Deif MTR-3 Installation Instructions Manual

Page 1
QUICK START GUIDE
INSTALLATION INSTRUCTIONS
SW version 3.0X.X or later
Multi-transducer, MTR-3
Page 2
MTR-3 Installation Instructions
DEIF A/S Page 2 of 51
Table of contents
1.
ABOUT THIS DOCUMENT ................................................................................................... 3
GENERAL PURPOSE ...................................................................................................................... 3
CONTENTS/OVERALL STRUCTURE .................................................................................................. 3
2. WARNINGS AND LEGAL INFORMATION ........................................................................... 4
LEGAL INFORMATION AND RESPONSIBILITY ..................................................................................... 4
ELECTROSTATIC DISCHARGE AWARENESS ..................................................................................... 4
SAFETY ISSUES ............................................................................................................................ 4
DEFINITIONS ................................................................................................................................ 4
SAFETY WARNINGS AND INSTRUCTIONS FOR USE ........................................................................... 5
WASTE ........................................................................................................................................ 5
3. BASIC DESCRIPTION AND OPERATION OF THE MTR-3 ................................................. 6
INTRODUCTION ............................................................................................................................. 6
USER INFORMATION ..................................................................................................................... 7
DESCRIPTION OF THE PRODUCT .................................................................................................... 7
PURPOSE AND USE OF ME ASURING TRANSDUCER ........................................................................... 8
4. CONNECTION ..................................................................................................................... 10
INTRODUCTION ........................................................................................................................... 10
MOUNTING ................................................................................................................................. 10
CONNECTION OF INPUT/OUTPUT MODULE S ................................................................................... 12
COMMUNICATION CONNECTION ................................................................................................... 12
CONNECTION OF AUXILIARY POWER SUPPLY ................................................................................ 14
5. SETTINGS ........................................................................................................................... 15
INTRODUCTION ........................................................................................................................... 15
M-SET SOFTWARE...................................................................................................................... 15
SETTING PROCEDURE ................................................................................................................. 16
GENERAL SETTINGS ................................................................................................................... 16
CONNECTION ............................................................................................................................. 18
COMMUNICATION ....................................................................................................................... 18
SECURITY .................................................................................................................................. 19
ENERGY .................................................................................................................................... 19
ANALOGUE OUTPUTS .................................................................................................................. 20
ALARMS ..................................................................................................................................... 23
RESET OPERATIONS ................................................................................................................... 23
6. MEASUREMENTS ............................................................................................................... 24
INTRODUCTION ........................................................................................................................... 24
SUPPORTED MEASUREMENTS ..................................................................................................... 24
AVAILABLE CONNECTIONS ........................................................................................................... 24
EXPLANATION OF BASIC CONCEPTS ............................................................................................. 26
CALCULATION AND DISPLAY OF MEASUREMENTS .......................................................................... 26
PRESENT VALUES ....................................................................................................................... 27
7. APPENDIX A: MODBUS PROTOCOL ............................................................................... 29
MODBUS COMMUNICATION PROTOCOL ......................................................................................... 29
8. APPENDIX B: CALCULATIONS AND EQUATIONS ......................................................... 49
CALCULATIONS .......................................................................................................................... 49
Page 3
MTR-3 Installation Instructions
DEIF A/S Page 3 of 51
1. About this document
General purpose
This document is the Installation Instructions for the Multi-configurable AC Transducer, the MTR-
3. T he general purpose of the document is to help th e user with the firs t steps of installing an d using the unit. It contains instructions for installations and use of the MTR-3.
Contents/overall structure
This document is divid ed into chapters, and in or der to make the struc ture simple and easy to use, each chapter will begin from the top of a new page.
Please make sure that you read this document before starting to work with the
MTR-3. Failure to do this could result in human injury or damage to the equipment.
Page 4
MTR-3 Installation Instructions
DEIF A/S Page 4 of 51
2. Warnings and legal information
This chapter includes important information about general legal issues relevant in the handling of DEIF products. Furthermore, some overall safety precautions will be introduced and recommended. Finall y, the highlighted notes and warnings, which will be us ed throughout this document, are presented.
Legal information and responsibility
DEIF takes no responsibility for installation or operation of the MTR-3. If there is any doubt regarding installation and use of the system in which the instrum ent is used for measuring or supervision, please contact the person or company responsible for the installation of such system.
Electrostatic discharge awareness
Sufficient care must be taken to protect the terminals against static discharges during the installation. Once the unit is installed and connected, these precautions are no longer necessary.
Safety issues
Installing the unit implies work with danger ous cur rents and voltag es. Ther efore, the instal lation of the unit should onl y be car ried o ut b y auth or ised p ersonnel who understa nd th e r isk s involved in the working with live electrical equipment.
Definitions
Throughout this document, a number of notes with helpful user information will be presented. To ensure that these are noticed, they will be highlighted in order to separate them from the general text.
Note symbol
Warnings
Be aware of the hazardous live currents and voltages. Do not touch any AC
measurement inputs as this could lead to injury or death.
The notes provide general informa tion which will b e helpful for the r eader to bea r
in mind.
The warnings indicate a potentially dangerous situation which could result in
death, personal injury or damaged equipment if certain guidelines are not followed.
The units are not to be opened by unauthorised personnel. If opened anyway, the
warranty will be lost.
Page 5
MTR-3 Installation Instructions
DEIF A/S Page 5 of 51
Safety warnings and instructions for use
Check the following before switching on the device:
Nominal voltage
Proper connection of auxiliary supply
Nominal frequency
Voltage ratio and phase sequence
Current transformer ratio and terminals’ integrity
Protection fuse – recommended maximal external fuse size is 6 A
Proper connection of I/O modules
Waste
It is forbidden to deposit electrical and electronic equipment as municipal waste. The manufacturer or provider shall take waste electrical and electronic equipment free of charge. The complete procedure after lifetime should comply with the Directive EZ 2002/96/EG about restriction on the use of certain hazardous substances in electrical and electronic equipment or a corresponding Url 118/04.
The secondary output of the current trans former should be short-circuited before
connecting the transducer.
Page 6
MTR-3 Installation Instructions
DEIF A/S Page 6 of 51
3. Basic description and operation of the MTR-3
Introduction
What is in the delivery?
The consignment includes:
Multi transducer MTR-3
Label for I/O functionality description
Quick Start Guide
Description of symbols
In different chapters or tables, different symbols may appear in the installation instructions. According to the position of symbols, they have different meanings.
Double insulation in compliance with the SIST EN 61010-1 standard.
Functional ground potential.
Note: this symbol is also used for marking a terminal for protective ground potential if it is used as a part of connection terminal or auxiliary supply
terminals.
Compliance of the product with directive 2002/96/EC, as first priority, the
prevention of waste electrical and electronic equipment
(WEEE), and in
addition, the reuse, recycling and other forms of recovery of such wastes so as to reduce the disposal of waste. It also seeks to improve the en vironmental performance of all operators involved in the life cycle of electrical and electronic
equipment.
Compliance of the product with European CE directives.
Subchapter
Symbols next to the s ubchapters indicate accessibility of functions described.
Accessibility of functions is indicated with the following symbols:
Function accessible via communication (M-Set software)
Tables
Supported functions and m easur ements are listed in t ables. S ymbols in ta bles indicate support of enabled functions. Additionally, a legend is placed the below table of used symbols. The meaning of symbols is:
Function is supported × Function is not supported Symbol meaning varies and is described in the legend below the table
Page 7
MTR-3 Installation Instructions
DEIF A/S Page 7 of 51
User information
For unknown technical terms, please refer to the below glossary.
Glossary
Term Explanation
RMS
Root Mean Square value
Modbus
Industrial protocol for data transmission
M-Set
Software for MTR-3
AC
Alternating voltage and current
PA total
Angle calculated from total active and apparent power
PA1, PA2, PA3
Angle between fundamental phase voltage and phase current
PF
Power factor
THD
Total Harmonic Distortion
MD
Measurement of average values in time interval
Hand-over place
Connection spot of consumer installation in public network
Mv − Sample factor
Defines a number of periods for measuring calculation on the basis of measured frequency
Mp − Average interval
Defines frequency of refreshing displayed measurements on the basis of a sample factor
Hysteresis
expressed as
percentage [%]
Percentage specifies increase or decrease of a measurement from a
certain limit after exceeding it.
Description of the product
The measuring tr ansducer is in tended for m easuring, ana lysing and m onitoring si ngle-phase or three-phase electrical power network. It measures RMS value by means of fast sampling of voltage and current signals, which makes the instrument suitable for acquisition of transient events. A built-in micro controller calculates measurements (voltage, current, frequency, energy, power, power factor, THD phase angles, etc.) from the measured signals.
Appearance
The measuring transducer can differ from yours depending on the type and functionality.
1 Communication ports 2 Outputs 3 Auxiliary supply 4 Voltage inputs 5 Current inputs 6 Power ON LED
Communication ports and LED indicators
Serial communication c an be connected by us ing screw-in connector (R S485). A USB can be connected through a USB-mini type connector at the bottom of the transducer. LED indicator is intended for POWER ON signalling (red LED).
The USB communication port is NOT galvanically insulated and can be used ONLY UN-connected to aux. supply and power inputs!
Page 8
MTR-3 Installation Instructions
DEIF A/S Page 8 of 51
Universal auxiliary supply
Auxiliary supply is connected by two screw-in connectors. For safety purposes, it is important that all wires are firmly fastened. Auxiliary supply is wide range (24V DC-300V DC; 40V AC-276V AC).
Voltage inputs
Each voltage input is connec ted to a measuring circuit thr ough an input resistor chain (3. 3 M per phase). Maximum value of input voltage is 600 V
L-N
(1000 V
L-L
).
Current inputs
Each current input is conn e c ted to a measuring circuit thr oug h a current transform er ( 0.01 per phase). Maximum allowed thermal value of input current is 15 A (cont.).
Purpose and use of measuring transducer
The instrument is used for monitoring and measuring electric qua nti ties of thr ee-phase electrical power distribution system. The meter is provided with 32 programme-adjustable alarms and communication. With the RS485 and USB communication, the transducer can be configured and by RS485 also m eas urements can be read. The transducer also f unc ti ons as an energy counter (up to four energy counters).
Page 9
MTR-3 Installation Instructions
DEIF A/S Page 9 of 51
Supported measurements
Basic measurements
Phase
Voltage U1, U2, U3 and U~
Current I1, I2, I3, In, It and I
a
Active power P1, P2, P3, and Pt
Reactive power Q1, Q2, Q3, and Qt
Apparent power S1, S2, S3, and St
Power factor PF1, PF2, PF3 and PF~
Power angle φ1, φ2, φ
3
and φ~
THD of phase voltage Uf1, Uf2 and Uf3
THD of power angle I1, I2 and I3
Phase-to­phase
Phase-to-phase voltage U12, U23, U31
Average phase-to-phase voltage Uff
Phase-to-phase angle φ
12
, φ23, φ
31
THD of phase−to−phase voltage
Energy
Counter 1
Counter 2
Counter 3
Counter 4
Active tariff
Other measurements
MD values
Phase current I1, I2, I3
Active power P (Positive)
Active power P (Negative)
Reactive power Q − L
Reactive power Q − C
Apparent power S
Other measurements
Measurements
Frequency
Internal temperature
Page 10
MTR-3 Installation Instructions
DEIF A/S Page 10 of 51
4. Connection
Introduction
This chapter deals with the instructions for connection of the measuring transducer. Both the use and connection of the device includes handling with dangerous currents and voltages. Only qualified persons should therefor e perform connection. DEIF does not take an y responsibility regarding the use and connection. If any doubt occurs regarding connection and use in the system, please contact the person or company responsible for such installations.
