Deif Multi-line 2 Designers Reference Handbook

DEI
F
A/
S
4189340358K SW version 2.40.X
Designer’s Reference Handbook
Functional description
s
Display unit and menu structure
PI-controller
Procedure for parameter setup
Parameter list
DEIF A/S, Frisenborgvej 33 Tel.: +45 9614 9614, Fax: +45 9614 9615 DK-7800 Skive, Denmark E-mail: deif@deif.com, URL: www.deif.com
AGC Designer’s Reference Handbook
DEIF A/S Page 2 of 168
Table of contents
1.
ABOUT THIS DOCUMENT....................................................................................................4
GENERAL PURPOSE...................................................................................................................... 4
INTENDED USERS.......................................................................................................................... 4
CONTENTS/OVERALL STRUCTURE ..................................................................................................4
2. WARNINGS AND LEGAL INFORMATION ...........................................................................6
LEGAL INFORMATION AND RESPONSIBILITY.....................................................................................6
ELECTROSTATIC DISCHARGE AWARENESS .....................................................................................6
SAFETY ISSUES ............................................................................................................................ 6
DEFINITIONS ................................................................................................................................6
3. GENERAL PRODUCT INFORMATION.................................................................................7
INTRODUCTION .............................................................................................................................7
TYPE OF PRODUCT .......................................................................................................................7
OPTIONS......................................................................................................................................7
PC UTILITY SOFTWARE WARNING ..................................................................................................7
4. FUNCTIONAL DESCRIPTIONS ............................................................................................8
STANDARD FUNCTIONS ................................................................................................................. 8
TERMINAL STRIP OVERVIEW .......................................................................................................... 9
APPLICATIONS............................................................................................................................ 11
SINGLE-LINE DIAGRAMS ..............................................................................................................23
FLOWCHARTS............................................................................................................................. 26
SEQUENCES...............................................................................................................................41
5. DISPLAY UNIT AND MENU STRUCTURE ......................................................................... 50
DISPLAY UNIT.............................................................................................................................50
MENU STRUCTURE...................................................................................................................... 54
MODE OVERVIEW .......................................................................................................................61
MODE SELECTION .......................................................................................................................62
PASSWORD................................................................................................................................63
6. ADDITIONAL FUNCTIONS..................................................................................................65
START FUNCTIONS......................................................................................................................65
BREAKER SPRING LOAD TIME.......................................................................................................68
ALARM INHIBIT ............................................................................................................................69
ACCESS LOCK ............................................................................................................................77
SHORT-TIME PARALLEL ...............................................................................................................78
DIGITAL MAINS BREAKER CONTROL.............................................................................................. 79
TIME DEPENDENT START/STOP....................................................................................................80
RUNNING OUTPUT....................................................................................................................... 81
DERATE GEN-SET ....................................................................................................................... 81
IDLE RUNNING ............................................................................................................................ 84
MASTER CLOCK.......................................................................................................................... 89
BATTERY TEST ...........................................................................................................................90
FAIL CLASS ................................................................................................................................91
SERVICE TIMERS ........................................................................................................................93
WIRE BREAK DETECTION.............................................................................................................93
DIGITAL INPUTS ..........................................................................................................................95
VDO INPUTS ............................................................................................................................ 101
MANUAL GOVERNOR CONTROL .................................................................................................. 105
MANUAL GOVERNOR CONTROL FROM AN AOP ...........................................................................105
INPUT FUNCTION SELECTION ..................................................................................................... 106
LANGUAGE SELECTION..............................................................................................................106
AGC Designer’s Reference Handbook
DEIF A/S Page 3 of 168
TEXTS IN STATUS LINE .............................................................................................................. 109
SERVICE MENU......................................................................................................................... 112
EVENT LOG ..............................................................................................................................113
COUNTERS...............................................................................................................................114
M-LOGIC ..................................................................................................................................115
GSM COMMUNICATION .............................................................................................................117
USW COMMUNICATION............................................................................................................. 118
NOMINAL SETTINGS .................................................................................................................. 119
7. PI CONTROLLER ..............................................................................................................121
CONTROLLERS .........................................................................................................................121
PRINCIPLE DRAWING.................................................................................................................122
PROPORTIONAL REGULATOR .....................................................................................................123
RELAY CONTROL ...................................................................................................................... 127
8. SYNCHRONISATION.........................................................................................................130
DYNAMIC SYNCHRONISATION ....................................................................................................130
STATIC SYNCHRONISATION .......................................................................................................133
GB CLOSING BEFORE EXCITATION .............................................................................................135
SEPARATE SYNCHRONISING RELAY............................................................................................ 140
9. PROCEDURE FOR PARAMETER SETUP .......................................................................142
FINDING THE SELECTED PARAMETER .........................................................................................142
PARAMETER DESCRIPTIONS ......................................................................................................143
SETUP .....................................................................................................................................143
10. PARAMETER LIST.........................................................................................................144
PARAMETER TABLE DESCRIPTION.............................................................................................. 144
OVERVIEW LIST ........................................................................................................................ 146
PROTECTION ............................................................................................................................ 148
CONTROL................................................................................................................................. 148
INPUT/OUTPUT.......................................................................................................................... 152
SYSTEM ...................................................................................................................................161
COMMUNICATION SETUP ........................................................................................................... 167
POWER MANAGEMENT SETUP....................................................................................................167
JUMP MENUS ............................................................................................................................167
AGC Designer’s Reference Handbook
DEIF A/S Page 4 of 168
1. About this document
This chapter includes general user information about this handbook concerning the general purpose, the intended users and the overall contents and structure.
General purpose
This document is the Designer’s Reference Handbook for DEIF’s Automatic Gen-set Controller, the AGC. The document mainly includes functional descriptions, presentation of display unit and menu structure, information about the PI-controller, the procedure for parameter setup and complete standard parameter lists.
The general purpose of the Designer’s Reference Handbook is to provide useful overall information about the functionality of the unit and its applications. This handbook also offers the user the information he needs in order to successfully set up the parameters needed in his specific application.
Intended users
The handbook is mainly intended for the person responsible for the unit parameter setup. In most cases, this would be a panel builder designer. Naturally, other users might also find useful information in the handbook.
Contents/overall structure
The Designer’s Reference Handbook is divided into chapters and in order to make the structure of the document simple and easy to use, each chapter will begin from the top of a new page. The following will outline the contents of each of the chapters.
About this document
This first chapter includes general information about this handbook as a document. It deals with the general purpose and the intended users of the Designer’s Reference Handbook. Furthermore, it outlines the overall contents and structure of the document.
Warnings and legal information
The second chapter includes information about general legal issues and safety precautions relevant in the handling of DEIF products. Furthermore, this chapter will introduce note and warning symbols, which will be used throughout the handbook.
General product information
The third chapter will deal with the unit in general and its place in the DEIF product range.
Functional descriptions
This chapter will include functional descriptions of the standard functions as well as illustrations of relevant application types. Flowcharts and single-line representations will be used in order to simplify the information.
Please make sure to read this handbook before working with the Multi-line 2 controller and the gen-set to be controlled. Failure to do this could result in human injury or damage to the equipment.
AGC Designer’s Reference Handbook
DEIF A/S Page 5 of 168
Display unit and menu structure
This chapter deals with the display unit including the push-button and LED functions. In addition, the unit menu structure will be presented. Furthermore, the selection of unit mode and password will be illustrated.
Additional functions
This chapter describes the additional functions of the unit.
PI-controller
This chapter offers information about the PI-controller in the form of principle drawings and descriptions.
Synchronising
This chapter has detailed information about the unit’s dynamic and static synchronisation.
Procedure for parameter setup
This chapter deals with the procedure to be followed, when the parameters are set up or changed. By use of various illustrations this chapter will guide the user through the procedure for parameter setup step by step.
Parameter list
This chapter includes a complete standard parameter list for setup. Therefore, this chapter is to be used for reference, when information about specific parameters is needed.
AGC Designer’s Reference Handbook
DEIF A/S Page 6 of 168
2. Warnings and legal information
This chapter includes important information about general legal issues relevant in the handling of DEIF products. Furthermore, some overall safety precautions will be introduced and recommended. Finally, the highlighted notes and warnings, which will be used throughout this handbook, are presented.
Legal information and responsibility
DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how to install or operate the generator set controlled by the unit, the company responsible for the installation or the operation of the set must be contacted.
Electrostatic discharge awareness
Sufficient care must be taken to protect the terminals against static discharges during the installation. Once the unit is installed and connected, these precautions are no longer necessary.
Safety issues
Installing the unit implies work with dangerous currents and voltages. Therefore, the installation should only be carried out by authorised personnel who understand the risks involved in working with live electrical equipment.
Definitions
Throughout this document a number of notes and warnings will be presented. To ensure that these are noticed, they will be highlighted in order to separate them from the general text.
Notes
Warnings
The notes provide general information which will be helpful for the reader to bear in mind.
The warnings indicate a potentially dangerous situation which could result in death, personal injury or damaged equipment, if certain guidelines are not followed.
Be aware of the hazardous live currents and voltages. Do not touch any AC measurement inputs as this could lead to injury or death.
The units are not to be opened by unauthorised personnel. If opened anyway, the
warranty will be lost.
AGC Designer’s Reference Handbook
DEIF A/S Page 7 of 168
3. General product information
This chapter will deal with the unit in general and its place in the DEIF product range.
Introduction
The AGC is part of the DEIF Multi-line 2 product family. Multi-line 2 is a complete range of multi­function generator protection and control products integrating all the functions you need into one compact and attractive solution.
The concept of the AGC is to offer a cost-effective solution to gen-set builders, who need a flexible generator protection and control unit for medium to large gen-set applications. Being part of the Multi-line product family the standard functions can be supplemented with a variety of optional functions.
Type of product
The Automatic Gen-set Controller is a micro-processor based control unit containing all necessary functions for protection and control of a gen-set.
It contains all necessary 3-phase measuring circuits, and all values and alarms are presented on the LCD display
Options
The Multi-line 2 product range consists of different basic versions which can be supplemented with the flexible options needed to provide the optimum solution. The options cover e.g. various protections for generator, busbar and mains, voltage/VAr/PF control, various outputs, power management, serial communication, additional operator display, etc.
PC utility software warning
It is possible to remote control the gen-set from the PC utility software M­Vision or the Graphical Display Unit (GDU) by use of a modem. To avoid personal injury make sure that it is safe to remote control the gen-set.
A full options list is included in the data sheet, document no. 4921240257.
AGC Designer’s Reference Handbook
DEIF A/S Page 8 of 168
4. Functional descriptions
This chapter includes functional descriptions of standard functions as well as illustrations of the relevant application types. Flowcharts and single-line diagrams will be used in order to simplify the information.
Standard functions
In the following paragraphs the standard functions are listed.
Operation modes
Automatic Mains Failure
Island operation
Fixed power/base load
Peak shaving
Load take over
Mains power export
Engine control
Start/stop sequences
Fuel solenoid selection
Relay outputs for governor control
Protections (ANSI)
Overcurrent, 2 levels (51)
Reverse power (32)
4-20mA inputs
PT100 or VDO inputs
Digital inputs
Display
Prepared for remote mounting
Push-buttons for start and stop
Push-buttons for breaker operations
Status texts
M-logic
Simple logic configuration tool
Selectable input events
Selectable output commands
GSM-communication
SMS messages at all alarms
Dial up from PC utility software to control unit
AGC Designer’s Reference Handbook
DEIF A/S Page 9 of 168
Terminal strip overview
Slots #1, #2, #5 and #6
The terminal strip overview shows I/Os for selectable standard and optional hardware.
Refer to the data sheet for accurate information about possible configurations of the AGC.
Refer to the input/output lists in the installation instructions for detailed information about the I/Os of the specific options.
AGC Designer’s Reference Handbook
DEIF A/S Page 10 of 168
Slots #3, #4, #7 and #8
AGC Designer’s Reference Handbook
DEIF A/S Page 11 of 168
Applications
The unit can be used for the applications listed in the table below.
