1 or -/5A AC
(UL/cUL Listed: From CTs 1-5A)
Consumption: Max. 0.3 VA/phase
Current overload: 4 x I
n
continuously
20 x I
n
, 10 sec. (max. 75A)
80 x I
n
, 1 sec. (max. 300A)
Measuring frequency: 30…70 Hz
Aux. supply: 18-36V DC Max. 11 W consumption
The aux. supply inputs are to be protected by a 2A slow blow fuse
(UL/cUL Listed: AWG 24)
Binary inputs: Optocoupler, bi-directional ON: 8…36V DC Impedance: 4.7 k OFF: <2V DC
Relay outputs: Electrical rating: 250V AC/30V DC, 5A (UL/cUL Listed: 250V AC/24V DC, 2A resistive load)
Thermal rating @ 50°C 2A: Continuously 4A: t
ON
= 5 sec., t
OFF
= 15 sec.
(Unit status output: 1A)
Open collector outputs: Supply 8…36V DC, max. 10 mA
Page 66
PPM Installation Instructions
DEIF A/S Page 66 of 69
Analogue inputs: -10…0…+10V DC Not galvanically separated Impedance: 100 k
(0)4…20 mA Impedance: 50 Not galvanically separated
Mounting: DIN-rail mounted or base mounted with six screws. DEIF recommends
base mounting for marine applications.
If DIN-rail mounted in marine applications, additional means
against excessive mechanical vibrations must be used.
Load sharing lines: -5…0…+5V DC Impedance: 23.5
Analogue outputs: 0(4)...20 mA and +/-25 mA Galvanically separated Active output (internal supply) Load max. 500
(UL/cUL Listed: Max. 20 mA output)
Safety: To EN 61010-1, installation category (overvoltage category) III, 600 V,
pollution degree 2
To UL 508 and CSA 22.2 no. 14-05, overvoltage category III, 300 V,
pollution degree 2
Galv. separation: Between AC voltage, AC current and other I/Os: 3250V AC, 50 Hz, 1 min.
Between analogue outputs and other I/Os: 500V DC, 1 min.
Between binary input groups and other I/Os: 500V DC, 1 min.
EMC/CE: To EN 61000-6-1/2/3/4 IEC 60255-26 IEC 60533 power distr. zone IACS UR E10 power distr. zone
Vibration: 3…13.2 Hz: 2 mmpp
13.2…100 Hz: 0.7 g To IEC 60068-2-6 & IACS UR E10
10…60 Hz: 0.15 mmpp 60…150 Hz: 1 g To IEC 60255-21-1 Response (class 2)
10…150 Hz: 2 g To IEC 60255-21-1 Endurance (class 2)
Shock (base mount): 10 g, 11 msec, half sine To IEC 60255-21-2 Response (class 2)
30 g, 11 msec, half sine To IEC 60255-21-2 Endurance (class 2)
50 g, 11 msec, half sine To IEC 60068-2-27
Page 67
PPM Installation Instructions
DEIF A/S Page 67 of 69
Bump: 20 g, 16 msec, half sine To IEC 60255-21-2 (class 2)
Material: All plastic materials are self-extinguishing according to UL94 (V1)
Plug connections: AC current: 0.2-4.0 mm
2
stranded wire (UL/cUL Listed: AWG 18)
AC voltage: 0.2-2.5 mm
2
stranded wire (UL/cUL Listed: AWG 20)
Relays: (UL/cUL Listed: AWG 22)
Other: 2.5 mm
2
multi stranded (UL/cUL Listed: AWG 24)
Display: 9-pole Sub-D female
PC: USB A-B
Ethernet: RJ45
Approvals: The PPM is approved by the major classification societies. Contact
DEIF for details
UL and cUL
UL markings: Wiring: Use 60/75°C copper conductors only
Mounting: For use on a flat surface of type 1 enclosure
Installation: To be installed in accordance with the NEC (US) or the CEC (Canada)
Governors: Multi-line 2 interfaces to all governors, including GAC, Barber-Colman,
Woodward and Cummins
See interfacing guide at www.deif.com
Weight: Main unit: 1.5 kg (3.40 lbs.) J1, cable 3 m: 0.2 kg (0.45 lbs.) Option J2: 0.4 kg (0.90 lbs.) Option J7: 0.2 kg (0.45 lbs.) Display: 0.4 kg (0.90 lbs.)
Protection: Unit: IP20 Display: IP52 (IP54 with gasket, option L)
(UL/cUL Listed: Type Complete Device, Open Type)
To IEC 529 and EN 60529
Page 68
PPM Installation Instructions
DEIF A/S Page 68 of 69
Unit dimensions
External 24V DC to 5V DC converter for the AOP-2
Page 69
PPM Installation Instructions
DEIF A/S Page 69 of 69
Panel cutout (in mm)
DEIF A/S reserves the right to change any of the above
Loading...