Before use: check voltages and phase rotation, supply voltage and nominal frequency. Check protective fuse rati ng (the recomm ended maximum r ating of the external protecti ve fuse
for this equipment is 6 A - Red Spot type or equivalent).
Mounting
The MTR-3 is designed for DIN rail mounting. It should be mounted on a 35 mm DIN rail by means of three plastic fasteners. Before installation, fasteners should be in open position (pulled). When the device is in place, lock (push) the fasteners to closed position.
Electric connection
Voltage inputs of the measuring transducer can be connected directly to a low-voltage network or via an appropriate voltage measuring transformer to a medium or high voltage network.
Current inputs of the measuring transducer can be connected directly to a low-voltage network or via a corresponding current transformer.
Choose the corresponding connecti on from the following figures and conn ect the corresponding voltages and currents. Information on electrical characteristics is given in the data s heet.
Wrong or incomplete connection of supply, measurement or other terminals may cause malfunction or damage the device.
After connection, settings are performed via communication (connection mode,
current and voltage transformers ratio...).
Page 11
MTR-3 Installation Instructions
DEIF A/S Page 11 of 51
System/connection Terminal assignment
Connection 1b (1W)
Single-phase connection
Connection 3b (1W3)
Three-phase – three-wire connection with balanced load
Connection 3u (2W3u)
Three-phase – three-wire connection with unbalanced load
Direct connection 3u (2W3u)
Three-phase, three-wire direct connection
Connection 4b (1W4)
Three-phase – four-wire connection with balanced load
Page 12
MTR-3 Installation Instructions
DEIF A/S Page 12 of 51
Connection 4u (3W4)
Three-phase – four-wire connection with unbalanced load
Connection of input/output modules
Connect the module contac ts as s pecified on the labe l. Ex am ples of lab els are gi ven b elo w and describe modules built in the device.
Analogue output module with analogue
output, proportional to measured qua ntities. The outputs may be either short- or open-circuited. The y are e lec tricall y ins ulated from each other and from all other circuits. (Example of analogue output 1).
Fast analogue output m odule with analogue
output, proportional to measured quantities. The outputs may be either short- or open­circuited. They are electr ically insulated from
each other and from all other circuits. (Example of analogue output 1).
Communication connection
The MTR-3 is equipped wit h one standard serial (RS4 85) communication port a nd one service communication port (USB).
Connect the communication line by means of the corresponding terminals. Connection information is stated on the instrument label. Connector terminals are marked on the label on the upper side of the instrument.
The USB connector is position ed on the bottom side of the instrum ent under rem ovable plastic cover. For driver installat ion, the below note. The ins trument will esta blish USB connect ion with the PC approx. 5 seconds after physical connection to the USB port.
More detailed information about communication specifications is available in the data sheet.
The USB communication port is NOT galvanically insulated and can be used ONLY UN-connected to aux. supply and power inputs!
Check the module features that are specified on the label, before connecting
module contacts. Wrong connection may cause damage or destruction of
module and/or device.
Page 13
MTR-3 Installation Instructions
DEIF A/S Page 13 of 51
Serial communication port (RS485)
SERVICE communication port (USB)
RS485
RS485 communication is intended for connection of devices to network where several instruments with RS485 communication are connected to a common communication interface.
It is necessary to provide the corresponding connection of individual terminals of the screw terminal connector (see the table below).
USB
USB communication s erves as a fast p eer-to-terminal data link. The instrument is detected b y host as a USB 2.0 com patible device. T he U SB conne ction is provid ed thro ugh a USB st andard type mini B connector.
When the MTR-3 is connected to a PC through USB communication for the first
time, a user is prompted to install a driver. The driver is provided when downloading M-Set. T he M-Set software can be downloaded at
www.deif.com.
When the driver is installed, the USB is redirect ed to a s erial p ort , w hich sh ould
be selected when using M-Set software.
Page 14
MTR-3 Installation Instructions
DEIF A/S Page 14 of 51
Survey of communication connections
Connector
Terminals
Position
RS485
SCREW TERMINAL
11 A 12 C 13 B
11 A 12
NC
13
B
USB-mini B
Standard USB 2.0 compatible cable recommended (type mini B plug)
Connection of auxiliary power supply
The MTR-3 multi transducer has universal (AC/DC) auxiliary power supply. Information on electric consumption is give n in the data sh eet. Auxiliar y supply is conn ected through a screw terminal connector.
Connection of universal power supply to terminals 1 and 2.
For safety purposes, it is important that both wires (Li ne and Ne utral) are firmly connected.
Page 15
MTR-3 Installation Instructions
DEIF A/S Page 15 of 51
5. Settings
Introduction
Instrument settings c an be remotely modified w ith communication (RS485 or USB) and M-Set software when connected to a PC.
M-Set software
M-Set is a software tool for complete monitoring of measuring instruments, connected to a PC via serial or USB communication. A user-friendly interface consists of four segments: device management, instrument settings, real-time measurements and software upgrading.
Device management
Select the instrument in a favourite’s line. Use the network explorer to set and explore the device’s network. Communic ation parameters of all dev ices and their addresses in the network c an be easily set.
Instrument settings
Multi register edit technology assures a simple modification of settings that are organised in a tree structure. Besides transf erring settings into t he instrum ent, storing and reading f rom the setting files are also available.
Real-time measurements
All supported meas ur ements can be captured in r ea l t ime in a table form. For further processi ng of the results of measurements, copying via a clipboard into standard Windows formats is supported.
Software upgrading
Always use the latest version of software, both M-Set and software in the instrument. The programme autom atically informs you on available upgrades that can be transf erred from the website and used for upgrading.
More information about the M-Set software can be found in the M-Set help system.
Page 16
MTR-3 Installation Instructions
DEIF A/S Page 16 of 51
M-Set user interface
Setting procedure
In order to modify instrument settings with M-Set, current parameters must be loaded first. Instrument settings c an be acquire d via a comm unication link (ser ial or USB) or c an be loaded off-line from a file on a local disk. Settings are displayed in the M-Set setting window - the left part displays a hierarchica l tree structur e of settings, the r ight part displa ys parameter values of the chosen setting group.
General settings
General settings are es sen tial for the tr ansducer . T hey ar e di vided int o four addit ional s uble vels (Connection, Communication, Display and Security).
Description and location
Two parameters that are intended for easier recognition of a certain unit. They are especially used for identification of the device or location on which measurements are performed.
Average interval
The averaging interv al def ines t he ref res h rate of m easur em ents on com m unication and r em ote display.
Temperature unit
Choose a unit for temperature display.
Maximum demand calculation (MD mode)
The instrument provides maximum demand values using therm al function. A thermal function assures exponent thermal characteristic based on simulation of bimetal meters. Maximum values and time of their oc cur r ence ar e s tored in the device. A t ime constant (t. c.) c a n b e s et from 1 to 255 minutes and is 6 times the thermal time constant (t. c. = 6 * thermal time constant).
You can download freeware M-Set from www.deif.com.
Page 17
MTR-3 Installation Instructions
DEIF A/S Page 17 of 51
Example:
Mode: thermal function Time constant: 8 min. Current MD and maximal MD: reset at 0 min.
Starting current for PF and PA (mA)
At all measuring inputs , noise is usually presen t. I t is c ons tant , and its influence o n the ac cur acy is increased by decreasin g measuring signals. It is pre s ent als o when measuring signals are not connected, and it oc curs at all f urther calc ulat ions as v ery sp oradic m easurem ents. B y settin g a common starting cur rent, a limit of input signal is d efined where measurements and all other calculations are still performed.
Starting current for all powers (mA)
Noise is limited with a starting current also at measurements and calculations of powers.
Minimum synchronisation voltage
If all phase voltages ar e smaller than this (nois e l imit) setting, the instrument uses current in puts for synchronisation. If also all phas e curr ents are s maller t han Starting current for PF and PA setting, synchronisation is not possible and frequency displayed is 0.
Reactive power and energy calculation
Two different principles of reactive power and energy calculation are used:
Standard method:
With this method, a r eactive power and energy is calculated, based on the ass umption that al l power (energy), which is not active, is reactive.
Q
2
= S2 – P2
This also means that all higher harmonics will be measured as reactive power (energy).
Delayed current method:
With this method, reacti ve po wer (ener gy) is c alculate d b y multipl ication of volta ge samples and delayed current samples (see chapter 8, “Ap pen dix B: Calc u lat ions and equations” on page 36):
Q = U × I|
+90°
With this method, reactive power (energy) only represents the true reactive component of apparent power (energy).
Thermal functi on
0 1 2 3
4
5 6
7 8
9
10 11
12 13 14 15
16
17 18
19 20
Time [min.]
Measured value
Present MD
MD peak
Input
Page 18
MTR-3 Installation Instructions
DEIF A/S Page 18 of 51
Connection
Connection
When connection is selected, load connection and the supported measurements are defined (see chapter 6, “Measurements” regarding connection mode, on page 23).
Setting of current and voltage ratios
Before setting current and voltage ratios, it is necessary to be familiar with the conditions in which the device is t o be used. All other measurements and calcul ati ons d epe nd o n these settings. Up to five decimal places can be set.
Settings range
VT primary
VT secondary
CT primary
CT secondary
Maximum value
1638.3 kV
13383 V
1638.3 kA
13383 A
Minimum value
0.1 V
1 mV
0.1 A
1 mA
Used voltage and current range
Setting of the rang e is connected with all settings of alarms, analogue outputs and a display (calculation) of energy and measurements recording, where 100% represents 500 V 5 A. In case of subsequent change of the range, alarms settings must be correspondingly changed, as well.
Nominal frequency
A valid frequency measur ement is within the r ange of nom inal frequenc y ±32 H z. This setting is used for alarms.
Energy flow direction
This setting allo ws m anual c hange of ener g y flow d irec tion (I MPORT to EX PORT or vice versa) in the readings tab. It has no influence on readings sent by communication.
CT connection
If this setting is set to REVERSED, it has the same influence as if CTs would be reversely connected. All power readings will also change their sign.
Communication
Serial Communication
Define parameters that are important for the operation in the RS485 network. Factory settings of communication are #3 3\115200,n,8,2 (address 1 to 247\baud rate 2400 to 115200 b/s, parity, data bits, stop bit).
Modbus table: with this setting, a Modbus table for measurements and settings is defined. Modbus addresses for measurements and settings can be compatible with the previous family of transducers (MTR-2). For a more detailed description, see chapter 7, “Appendix A: Modbus protocol”, on page 28.