Application Comment
Automatic Mains Failure (no back sync.) Standard Automatic Mains Failure (with back sync.) Standard Island operation Standard Fixed power/base load Standard Peak shaving Standard Load take over Standard Mains power export (fixed power to mains) Standard Multiple gen-sets, load sharing Requires option G3 Multiple gen-sets, power management Requires option G5
Gen-set mode Running mode
Auto Semi Test Man Block Automatic Mains Failure (no back sync.) X X X X X Automatic Mains Failure (with back sync.) X X X X X Island operation X X X X Fixed power/base load X X X X X Peak shaving X X X X X Load take over X X X X X Mains power export X X X X X Multiple gen-sets, load sharing X X X X Multiple gen-sets, power management X X X X X
AMF (no back synchronisation)
Auto mode description The unit automatically starts the gen-set and switches to generator supply at a mains failure
after an adjustable delay time. It is possible to adjust the unit to change to gen-set operation in two different ways.
1. The mains breaker will be opened at gen-set start-up.
2. The mains breaker will remain closed, until the gen-set is running, and the gen-set voltage and frequency is OK.
In both cases, the generator breaker will be closed, when the generator voltage and frequency is OK, and the mains breaker is open.
When the mains returns, the unit will switch back to mains supply and cool down and stop the gen-set. The switching back to mains supply is done without back synchronisation, when the adjusted ‘mains OK delay’ has expired.
See mode overview in chapter 6 on page 61 for short description.
The flowcharts below illustrate the full functionality of the mentioned gen-set modes.
This section about applications is to be used for reference using the particular gen-set mode as starting point. It is not suitable for reading from beginning to end.
AGC Designer’s Reference Handbook
DEIF A/S Page 12 of 168
Semi-auto mode description When the generator breaker is closed, the unit will use the nominal frequency as the setpoint for
the speed governor. If AVR control (option D1) is selected, then the nominal voltage is used as setpoint.
Test mode description
Manual mode description
Block mode description
AMF (with back synchronisation)
Auto mode description The unit automatically starts the gen-set and switches to generator supply at a mains failure
after an adjustable delay time. It is possible to adjust the unit to change to gen-set operation in two different ways:
1. The mains breaker will be opened at gen-set start-up.
2. The mains breaker will remain closed until the gen-set is running and the gen-set voltage and frequency is OK.
In both cases, the generator breaker will be closed, when the generator voltage and frequency is OK, and the mains breaker is open.
When the mains returns, the unit will synchronise the mains breaker to the busbar, when the ‘mains OK delay’ has expired. Then the gen-set cools down and stops.
Semi-auto description When the generator breaker is closed and the mains breaker is opened, the unit will use the
nominal frequency as the setpoint for the speed governor. If AVR control (option D1) is selected, the nominal voltage is used as the setpoint.
When the generator is paralleled to the mains, the governor regulation will be active afterwards. It will use the setting ‘generator minimum load as the setpoint’ (menu 6523). If AVR control (option D1) is selected, then the setpoint will be the adjusted power factor (6550 Fixed power setpoint).
See general semi-auto mode description on page 19.
See general test mode description valid for all gen-set modes on page 20.
See general manual mode description valid for all gen-set modes on page 21.
See general block mode description valid for all gen-set modes on page 21.
The automatic mains failure mode can be combined with the short time parallel function. In that case, the generator breaker and the mains breaker will never be closed at the same time for a longer period than the adjusted ‘short time parallel’ time.
AGC Designer’s Reference Handbook
DEIF A/S Page 13 of 168
Test mode description
Manual mode description
Block mode description
Island operation
Auto mode description The unit automatically starts the gen-set and closes the generator breaker at a digital start
command. When the stop command is given, the generator breaker is tripped, and the gen-set will be stopped after a cooling-down period. The start and stop commands are used by activating and deactivating a digital input. If the time dependent start/stop commands are to be used, then the auto mode must also be used. In this case, the digital input ‘auto start/stop’ cannot
be used.
Semi-auto mode description When the generator breaker is closed, the unit will use the nominal frequency as setpoint for the
speed governor. If AVR control (option D1) is selected, the nominal voltage is used as setpoint.
Test mode description
Manual mode description
Block mode description
See general semi-auto mode description on page 19.
See general test mode description valid for all gen-set modes on page 20.
See general manual mode description valid for all gen-set modes on page 21.
See general block mode description valid for all gen-set modes on page 21.
See general semi-auto mode description on page 19.
See general test mode description valid for all gen-set modes on page 20.
See general manual mode description valid for all gen-set modes on page 21.
See general block mode description valid for all gen-set modes on page 21.
AGC Designer’s Reference Handbook
DEIF A/S Page 14 of 168
Fixed power/base load
Auto mode description The unit automatically starts the gen-set and synchronises to the mains, when the digital input
‘auto start/stop’ is activated. After the generator breaker closure, the unit ramps up the load to the setpoint level. When the stop command is given, the gen-set is deloaded and stopped after the cooling-down period. The start and stop commands are used by activating and deactivating a digital input. If the time dependent start/stop commands are to be used, then the auto mode must also be used. In this case, the digital input ‘auto start/stop’ cannot
be used.
Diagram, fixed power - principle
Semi-auto mode description When the generator breaker is closed and the mains breaker is opened, the unit will use the
nominal frequency as the setpoint for the speed governor. If AVR control (option D1) is selected, the nominal voltage is used as setpoint.
When the generator is paralleled to the mains, the generator power will be increased to the fixed power setpoint (6550 Fixed power setpoint). If AVR control (option D1) is selected, then the setpoint will be the adjusted power factor (6550 Fixed power setpoint).
Test mode description
Manual mode description
Block mode description
kW
Start signal
Stop signal
t
RAMP-UP
t
See general semi-auto mode description on page 19.
See general test mode description valid for all gen-set modes on page 20.
See general manual mode description valid for all gen-set modes on page 21.
See general block mode description valid for all gen-set modes on page 21.
AGC Designer’s Reference Handbook
DEIF A/S Page 15 of 168
Peak shaving
Auto mode description The gen-set will start at a predefined mains import level and run at a fixed minimum load, e.g.
10%. When the mains import increases above the maximum mains import setpoint, the gen-set will supply the extra load in order to maintain the mains import at the maximum import level.
When the load drops below the max. mains import setpoint, the gen-set will run at min. load again. When the mains import decreases below the stop setpoint, the gen-set will cool down and stop.
A 4-20mA transducer is used for indication of the power imported from the mains.
Diagram, peak shaving - example
Max. mains import level
Gen-set start level
Gen-set stop level
t
STOP
Gen-set minimum load
kW
Generator power
t
Mains power
Peak/total power
AGC Designer’s Reference Handbook
DEIF A/S Page 16 of 168
Semi-auto mode description When the generator breaker is closed and the mains breaker is opened, the unit will use the
nominal frequency as setpoint for the speed governor. If AVR control (option D1) is selected, the nominal voltage is used as setpoint.
When the generator is paralleled to the mains, the generator will be controlled according to the peak shaving setpoint. So the maximum mains import will not be exceeded in spite of the semi­auto mode. If AVR control (option D1) is selected, the setpoint is the adjusted power factor (6550 Fixed power setpoint).
Test mode description
Manual mode description
Block mode description
Load take over
Auto mode description Back synchronising ON
The purpose of the load take over mode is to transfer the load imported from the mains to the gen-set for operation on generator supply only.
When the start command is given, the gen-set will start and synchronise the generator breaker to the busbar that is being supplied by the mains. When the generator breaker is closed, the imported load is decreased (the power is being transferred to the gen-set), until the load is at the open breaker point. Then the mains breaker opens.
When the stop command is given, the mains breaker is synchronised to the busbar and after closure the gen-set is deloaded, cooled down and stopped.
See general semi-auto mode description on page 19.
See general test mode description valid for all gen-set modes on page 20.
See general manual mode description valid for all gen-set modes on page 21.
See general block mode description valid for all gen-set modes on page 21.
AGC Designer’s Reference Handbook
DEIF A/S Page 17 of 168
A 4-20mA transducer is used for indication of the power imported from the mains.
Diagram, load take over - example
Back synchronising OFF When the start command is given, the gen-set will start. When the frequency and voltage is OK, the mains breaker is opened and the generator breaker is closed. Now the generator supplies the load, until the stop command is given. Then the generator breaker opens and the mains breaker closes. The gen-set cools down and stops.
A 4-20mA transducer is used for indication of the power imported from the mains.
Semi-auto mode When the generator breaker is closed, and the mains breaker is opened, the unit will use the
nominal frequency as setpoint for the speed governor. If AVR control (option D1) is selected, the nominal voltage is used as setpoint.
When the generator is paralleled to the mains, it will be controlled, so the imported power from the mains will be kept at 0 kW. If AVR control (option D1) is selected, the setpoint is the adjusted power factor (6550 Fixed power setpoint).
kW
Start signal
Stop signal
Mains power Generator powe
r
MB opens
GB opens
t
The load take over mode can be combined with the short time parallel. In that case, the generator and the mains breakers will never be closed at the same time for a longer period than the adjusted ‘short time parallel’ time.
If the imported load is higher than the nominal gen-set an alarm appears, and the load take over sequence is paused.
If the imported load is higher than the nominal gen-set power, an alarm appears and the load take over sequence is paused.
See general semi-auto mode description on page 19.
AGC Designer’s Reference Handbook
DEIF A/S Page 18 of 168
Test mode description
Manual mode description
Block mode description
Mains power export (fixed power to mains)
Auto mode description The mains power export mode can be used to maintain a constant level of power through the
mains breaker. The power can be exported to the mains or imported from the mains, but always at a constant level.
The gen-set starts as a result of a digital start command. It synchronises to the mains and will start to export power to the mains. The amount of power exported or imported will be kept at a fixed level regardless of the load on the busbar (the factory).
The stop command will cause the gen-set to deload and trip the generator breaker. Afterwards, it will cool down and stop.
A 4-20mA transducer is used for indication of the power exported from the mains. The example below shows a situation where the setpoint is adjusted to exporting power to the mains.
Diagram, mains power export - example
See general test mode description valid for all gen-set modes on page 20.
See general manual mode description valid for all gen-set modes on page 21.
See general block mode description valid for all gen-set modes on page 21.
Mains power export setpoint
Ramp up
Ramp down
kW
t
Start si
g
nal
Stop si
g
nal
If a fixed level of imported power must be used, it is still the mains power export mode that must be selected! This mode covers import as well as export.
AGC Designer’s Reference Handbook
DEIF A/S Page 19 of 168
Semi-auto description When the generator breaker is closed and the mains breaker is opened, the unit will use the
nominal frequency as setpoint for the speed governor. If AVR control (option D1) is selected the nominal voltage is used as setpoint.
When the generator is paralleled to the mains, it will be controlled according to the mains power export setpoint. If AVR control (option D1) is selected, the setpoint is the adjusted power factor (6550 Fixed power setpoint).
Test mode description
Manual mode description
Block mode description
General semi-auto mode description
The unit can be operated in semi-automatic mode. Semi-auto means that the unit will not initiate any sequences automatically, as is the case with the auto mode. It will only initiate sequences, if external signals are given.
An external signal may be given in three ways:
1. Push-buttons on the display are used
2. Digital inputs are used
3. Modbus command.
Please notice that the set point of the mains power export can be adjusted to 0 kW. This means that the gen-set will be parallel to the mains but no power import or export.
See general semi-auto mode description on page 19.
See general test mode description valid for all gen-set modes on page 20.
See general manual mode description valid for all gen-set modes on page 21.
See general block mode description valid for all gen-set modes on page 21.
The standard AGC is only equipped with a limited number of digital inputs, please refer to page 95 in this document and the data sheet for additional information about availability.
AGC Designer’s Reference Handbook
DEIF A/S Page 20 of 168
When the gen-set is running in semi-auto mode, the unit will control the speed governor and the AVR, if option D1 is selected.
The following sequences can be activated in semi-auto:
Command Description Comment
Start The start sequence is initiated and continues until the gen-
set starts or the maximum number of start attempts has been reached. The frequency (and voltage) will be regulated to make the GB ready to close.
Stop The gen-set will be stopped. After disappearance of the
running signal, the stop sequence will continue to be active in the ‘extended stop time’ period. The gen-set is stopped without cooling-down time.
Close GB The unit will close the generator breaker, if the mains
breaker is open, synchronise and close the generator breaker, if the mains breaker is closed.