USB Communication
For description of a ll settings see Serial Commun ication, appendix A. For driver inst allation, see the note on page 13. The instrum ent will establish a USB connection with the PC approx. 5 seconds after physical connection to the USB port.
Settings of connections must reflect actual state, otherwise measurements are
not valid.
Page 19
MTR-3 Installation Instructions
DEIF A/S Page 19 of 51
Security
Parameter settings are divided int o three groups regarding security level:
1. At the firs t level ( PL1), sett ings of a real t im e clock c an be cha ng ed, an d energy meters and MD can be reset.
2. At the second l evel (PL2), the access to all d ata that are protected with t he first level (PL1) and setting of all other parameters in the »SETTINGS« menu is available.
3. A backup password (B P) is used if pas swords at levels 1 (PL1) and 2 (PL2) have been forgotten, and it is different for each device (depending on a serial number of the meter). The BP password is available in the support department at DEIF, and is entered instead of the password PL1 or/an d PL2. Do not forget to sta te the meter serial number when contacting the personnel at DEIF.
User information
Password setting
A password consists of four letters taken from the British alphabet from A to Z. When setting a password, only the letter being set is visible while the others are covered with *. Two passwords (PL1, PL2) and the time of automatic activation could be set.
Password modification
A password can be modified; however, only that password can be modified to which the access is unlocked at the moment.
Password disabling
A password is disabled by setting the "AAAA" password.
Energy
Active tariff
When active tariff is set, one of the tariffs (up to four) is defined as active.
Common energy exponent
Common energy expon ent def ines minimal energy that c an be displayed on the energ y c oun ter .
On the basis of this and a counter divider, a basic calculation prefix for energy is defined (−3 is
10
3
Wh = mW h, 4 is 104Wh = 10 kW h). A com m on energy expo nent als o inf luenc es in sett ing a
number of impulses for energy of pulse output or alarm output functioning as an energy meter. Define the common energy exponent as recommended in the table below, where counter divider
is value 10 as default. Values of primary voltage and current determine a proper common energy exponent.
A serial number of devic e is stated on the lab el and also acc essible wit h the M-
Set software.
A factory-set password is “AAAA” at both access levels (L1 and L2). This
password does not limit access.
After modification of energy parameters, the energy meters must be reset. Otherwise, all further energy measurements could be incorrect.
Page 20
MTR-3 Installation Instructions
DEIF A/S Page 20 of 51
Current
Voltage
1 A
5 A
50 A
100 A
1000 A
110 V
-1 0 1 1 2
230 V 0 0 1 2
3
1000 V 0 1 2 3
4
30 kV 2 2 3 4
4*
* Counter divider should be at least 100
Counter divider
Additionally, the counter divider def ines precis ion of a cer tain co unter, ac cordi ng to s ettings of a common energy exponent. This is done to prevent the counter from having an early energy overflow.
An example for 23.331 kWh of consumed active energy:
Divider
Exponent
Resolution
Displayed
1 0 1 x 10^0 = 1 W
23.331 kW
10 0 10 x 10^0 = 10 W
23.33 kW
100 0 100 x 10^0 = 100 W
0.0233 MW
1000
0
1000 x 10^0 = 1 kW
0.023 MW
1 1 1 x 10^1 = 10 W
23.33 kW
1 2 1 x 10^2 = 100 W
0.0233 MW
1 3 1 x 10^3 = 1 kW
0.023 MW
1 4 1 x 10^4 = 10 kW
0.02 MW
10 2 10 x 10^2 = 1 kW
0.023 MW
Analogue outputs
Number of analogue outputs depends on the version of MTR-3.
Analogue outputs
Each of up to four an alogue out puts is f ully programm able and can be set to an y of 6 full-scale ranges. Within each of tho se 6 ranges, other required outp ut ranges can be set. For example, 4…20 mA range can be set when ±20 mA full-scale range is selected:
Output parameter
Sets the measured parameter to be transformed onto the analogue output.
Page 21
MTR-3 Installation Instructions
DEIF A/S Page 21 of 51
Output range
Defines analogue output full-scale ranges:
DC current output
DC voltage output
-1…0…1 mA
-1…0…1 V
-5…0…5 mA
-10...0...10 mA
-10…0…10 V
-20...0...20 mA
Output characteristics
Defines the shape and up to 5 break points of an analogue output. For intrinsic-error for analogue outputs with bent or lin ear zoom character istic m ultiply accur acy class with corre ction factor (c). Correction factor c (the highest value applies):
Linear characteristic
Bent characteristic
1
1
1
0
0
=
= cor
x
x
y
y
c
e
e
bb
xxx
1
b – number of break points (1 to 5)
1
1
1
=
=
cor
y
x
xx
yy
c
e
e
bb
bb
Example of settings with linear and bent characteristic:
Average interval for analogue output
Defines the average interval for measurements on the analogue output. Avail able settings are from 1 period (0.02 sec by 50 Hz) up to 128 periods (2.56 sec by 50 Hz).
Fast analogue output
Functionality of the fast analogue output module is the same as with the standard analogue output module.
The only difference is its faster response time (≤ 50 ms), and consequential higher ripple. For a
proper behaviour of the fast analogue output module (f ast response), the average inter val must be set to minimum (1 period).
Relay output module
Relay output module can be assigned different functions.
Alarm notification functionality (alarm output)
Pulse output for energy measurement (pulse output)
General purpose digital output (digital output)
Page 22
MTR-3 Installation Instructions
DEIF A/S Page 22 of 51
Pulse output functionality A corresponding energy counter (up to 4) can be assigned to a pulse output. A number of pulses
per energy unit, pulse length, and a tariff in which output is active are set.
Calculation of recommended pulse parameters
Number of pulses per energy unit s hould be in cer tain lim its acc ording to expec ted po wer. If not so, the measurement from pulse output can be incorrect. Settings of current and voltage transformers can help in estimation of expected power.
Principle described belo w f or pulse setting, where e is prefix, satisfies SIST EN 62053−31: 2001 standards pulse specifications:
eWhpeW 1100155.1 K
Examples:
Expected power
Pulse output settings
150 − 1500 kW
1 p/1kWh
1.5 − 15 MW
100 p/1MWh
15 − 150 MW
10 p/1MWh
150 − 1500 MW
1 p/1MWh
Alarm notification functionality An alarm notificatio n function ca n also be as signed to out put. In cas e of an y alarm occ urrence,
alarm output will trigger passive electromechanical relay or passive solid-state relay. Two parameters should be defined for each alarm output:
The source for assigned alarm (alarm group 1, 2 or both)
Type of output signal when alarm is detected.
General purpose digital output This functionality allows user to enable/disable output relay by software settings (when
appropriate values are set in Modbus table).
MODULE NUMBER
MODBUS REGISTER
REGISTER VALUE
Module 1 (if installed)
40722
3 - ON
4 - OFF
Module 2 (if installed) 40725 3 - ON 4 - OFF
Module 3 (if installed)
40728
3 - ON
4 - OFF
Module 4 (if installed)
40731
3 - ON
4 - OFF
Pulse parameters are defined by SIST EN 62053−31 standard. In the section
“Calculation of recommended pulse parameters” below, a simplified rule is described to assist you in setting the pulse o utp ut parameters.
Page 23
MTR-3 Installation Instructions
DEIF A/S Page 23 of 51
Alarms
Alarms are used for alarming exceeded set values of the measured quantities.
Alarms setting
MTR-3 supports recording and storage of 16 alarm s in two groups. For each grou p of alarms , a time constant of maximal values in thermal mode, a delay time and alarm deactivation hysteresis can be defined.
Quantity, value (a current value or a MD – thermal function) are defined for every individual alarm.
Reset operations
Reset energy counters (E1, E2, E3, E4)
All or individual energy meters are reset.
Reset MD values
Current and stored MDs are reset.
Reset the last MD period
Current MD value is reset.
Reset alarm output
All alarms are reset.
New values of alarms a re calculated in percentage at the modification of the
connection settings. If used voltage, current range is changed, the limit values
of alarms will change proportionally.
Page 24
MTR-3 Installation Instructions
DEIF A/S Page 24 of 51
6. Measurements
Introduction
In the following chapters, the device operation is explained in more details.
Supported measurements
Selection of supporte d measurements is changed with the c onnection settings. All supported measurements can be read via communication (M-Set and Modbus).
Available connections
Different electric con nections are described in more details in “ Electric conn ection” in chapter 4 “Connection”. Connections are marked as follows:
Connection 1b (1W) − single phase connection
Connection 3b (1W3) − three-phase – three-wire connection with balanced load
Connection 4b (1W4) − three-phase – four-wire connection with balanced load
Connection 3u (2W3) − three-phase – three-wire connection with unbalanced load
Connection 4u (3W4) − three-phase – four-wire connection with unbalanced load
Survey of supported measurements regarding connection mode
Basic measurements
Designat.
Unit
1b
3b
3u
4b
4u
Phase
Voltage U1
U1
V
● × × ● ●
Voltage U2
U2
V
× × × ○ ●
Voltage U3
U3
V
× × × ○ ●
Average voltage U~
U
V
× × × ○ ●
Current I1
I1
A
● ● ● ● ●
Current I2
I2
A
× ○ ● ○ ●
Current I3
I3
A
× ○ ● ○ ●
Current In
Inc
A
× ○ ○ ○ ●
Total current I
t
I
A
● ○ ○ ○ ●
Average current I
a
Iavg
A
× ○ ○ ○ ●
Active power P1
P1
W
● × × ● ●
Active power P2
P2
W
× × × ○ ●
Active power P3
P3
W
× × ×
Total active power Pt
P
W
● ● ● ○ ●
Reactive power Q1
Q1
VAr
● × × ● ●
Reactive power Q2
Q2
VAr
× × × ○ ●
Reactive power Q3
Q3
VAr
× × ×
Total reactive power Qt
Q
VAr
● ● ● ○ ●
– supported ○ − calculated × − not supported
Measurement support depends on the connection mode of the instrument type.
Calculated measurements are only informative.
Page 25
MTR-3 Installation Instructions
DEIF A/S Page 25 of 51
Basic measurements
Designat.