When AMF mode is selected, the unit will not regu­late after breaker closure.
Open GB The unit will ramp down and open the generator breaker at
the breaker open point, if the mains breaker is closed. The unit will open the generator breaker instantly, if the mains breaker is open or the gen-set mode is island mode.
Close MB The unit will close the mains breaker, if the generator
breaker is open, synchronise and close the mains breaker,
if the generator breaker is closed. Open MB The unit opens the mains breaker instantly. Manual GOV UP
The regulator is deactivated and the governor output is
activated as long as the GOV input is ON. Manual GOV DOWN
The regulator is deactivated and the governor output is
activated as long as the GOV input is ON. Manual AVR UP
The regulator is deactivated and the governor output is
activated as long as the AVR input is ON.
Option D1 is
required. Manual AVR DOWN
The regulator is deactivated and the governor output is activated as long as the AVR input is ON.
Option D1 is
required.
General test mode description
The test mode function is activated by selecting test with the MODE push-button on the display or by activating a digital input, if one of them is configured to ‘test’. The test mode will only test synchronising, if the ‘Sync. to mains’ function is enabled. If this is the case, the gen-set will start, and the unit will synchronise and close the generator breaker to let the gen-set run in parallel, until the test time expires. If the ‘Sync. to mains’ function is not activated, then the gen-set will start and run at the nominal frequency with the generator breaker open.
It is possible to manually increase and decrease the speed/voltage when semi­auto is selected. When the digital up/down input is activated, then the regulator is deactivated as long as the manual up/down inputs are activated.
Manual voltage control is option dependent (option D1).
AGC Designer’s Reference Handbook
DEIF A/S Page 21 of 168
The settings for the test function are set up in menu 6540 Test running
.
Setpoint: Load setpoint when paralleling to mains.
Timer: Engine run time during the test period
Return: When the test is completed, the unit will return to the selected mode
(semi-auto or auto).
General manual mode description
When manual mode is selected, the gen-set can be controlled with digital inputs. The following commands are possible:
Command Comment
Start Gen-set starts. Stop Gen-set opens GB and stops
without cooling-down.
Manual increase speed Unit gives increase signal to
speed governor.
Manual decrease speed Unit gives decrease signal to
speed governor.
Manual increase voltage Unit gives increase signal to
the AVR. (Option D1).
Manual decrease voltage Unit gives decrease signal to
the AVR. (Option D1).
General block mode description
When the block mode is selected, the unit is locked for certain actions. This means that it cannot start the gen-set or perform any breaker operations.
To change the running mode from the display, the user will be asked for a password, before the change can be made. It is not possible to select ‘block mode’, when running feedback is present.
Short time parallel is ignored in test mode.
Test mode cannot be used, if the gen-set is in island operation (gen-set mode selected to island mode).
It is not possible to open and close the generator breaker or the mains breaker in manual mode.
It is necessary to configure the digital inputs through the PC utility software to use the manual commands. The number of configurable digital inputs is option dependent.
MAN mode cannot be selected, when AUTO mode is selected. To go from AUTO to MAN it is necessary to go to SEMI-AUTO to make MAN available.
AGC Designer’s Reference Handbook
DEIF A/S Page 22 of 168
The purpose of the block mode is to make sure that the gen-set does not start for instance during maintenance work.
If the digital inputs are used to change the mode, then it is important to know that the input configured to block mode is a constant signal. So, when it is ON the unit is in a blocked state, and when it is OFF, it returns to the mode it was in before block mode was selected.
Alarms are not influenced by block mode selection.
The gen-set can be started from the local engine control panel, if such is installed. Therefore, DEIF recommends to avoid local cranking and starting of the gen-set.
If block mode is selected using the display after the digital block input is activated, the AGC will stay in block mode after the block input is deactivated. The block mode must now be changed using the display. The block mode can only be changed locally by display or digital input.
Before the running mode is changed it is important to check that persons are clear of the gen-set and that the gen-set is ready for operation.
AGC Designer’s Reference Handbook
DEIF A/S Page 23 of 168
Single-line diagrams
In the following, single-line diagrams illustrating the various applications are presented.
Automatic Mains Failure
Island operation
Fixed power/base load
Peak shaving
AGC Designer’s Reference Handbook
DEIF A/S Page 24 of 168
Load take over
Mains power export
Multiple gen-sets, load sharing
AGC Designer’s Reference Handbook
DEIF A/S Page 25 of 168
Multiple gen-sets, power management
Island mode application
Parallel to mains application
33
3 3
3
AGC Designer’s Reference Handbook
DEIF A/S Page 26 of 168
Flowcharts
Using flowcharts, the principles of the most important functions will be illustrated in the next sections. The functions included are:
Mode shift
MB open sequence
GB open sequence
Stop sequence
Start sequence
MB close sequence
GB close sequence
Fixed power
Load take over
Island operation
Peak shaving
Mains power export
Automatic Mains Failure
Test sequence
The flowcharts below are for guidance only. For illustrative purposes the flowcharts are simplified in some extent.
AGC Designer’s Reference Handbook
DEIF A/S Page 27 of 168
Mode shift
Start
Mode shift
enabled
Plant mode not
island and AMF
Yes
mains failure
Yes
initiate AMF
sequence
Yes
mains OK timer
timed out
initiate mains
return
sequence
Yes
END
No
No
No
No
MB close sequence
continue in
selected mode
AGC Designer’s Reference Handbook
DEIF A/S Page 28 of 168
MB open sequence
Start
MB closed
load take over
Yes
deload MB
Yes
load = 0
open MB
Yes
MB opened
alarm 'MB
open failure'
No
load too high
No
alarm
Yes
END
mains failure
No
No
No
Yes
AGC Designer’s Reference Handbook
DEIF A/S Page 29 of 168
GB open sequence
Start
stop conditions
OK
is GB closed
Yes
No
No
Soft open
Yes
failclass
shutdown
No
deload DG
Yes
load< open set
point
No
open GB
Yes
GB opened Alarm
No
end
Yes
ramp down
timer expired
Yes
No
AGC Designer’s Reference Handbook
DEIF A/S Page 30 of 168
Stop sequence
Start
st op
condi ti o
ns O K
GB open
seq O K
Yes
AUTO
mode
Yes
cool down timer run
out
Yes
run c oil
Yes
No
No
No
No
st op r elay
No
activate stop
relay
deact iv ate
'stop' relay
Yes
genset
st opped
alarm
No
end
Yes
AGC Designer’s Reference Handbook
DEIF A/S Page 31 of 168
Start sequence
Start
start condition
OK
start prepare
timer
Yes
No
No
Start relay ON
Yes
start relay ti m er
timeout
genset started
No No
run feedback
detected
Yes
off relay ON
Yes
stop relay ti m er
timed out
max start
attempts
Yes
No
No
Alarm
No
f/U OK
Yes
end
ready to close
GB
Yes
No
Start failure
alarm
Yes
AGC Designer’s Reference Handbook
DEIF A/S Page 32 of 168
MB close sequence
Start
is MB open
voltage on gen
No
GB closed
Yes
back sync ON
Yes
di rect cl ose OK
No
voltage on
mains/bus
No
Yes
Yes
No
GB open
sequence
No
syn c M B
Yes
synchronised
close MB
Yes
MB closed
end
Yes
close failure
alarm
No
sync timer
runout
No
No
alarm sync.
failure
Yes
alarm GB open
fail ure
No
Yes
AGC Designer’s Reference Handbook
DEIF A/S Page 33 of 168
GB close sequence
Start
is GB open
No
Start seq OK
Yes
No
DG freq mat ch
BB freq
tim e runout
No
direc t cl osing
OK
close GB
Yes
alarm sync
fail ure
Yes
GB clos ed alarm
No
end
Yes
single DG
applic ation
Yes
voltage on
busbar
No
island mode
Yes
voltage on bus
Yes
MB close
No
Yes Yes
All GBs OFF
No
TB Present
Yes
TB open
Yes
MB open
No
Sync GB
No
Yes
No
Yes
No
Yes
No
No
No
AGC Designer’s Reference Handbook
DEIF A/S Page 34 of 168
Fixed power
Start
Activate start
input
start sequence
GB close
sequenc e
ramp-up to
load set-point
deact ivate st art
input
operation
GB open
sequenc e
stop sequenc e
end
AGC Designer’s Reference Handbook
DEIF A/S Page 35 of 168
Load take over
Start
Activate start
input
start sequence
GB close sequence
Mains load
= 0 kW
ramp-up
genset load
No
MB open
sequence
Yes
deactivate start
input
MB close sequence
GB open
sequence
genset
operation
stop sequence end
AGC Designer’s Reference Handbook
DEIF A/S Page 36 of 168
Island operation
Start
start input
active
start sequence
GB close
sequence
operation
start input
deactivated
GB open
sequence
stop sequence
end
AGC Designer’s Reference Handbook
DEIF A/S Page 37 of 168
Peak shaving
Start
mains power
above start set
point
start sequence
GB close
sequence
operation:
produce power
above set point
mains power
below stop set
point
GB open
sequence
stop sequence
end
AGC Designer’s Reference Handbook
DEIF A/S Page 38 of 168
Mains power export
Start
activate start
input
start sequence
close GB
sequence
ramp up to
MPE set point
Operation
deactivate start
input
GB open
sequence
stop sequence
end
AGC Designer’s Reference Handbook
DEIF A/S Page 39 of 168
Automatic Mains Failure
Start
mains failure
No
#6595: start
eng+open MB
Yes
start sequence
No
open MB
Yes
open MB
start sequence
GB close sequence
GB close
sequence
mains ok
No
time out
Yes
MB close sequence
end
AGC Designer’s Reference Handbook
DEIF A/S Page 40 of 168
Test sequence
Start
select test
mode
start sequence
test timer
timer run out
engine running
No
freq/voltage OK
Yes
Sync of GB
allowed
Yes
stop sequence
Yes
engine stopped
return to
running mode,
menu 6544
No
end
sync GB
Yes
ramp up to P
set point
No
No
No
AGC Designer’s Reference Handbook
DEIF A/S Page 41 of 168
Sequences
The following contains information about the sequences of the engine, the generator breaker and, if installed, the mains breaker. These sequences are automatically initiated if the auto mode is selected, or if the commands are selected in the semi-auto mode.
In the semi-auto mode the selected sequence is the only sequence initiated (e.g. press the START push-button: The engine will start, but no subsequent synchronising is initiated).
The following sequences will be illustrated below:
START sequence
STOP sequence
Breaker sequences
If island operation is selected, the digital input ‘MB closed’ must NOT be activated with a 12/24 volt input signal. A ‘mains breaker failure’ will occur, if the wiring of the mains breaker feedback inputs is wrong.
START sequence
The drawings illustrate the start sequences of the gen-set.
Start sequence: Run coil
Start prepare
Crank
Running feedback
Run coil
Start attempts
1 2
tOFF tOFF
Refer to our ‘Application Notes’ for information about the required breaker wiring.
AGC Designer’s Reference Handbook
DEIF A/S Page 42 of 168
4 different types of running feedback can be used to detect if the motor is running. Refer to menu 4300 for selection of the running feedback type.
The running detection is made with a built-in safety routine. The running feedback selected in menu 4300 is the primary feedback. At all times all the types of running feedback is used for running detection. If for some reason the primary choice is not detecting any running feedback, the starter relay will stay activated for additionally 1 second. If a running feedback is detected based on one of the secondary choices, the gen-set will start. This way the gen-set will still be functional even though a tacho sensor is damaged or dirty.
As soon as the gen-set is running, no matter if the gen-set is started based on the primary or secondary feedback, the running detection will be made based on all 4 types.
The sequence is shown in the diagram below.
Start sequence: Stop coil
Start prepare
Crank
Running feedback
Stop output
Start attempts
1 2
AGC Designer’s Reference Handbook
DEIF A/S Page 43 of 168
Running feedback error: Run coil
Start prepare
Crank
Primary Running f
k
Run coil
Start attempts
1 2
tOFF tOFF
3
Secondary Runnin
g
feedback
tOFF tOFF
Engine running
Alarm
1
sec
t
Alarm
AGC Designer’s Reference Handbook
DEIF A/S Page 44 of 168
Interruption of start sequence The start sequence is interrupted in the following situations:
Start failure alarm
(6180 Start attempts)
The start failure alarm occurs, if the gen-set has not started after the last start attempt. Output A (OA) and output B (OB) in this menu indicate the relay output(s) which will be activated at a start failure alarm.