Unit
1b
3b
3u
4b
4u
Phase
Apparent power S1
S1
VA ● × × ●
Apparent power S2
S2
VA × × × ○ ● Apparent power S3
S3
VA × × × ○ ● Total apparent power St
S
VA ● ● ● ○ ● Power factor PF1
PF1/ePF1
● × × ● ● Power factor PF2
PF2/ePF2
× × × ○ ● Power factor PF3
PF3/ePF3
× × × ○ ● Total power factor PF~
PF/ePF
● ● ● ○
Power angle φ
1
φ1
° ● × × ●
Power angle φ
2
φ2
° × × × ○
Power angle φ
3
φ3
° × × × ○
Total power angle φ
~
φ ° ●
THD of phase voltage Uf1
U1 %
%THD
× × ●
THD of phase voltage Uf2
U2 %
%THD
× × × ○ ●
THD of phase voltage Uf3
U3 %
%THD
× × × ○ ●
THD of phase current I1
I1 %
%THD
THD of phase current I2
I2 %
%THD
× ○ ● ○ ●
THD of phase current I3
I3 %
%THD
× ○ ● ○ ●
Phase-to-phase
Phase-to-phase voltage U12
U12
V × ● ● ○
Phase-to-phase voltage U23
U23
V × ● ● ○ ● Phase-to-phase voltage U31
U31
V × ● ● ○ ● Average phase-to-phase voltage (Uff)
U
V × ● ● ○ ● Phase-to-phase angle φ12
φ12
° × × × ○ ● Phase-to-phase angle φ23
φ23
° × × × ○ ● Phase-to-phase angle φ31
φ31
° × × × ○ ● THD of phase-to-phase voltage U
12
U12 %
%THD
× ● ● ○ ●
THD of phase-to-phase voltage U23
U23 %
%THD
× ● ● ○ ●
THD of phase-to-phase voltage U31
U31 %
%THD
× ● ● ○ ●
Energy
Counters 1−4
E1, E2,
E3, E4
Wh
VAh
VArh
Active tariff
Atar
● ● ● ●
Max. values MD
MD current I1
I1
A
MD current I2
I2
A × ○ ● ○ ● MD current I3
I3
A × ○ ● ○ ● MD active power P (positive)
P+
W ● ● ● ● ● MD active power P (negative)
P−
W ● ● ● ● ● MD reactive power Q−L
Q
VAr ● ● ● ● ● MD reactive power Q−C
Q
VAr ● ● ● ● ● MD apparent power S
S
VA ● ● ● ●
– supported ○ − calculated × − not supported
For 3b and 3u connection modes, only phase-to-phase voltages are measured.
Because of that, factor √3 i s applied to calculation of quality consi dering nominal phase voltage.
For 4u connection mode, measurement support is the same as for 1b.
Page 26
MTR-3 Installation Instructions
DEIF A/S Page 26 of 51
Explanation of basic concepts
Sample factor − MV
A meter measures al l primary quantities with sample frequenc y which cannot exc eed a certain number of samples i n a time p eriod. Based o n these li mitations (65 Hz·128 sam ples) a sam ple factor is calculated. A sample factor (M
V
), depending on frequency of a measured signal, defines a number of periods for a measurement calculation a nd th us a n umber of harmonics c onsid er ed in THD calculations.
Average interval − M
P
Due to readability of m easurem ents from c ommunication, an average interval ( M
P
) is calculate d with regard to the measur ed signal frequency. The average interval (see “A verage interval” on page 16) defines the refresh rate of displayed measurements based on a sampling factor.
Power and energy flow
The figure below shows a flow of active power, reactive power and energy for 4u connection.
Calculation and display of measurements
This chapter deals with capture, calculation and display of all supported quantities of measurement. Only the most important equations are described; however, all of them are shown in chapter 8, “Appendix B: Calc ulations and equations” on page 36 with additional descr iptions and explanations.
The power and energ y flow is defined as standard from a generator’s point of
view. This means t hat a consumer using energy will be exporting power. It is possible to change export/impor t definition via the M-Set, by changing the energy flow direction.
Calculation and display of measurements depend on the used connection. For
more detailed information, see “Survey of supported measurements regarding connection mode” on page 23.
Page 27
MTR-3 Installation Instructions
DEIF A/S Page 27 of 51
Present values
All values are calculated as an average of number of periods set in general sett ings/average interval.
Voltage
The instrument meas ures true RMS values of all phas e voltag es (U 1, U2, U3), c onnect ed to the transducer. Phase-to-phas e v olt ages ( U12, U 2 3, U 31), average phase volt age ( U f) and average phase-to-phase voltage (Ua) are calculated from measured phase voltages (U1, U2, U3).
N
u
=
U
2 n
N
1=n
f
( )
N
2
yn
xn
N
1=n
xy
uu
=
U
All voltage measurements are available via communication.
Current
Instrument meas ures true RMS values of phase currents, connec ted to current inp uts. Neutral current (I
n
), average current ( Ia) and a sum of all phase current s (It) are calculated from phas e
currents.
N
i
=
2 n
I
N
1=n
RMS
All current measurements are available via communication.
Active, reactive and apparent power
Active power is calculated from instantaneous phase voltages and currents. Two different principles of reactive power calculation are used:
Standard method:
With this method, a reactive power is calculated based on the assumption that all power which is not active is reactive.
Q
2
= S2 – P2
This also means that all higher harmonics will be measured as reactive power.
Delayed current method:
With this method, reacti ve po wer (ener gy) is calcul ated b y multipl ication of volta ge s am ples and delayed current samples (see chapter 8, “Ap pen dix B: C alcu lat ions a nd equations” on page 36:
Q = U × I|
+90°
With this method, reactive power (energy) only represents the true reactive component of apparent power (energy).
All measurements are s een vi a communication. For m ore det ai led inf or mation about calculation, see chapter 8, “Appendix B: Calculations and equations” on page 36.
Page 28
MTR-3 Installation Instructions
DEIF A/S Page 28 of 51
Power factor and power angle
Power factor is calculat ed as quotient of acti ve and apparent power for each phase separ ately (cosϕ
1
, cosϕ2, cosϕ3) and total power angle (cosϕt). For correct display of PF via analogue output and application of the alar m, ePF (extended power factor ) is applied. It illustrates po wer factor with one value as described in the table below. For a display on the remote display, both of them have an equal display function: between −1 and −1 with the icon for inductive or capacitive load.
Load C
L
Angle [°] 180 90 0 +90 +180 (179.99)
PF
1 0 1 0 −1
ePF
1 0 1 2 3
Example of analogue output for PF and ePF:
The power angle represent s the angle between the first voltage harm onic and the first current harmonic for each ind ivid ua l ph as e. T he t ot al p o wer a n gle is c alcu late d from the total act ive a nd reactive power (see equati ons for total power ang le, in chapter 8, “Append ix B: Calcu lat ions an d equations on page 36). A positive sign shows inductive load, and a negative sign shows capacitive load.
Frequency
Network frequency is calculated from time periods of measured voltage. Frequency is an average of number of periods set in general settings/average interval.
Energy
The energy of each of four energy counters is available.
MD values
Measurements of MD values.
THD − Total Harmonic Distortion
THD is calculated for phas e currents, phase and ph ase-to-phase vol tages and is expres sed as percent of high harmonic components regarding RMS value or relative to first harmonic. The instrument uses a measuring technique of true RMS values that assures exact measurements with the presence of high harmonics up to 31st harmonic.
Page 29
MTR-3 Installation Instructions
DEIF A/S Page 29 of 51
7. Appendix A: Modbus protocol
Modbus communication protocol
Modbus is enabled via RS485 or USB. The response is the same type as the request. Two versions of Modbus register tables are available:
VERSION 1: MTR-3 Modbus registers
VERSION 2: Compatibilit y with previous version of the product, the MTR-2
Modbus
Modbus protocol enables operation of device on Modbus networks. For device with serial communication, the Modbus protocol enables point-to-point (for example device to PC) multi-drop communication via RS485 communication. Modbus protocol is a widely supported open interconnect originally designed by Modicon.
The memory reference for input and holding registers is 300001 and 400001 respectively. The register tables no the next pages shows both the PLC address and Modbus address to read
from the desired register.
Example for reading Frequency parameter:
PLC: Read address 300106-300107 Modbus: Read address 105-106 with function 4
The Modbus address will always be 1 lower than the PLC address because PLC addresses starts with 1 where Modbus addresses starts with 0.
Page 30
MTR-3 Installation Instructions
DEIF A/S Page 30 of 51
VERSION 1:
Register table for the actual measurements
Parameter
PLC
Modbus Reading
Address
Address
Function Type
Start
End
Start
End
Frequency
300106
300107
105
106
04
T5
U1
300108
300109
107
108
04
T5
U2
300110
300111
109
110
04
T5
U3
300112
300113
111
112
04
T5