Start prepare (
6170 Starter
) The start prepare timer can be used for start preparation purposes, e.g. pre-lubrication or pre­glowing.
Event Comment
Stop signal Start failure Remove starter feedback
Tacho setpoint.
Running feedback Digital input. Running feedback Tacho setpoint. Running feedback Frequency measurement above 32Hz.
The frequency measurement requires a voltage measurement of 30% * U
NOM
.
The running detection based on the frequency measurement can replace the running feedback based on tacho or digital input or engine
communication. Emergency stop Alarm Alarms with ‘shutdown’ or ‘trip and stop’ fail class. Stop push-button on display
Only in semi-auto or manual mode.
Modbus stop command Semi-auto or manual mode. Binary stop input Semi-auto or manual mode. Deactivate the ‘auto start/stop’
Auto mode in the following gen-set modes:
Island operation, fixed power, load take over or mains power export
mode. Running mode It is not possible to change the running mode to ‘block’ as long as the
gen-set is running.
If the tacho input is to be used to remove the starter, it has to be set up in menu
6161. If the digital input is to be used as running feedback, then terminal 115 has to be used.
The only protections that can stop the gen-set/interrupt the start sequence when the ‘fire pump’ input is activated, are the digital input ‘emergency stop’ and the tacho alarm ‘overspeed 2’. Both of these must have the fail class ‘shut down’.
AGC Designer’s Reference Handbook
DEIF A/S Page 45 of 168
Stop sequence
The drawings illustrate the stop sequence.
Cooling-down time
Run coil
Running feedback
Stop sequence/RUN coil
tCOOL
Cooling-down time
Stop coil
Running feedback
Stop sequence/STOP coil
tEXT
tEXT
AGC Designer’s Reference Handbook
DEIF A/S Page 46 of 168
Stop sequence, description The stop sequence will be activated, if a stop command is given. The stop sequence includes
the cooling-down time, if the stop is a normal or controlled stop.
Description Cooling-down Stop Comment
Auto mode stop X X Trip and stop alarm X X Stop button on display X Semi-auto or manual. Remove ‘auto start/stop’ X X Auto mode: Island operation, fixed
power, load take over, mains power export.
Emergency stop X Engine shuts down and GB opens.
The stop sequence can only be interrupted during the cooling-down period. Interruptions can occur in these situations:
Stop failure alarm
A stop failure alarm will occur, if the running feedback or the generator voltage and frequency are still active. The stop failure timer is adjusted in
6220 Stop failure
. Output A (OA) and output B (OB) in this menu indicate the relay output(s) that will be activated at a stop failure alarm.
Breaker sequences
The breaker sequences will be activated depending on the selected mode:
Mode Gen-set mode Breaker control
Auto All Controlled by the unit Semi-auto All Push-button Manual All None Block All None
Event Comment
Mains failure AMF mode selected (or mode shift selected ON) and auto
mode selected.
Start button is pressed Semi-auto mode: Engine will run in idle speed. Binary start input Auto mode: Island operation and fixed power, load take over or
mains power export.
Exceeding setpoint Auto mode: Peak shaving. GB close button is pressed Semi-auto mode only.
The stop sequence can only be interrupted during the cooling-down period.
When the engine is stopped, then the speed governor output is reset to the offset value if option E1 or EF2 is selected, or the initial value if option EF3/EF5 is selected and the PWM output is used. Please refer to the descriptions of the mentioned options.
AGC Designer’s Reference Handbook
DEIF A/S Page 47 of 168
Before closing the breakers it must be checked that the voltage and frequency are OK. The limits are adjusted in
2040 Sync. blackout
AMF MB opening function
(6590 Mains failure voltage
)
It is possible to select the functionality of the mains breaker closing function. This is necessary, if the unit operates in Automatic Mains Failure (AMF).
The possibilities are:
Selection Description
Start engine and open mains breaker
When a mains failure occurs, the mains breaker opens, and the engine starts at the same time.
Start engine When a mains failure occurs, the engine starts.
When the generator is running and the frequency and voltage are OK, the MB opens and the GB closes.
AMF timers
The time charts describe the functionality at a mains failure and at mains return. Back synchronisation is deactivated. The timers used by the AMF function are indicated in the table below:
Timer Description Menu number
tFD Mains failure delay
6600 Mains failure frequency
6590 Mains failure voltage
tFU Frequency/voltage OK
6190 f/U OK
t
FOD
Mains failure OK delay
6600 Mains failure frequency
t
GBC
GB ON delay
6250 GB control
t
MBC
MB ON delay
6610 Mains breaker control
The timer t
MBC
is only active, if back synchronisation is deactivated (6610 Mains breaker
AGC without back synchronisation: The GB can only be closed, if the mains breaker is open. The MB can only be closed, if the generator breaker is open.
AGC with back synchronisation: If the GB or MB push-button is activated the AGC will start synchronising, if the generator or mains voltage is present. The GB can close directly, if the MB is open. The MB can close directly, if the GB is open.
AGC Designer’s Reference Handbook
DEIF A/S Page 48 of 168
control
).
AGC Designer’s Reference Handbook
DEIF A/S Page 49 of 168
Example 1 (6590 Mains failure voltage
)
Start engine and open MB:
Example 2 (6590 Mains failure voltage
)
Start engine:
Conditions for breaker operations The breaker sequences react depending on the breaker positions and the frequency/voltage
measurements.
GB On
MB On
Mains failure detected
Gen start seq
t
FD
Gen stop seq
Mains O
K
Mains OK
t
FOD
Gen running
Gen f/U OK
t
MCB
t
F
U
t
GBC
GB On
MB On
Mains failure detected
Gen start seq
t
FD
Gen stop seq
Mains OK
Mains O
K
t
FOD
t
F
U
t
MBC
Gen running
Gen f/U OK
AGC Designer’s Reference Handbook
DEIF A/S Page 50 of 168
The conditions for the ON and OFF sequences are described in the table below:
Conditions for breaker operations Sequence Condition
GB ON, direct closing Running feedback
Generator frequency/voltage OK MB open
MB ON, direct closing Mains frequency/voltage OK
GB open
GB ON, synchronising Running feedback
Generator frequency/voltage OK MB closed No generator failure alarms
MB ON, synchronising Mains frequency/voltage OK
GB closed No generator failure alarms
GB OFF, direct opening MB open MB OFF, direct opening Alarms with fail classes:
Shut down
Trip GB alarms GB OFF, deloading MB closed MB OFF, deloading Alarms with fail classes:
Trip and stop
When the breakers open and they need to reclose immediately, then the adjustable timer 6252 GB load time or 6615 MB load time must expire before closing is possible. This is the time the breaker uses to reload the spring.
If the digital inputs ‘MB spring loaded’ and ‘GB spring loaded’ are configured, then they must be activated before the breakers can close.
AGC Designer’s Reference Handbook
DEIF A/S Page 51 of 168
5. Display unit and menu structure
This chapter deals with the display unit including the push-button and LED functions. In addition, the unit menu structure will be presented.
Display unit
The display has 4 different lines, each with 20 characters, and holds a number of push-button functions.
Push-button functions
The display unit holds a number of push-button functions which are presented below.
INFO: Shifts the display 3 lower lines to show the alarm list.
JUMP: Enters a specific menu number selection. All settings have a specific number
attached to them. The JUMP button enables the user to select and display any setting without having to navigate through the menus (see later).
VIEW: Shifts the first line displaying in the setup menus.
LOG: Shifts the display 3 lower lines to show the event and alarm list. The list holds
150 events. The events are not deleted when the auxiliary supply is switched off.
: Moves the cursor left for manoeuvring in the menus.
: Increases the value of the selected setpoint (in the setup menu). In the daily use
display, this button function is used for scrolling the second line displaying of generator values.
SEL: Is used to select the underscored entry in the fourth line of the display.
: Decreases the value of the selected setpoint (in the setup menu). In the daily
use display, this button function is used for scrolling the second line displaying of generator values.
: Moves the cursor right for manoeuvring in the menus.
BACK: Jumps one step backwards in the menu (to previous display or to the entry
window).
START: Start of the gen-set if ‘SEMI-AUTO’ or ‘MANUAL’ is selected.
STOP: Stop of the gen-set if ‘SEMI-AUTO’ or ‘MANUAL’ is selected.
(GB) ON: Manual activation of close breaker and open breaker sequence if ‘SEMI-AUTO’
is selected
.
(MB) ON: Manual activation of close breaker and open breaker sequence if ‘SEMI-AUTO’
is selected
.
MODE: Changes the menu line (line 4) in the display to mode selection.
Display dimensions are H x W = 115 x 220 mm (4.528” x 9.055”).
AGC Designer’s Reference Handbook
DEIF A/S Page 52 of 168
The push-buttons are placed as follows:
INFO: Shifts the display three lower lines to show the alarm list.
JUMP: Enters a specific menu number selection.
START: Start of the gen-set if ‘SEMI-AUTO’ or ‘MANUAL’ is selected.
STOP: Stop of the gen-set if ‘SEMI-AUTO’ or ‘MANUAL’ is selected.
GB: Opens the GB, if it is closed. Closes (sync.) the GB, if it is opened.
MB: Opens the MB, if it is closed. Closes (sync.) the MB, if it is opened.
VIEW: Shifts the first line displaying in the setup menus.
LOG: Shifts the display three lower lines to show the event and alarm list.
SEL: Selects the underscored entry in the fourth display line.
BACK: Jumps one step backwards in the menu.
MODE: Changes the display menu line (line four) to mode selection.
AGC Designer’s Reference Handbook
DEIF A/S Page 53 of 168
LED functions
The display unit holds 10 LED functions. The colour is green or red or a combination in different situations.
Alarm: LED flashing indicates that unacknowledged alarms are present. LED fixed light indicates that ALL alarms are acknowledged.
Power: LED indicates that the auxiliary supply is switched on.
Self check OK: LED indicates that the self check is OK.
Alarm inh: Gen-set is stopped:
LED fixed light indicates that the unit does not receive a running signal. The inhibit lamp will be switched off when the run status timer times out
(6150 Running status )
.
Gen-set is running: LED fixed light indicates that the digital input is activated.
Run: LED indicates that the generator is running.
(Gen.) OK: LED green light indicates that the voltage/frequency is present and OK.
(GB) ON: LED green light indicates that the generator breaker is closed. LED yellow light indicates that the generator breaker has received a command
to close on a black BUS, but the breaker is not yet closed due to interlocking of the GB.
(MB) ON: LED indicates that the mains breaker is closed.
(Mains) OK: LED is green, if the mains is present and OK. LED is red at a measured mains failure. LED is flashing green when the mains returns during the ‘mains OK delay’ time.
Auto: LED indicates that auto mode is selected.
AGC Designer’s Reference Handbook
DEIF A/S Page 54 of 168
The display LEDs are indicating as follows:
Alarm inh.: Indicates alarm inhibit active.
Power: Indicates auxiliary supply ON.
Alarm: Flashing: Unacknowledged alarms present. Fixed: Acknowledged alarms present.
Self check OK: Indicates self check OK.
Generator running.
Generator voltage OK.
Generator breaker ON.
Mains breaker ON.
Mains voltage OK.
Auto: ON. Semi-auto: OFF.
AGC Designer’s Reference Handbook
DEIF A/S Page 55 of 168
Menu structure
The display includes two menu systems which can be used without password entry:
View menu system
This is the commonly used menu system. 15 windows are configurable and can be entered by using the arrow push-buttons.
Setup menu system
This menu system is used for setting up the unit, and if the user needs detailed information that is not available in the view menu system. Changing of parameter settings is password protected.
Entry window
When the unit is powered up, an entry window appears. The entry window is the turning point in the menu structure and as such the gateway to the other menus. It can always be reached by pressing the BACK push-button 3 times.
The event and alarm list will appear at power up, if an alarm is present.
AGC Designer’s Reference Handbook
DEIF A/S Page 56 of 168
View menu
The view menus (V1, V2 and V3) are the most commonly used menus of the unit.
First display line Second and third display line
Operational status or measurements Measurements relating to operational status
Fourth display line
Selection of setup and view menus
In the view menus various measured values are on display.
View window configuration The individual view windows need to be configured through the PC software in the dialog box
illustrated below.
Use this button to go to the configuration.
Select the view window to be configured.
AGC Designer’s Reference Handbook
DEIF A/S Page 57 of 168
The selectable values and measurements are presented in the table on page 59 in this handbook.
If the text ‘no text’ is selected in all 3 lines in a window, it will not be displayed. This is to get a continuous displaying, if a window is not to be used.
Click here to change the configuration.
It is only possible to configure the view windows via the PC software – configuration via the display unit is not possible.
There is a maximum of 15 configurable view windows in V1.
AGC Designer’s Reference Handbook
DEIF A/S Page 58 of 168
View window overview
* The default window is automatically selected after the generator breaker closure when the
gen-set is in normal operation, e.g. fixed power mode after the ramping up.
Windows V1
View 1 View 2 View 3 View 4 View 5 View 6 View 7 View 8 View 9 View 10 View 11 View 12 View 13 View 14 View 15
Manual selection with key UP or key DOWN push­buttons
Windows V 2 V 3
View 1 View 2 View 3 View 4 View 5
Changes automatically be­tween the 5 first views:
1. View 1 (Start prepare)
2. View 2 (Sync.)
3. View 3 (Ramp up/down)
4. View 4
5. View 5 (Default*)
No manual selection.
All three lines show measuring values.
Changes automatically be­tween the 5 first views:
1. View 1 (Start prepare)
2. View 2 (Sync.)
3. View 3 (Ramp up/down)
4. View 4
5. View 5 (Default*)
No manual selection. Line 1 shows the text 1…5 (above). Line 2 and line 3 show measurements.
AGC Designer’s Reference Handbook
DEIF A/S Page 59 of 168
View menu example The following is an example of a configured view menu system. In this example 4 of 15 windows
have been configured in view 1.
ML 2- AGC V. 2.10.0
2004-12-01 09.35.54 SETUP
V3 V2 V1
G 440 438 440V G-L1 50Hz 440V B-L1 50Hz 440V SETUP V3 V2 V1
MANUAL B 440 438 440V G 439 438 440V SETUP V3
V2 V1
G 150 140 150A B 440 438 440V G 440 438 440V SETUP V3 V2
V1
I-L1 150A I-L2 140A I-L3 150A SETUP V3 V2 V1
G 150 140 150A G 0.90PF 103KW
SETUP V3 V2 V1
U-SUPPLY 24V
SETUP V3 V2 V1
G 439 440 440V
f-L1 50.02Hz PROTECTION SETUP PROT
CTRL I/O SYST
BACKSEL
...Etc. (max. 15)
The menu navigating starts from the fourth display line in the entry window and is carried out
using the
, , and push-buttons.
The entry window displays view 3, (in the illustration above the window where ‘manual’ is displayed).
Moving the cursor left or right offers the following possibilities.
Setup menu – access to the following sub-menus:
- Protection setup
- Control setup
- I/O setup
- System setup
View 3 – window displays operational status and selectable measurements
View 2 – window displays selectable measurements
View 1 – access to up to 15 selectable windows displaying selectable measurements
AGC Designer’s Reference Handbook
DEIF A/S Page 60 of 168
Setup menu
The setup menu system is used for parameter setup of the unit, and if the user needs detailed information that is not available in the view menu system. So, this menu can be used for both daily use and setup purposes. The menu is entered from the entry window by selecting the entry SETUP in the fourth display line.
First display line
(Daily use) The first line is used to display generator and BUS values
Second display line
(Daily use) Various values can be displayed
(Menu system) Information about the selected channel number (Alarm/event list) The latest alarm/event is displayed
Third display line
(Daily use) Explanation for the fourth line cursor selection (Setup menu) Presents setting of the selected function, and, if
changes are made, the possible max. and min. values for the setting
Fourth display line (Daily use) Entry selection for the setup menu. Press SEL to enter the underscored menu
(Setup menu) Sub-functions for the individual parameters, e.g. limit
Possible values in second display line
View line/second display line configuration For generator For bus/mains For analogue input Communication/
other
Voltage L1 L2 L3 (V AC) Voltage L1 L2 L3 (V AC) Analogue 98 PID Value #1.1 Voltage L1-N (V AC) Voltage L1-N (V AC) Analogue 100 (oil
press.)
PID Value #1.2
Voltage L2-N (V AC) Voltage L2-N (V AC) PID value #1.3 Voltage L3-N (V AC) Voltage L3-N (V AC) Analogue 102 (fuel
level)
PID value #1.4
Voltage L1-L2 (V AC) Voltage L1-L2 (V AC) Analogue 104 PID value #1.5 Voltage L2-L3 (V AC) Voltage L2-L3 (V AC) Analogue 91 PID value #1.6 Voltage L3-L1 (V AC) Voltage L3-L1 (V AC) Analogue 93 PID value #1.7 Voltage max. (V AC) Voltage max. (V AC) Analogue 95 PID value #1.8 Voltage min. (V AC) Voltage min. (V AC) Analogue 97 PID value #2.1 Current L1 L2 L3 (A) Frequency (Hz) PT100 no. 106 PID value #2.2 Current L1 (A) Frequency/voltage L1 (Hz/ PT100 no. 109 PID value #2.3
AGC Designer’s Reference Handbook
DEIF A/S Page 61 of 168
View line/second display line configuration For generator For bus/mains For analogue input Communication/
other
V AC) Current L2 (A) Tacho PID value #2.4 Current L3 (A) Voltage angle between L1-
L2 (deg.)
VDO 104 (pressure) PID value #2.5
Frequency/voltage L1 (Hz/V AC)
VDO 105 (temperature) PID value #2.6
Frequency L1 (Hz) VDO 106 (fuel level) PID value #2.7 Frequency L2 (Hz) PID value #2.8 Frequency L3 (Hz)
Voltage angle between
generator voltage and bus
voltage (deg.)
Status line Power factor/active power (PF/kW)
Power supply voltage (V DC) Synchroscope
Active power (kW) Mains power (kW) Date and time Reactive power/apparent power
Negative voltage
(kVAr)/(kVA) Negative current Reactive power (kVAr) Zero voltage Apparent power (kVA) Zero current Energy counter (kWh) Power factor Voltage angle between L1­L2 (deg.) Voltage angle between L2­L3 (deg.) Voltage angle between L3­L1 (deg.) Absolute run time (h) Relative run time (h) Next priority shift (h and min.) Fire run Number of GB operations Number of MB operations Next service
Setup structure
ML 2- AGC V. 2.10.0
2004-12-01 09.35.54 SETUP
V3 V2 V1
G 439 440 440V
f-L1 50.02Hz
PROTECTION SETUP
PROT
CTRL I/O SYST
G 439 440 440V
f-L1 50.02Hz INPUT/OUTPUT SETUP PROT CTRL I/O SYST
G 439 440 440V
f-L1 50.02Hz
SYSTEM SETUP
PROT CTRL I/ O SY ST
G 439 440 440V
f-L1 50.02Hz
CONT ROL SET UP
PROT CTRL I/O SYST
G 439 440 440V PROTECTION SETUP SET POINT 1 SETUP PROT1
PROT2
G 439 440 440V SYSTEM SETUP GENERA L S ET UP GEN
MAINS COMM PM
G 439 440 440V CONTROL SET UP SYNCHRONICE SETUP SYNC
REG
G 439 440 440V INPUT/OUTPUT SETUP BINARY INPUT SETUP BIN
AIN OUT
AGC Designer’s Reference Handbook
DEIF A/S Page 62 of 168
Setup example The following example illustrates how a specific setting is changed in the setup menu. In this
case
Reverse power is the selected parameter.
G 439 440 440V 1010 Reverse Power Setpo int -5.0 % LIM
DEL OA OB ENA FC
firs t entry
G 439 440 440V 1020 Over current 1 Setpoint 115.0 % LIM
DEL OA OB ENA FC
G 439 440 440V Enter passw. 1999
ENTER
G 439 440 440V 1011 Reverse power
-50.0 -5.0
0.0%
RESET
SAV E
Ye s
No
BACK SEL
INCREASE NO
DECREASE NO
Increase setting
Decrease setting
moves the cursor
G 439 440 440V PROTECTION SETUP SET POINT 1 SETUP PROT1
PROT2
SELBACK
Mode overview
The unit has four different running modes and one block mode. For detailed information see page 11.
Auto
In auto mode the unit will operate automatically, and the operator cannot initiate any sequences manually.
Semi-auto
In semi-auto mode the operator has to initiate all sequences. This can be done via the push­button functions, Modbus commands or digital inputs. When started in semi-automatic mode, the gen-set will run at nominal values.
Test
AGC Designer’s Reference Handbook
DEIF A/S Page 63 of 168
The test sequence will start when the test mode is selected.
Manual
When manual mode is selected, the binary increase/decrease inputs can be used (if they have been configured) as well as the start and stop push-buttons. When starting in manual mode, the gen-set will start without any subsequent regulation.
Block
When the block mode is selected, the unit is not able to initiate any sequences, e.g. the start sequence.
Mode selection
The following drawings illustrate how the mode selection is carried out.
Pushing the MODE push-button will change the displayed text. After pushing ‘MODE’, the fourth display line indicates the selectable modes. In the third display line, the underscored (fourth line) selection will be displayed.
Two possibilities are now available:
If ‘BACK’ is pushed, the display returns to the original text without changing the mode.
AGC V. 2.10.0 2005-01-01 13 : 45 : 18 SETUP MENU SETUP
V3 V2 V1
1. push
‘MODE’ Æ
AGC V. 2.10.0 2005-01-01 13 : 45 : 18 SEMI-AUTO MODE SEMI
TST AUT MAN BLK
2. push
‘BACK’ Æ
or
G 0 0 0V f-L1 0.00Hz PROTECTION SETUP PROT CTRL
I/O SYST
1. push
‘MODE’ Æ
G 0 0 0V f-L1 0.00Hz SEMI-AUTO MODE SEMI TST AUT MAN BLK
2. push
‘BACK’ Æ
If ‘SEL’ is pushed, the underlined mode is selected, and the display returns to the original text. In this example the SEMI-AUTO mode is selected.
AGC V. 2.10.0 2005-01-01 13 : 45 : 18 SETUP MENU SETUP
V3 V2 V1
3. push
‘MODE’ Æ
AGC V. 2.10.0 2005-01-01 13 : 45 : 18 SEMI-AUTO MODE SEMI
TST AUT MAN BLK
4. push
‘SEL’ Æ
or
G 0 0 0V f-L1 0.00Hz PROTECTION SETUP PROT CTRL
I/O SYST
3. push
‘MODE’ Æ
G 0 0 0V f-L1 0.00Hz SEMI-AUTO MODE SEMI TST AUT MAN BLK
4. push
‘SEL’ Æ
Block mode must be selected, when maintenance work is carried out on the gen­set.
AGC Designer’s Reference Handbook
DEIF A/S Page 64 of 168
Password
The unit includes three password levels. All levels can be adjusted in the PC software.
Available password levels:
Access Password level Factory setting
Customer Service Master
Customer 2000 X Service 2001 X X Master 2002 X X X
A parameter cannot be entered with a too low ranking password. But the settings can be displayed without password entry.
Each parameter can be protected at a specific password level. To do so, the PC utility software must be used. Enter the parameter to be configured and select the correct password level.
AGC Designer’s Reference Handbook
DEIF A/S Page 65 of 168
Parameter access
To get access to adjust the parameters, the password level must be entered:
If the password level is not entered, it is not possible to enter the parameters.
The customer password can be changed in menu 9116 page 167. The service password can be changed in menu 9117 page 167. The master password can be changed in menu 9118 page 167.
The factory passwords must be changed, if the operator of the gen-set is not allowed to change the parameters.
It is not possible to change the password at a higher level than the password entered.
AGC Designer’s Reference Handbook
DEIF A/S Page 66 of 168
6. Additional functions
This chapter describes the additional functions.