Uavg (phase to neutral)
300114
300115
113
114
04
T5
ϕ12 (angle between U1 and U2)
300116
300116
115
115
04
T17
ϕ23 (angle between U2 and U3)
300117
300117
116
116
04
T17
ϕ31 (angle between U3 and U1)
300118
300118
117
117
04
T17
U12
300119
300120
118
119
04
T5
U23
300121
300122
120
121
04
T5
U31
300123
300124
122
123
04
T5
Uavg (phase to phase)
300125
300126
124
125
04
T5
I1
300127
300128
126
127
04
T5
I2
300129
300130
128
129
04
T5
I3
300131
300132
130
131
04
T5
INc
300133
300134
132
133
04
T5
INm - reserved
300135
300136
134
135
04
T5
Iavg
300137
300138
136
137
04
T5
Σ I
300139
300140
138
139
04
T5
Active Power Total (Pt)
300141
300142
140
141
04
T6
Active Power Phase L1 (P1)
300143
300144
142
143
04
T6
Active Power Phase L2 (P2)
300145
300146
144
145
04
T6
Active Power Phase L3 (P3)
300147
300148
146
147
04
T6
Reactive Power Total (Qt)
300149
300150
148
149
04
T6
Reactive Power Phase L1 (Q1)
300151
300152
150
151
04
T6
Reactive Power Phase L2 (Q2)
300153
300154
152
153
04
T6
Reactive Power Phase L3 (Q3)
300155
300156
154
155
04
T6
Apparent Power Total (St)
300157
300158
156
157
04
T5
Apparent Power Phase L1 (S1)
300159
300160
158
159
04
T5
Apparent Power Phase L2 (S2)
300161
300162
160
161
04
T5
Apparent Power Phase L3 (S3)
300163
300164
162
163
04
T5
Power Factor Total (PFt)
300165
300166
164
165
04
T7
Power Factor Phase 1 (PF1)
300167
300168
166
167
04
T7
Power Factor Phase 2 (PF2)
300169
300170
168
169
04
T7
Power Factor Phase 3 (PF3)
300171
300172
170
171
04
T7
Power Angle Total atan2(Pt,Q t ) )
300173
300173
172
172
04
T17
ϕ1 (angle between U1 and I1)
300174
300174
173
173
04
T17
ϕ2 (angle between U2 and I2)
300175
300175
174
174
04
T17
ϕ3 (angle between U3 and I3)
300176
300176
175
175
04
T17
Internal Temperature
300182
300182
181
181
04
T17
Page 31
MTR-3 Installation Instructions
DEIF A/S Page 31 of 51
Register table for the actual measurements (VERSION 1)
Parameter
PLC
Modbus Reading
Address
Address
Function Type
Start
End
Start
End
Reactive Power Total (Qt)
300149
300150
148
149
04
T6
Reactive Power Phase L1 (Q1)
300151
300152
150
151
04
T6
Reactive Power Phase L2 (Q2)
300153
300154
152
153
04
T6
Reactive Power Phase L3 (Q3)
300155
300156
154
155
04
T6
Apparent Power Total (St)
300157
300158
156
157
04
T5
Apparent Power Phase L1 (S1)
300159
300160
158
159
04
T5
Apparent Power Phase L2 (S2)
300161
300162
160
161
04
T5
Apparent Power Phase L3 (S3)
300163
300164
162
163
04
T5
Power Factor Total (PFt)
300165
300166
164
165
04
T7
Power Factor Phase 1 (PF1)
300167
300168
166
167
04
T7
Power Factor Phase 2 (PF2)
300169
300170
168
169
04
T7
Power Factor Phase 3 (PF3)
300171
300172
170
171
04
T7
Power Angle Total (atan2(Pt,Qt))
300173 300173 172 172 04 T17
ϕ1 (angle between U1 and I1)
300174
300174
173
173
04
T17
ϕ2 (angle between U2 and I2)
300175
300175
174
174
04
T17
ϕ3 (angle between U3 and I3)
300176
300176
175
175
04
T17
Internal Temperature
300182
300182
181
181
04
T17
THD HARMONIC DATA
U1 THD%
300183
300183
182
182
04
T16
U2 THD%
300184
300184
183
183
04
T16
U3 THD%
300185
300185
184
184
04
T16
U12 THD%
300186
300186
185
185
04
T16
U23 THD%
300187
300187
186
186
04
T16
U31 THD%
300188
300188
187
187
04
T16
I1 THD%
300189
300189
188
188
04
T16
I2 THD%
300190
300190
189
189
04
T16
I3 THD%
300191
300191
190
190
04
T16
I/O STATUS
Alarm Status Flags (No. 1…16)
300192
300192
191
191
04
T1
I/O 1 Value
300194
300194
193
193
04
T17
I/O 2 Value
300195
300195
194
194
04
T17
I/O 3 Value
300196
300196
195
195
04
T17
I/O 4 Value
300197
300197
196
196
04
T17
ENERGY (see note)
Energy Counter 1 Exponent
300401
300401
400
400
04
T2
Energy Counter 2 Exponent
300402
300402
401
401
04
T2
Energy Counter 3 Exponent
300403
300403
402
402
04
T2
Energy Counter 4 Exponent
300404
300404
403
403
04
T2
Current Active Tariff
300405
300405
404
404
04
T1
Energy Counter 1
300406
300407
405
406
04
T3
Energy Counter 2
300408
300409
407
408
04
T3
Energy Counter 3
300410
300411
409
410
04
T3
Energy Counter 4
300412
300413
411
412
04
T3
Note: Energy counters actual value is calculated: Counter * 10
Exponent
Page 32
MTR-3 Installation Instructions
DEIF A/S Page 32 of 51
Register table for the actual measurements (VERSION 1)
Parameter
PLC
Modbus Reading
Address
Address
Function Type
Start
End
Start
End
DYNAMIC DEMAND VALUES
Time Into Period (minutes)
300502
300502
501
501
04
T1
I1
300503
300504
502
503
04
T5
I2
300505
300506
504
505
04
T5
I3
300507
300508
506
507
04
T5
Apparent Power Total (St)
300509
300510
508
509
04
T5
Active Power Total (Pt) ­(positive)
300511
300512
510
511
04
T6
Active Power Total (Pt) ­(negative)
300513
300514
512
513
04
T6
Reactive Power Total (Qt) - L
300515
300516
514
515
04
T6
Reactive Power Total (Qt) - C
300517
300518
516
517
04
T6
MAX DEMAND SINCE LAST RESET
I1
300519
300520
518
519
04
T5
I2
300525
300526
524
525
04
T5
I3
300531
300532
530
531
04
T5
Apparent Power Total (St)
300537
300538
536
537
04
T5
Active Power Total (Pt) ­(positive)
300543
300544
542
543
04
T6
Active Power Total (Pt) ­(negative)
300549
300550
548
549
04
T6
Reactive Power Total (Qt) - L
300555
300556
554
555
04
T6
Reactive Power Total (Qt) - C
300561
300562
560
561
04
T6
Page 33
MTR-3 Installation Instructions
DEIF A/S Page 33 of 51
MEASUREMENTS (IEEE 754) (VERSION 1)
Parameter
PLC
Modbus reading
Address
Address
Function
Type
Start
End
Start
End
Uavg (phase to neutral)
30248
5
302486
2484
2485
04
T_float
Uavg (phase to phase)
30248
7
302488
2486
2487
04
T_float
Sum I
30248
9
302490
2488
2489
04
T_float
Active Power Total (Pt)
30249
1
302492
2490
2491
04
T_float
Reactive Power Total (Qt)
30249
3
302494
2492
2493
04
T_float
Apparent Power Total (St)
30249
5
302496
2494
2495
04
T_float
Power Factor Total (PFt)
30249
7
302498
2496
2497
04
T_float
Frequency
30249
9
302500
2498
2499
04
T_float
U1
30250
1
302502
2500
2501
04
T_float
U2
30250
3
302504
2502
2503
04
T_float
U3
30250
5
302506
2504
2505
04
T_float
Uavg (phase to neutral)
30250
7
302508
2506
2507
04
T_float
U12
30250
9
302510
2508
2509
04
T_float
U23
30251
1
302512
2510
2511
04
T_float
U31
30251
3
302514
2512
2513
04
T_float
Uavg (phase to phase)
30251
5
302516
2514
2515
04
T_float
I1
30251
7
302518
2516
2517
04
T_float
I2
30251
9
302520
2518
2519
04
T_float
I3
30252
1
302522
2520
2521
04
T_float
Sum I
30252
3
302524
2522
2523
04
T_float
I neutral (calculated)
30252
5
302526
2524
2525
04
T_float
I neutral (measured)
30252
7
302528
2526
2527
04
T_float
Iavg
30252
9
302530
2528
2529
04
T_float
Active Power Phase L1 (P1)
30253
1
302532
2530
2531
04
T_float
Active Power Phase L2 (P2)
30253
3
302534
2532
2533
04
T_float
Active Power Phase L3 (P3)
30253
5
302536
2534
2535
04
T_float
Page 34
MTR-3 Installation Instructions
DEIF A/S Page 34 of 51
Active Power Total (Pt)
30253
7
302538
2536
2537
04
T_float
Reactive Power Phase L1 (Q1)
30253
9
302540
2538
2539
04
T_float
Reactive Power Phase L2 (Q2)
30254
1
302542
2540
2541
04
T_float
Reactive Power Phase L3 (Q3)
30254
3
302544
2542
2543
04
T_float
Reactive Power Total (Qt)
30254
5
302546
2544
2545
04
T_float
Apparent Power Phase L1 (S1)
30254
7
302548
2546
2547
04
T_float
Apparent Power Phase L2 (S2)
30254
9
302550
2548
2549
04
T_float
Apparent Power Phase L3 (S3)
30255
1
302552
2550
2551
04
T_float
Apparent Power Total (St)
30255
3
302554
2552
2553
04
T_float
Power Factor Phase 1 (PF1)
30255
5
302556
2554
2555
04
T_float
Power Factor Phase 2 (PF2)
30255
7
302558
2556
2557
04
T_float
Power Factor Phase 3 (PF3)
30255
9
302560
2558
2559
04
T_float
Power Factor Total (PFt)
30256
1
302562
2560
2561
04
T_float
CAP/IND P. F. Phase 1 (PF1)
30256
3
302564
2562
2563
04
T_float
CAP/IND P. F. Phase 2 (PF2)
30256
5
302566
2564
2565
04
T_float
CAP/IND P. F. Phase 3 (PF3)
30256
7
302568
2566
2567
04
T_float
CAP/IND P. F. Total (PFt)
30256
9
302570
2568
2569
04
T_float
φ1 (angle between U1 and I1)
30257
1
302572
2570
2571
04
T_float
φ2 (angle between U2 and I2)
30257
3
302574
2572
2573
04
T_float
φ3 (angle between U3 and I3)
30257
5
302576
2574
2575
04
T_float
Power Angle Total atan2(Pt,Qt))
30257
7
302578
2576
2577
04
T_float
MEASUREMENTS (IEEE 754) (VERSION 1)
Parameter
PLC
Modbus reading
Address
Adress
Funktion
Type
Start
End
Start
End
φ12 (angle between U1 and U2)
30257
9
302580
2578
2579
04
T_float
φ23 (angle between U2 and U3)
30258
1
302582
2580
2581
04
T_float
φ31 (angle between U3 and U1)
30258
3
302584
2582
2583
04
T_float
Frequency
30258
5
302586
2584
2585
04
T_float
Page 35
MTR-3 Installation Instructions
DEIF A/S Page 35 of 51
Reserved
30258
7
302588
2586
2587
I1 THD%
30258
9
302590
2588
2589
04
T_float
I2 THD%
30259
1
302592
2590
2591
04
T_float
I3 THD%
30259
3
302594
2592
2593
04
T_float
U1 THD%
30259
5
302596
2594
2595
04
T_float
U2 THD%
30259
7
302598
2596
2597
04
T_float
U3 THD%
30259
9
302600
2598
2599
04
T_float
U12 THD%
30260
1
302602
2600
2601
04
T_float
U23 THD%
30260
3
302604
2602
2603
04
T_float
U31 THD%
30260
5
302606
2604
2605
04
T_float
MAX DEMAND SINCE LAST RESET
Active Power Total (Pt) ­(positive)
30260
7
302608
2606
2607
04
T_float
Active Power Total (Pt) ­(negative)
30260
9
302610
2608
2609
04
T_float
Reactive Power Total (Qt) - L
30261
1
302612
2610
2611
04
T_float
Reactive Power Total (Qt) - C
30261
3
302614
2612
2613
04
T_float
Apparent Power Total (St)
30261
5
302616
2614
2615
04
T_float
I1
30261
7
302618
2616
2617
04
T_float
I2
30261
9
302620
2618
2619
04
T_float
I3
30262
1
302622
2620
2621
04
T_float
DYNAMIC DEMAND VALUES
Active Power Total (Pt) ­(positive)
30262
3
302624
2622
2623
04
T_float
Active Power Total (Pt) ­(negative)
30262
5
302626
2624
2625
04
T_float
Reactive Power Total (Qt) - L
30262
7
302628
2626
2627
04
T_float
Reactive Power Total (Qt) - C
30262
9
302630
2628
2629
04
T_float
Apparent Power Total (St)
30263
1
302632
2630
2631
04
T_float
I1
30263
3
302634
2632
2633
04
T_float
I2
30263
5
302636
2634
2635
04
T_float
I3
30263
7
302638
2636
2637
04
T_float
Page 36
MTR-3 Installation Instructions
DEIF A/S Page 36 of 51
ENERGY
Energy Counter 1
30263
9
302640
2638
2639
04
T_float
Energy Counter 2
30264
1
302642
2640
2641
04
T_float
Energy Counter 3
30264
3
302644
2642
2643
04
T_float
Energy Counter 4
30264
5
302646
2644
2645
04
T_float
Reserved
30264
7
302656
2646
2655
Aktiv Tariff
30265
7
302658
2656
2657
04
T_float
Internal Temperature
30265
9
302660
2658
2659
04
T_float
Register table for the normalised actual measurements (in %) (VERSION 1)
PLC
Modbus Reading
100% value
Parameter
Address
Address
Function Type
Start End Start End
U1
300802
300802
801
801
04
T16
Un
U2
300803
300803
802
802
04
T16
Un
U3
300804
300804
803
803
04
T16
Un
Uavg (phase to neutral)
300805
300805
804
804
04
T16
Un
U12
300806
300806
805
805
04
T16
Un
U23
300807
300807
806
806
04
T16
Un
U31
300808
300808
807
807
04
T16
Un
Uavg (phase to phase)
300809
300809
808
808
04
T16
Un
I1
300810
300810
809
809
04
T16
In
I2
300811
300811
810
810
04
T16
In
I3
300812
300812
811
811
04
T16
In
Σ I
300813
300813
812
812
04
T16
It
I neutral (calculated)
300814
300814
813
813
04
T16
In
I neutral (measured)
300815
300815
814
814
04
T16
In
Iavg
300816
300816
815
815
04
T16
In
Active Power Phase L1 (P1)
300817
300817
816
816
04
T17
Pn
Active Power Phase L2 (P2)
300818
300818
817
817
04
T17
Pn
Active Power Phase L3 (P3)
300819
300819
818
818
04
T17
Pn
Active Power Total (Pt)
300820
300820
819
819
04
T17
Pt
Reactive Power Phase L1 (Q1)
300821
300821
820
820
04
T17
Pn
Reactive Power Phase L2 (Q2)
300822
300822
821
821
04
T17
Pn
Reactive Power Phase L3 (Q3)
300823
300823
822
822
04
T17
Pn
Reactive Power Total (Qt)
300824
300824
823
823
04
T17
Pt
Apparent Power Phase L1 (S1)
300825
300825
824
824
04
T16
Pn
Apparent Power Phase L2 (S2)
300826
300826
825
825
04
T16
Pn
Apparent Power Phase L3 (S3)
300827
300827
826
826
04
T16
Pn
Apparent Power Total (St)
300828
300828
827
827
04
T16
Pt
Power Factor Phase 1 (PF1)
300829
300829
828
828
04
T17
1
Power Factor Phase 2 (PF2)
300830
300830
829
829
04
T17
1
Power Factor Phase 3 (PF3)
300831
300831
830
830
04
T17
1
Power Factor Total (PFt)
300832
300832
831
831
04
T17
1
CAP/IND P. F. Phase 1 (PF1)
300833
300833
832
832
04
T17
1
CAP/IND P. F. Phase 2 (PF2)
300834
300834
833
833
04
T17
1
CAP/IND P. F. Phase 3 (PF3)
300835
300835
834
834
04
T17
1
CAP/IND P. F. Total (PFt)
300836
300836
835
835
04
T17
1
ϕ1 (angle between U1 and I1)
300837
300837
836
836
04
T17
100°
Page 37
MTR-3 Installation Instructions
DEIF A/S Page 37 of 51
ϕ2 (angle between U2 and I2)
300838
300838
837
837
04
T17
100°
ϕ3 (angle between U3 and I3)
300839
300839
838
838
04
T17
100°
Power Angle Total (atan2(Pt,Qt))
300840
300840
839
839
04
T17
100°
ϕ12 (angle between U1 and U2)
300841
300841
840
840
04
T17
100°
ϕ23 (angle between U2 and U3)
300842
300842
841
841
04
T17
100°
ϕ31 (angle between U3 and U1)
300843
300843
842
842
04
T17
100°
Frequency
300844
300843
843
843
04
T17
Fn+10
Hz
I1 THD%
300845
300845
844
844
04
T16
100%
I2 THD%
300846
300846
845
845
04
T16
100%
I3 THD%
300847
300847
846
846
04
T16
100%
U1 THD%
300848
300848
847
847
04
T16
100%
U2 THD%
300849
300849
848
848
04
T16
100%
U3 THD%
300850
300850
849
849
04
T16
100%
Page 38
MTR-3 Installation Instructions
DEIF A/S Page 38 of 51
Register table for the normalised actual measurements (in %) (VERSION 1)
PLC
Modbus Reading
Parameter
Address
Address
Function Type
100% value
Start
End
Start
End
U12 THD%
300851
300851
850
850
04
T16
100%
U23 THD%
300852
300852
851
851
04
T16
100%
U31 THD%
300853
300853
852
852
04
T16
100%
MAX DEMAND SINCE LAST RESET
Active Power Total (Pt) ­(positive)
300854
300854
853
853
04
T16
Pt
Active Power Total (Pt) ­(negative)
300855
300855
854
854
04
T16
Pt
Reactive Power Total (Qt) - L
300856
300856
855
855
04
T16
Pt
Reactive Power Total (Qt) - C
300857
300857
856
856
04
T16
Pt
Apparent Power Total (St)
300858
300858
857
857
04
T16
Pt
I1
300859
300859
858
858
04
T16
In
I2
300860
300860
859
859
04
T16
In
I3
300861
300861
860
860
04
T16
In
DYNAMIC DEMAND VALUES
Active Power Total (Pt) ­(positive)
300862
300862
861
861
04
T16
Pt
Active Power Total (Pt) ­(negative)
300863
300863
862
862
04
T16
Pt
Reactive Power Total (Qt) - L
300864
300864
863
863
04
T16
Pt
Reactive Power Total (Qt) - C
300865
300865
864
864
04
T16
Pt
Apparent Power Total (St)
300866
300866
865
865
04
T16
Pt
I1
300867
300867
866
866
04
T16
In
I2
300868
300868
867
867
04
T16
In
I3
300869
300869
868
868
04
T16
In
ENERGY
Energy counter 1
300870
300870
869
869
04
T17
Actual
counter
value MOD
20000 is
returned
Energy counter 2
300871
300871
870
870
04
T17
Energy counter 3
300872
300872
871
871
04
T17
Energy counter 4
300873
300873
872
872
04
T17
Aktiv tariff
300879
300879
878
878
04
T1
Internal temperature
300880
300880
879
879
04
T17
100°
Page 39
MTR-3 Installation Instructions
DEIF A/S Page 39 of 51
Register table for the fast response normalised actual measurements (in %) (VERSION 1)
The measurements in the registers below are not averaged and therefore the response time is less than 50 mS.
PLC
Modbus Reading
100 %
value
Parameter
Address
Address
Function Type
Start
End
Start
End
U1
300902
300902
901
901
04
T16
Un
U2
300903
300903
902
902
04
T16
Un
U3
300904
300904
903
903
04
T16
Un
Uavg (phase to neutral)
300905
300905
904
904
04
T16
Un
U12
300906
300906
905
905
04
T16
Un
U23
300907
300907
906
906
04
T16
Un
U31
300908
300908
907
907
04
T16
Un
Uavg (phase to phase)
300909
300909
908
908
04
T16
Un
I1
300910
300910
909
909
04
T16
In
I2
300911
300911
910
910
04
T16
In
I3
300912
300912
911
911
04
T16
In
Σ I
300913
300913
912
912
04
T16
It
I neutral (calculated)
300914
300914
913
913
04
T16
In
I neutral (measured)
300915
300915
914
914
04
T16
In
Iavg
300916
300916
915
915
04
T16
In
Active Power Phase L1 (P1)
300917
300917
916
916
04
T17
Pn
Active Power Phase L2 (P2)
300918
300918
917
917
04
T17
Pn
Active Power Phase L3 (P3)
300919
300919
918
918
04
T17
Pn
Active Power Total (Pt)
300920
300920
919
919
04
T17
Pt
Reactive Power Phase L1 (Q1)
300921
300921
920
920
04
T17
Pn
Reactive Power Phase L2 (Q2)
300922
300922
921
921
04
T17
Pn
Reactive Power Phase L3 (Q3)
300923
300923
922
922
04
T17
Pn
Reactive Power Total (Qt)
300924
300924
923
923
04
T17
Pt
Apparent Power Phase L1 (S1)
300925
300925
924
924
04
T16
Pn
Apparent Power Phase L2 (S2)
300926
300926
925
925
04
T16
Pn
Apparent Power Phase L3 (S3)
300927
300927
926
926
04
T16
Pn
Apparent Power Total (St)
300928
300928
927
927
04
T16
Pt
Power Factor Phase 1 (PF1)
300929
300929
928
928
04
T17
1
Power Factor Phase 2 (PF2)
300930
300930
929
929
04
T17
1
Power Factor Phase 3 (PF3)
300931
300931
930
930
04
T17
1
Power Factor Total (PFt)
300932
300932
931
931
04
T17
1
CAP/IND P. F. Phase 1 (PF1)
300933
300933
932
932
04
T17
1
CAP/IND P. F. Phase 2 (PF2)
300934
300934
933
933
04
T17
1
CAP/IND P. F. Phase 3 (PF3)
300935
300935
934
934
04
T17
1
CAP/IND P. F. Total (PFt)
300936
300936
935
935
04
T17
1
ϕ1 (angle between U1 and I1)
300937
300937
936
936
04
T17
100°
ϕ2 (angle between U2 and I2)
300938
300938
937
937
04
T17
100°
ϕ3 (angle between U3 and I3)
300939
300939
938
938
04
T17
100°
Power Angle Total (atan2(Pt,Qt))
300940
300940
939
939
04
T17
100°
ϕ12 (angle between U1 and U2)
300941
300941
940
940
04
T17
100°
ϕ23 (angle between U2 and U3)
300942
300942
941
941
04
T17
100°
ϕ31 (angle between U3 and U1)
300943