Start functions
The unit will start the gen-set when the start command is given. The start sequence is deactivated when the remove starter event occurs or when the running feedback is present.
The reason for having two possibilities to deactivate the start relay is to be able to delay the alarms with run status.
If it is not possible to activate the run status alarms at low revolutions, the remove starter function must be used.
An example of a critical alarm is the oil pressure alarm. Normally, it is configured according to the shutdown fail class. But if the starter motor has to disengage at 400 RPM, and the oil pressure does not reach a level above the shutdown setpoint before 600 RPM, then, obviously, the gen-set would shut down, if the specific alarm was activated at the preset 400 RPM. In that case, the running feedback must be activated at a higher number of revolutions than 600 RPM.
Digital feedbacks
If an external running relay is installed, then the digital control inputs for running detection or remove starter can be used.
Running feedback When the digital running feedback is active, the start relay is deactivated and the starter motor
will be disengaged.
t
RPM
Oil
p
ressure
400
1000
RPM
600
Running
Remove starte
r
See page 41 for detailed information about start sequence.
AGC Designer’s Reference Handbook
DEIF A/S Page 67 of 168
The diagram illustrates how the digital running feedback (terminal 115) is activated, when the engine has reached its firing speed.
Remove starter When the digital remove starter input is present, the start relay is deactivated and the starter
motor will be disengaged.
The diagram illustrates how the remove starter input (terminal 118) is activated, when the engine has reached its firing speed. At the running speed the digital running feedback is activated.
t
RPM
RPM
N
M
Run. feedback, terminal 115
RPM
Firing speed
t
RPM
RPM
N
M
Remove starter, terminal 118
Run. feedback, terminal 115
RPM
Firing speed Runnin
g
The remove starter input must be configured from a number of available digital inputs. In the example above terminal 118 is used.
The running feedback is detected by the digital input (see diagram above). Frequency measurement above 32Hz or RPM is measured by magnetic pick-up.
AGC Designer’s Reference Handbook
DEIF A/S Page 68 of 168
Analogue tacho feedback
When a magnetic pick-up is being used, the specific level of revolutions for deactivation of the start relay can be adjusted.
Running feedback. The diagram below shows how the running feedback is detected at the firing speed level. The
factory setting is 1000 RPM
(4300 Running detection
)
.
Remove starter input The drawing below shows how the setpoint of the remove starter is detected at the firing speed
level. The factory setting is 400 RPM
(6160 Remove starter
)
.
RPM
RPM
Remove starter, menu 6161
Run. feedback, menu 4301
RPM
Firing speed Running
t
RPM
RPM
Run. feedback, menu 4301
RPM
Firing speed
The number of teeth on the flywheel must be adjusted when the tacho input is used (6160 Remove starter ).
Notice that the factory setting of 1000 RPM is higher than the RPM level of starter motors of typical design. Adjust this value to a lower value to avoid damage of the starter motor.
AGC Designer’s Reference Handbook
DEIF A/S Page 69 of 168
Breaker spring load time
If the breaker needs time to reload the spring after it has opened, then the AGC can take this delay into account. This can be controlled through timers in the AGC or through digital feedbacks from the breaker, depending on the breaker type.
Principle
The diagram shows an example where a single AGC in island mode is controlled by the AUTO start/stop input.
This is what happens: When the AUTO start/stop input deactivates, the GB opens. The AUTO start/stop is reactivated immediately after the GB has opened, e.g. by the operator through a switch in the switchboard. However, the AGC waits a while before it issues the close signal again, because the spring load time must expire (or the digital input must be activated - not shown in this example). Then the AGC issues the close signal.
Digital input
This can be used e.g. when the breaker is able to send a feedback to the AGC when its spring is reloaded.
There is one input for the generator breaker and one for the mains breaker. The input configuration is done through the PC utility software. The names of the inputs are ‘GB spring loaded’ and ‘MB spring loaded’. In the example below they are configured to terminal 91 and 92.
AGC Designer’s Reference Handbook
DEIF A/S Page 70 of 168
When the feedback is not activated, the breaker cannot close. The LED above the breaker symbol will be flashing (yellow), and the AGC will not attempt to issue a close signal before the spring load feedback is on.
Timer-controlled
On breakers where no feedback can be issued when the spring is in loaded position, timer settings can be used instead. There are timers for all breakers that can be controlled by the AGC, i.e. the generator breaker (menu 6252), the mains breaker (menu 6615) and the tie breaker (option G5, menu 7632).
When the timers are counting, then the remaining time is shown in the display, the LED above the breaker symbol will be flashing (yellow) and the AGC will not attempt to issue a close signal before the timer has expired.
Alarm inhibit
The purpose of the alarm inhibit function is to avoid nuisance alarms when the gen-set is in a controlled operational state (stop). For example it is not necessary to have the low lubricating oil pressure alarm displayed when the gen-set stops.
Four possibilities exist for the alarm inhibit functionality:
1. Digital input 23 can be used.
2. The alarms can be given
RUN status.
3. Selectable alarms can be given
Parallel status.
4. Selectable alarms can be ‘custom inhibit’ by using a configurable input in the utility SW.
Digital input 23
The functionality of the alarm inhibit input is indicated in the table below:
The inhibit LED on the unit and on the display will activate when the voltage is below 30% of the nominal voltage.
On the AGC mains unit (option G5) the spring load feedback from the tie breaker can be connected instead of the GB spring load feedback.
AGC Designer’s Reference Handbook
DEIF A/S Page 71 of 168
Standard PCBs
M1 M2
Alarm inhibit input 23
Alarm/input
Terminal
number
Input ON Input OFF Comment
Generator low f
-
Active Option dependent
Generator low U
-
Active Option dependent
Generator high f
Active
Active Option dependent
Generator high U
Active
Active Option dependent
Busbar low f
-
Active Option dependent
Busbar low U
-
Active Option dependent
Busbar high f
Active
Active Option dependent
Busbar high U
Active
Active Option dependent
4…20mA input 98 98
-
Active
4…20mA input 100 100
-
Active
4…20mA input 102 102
-
Active
4…20mA input 104
-
Active VDOinput 104 - Active VDO input 105
-
Active VDO input 106
-
Active PT100 106 - Active PT100 109 - Active Tacho input
112 108
Active
Active Binary input
110
-
Active Configurable input Binary input
111
-
Active Configurable input Binary input
112
-
Active Configurable input Binary input
113
-
Active Configurable input Binary input
114 114
Active
Active Access lock Binary input
115 115
Active
Active Running feedback Binary input
116 116
Active
Active External engine fail. Binary input
117 117
Active
Active Emergency stop Binary input
118 118
-
Active Configurable input Positive sequence U
-
Active Option dependent
AGC Designer’s Reference Handbook
DEIF A/S Page 72 of 168
Optional PCBs
Automatic RUN status
Alarms can be adjusted to activate only when the running feedback is active and a specific time delay has expired.
The diagram below illustrates that after activation of the running feedback, a run status delay will expire. When the delay expires, alarms with
RUN status will be activated.
Alarm inhibit input 23
Input
Input ON Input OFF Comment
Option M12 -
Active Digital inputs
Option M13 -
Active Digital inputs
Option M15 -
Active 4-20mA inputs
t
R
N
Run. feedback
Alarms active
Function inputs such as running feedback, remote start or access lock are never inhibited. Only alarm inputs can be inhibited.
If an alarm is configured to activate a limit relay the relay will activate despite that the inhibit input is ON.
AGC Designer’s Reference Handbook
DEIF A/S Page 73 of 168
The alarms are set up from the display or the PC utility software. In the PC utility software it looks like this:
The adjustment is made in the drop down menu in the lower left corner.
The timer is adjusted in the following dialog box:
Only the timer needs adjustment to achieve this function. The additional roll down panels are used, if a digital running status output is needed. Refer to page
81.
AGC Designer’s Reference Handbook
DEIF A/S Page 74 of 168
Parallel status
If an alarm is to be activated only when both the GB and the MB is closed, then the alarm can be adjusted to ‘parallel’. This is possible for the following alarms:
Menu Description Comment
1180 BUS high voltage 1 1 second delay after breaker closure 1190 BUS high voltage 2 1 second delay after breaker closure 1200 BUS low voltage 1 1 second delay after breaker closure 1210 BUS low voltage 2 1 second delay after breaker closure 1220 BUS high frequency 1 1 second delay after breaker closure 1230 BUS high frequency 2 1 second delay after breaker closure 1240 BUS low frequency 1 1 second delay after breaker closure 1250 BUS low frequency 2 1 second delay after breaker closure 1350 df/dt (ROCOF) 1 second delay after breaker closure 1360 Vector jump 1 second delay after breaker closure 1390 Positive sequence U 1 second delay after breaker closure
Custom inhibit input
The custom inhibit function is made to give the user a possibility to decide which protections should be inhibited when an input is activated.
To activate the custom inhibit function two things are needed:
1. Configure an input in the input settings in the utility SW.
2. Enable the function as shown in the dialog box below.
For detailed information please refer to the separate manual for option A1-A4.
AGC Designer’s Reference Handbook
DEIF A/S Page 75 of 168
AGC Designer’s Reference Handbook
DEIF A/S Page 76 of 168
The functionality of the custom inhibit input is indicated in the table below:
Standard PCBs
Optional PCBs
M1 M2 Custom inhibit input
configured
Alarm/input
Terminal number
Input ON and custom inhibit enabled
Input OFF Comment
Generator low f
-
Active Option dependent
Generator low U
-
Active Option dependent
Generator high f
Active
Active Option dependent
Generator high U
Active
Active Option dependent
Busbar low f
-
Active Option dependent
Busbar low U
-
Active Option dependent
Busbar high f
Active
Active Option dependent
Busbar high U
Active
Active Option dependent
4…20mA input 98 98
-
Active
4…20mA input 100 100
-
Active
4…20mA input 102 102
-
Active
4…20mA input 104
-
Active
VDO input 104
-
Active
VDO input 105
-
Active
VDO input 106
-
Active PT100 106 - Active PT100 109 - Active Tacho input
112 108
Active
Active Binary input
110
-
Active Configurable input Binary input
111
-
Active Configurable input Binary input
112
-
Active Configurable input Binary input
113
-
Active Configurable input Binary input
114 114
Active
Active Access lock Binary input
115 115
Active
Active Running feedback Binary input
116 116
Active
Active External engine fail. Binary input
117 117
Active
Active Emergency stop Binary input
118 118
-
Active Configurable input Positive sequence U
-
Active Option dependent
Custom inhibit input configured
Input
Input ON and custom inhibit enabled
Input OFF Comment
Option M12 -
Active Digital inputs
Option M13 -
Active Digital inputs
Option M15 -
Active 4-20mA inputs
AGC Designer’s Reference Handbook
DEIF A/S Page 77 of 168
Optional protections
Custom inhibit input configured
Input
Alarm limit exceeded and custom inhibit enabled
Input OFF Comment
Option A1 -
Active
Option A2 -
Active
Option A3 -
Active
Option A4 -
Active
Option B1 -
Active
Option C1 -
Active
Option C2 -
Active
If an alarm is configured to activate a limit relay, the relay will activate in spite of the fact that the inhibit input is ON.
If the protection is configured to ‘RUN’ or ‘PARALLEL’ the custom inhibit will overrule these functions, if the input is active after the conditions for ‘RUN’ or ‘PARALLEL’ have been removed.
Function inputs such as running feedback, remote start or access lock are never inhibited. Only alarm inputs can be inhibited.
AGC Designer’s Reference Handbook
DEIF A/S Page 78 of 168
Access lock
The digital input number 114 is preconfigured to the function ‘access lock’. The purpose of access lock is to deny the operator the possibility to configure the unit parameters and change the running modes.
Access lock will typically be activated from a key switch installed behind the door of the switchboard cabinet.
Button Button status Comment
INFO Active
It is possible to read all alarms, but it is not possible to
acknowledge any of them. JUMP Not active START Not active STOP Not active GB ON Not active MB ON Not active VIEW Active LOG Active
LEFT
Active
UP
Active
SELECT Not active
If the access lock is activated when the view menu
system is displayed, then the button is not active. SELECT Active
If the access lock is activated when the setup menu
system is displayed, then the button is active.