300943
942
942
04
T17
100°
Frequency 300944
300944
943 943 04 T17
Fn+10
Hz
Reserved
300945
300945
944
944
I1 THD%
300946
300946
945
945
04
T16
100%
I2 THD%
300947
300947
946
946
04
T16
100%
I3 THD%
300948
300948
947
947
04
T16
100%
U1 THD%
300949
300949
948
948
04
T16
100%
U2 THD%
300950
300950
949
949
04
T16
100%
U3 THD%
300951
300951
950
950
04
T16
100%
U12 THD%
300952
300952
951
951
04
T16
100%
U23 THD%
300953
300953
952
952
04
T16
100%
U31 THD%
300954
300954
953
953
04
T16
100%
Page 40
MTR-3 Installation Instructions
DEIF A/S Page 40 of 51
VERSION2 (MTR-2-compatible): Register table for the actual measurements
Parameter
PLC
Modbus reading
Address
Address
Function Type
Start
End
Start
End
Frequency
300050
300051
49
50
04
T5
U1
300058
300059
57
58
04
T5
U2
300060
300061
59
60
04
T5
U3
300062
300063
61
62
04
T5
Uavg (phase to neutral)
300064
300065
63
64
04
T5
ϕ12 (angle between U1 and U2)
300066
300066
65
65
04
T17
ϕ23 (angle between U2 and U3)
300067
300067
66
66
04
T17
ϕ31 (angle between U3 and U1)
300068
300068
67
67
04
T17
U12
300069
300070
68
69
04
T5
U23
300071
300072
70
71
04
T5
U31
300073
300074
72
73
04
T5
Uavg (phase to phase)
300075
300076
74
75
04
T5
I1
300077
300078
76
77
04
T5
I2
300079
300080
78
79
04
T5
I3
300081
300082
80
81
04
T5
INc
300083
300084
82
83
04
T5
INm - reserved
300085
300086
84
85
04
T5
Iavg
300087
300088
86
87
04
T5
Σ I
300089
300090
88
89
04
T5
Active Power Total (Pt)
300091
300092
90
91
04
T6
Active Power Phase L1 (P1)
300093
300094
92
93
04
T6
Active Power Phase L2 (P2)
300095
300096
94
95
04
T6
Active Power Phase L3 (P3)
300097
300098
96
97
04
T6
Reactive Power Total (Qt)
300099
300100
98
99
04
T6
Reactive Power Phase L1 (Q1)
300101
300102
100
101
04
T6
Reactive Power Phase L2 (Q2)
300103
300104
102
103
04
T6
Reactive Power Phase L3 (Q3)
300105
300106
104
105
04
T6
Apparent Power Total (St)
300107
300108
106
107
04
T5
Apparent Power Phase L1 (S1)
300109
300110
108
109
04
T5
Apparent Power Phase L2 (S2)
300111
300112
110
111
04
T5
Apparent Power Phase L3 (S3)
300113
300114
112
113
04
T5
Power Factor Total (PFt)
300115
300116
114
115
04
T7
Power Factor Phase 1 (PF1)
300117
300118
116
117
04
T7
Power Factor Phase 2 (PF2)
300119
300120
118
119
04
T7
Power Factor Phase 3 (PF3)
300121
300122
120
121
04
T7
Power Angle Total (atan2(Pt,Qt))
300123
300123
122
122
04
T17
ϕ1 (angle between U1 and I1)
300124
300124
123
123
04
T17
ϕ2 (angle between U2 and I2)
300125
300125
124
124
04
T17
ϕ3 (angle between U3 and I3)
300126
300126
125
125
04
T17
Internal Temperature
300127
300127
126
126
04
T17
Page 41
MTR-3 Installation Instructions
DEIF A/S Page 41 of 51
Register table for the actual measurements (VERSION 2)
Parameter
PLC
Modbus Reading
Address
Address
Function Type
Start
End
Start
End
THD HARMONIC DATA
U1 THD%
300639
300639
639
639
04
T16
U2 THD%
300640
300640
640
640
04
T16
U3 THD%
300641
300641
641
641
04
T16
U12 THD%
300642
300642
642
642
04
T16
U23 THD%
300643
300643
643
643
04
T16
U31 THD%
300644
300644
644
644
04
T16
I1 THD%
300645
300645
645
645
04
T16
I2 THD%
300646
300646
646
646
04
T16
I3 THD%
300647
300647
647
647
04
T16
Parameter
PLC
Modbus reading
Address
Address
Function Type
Start
End
Start
End
DYNAMIC DEMAND VALUES
Time Into Period (minutes)
300175
300175
174
174
04
T1
I1
300176
300177
175
176
04
T5
I2
300178
300179
177
178
04
T5
I3
300180
300181
179
180
04
T5
Apparent Power Total (St)
300182
300183
181
182
04
T5
Active Power Total (Pt) ­(positive)
300184
300185
183
184
04
T6
Active Power Total (Pt) ­(negative)
300186
300187
185
186
04
T6
Reactive Power Total (Qt) - L
300188
300189
187
188
04
T6
Reactive Power Total (Qt) - C
300190
300191
189
190
04
T6
MAX DEMAND SINCE LAST RESET
I1
300208
300209
207
208
04
T5
I2
300214
300215
213
214
04
T5
I3
300220
300221
219
220
04
T5
Apparent Power Total (St)
300226
300227
225
226
04
T5
Active Power Total (Pt) ­(positive)
300232
300233
231
232
04
T6
Active Power Total (Pt) ­(negative)
300238
300239
237
238
04
T6
Reactive Power Total (Qt) - L
300244
300245
243
244
04
T6
Reactive Power Total (Qt) - C
300250
300251
249
250
04
T6
Page 42
MTR-3 Installation Instructions
DEIF A/S Page 42 of 51
Register table for the normalised actual measurements (VERSION 2)
PLC
Modbus Reading
Parameter
Address
Address
Function Type
100% value
Start
End
Start
End
U1
300802
300802
801
801
04
T16
Un
U2
300803
300803
802
802
04
T16
Un
U3
300804
300804
803
803
04
T16
Un
Uavg (phase to neutral)
300805
300805
804
804
04
T16
Un
U12
300806
300806
805
805
04
T16
Un
U23
300807
300807
806
806
04
T16
Un
U31
300808
300808
807
807
04
T16
Un
Uavg (phase to phase)
300809
300809
808
808
04
T16
Un
I1
300810
300810
809
809
04
T16
In
I2
300811
300811
810
810
04
T16
In
I3
300812
300812
811
811
04
T16
In
Σ I
300813
300813
812
812
04
T16
It
I neutral (calculated)
300814
300814
813
813
04
T16
In
I neutral (measured)
300815
300815
814
814
04
T16
In
Iavg
300816
300816
815
815
04
T16
In
Active Power Phase L1 (P1)
300817
300817
816
816
04
T17
Pn
Active Power Phase L2 (P2)
300818
300818
817
817
04
T17
Pn
Active Power Phase L3 (P3)
300819
300819
818
818
04
T17
Pn
Active Power Total (Pt)
300820
300820
819
819
04
T17
Pt
Reactive Power Phase L1 (Q1)
300821
300821
820
820
04
T17
Pn
Reactive Power Phase L2 (Q2)
300822
300822
821
821
04
T17
Pn
Reactive Power Phase L3 (Q3)
300823
300823
822
822
04
T17
Pn
Reactive Power Total (Qt)
300824
300824
823
823
04
T17
Pt
Apparent Power Phase L1 (S1)
300825
300825
824
824
04
T16
Pn
Apparent Power Phase L2 (S2)
300826
300826
825
825
04
T16
Pn
Apparent Power Phase L3 (S3)
300827
300827
826
826
04
T16
Pn
Apparent Power Total (St)
300828
300828
827
827
04
T16
Pt
Power Factor Phase 1 (PF1)
300829
300829
828
828
04
T17
1
Power Factor Phase 2 (PF2)
300830
300830
829
829
04
T17
1
Power Factor Phase 3 (PF3)
300831
300831
830
830
04
T17
1
Power Factor Total (PFt)
300832
300832
831
831
04
T17
1
100 % value calculations for normalised measurements
Un =
(R40147/R40146) * R39015 * R40149
In =
(R40145/R40144) * R39017 * R40148
Pn =
Un*In
It =
In Connection Mode: 1b
It =
3*In Connection Modes: 3b, 4b, 3u, 4u
Pt =
Pn Connection Mode: 1b
Pt =
3*Pn Connection Modes: 3b, 4b, 3u, 4u
Fn =
R40150
Page 43
Register table for Settings (VERSION 2)
Parameter
PLC
Modbus reading
Values/dependences
Address
Adress
Type Ind
Start
End
Start
End
SYSTEM COMMANDS
User Password (L1, L2) 400001
400002
0 1 T_Str4
A...Z
Password to attempt user access
level upgrade
Factory Password (FAC) 400003
400005
2 4 T_Str6
A...Z
Password to attempt factory access
level upgrade
Level 1 - User password
400006
400007
5 6 T_Str4
A...Z
Level 2 - User password
400008
400009
7 8 T_Str4
A...Z
Active Access Level
400010
9
T1 0 Full protection
1 Access up to level 1 user password
2 Access up to level 2 user password
3 Access up to level 2 (backup pass.)
4 Factory access level
Manual password activation
400011
10 T1 1 Lock instrument
Operator Command Register
400012
11 T1 1 Save Settings
2 Abort Settings
3 Restart Instrument
Reset command register 1
400013
12 T1
Bit-0
Reset counter 1
Bit-1
Reset counter 2
Bit-2
Reset counter 3
Bit-3
Reset counter 4
Bit-10
Reset last period MD
Bit-11
Reset MD values
Reset command register 2
400014
13 T1
Bit-0
Reset alarm output relay 1
Bit-1
Reset alarm output relay 2
Bit-2
Reset alarm output relay 3
Bit-3
Reset alarm output relay 4
Reserved
400015
400099
14
98
GENERAL SETTINGS
Modbus register tables for measurements
400101
100 T1 0 Version 1 - MTR-3
1 Version 2 - compatible with MTR-2
Description 400102
400120
101
119 T-Str40
Location 400123
400140
122
139 T-Str40
Password activation
400142
141 Reserved
Password lock time
400143
142 T1 Minutes, 0 = No lock
Conection Mode
400144
143 T1 0 No mode
1 1b - Single Phase
2 3b - 3 phase 3 wire balanced
3 4b - 3 phase 4 wire balanced
4 3u - 3 phase 3 wire unbalanced
5 4u - 3 phase 4 wire unbalanced
CT Secundary
400145
144 T4 mA
CT Primary
400146
145 T4 A/10
VT Secundary
400147
146 T4 mV
VT Primary
400148
147 T4 V/10
Current input range (%)
400149
148 T16
10000 for 100%
Voltage input range (%)
400150
149 T16
10000 for 100%
Frequency nominal value
400151
150 T1 Hz
CT Connection
400152
151 T1
Bit-0
Disable display "Wrong connection"
Bit-1
Reverse Energy flow direction
Bit-2
Reverse CT connection
MD Time constant
400153
152 T1 minutes (0=disabled)
Page 44
MTR-3 Installation Instructions
DEIF A/S Page 44 of 51
Reserved
400154
153
Starting total current for PFt & Pat
400155
154 T16
2000 for 20 mA
400156
155 T16
200 for 2 mA
Reserved
400157
400159
156
158
Temperature unit
400160
159 T1 0 °C 1 °F
Reserved
400161
400167
160
166
Starting voltage for SYNC.