DOWN
Active
BACK Active
RIGHT
Active
MODE Active
If the access lock is activated when the view menu
system is displayed, the button is not active. MODE Active
If the access lock is activated when the setup menu
system is displayed, then the button is active.
After three minutes the display returns to the view menu system. The setup menu system can only be entered again, if the access lock is deactivated.
The stop push-button is not active in semi-auto mode when the access lock is activated. For safety reasons it is recommended to install an emergency stop switch.
AGC Designer’s Reference Handbook
DEIF A/S Page 79 of 168
Input name Input status Comment
Fire pump Active Access lock Running feedback Active Remote start Not active Remote stop Not active Semi-auto Not active Test Not active Auto Not active Manual Not active Block Not active Remote GB ON Not active Remote GB OFF Not active Remote MB ON Not active Remote MB OFF Not active Remote TB ON Not active Remote TB OFF Not active Remote alarm acknowledge Active Gen-set start sequence Active Remove starter Active Reset analogue governor output Active Manual GOV up Active Manual GOV down Active Manual AVR up Active Manual AVR down Active Alarm inhibit Active GB position ON Active GB position OFF Active MB position ON Active MB position OFF Active Emergency stop Active External engine failure Active AOP buttons Active
Short-time parallel
The purpose of the short time parallel function is to be able to define a maximum paralleling time between the generator and the mains supply.
The function is typically used, if there are local requirements to maximum allowed paralleling time.
The short time paralleling function is only available in the automatic mains failure and load take over gen-set modes.
AGC Designer’s Reference Handbook
DEIF A/S Page 80 of 168
The diagram shows that when the generator breaker is synchronised, the mains breaker will be opened automatically after a time delay (t). Later the mains breaker is synchronised, and the generator breaker is opened after the time delay (t).
The time delay is measured in seconds and can be adjusted from 0.10 to 99.90 seconds.
The short time parallel function is set up in
2700 Short time paralleling
.
Digital mains breaker control
The unit will normally execute the automatic mains failure sequence based on the settings adjusted in the system setup. Besides these settings it is possible to configure a digital input that can be used to control the mains return sequence. This input is the ‘mains OK’ input. The purpose of this function is to let an external device or an operator control the mains return sequence. The external device can e.g. be a PLC.
The flowchart below shows that if the input is configured, it needs to be
deactivated in order to
initiate the mains return sequence. The load will continue on generator supply, if the input is still activated.
The mains OK delay is not used at all when the ‘mains OK’ input is configured.
MB
GB
tt
t
The same time delay is used for both generator and mains breaker synchro­nisation.
If the function is used in a Power Management (option G5) application, then the short time paralleling will occur between the mains breaker and the tie breaker on the AGC mains.
The time delay typed in the set point is a maximum time. This means that if 0.10 seconds are used, the two breakers will never be closed at the same time for a longer delay than the set point.
AGC Designer’s Reference Handbook
DEIF A/S Page 81 of 168
Time dependent start/stop
The purpose of the time dependent start/stop function is to be able to start and stop the gen-set automatically at specific times each weekday or certain weekdays. If auto mode is activated, this function is available in island operation, load take over, mains power export and fixed power operation. Up to 8 commands can be used for either start or stop. The settings are set up through the PC utility software. Each command can be set for the following time periods:
Individual days (MO, TU, WE, TH, FR, SA, SU)
MO, TU, WE, TH
MO, TU, WE, TH, FR
MO, TU, WE, TH, FR, SA, SU
SA, SU
The digital input ‘auto start/stop’ cannot be used, when this function is enabled.
Mains OK
MB i nput
configured
MB and GB
operatio ns
MB co ntrol
input
Yes
ON
No
Mains OK
delay
No
expired
Yes
No Yes
Sequence
AGC Designer’s Reference Handbook
DEIF A/S Page 82 of 168
Running output
6150 Running status
can be adjusted to give a digital output when the gen-set is running.
Select the correct relay number in output A and output B and enable the function. Change the relay function to limit in the I/O menu. Then the relay will activate, but no alarm will appear.
Derate gen-set
The purpose of the derate function is to be able to reduce the maximum output power of the gen-set, if specific conditions require this. An example of such a condition is the ambient
It is necessary to use the PC utility software when setting up the time dependent start/stop function.
If the relay function is not changed to ‘limit’ function, an alarm will appear at every running situation.
AGC Designer’s Reference Handbook
DEIF A/S Page 83 of 168
temperature. If the ambient temperature increases to a level where the cooling water coolers decrease in cooling capacity, it will be necessary to reduce the power of the gen-set. If the gen-set is not derated, alarms and shutdown events will very likely occur.
Input selection
The derate function can be configured to one of the following inputs:
Engine interface
selection
Input
M1 M2
Analogue input 100 X X PT100 input 106 X PT100 input 109 X VDO input 105 X VDO input 106 X
Select the needed input in
6260 P
nom
derate
.
Derate parameters
The parameters that define the derate characteristics are the following:
Start derate point (
6260 P
nom
derate
):
This is the setting where the derating must start. The setting can be in mA (max. 20mA) or in centigrades ºC (max 200ºC).
Slope (
6260 P
nom
derate
):
Adjust the derating speed. The adjustment is in percent per unit, i.e. if the 4…20mA input is used (analogue 100), then the derating will be in %/mA, and if the PT100/VDO input is used, then the derating will be in %/C.
The derate function is typically used when cooling problems are expected.
Refer to the type label for information about engine interface selection.
Be aware that the 4…20mA input can be configured with different minimum and maximum settings. In this case the settings ‘start derate point’ and ‘slope’ use these new settings.
AGC Designer’s Reference Handbook
DEIF A/S Page 84 of 168
Derate limit (
6260 P
nom
derate
):
This is the lowest derate level.
Derate characteristic
It can be selected whether the characteristic of the derating should be proportional or inverse proportional. The drawing above shows the inverse characteristic.
The proportional characteristic is illustrated below.
PNOM
PLIMIT
P
Start
derate
1
1
0
2
mA
PNOM
PLIMIT
P
Start
increase
1
1
0
2
mA
AGC Designer’s Reference Handbook
DEIF A/S Page 85 of 168
The gen-set is derated when the control value is lower than the setpoint (in the example above the control value is an mA signal).
The derate characteristic is selected in
6260
Pnom derate
.
Setting OFF: Inverse characteristic Setting ON: Proportional characteristic
AGC Designer’s Reference Handbook
DEIF A/S Page 86 of 168
Idle running
The purpose of the idle run function is to change the start and stop sequences to allow the gen­set to operate under low temperature conditions.
It is possible to use the idle run function with or without timers. Two timers are available. One timer is used in the start sequence, and one timer is used in the stop sequence.
The main purpose of the function is to prevent the gen-set from stopping. The timers are available to make the function flexible.
The function is typically used in installations where the gen-set is exposed to low temperatures which could generate starting problems or damage the gen-set.
Description
The function is enabled and configured in 6310 Idle running. It has to be noted that the governor itself must handle the idle speed based on a digital signal from the unit (see the principle diagram below).
When the function is enabled, two digital inputs are used for control purposes:
No. Input Description
1 Low speed input This input is used to change between idle speed and
nominal speed. This input does not prevent the gen-set from
stopping - it is only a selection between idle and nominal
speed.
2 Temperature control input When this input is activated, the gen-set will start. It will not
be able to stop as long as this input is activated.
The speed governor must be prepared for the idle run function, if this function is to be used.
The input must be configured through the PC software at commissioning.
One extra relay output must be available on the unit. Notice that this is option dependent.
Turbo chargers not originally prepared for operating in the low speed area can be damaged, if the gen-set is running in ‘idle run’ for too long.
AGC Designer’s Reference Handbook
DEIF A/S Page 87 of 168
Examples
Idle speed during starting and stopping In this example both the start and the stop timers are activated.
The start and stop sequences are changed in order to let the gen-set stay at the idle level before speeding up. It also decreases the speed to the idle level for a specified delay time before stopping.
Start Sto
p
RPM
300
1500
t
tSTART tSTOP
GOVERNOR
AGC
Low speed
input
High/low
speed
selection
Actuator
Idle run input
Relay
Temperature
control input
Start/stop
g
en-set
AGC Designer’s Reference Handbook
DEIF A/S Page 88 of 168
Idle speed, no stopping In this example both timers are deactivated.
If the gen-set is to be prevented from stopping, then the digital input ‘temp control’ must be left ON at all times. In that case the characteristic looks like this:
Configuration of digital input
The digital input is configured via the PC software.
Inhibit
The alarms that are deactivated by the inhibit function or the alarms with run status are inhibited like usual except for the oil pressure alarms, i.e. VDO 104 if option M2 is selected, and 4…20mA input 100 if option M1 is selected.
Start Sto
p
RPM
300
1500
t
The run status is deactivated, when idle run is active. This means that all protections set to ‘RUN’ will be inhibited.
The oil pressure alarm will be enabled at all times, no matter if it is set to ‘RUN’ or ‘ON’.
AGC Designer’s Reference Handbook
DEIF A/S Page 89 of 168
Running signal
The running feedback must be activated when the gen-set is running in idle mode.
Idle speed flowcharts
The flowcharts illustrate the starting and stopping of the gen-set by use of the inputs ‘temp control’ and ‘low speed’.
Start
Start
Auto
st art/stop
ON
temp control
ON
No
No starting
No
start the genset
Yes
low speed ON
Genset running
at idle speed
idle timer ON
idle timer
expired
genset running
at f
NOM
Yes
END
start the genset
Yes
No
Yes
Yes
NoNo
AGC Designer’s Reference Handbook
DEIF A/S Page 90 of 168
Stop
st ar t
tem p con trol
OFF
auto start/stop
OFF
Yes
genset is
running
No
No
gen-set stop
sequence
Yes
Low speed ON
Yes
genset running
at idle speed
idle timer ON
No
idle timer
expired
Yes
No
genset stop
sequence
end
No
Yes
AGC Designer’s Reference Handbook
DEIF A/S Page 91 of 168
Master clock
The purpose of the master clock is to control the frequency of the gen-set in order to obtain the correct number of periods.
In a 50Hz system one period lasts 20 ms. If this changes, e.g. due to the dead band setting of the frequency controller, a difference will exist between the actual number of periods and the theoretical number of periods.
Equipment that works based on the zero crossings will be affected by the surplus or missing zero crossings. The most common example of such equipment is alarm clocks.
The unit’s internal clock is a timekeeper which is included in the battery backed memory circuit. The timekeeper function works based on an oscillating crystal instead of zero crossings of the AC measurements. Due to the accuracy of the timekeeper, it is recommended to synchronise the clock on a regular basis, e.g. once every month.
Setting Description Comment
6401 Start Start time. The compensation period starts at the
adjusted time.
6402 Stop Stop time. The compensation period stops at the
adjusted time.
6403 Difference The setpoint in seconds
that initiates the compen­sation.
6404 Compensation Frequency difference when
the compensation is ini­tiated.
+/- value.
6405 Enable Enables the function.
Compensation time
The time for the compensation can easily be calculated at a given adjustment of 6403 and 6404 (example):
6403 = 30 seconds
6404 = +/- 0.1Hz
This function can only be used, if island operation is selected.
If the power management option is selected (option G5), then the adjustment is made in the command unit.
hoursst
HzHzst
fftt
TOTAL
TOTAL
DIFFNOMSETTOTAL
1,4~15030
)1,50/501/(30
)/1/(
=
=
=
The compensation frequency must be adjusted to a value higher than the dead band setting.
AGC Designer’s Reference Handbook
DEIF A/S Page 92 of 168
Battery test
This function gives the possibility to test the condition of the battery. The battery test initiates with a digital input and is available when the gen-set is in semi-auto mode.
If a mains failure occurs during the battery test sequence, the test will automatically be interrupted, and the automatic mains failure start up sequence will be activated.
During the test the battery voltage will decrease, and an alarm will occur if it drops to the setpoint.
The drawing shows that test #1 is carried out without a large voltage drop of the battery voltage, whereas test #2 reaches the alarm setpoint.
As there is no reason to wear the battery down even more, the test stops when the battery test alarm occurs.
The test is typically used at periodical intervals, e.g. once every week. The engine must be at a standstill when the test is started. Otherwise, the test command will be ignored.
The stop relay will act depending on the coil type selection in
6210 Stop
:
Stop coil:
The stop relay activates during the test.
Run coil:
The stop relay stays deactivated during the test.
t
BAT TEST
t
BAT TEST
Cancel test
U
BATTER
Y
t
Alarm
Test 2Test 1
AGC Designer’s Reference Handbook
DEIF A/S Page 93 of 168
The drawing below shows that when the test is started, the start relay activates making the engine turn.
Input configuration
If this function is to be used, it is necessary to configure a digital input that initiates the function. This is done in the dialog box below.
Fail class
All activated alarms must be configured with a fail class. The fail classes define the category of the alarms and the subsequent alarm action.
Six different fail classes can be used. The tables below illustrate the action of each fail class when the engine is running or stopped.
Start relay
Run coil
Stop coil
or
Start test
If AUTO mode is selected, the mains failure sequence will be initiated, if a mains failure occurs during the battery test.
AGC Designer’s Reference Handbook
DEIF A/S Page 94 of 168
Engine running
The table illustrates the action of the fail classes. If, for instance, an alarm has been configured with the ‘shutdown’ fail class, the following actions occur.
The alarm horn relay will activate
The alarm will be displayed in the alarm info screen
The generator breaker will open instantly
The gen-set is stopped instantly
The gen-set cannot be started from the unit (see next table)
Engine stopped
Action Fail class
Block engine start Block MB sequence Block GB sequence
1 Alarm X 2 Warning 3 Trip of GB X X 4 Trip and stop X X 5 Shutdown X X 6 Trip of MB X
Fail class configuration
The fail class can be selected for each alarm function either via the display or the PC software.
To change the fail class via the PC software, the alarm function to be configured must be selected. Select the desired fail class in the fail class roll-down panel.
Action
Fail class
Alarm
horn relay
Alarm
display
Deload Trip of
gen.
breaker
Trip of
mains
breaker
Cooling-
down
gen-set
Stop
gen-set
1 Alarm X X 2 Warning X X 3 Trip of GB X X X 4 Trip and stop X X (X) X X X 5 Shutdown X X X X 6 Trip of MB X X X
In addition to the actions defined by the fail classes, it is possible to activate one or two relay outputs, if additional relays are available in the unit.
The fail class ‘trip and stop’ will only deload the gen-set before opening the breaker, if option G5 (power management) is included.
AGC Designer’s Reference Handbook
DEIF A/S Page 95 of 168
Service timers
The unit is able to monitor the maintenance intervals. The menu is available in the system setup.
6090 Service timer
The function is based on running hours. When the adjusted time expires, the unit will display an alarm. The ‘alarm acknowledge’ function resets this alarm.
When acknowledging the alarm, the timer will be reset and a new service timer alarm will only reoccur after the adjusted time has elapsed. The running hours is counting, when the running feedback is present.
Wire break detection
If it is necessary to supervise the sensors/wires connected to the analogue inputs (4-20mA, VDO and PT100), then it is possible to use the menus 4370-4430 depending on the HW options available in the unit. If the measured value on the input is outside the normal dynamic area of the input, it will be detected, as if the wire has made a short circuit or a break. An alarm with a configurable fail class will be activated.
Wire failure area Normal range Wire failure area
4-20mA Below 4mA 4-20mA Above 20mA
VDO 104 0…40% - 60…100% VDO 105 0…40% - 60…100% VDO 106 0…40% - 60…100%
PT100 – 106 0…40% - 60…100% PT100 – 109 0…40% - 60…100%
The fail class drop down panel is acti­vated, and the user wants to select the ‘trip of GB’ fail class.
AGC Designer’s Reference Handbook
DEIF A/S Page 96 of 168
Principle
The illustration below shows that when the wire of the input breaks, the measured value will drop to zero. Then the alarm will occur.
PT100 settings
The alarm setpoint of the PT100 inputs can be calculated in percent like this:
Example:
Required setpoint is 200 °C. The adjustment must be:
VDO settings
The alarm setpoint of the VDO inputs can be calculated in percent like this:
VDO 104, oil pressure:
VDO 105, cooling temp.:
VDO 106, fuel level:
The deviation is the alarm value entered in percent, and the setting is the required alarm setting
in ohms.
Example:
Required setpoint of VDO104 is 180. The adjustment must be:
Wire failure
Wire failure
Wire break
Lower failure limit
Upper failure limit
Input signal
(mA, °C, b, %)
t
9,2/)40(% += tdeviation
100*240/% settingdeviation =
%83
9,2/)40200(
%
%
=
+=
deviation
deviation
%75
100*240/180
%
%
=
=
deviation
deviation
100*530/
% settingdeviation =
100*240/
% settingdeviation =
AGC Designer’s Reference Handbook
DEIF A/S Page 97 of 168
Digital inputs
The unit has a number of binary inputs some of which are configurable and some are not. The number of digital inputs on the standard unit depends on the selected engine interface card.
Engine interface card Available digital inputs
– not configurable
Available digital inputs – configurable
M1 (standard) 2 3 M2 (option) 2 7
Input function Auto Semi Test Man Block Configurable Input
type
1 Fire pump X X X X Configurable Constant 2 Access lock X X X X X Not configurable Constant 3 Running feedback X X X X Not configurable Constant 4 Remote start X X Configurable Pulse 5 Remote stop X X Configurable Pulse 6 Semi-auto X X X X Configurable Pulse 7 Test X X X X Configurable Pulse 8 Auto X X X X Configurable Pulse 9 Manual X X X Configurable Pulse 10 Block X X X X Configurable Constant 11 Remote GB ON X Configurable Pulse 12 Remote GB OFF X Configurable Pulse 13 Remote MB ON X Configurable Pulse 14 Remote MB OFF X Configurable Pulse 15 Remote alarm
acknowledge
X X X X X Configurable Constant
16 Auto start/stop X Configurable Constant 17 Remove starter X X X X Configurable Constant 18 Reset analogue
GOV/AVR outputs
X X X X Configurable Pulse
19 Manual GOV up X Configurable Constant 20 Manual GOV down X Configurable Constant 21 Manual AVR up X Configurable Constant 22 Manual AVR down X Configurable Constant 23 Alarm inhibit X X X X X Not configurable Constant 24 GB position ON X X X X X Not configurable Constant 25 GB position OFF X X X X X Not configurable Constant 26 MB position ON X X X X X Not configurable Constant 27 MB position OFF X X X X X Not configurable Constant 28 Emergency stop X X X X X Text
configurable
Constant
29 External engine
failure
X X X X X Text
configurable
Constant
30 Low speed X X X Configurable Constant 31 Temperature
control
X X X Configurable Constant
32 Battery test X Configurable Pulse 33 Mains OK X X X X X Configurable Constant 34 External f control X X X Configurable Constant 35 External P control X X X Configurable Constant 36 External PF
control
X X X Configurable Constant
37 External U control X X X Configurable Constant
AGC Designer’s Reference Handbook
DEIF A/S Page 98 of 168
Input function Auto Semi Test Man Block Configurable Input
type
38 External Q power X X X Configurable Constant 39 Print status X X X Configurable Pulse 40 Print event log X X X Configurable Pulse 41 MB close inhibit X X X X X Configurable Constant 42 Engine comm.
inhibit
X X X X X Configurable Constant
43 Enable mode shift X Configurable Constant 44 Enable GB black
close
X X X X X Configurable Constant
45 Enable sep. sync. X X X X X Configurable Constant 46 Custom alarm
inhibit
X X X X X Configurable Constant
47 Start enable X X X X NA Configurable Constant 48 GB spring loaded X X X Configurable Constant 49 MB spring loaded X X X Configurable Constant
Functional description
1. Fire pump This input deactivates all protections except the overspeed protection and the emergency stop
input. The number of start attempts is 7 by default, but it can be configured in
6180 Start
attempts
. Also a special cool down timer is used in the stop sequence after an activation of this
input.
2. Access lock Activating the access lock input deactivates the control display push-buttons. It will only be
possible to view measurements, alarms and the log.
3. Running feedback The input is used as a running indication of the engine. When the input is activated, the start
relay is deactivated.
4. Remote start This input initiates the start sequence of the gen-set when semi-auto or manual mode is
selected.
5. Remote stop This input initiates the stop sequence of the gen-set when semi-auto or manual mode is
selected. The gen-set will stop without cooling-down.
6. Semi-auto Changes the present running mode to semi-auto.
7. Test Changes the present running mode to test.
8. Auto Changes the present running mode to auto.
9. Manual Changes the present running mode to manual.
AGC Designer’s Reference Handbook
DEIF A/S Page 99 of 168
10. Block Changes the present running mode to block.
11. Remote GB ON The generator breaker ON sequence will be initiated and the breaker will synchronise, if the
mains breaker is closed, or close without synchronising if the mains breaker is opened.
12. Remote GB OFF The generator breaker OFF sequence will be initiated. If the mains breaker is opened, then the
generator breaker will open instantly. If the mains breaker is closed, the generator load will be deloaded to the breaker open limit followed by a breaker opening.
13. Remote MB ON The mains breaker ON sequence will be initiated and the breaker will synchronise, if the
generator breaker is closed, or close without synchronising if the generator breaker is opened.
14. Remote MB OFF The mains breaker OFF sequence will be initiated, and the breaker will open instantly.
15. Remote alarm acknowledge Acknowledges all present alarms, and the alarm LED on the display stops flashing.
16. Auto start/stop The gen-set will start when this input is activated. The gen-set will be stopped, if the input is
deactivated. The input can be used when the unit is in island operation, fixed power, load take over or mains power export and the AUTO running mode is selected.
17. Remove starter The start sequence is deactivated. This means the start relay deactivates, and the starter motor
will disengage.
18. Reset analogue GOV/AVR outputs The analogue +/-20mA controller outputs will be reset to 0mA.
19. Manual GOV up If manual mode is selected, then the governor output will be increased.
20. Manual GOV down If manual mode is selected, then the governor output will be decreased.
21. Manual AVR up If manual mode is selected, then the AVR output will be increased.
When block mode is selected, the running mode cannot be changed by activatin
g
the digital inputs.
All analogue controller outputs are reset. That is the governor output and the AVR output, if option D1 is selected.
If an offset has been adjusted in the control setup, then the reset position will be the specific adjustment.
AGC Designer’s Reference Handbook
DEIF A/S Page 100 of 168
22. Manual AVR down If manual mode is selected, then the AVR output will be decreased.
23. Alarm inhibit Specific alarms are inhibited to prevent the alarms from occurring. Refer to page 69.
24. Generator breaker closed feedback (GB position ON) The input function is used as an indication of the generator breaker position. The unit requires
this feedback when the breaker is closed or a position failure alarm occurs.
25. Generator breaker open feedback (GB position OFF) The input function is used as an indication of the generator breaker position. The unit requires
this feedback, when the breaker is opened or a position failure alarm occurs.
26. Mains breaker closed feedback (MB position ON) The input function is used as an indication of the mains breaker position. The unit requires this
feedback, when the breaker is closed or a position failure alarm occurs.
27. Mains breaker open feedback (MB position OFF) The input function is used as an indication of the mains breaker position. The unit requires this
feedback, when the breaker is opened or a position failure alarm occurs.
28. Emergency stop The input shuts down the engine immediately. At the same time it opens the generator breaker.
29. External engine failure This input is an alarm input that can be given one of all the selectable fail classes.
30. Low speed Disables the regulators and keeps the gen-set running at a low RPM. All alarms set to ‘RUN’ will
be inhibited as long as the function is active.
31. Temperature control This input is part of the idle mode function. When the input is high, then the gen-set starts. It
starts at high or low speed, depending on the activation of the low speed input. When the input is deactivated, then the gen-set goes to idle mode (low speed = ON), or it stops (low speed = OFF).
32. Battery test Activates the starter motor without starting the gen-set. If the battery is weak, the test will cause
the battery voltage to drop more than acceptable, and an alarm will occur.
The manual governor and AVR increase and decrease inputs can only be used in manual mode.
Essential protections might also be inhibited, if this input is used.
The governor must be prepared for this function.
The shut-down fail class must be selected.
Loading...