400168
167 T1 5000 for 5 V (for R30015 = 500 V)
Reserved
400168
400169
168
169
Comm. average interval
400171
170 T1 0 1 period (0.02 s @50 Hz) default
1 2 periods (0.04 s @50 Hz)
2 4 periods (0.08 s @50 Hz)
3 8 periods (0.16 s @50 Hz)
4 16 periods (0.32 s @50 Hz)
5 32 periods (0.64 s @50 Hz)
6 64 periods (1.28 s @50 Hz) default
7 128 periods (2.56 s @50 Hz)
8 256 periods (5.12 s @50 Hz)
Reserved
400172
400201
171
200
COMMUNICATION
Res. for Port 1: Device Address (DNP3)
400201
200
Port 1: Device Address (Modbus)
400203
202 T1
Port 1: Baud Rate
400204
203 T1 0 Baud rate 1200
1 Baud rate 2400
2 Baud rate 4800
3 Baud rate 9600
4 Baud rate 19200
5 Baud rate 38400
6 Baud rate 57600
7 Baud rate 115200
Port 1: Stop Bit
400205
204 T1 0 1 Stop bit
1 2 Stop bits
Port 1: Parity
400206
205 T1 0 No parity
1
Odd parity
2 Even parity
Port 1: Data Bits
400207
206 T1 0 8 bits 1 7 bits
Reserved
400208
400400
207
399
Page 45
MTR-3 Installation Instructions
DEIF A/S Page 45 of 51
Register table for Settings (VERSION 2)
Parameter
PLC
Modbus reading
Values/dependences
Address
Adress
Type Ind
Start
End
Start
End
ENERGY
Active Tariff 400401
400 T1
0
Tariff input (Tariff 1, if input not available)
1..4
Tariff 1..4
Common Energy Counter Exponent
400402
401 T2
Reserved
400403
400419
402
418
Reactive power calculation
400420
419 T1 0 Standard calculation (Q2=S2-P2)
1 Delayed Current method
Energy Counter 1 Parameter
400421
420 T1 0 No Parameter
1 Active Power
2 Reactive Power
3 Apparent Power
5 Active Power Phase 1
6 Reactive Power Phase 1
7 Apparent Power Phase 1
9 Active Power Phase 2
10
Reactive Power Phase 2
11
Apparent Power Phase 2
13
Active Power Phase 3
14
Reactive Power Phase 3
15
Apparent Power Phase 3
16
Pulse input 1 (reg.40402 not used)
17
Pulse input 2 (reg.40402 not used)
18
Pulse input 3 (reg.40402 not used)
19
Pulse input 4 (reg.40402 not used)
Energy Counter 1 Configuration
400422
421 T1
Bit-0
Quadrant I Enabled
Bit-1
Quadrant II Enabled
Bit-2
Quadrant III Enabled
Bit-3
Quadrant IIII Enabled
Bit-4
Absolute Value
Bit-5
Invert Value
Energy Counter 1 Divider
400423
422 T1 0 1 1 10 2 100 3 1000 4 10000
Energy Counter 1 Tarif Selector
400424
423 T1
Bit-0
Tarif 1 Enabled
Bit-1
Tarif 2 Enabled
Bit-2
Tarif 3 Enabled
Bit-3
Tarif 4 Enabled
Reserved
400425
400430
424
429
Energy Counter 2 Parameter
400431
430 T1 see Energy Counter 1 Param.
Energy Counter 2 Configuration
400432
431 T1 see Energy Counter 1 Config.
Energy Counter 2 Divider
400433
432 T1 see Energy Counter 1 Divider
Energy Counter 2 Tarif Selector
400434
433 T1 see Energy Counter 1 Tarif Selector
Reserved
400435
400440
434
439
Energy Counter 3 Parameter
400441
440 T1 see Energy Counter 1 Param.
Energy Counter 3 Configuration
400442
441 T1 see Energy Counter 1 Config.
Energy Counter 3 Divider
400443
442 T1 see Energy Counter 1 Divider
Energy Counter 3 Tarif Selector
400444
443 T1 see Energy Counter 1 Tarif Selector
Page 46
MTR-3 Installation Instructions
DEIF A/S Page 46 of 51
Reserved
400445
400450
444
449
Energy Counter 4 Parameter
400451
450 T1 see Energy Counter 1 Param.
Energy Counter 4 Configuration
400452
451 T1 see Energy Counter 1 Config.
Energy Counter 4 Divider
400453
452 T1 see Energy Counter 1 Divider
Energy Counter 4 Tarif Selector
400454
453 T1 see Energy Counter 1 Tarif Selector
Reserved
400455
400800
454
799
ANALOGUE OUTPUTS
Reserved
400801
800
Reserved
400802
801
Output 1 type
400803
802 T1 0 1 mA 1 5 mA 2 10 mA 3 20 mA 4 1 V 5 10 V
Output 1 Parameter
400804
803 T1 See OutTypes
Output 1 Function Type
400805
804 T1 0 Linear
Output 1 Number of Breakpoints
400806
805 T1 1 Quadratic
Output 1 Lower X Point (X0)
400807
806 T17 % of parameter value
Output 1 Lower Y Point (Y0)
400808
807 T17 % of output type
Output 1 X Breakpoint 1 (X1)
400809
808 T17 % of parameter value
Output 1 Y Breakpoint 1 (Y1)
400810
809 T17 % of output type
Output 1 X Breakpoint 2 (X2)
400811
810 T17 % of parameter value
Output 1 Y Breakpoint 2 (Y2)
400812
811 T17 % of output type
Output 1 X Breakpoint 3 (X3)
400813
812 T17 % of parameter value
Output 1 Y Breakpoint 3 (Y3)
400814
813 T17 % of output type
Output 1 X Breakpoint 4 (X4)
400815
814 T17 % of parameter value
Output 1 Y Breakpoint 4 (Y4)
400816
815 T17 % of output type
Output 1 X Breakpoint 5 (X5)
400817
816 T17 % of parameter value
Output 1 Y Breakpoint 5 (Y5)
400818
817 T17 % of output type
Output 1 X Breakpoint 6 (X6)
400819
818 T17 % of parameter value
Output 1 Y Breakpoint 6 (Y6)
400820
819 T17 % of output type
Output 1 Average interval
400821
820 T1 0 1 period (0.02 s @50 Hz) default
1 2 periods (0.04 s @50 Hz)
2 4 periods (0.08 s @50 Hz)
3 8 periods (0.16 s @50 Hz)
4 16 periods (0.32 s @50 Hz)
5 32 periods (0.64 s @50 Hz)
6 64 periods (1.28 s @50 Hz)
7 128 periods (2.56 s @50 Hz)
8 256 periods (5.12 s @50 Hz)
Reserved
400822
400823
821
ANALOGUE OUTPUT 2
400824
400842
823 See ANALOGUE OUTPUT 1
Reserved
400843
400844
842
ANALOGUE OUTPUT 3
400845
400863
844 See ANALOGUE OUTPUT 1
Reserved
400864
400865
863
ANALOGUE OUTPUT 4
400866
400884
865 See ANALOGUE OUTPUT 1
Reserved
400885
401000
884
ALARMS
Alarm Enable Flags 1…16
T1
Bit-1
Enable Alarm i
Reserved
401002
1001
ALARM GROUP 1 (No. 1..8)
Thermal function time constant
401003
T1 Minutes
Page 47
MTR-3 Installation Instructions
DEIF A/S Page 47 of 51
Compare time delay
401004
T1 Seconds
Hysteresis 401005
T16
% of compare value, if 0 then % of
nominal value
Reserved
401006
401007
1005
1006
ALARM 1
Alarm 1 parameter
401008
1007 T1
See OutTypes
Alarm 1 function
401009
1008 T1
Bit-1
Reserved: Store into memory (all)
Bit-2
Store into memory (1 per minute)
Bit-3
Activate LED
Bit-4
Activate Alarm Output
Bit-5
Activate Beep Output
Bit-6
Alarm Condition > (< if 0)
Bit-7
Use Thermal function
Alarm 1 compare value
401010
1009 T17 % of parameter value
ALARM 2
401011
401013
1010
1012
See ALARM 1
ALARM 3
401014
401016
1013
1015
See ALARM 1
ALARM 4
401017
401019
1016
1018
See ALARM 1
ALARM 5
401020
401022
1019
1021
See ALARM 1
ALARM 6
401023
401025
1022
1024
See ALARM 1
ALARM 7
401026
401028
1025
1027
See ALARM 1
ALARM 8
401029
401031
1028
1030
See ALARM 1
ALARM GROUP 2 (No. 9…16)
401032
401060
1031
1059
See ALARM GROUP 1
All other Modbus registers are a subjec t to change. For the latest Modbus register definiti on s, go to DEIF’s web page www.deif.com
Page 48
MTR-3 Installation Instructions
DEIF A/S Page 48 of 51
Data types decoding
Type
Bit mask
Description
T1
Unsigned Value (16 bit)
Example: 12345 = 3039(16)
T2
Signed Value (16 bit)
Example: -12345 = CFC7(16)
T3
Signed Long Value (32 bit)
Example: 123456789 = 075B CD 15(16)
T4
bits # 15…14 bits # 13…00
Short Unsigned float (16 bit)
Decade Exponent (Unsigned 2 bit) Binary Unsigned Value (14 bit)
Example: 10000*102 = A710(16)
T5
bits # 31…24 bits # 23…00
Unsigned Measurement (32 bit)
Decade Exponent (Signed 8 bit) Binary Unsigned Value (24 bit)
Example: 123456*10-3 = FD01 E240(16)
T6
bits # 31…24 bits # 23…00
Signed Measurement (32 bit)
Decade Exponent (Signed 8 bit) Binary Signed value (24 bit)
Example: - 123456*10-3 = FDFE 1DC0(16)
T7
bits # 31…24 bits # 23…16 bits # 15…00
Power Factor (32 bit)
Sign: Import/Export (00/FF) Sign: Inductive/Capacitive (00/FF) Unsigned Value (16 bit), 4 decimal places
Example: 0.9876 CAP = 00FF 2694(16)
T9
bits # 31…24 bits # 23…16 bits # 15…08 bits # 07…00
Time (32 bit)
1/100s 00 - 99 (BCD) Seconds 00 - 59 (BCD) Minutes 00 - 59 (BCD) Hours 00 - 24 (BCD)
Example: 15:42:03.75 = 7503 4215(16)
T10
bits # 31…24 bits # 23…16 bits # 15…00
Date (32 bit)
Day of month 01 - 31 (BCD) Month of year 01 - 12 (BCD) Year (unsigned integer) 1998..4095
Example: 10, SEP 2000 = 1009 07D0(16)
T16
Unsigned Value (16 bit), 2 decimal places
Example: 123.45 = 3039(16)
T17
Signed Value (16 bit), 2 decimal places
Example: -123.45 = CFC7(16)
T_Str4
Text: 4 characters (2 characters for 16 bit register)
T_Str6
Text: 6 characters (2 characters for 16 bit register)
T_Str8
Text: 8 characters (2 characters for 16 bit register)
T_Str16
Text: 16 characters (2 characters for 16 bit register)
T_Str40
Text: 40 characters (2 characters for 16 bit register)
T_float
bits # 31 bits # 30..23 bits # 22..0
IEEE 754 Floating-Point Single Precision Value (32 bit)
Sign Bit (1 bit) Exponent Field (8 bit) Significand (23 bit)
Example: 123.45 stored as 123.450 00 = 42F6 E66 6( 16 )
Page 49
MTR-3 Installation Instructions
DEIF A/S Page 49 of 51
8. Appendix B: Calculations and equations
Calculations
Definitions of symbols
No.
Symbol
Definition
1
Mv Sample factor
2
MP Average interval
3
Uf Phase voltage (U1, U2 or U3)
4
U
ff
Phase-to-phase voltage (U12, U23 or U31)
5 N Total number of samples in a period
6 n Sample number (0 ≤ n ≤ N)
7
x, y
Phase number (1, 2 or 3)
8
in Current sample n
9
u
fn
Phase voltage sample n
10
u
fFn
Phase-to-phase voltage sample n
11
φf Power angle between current and phase voltage f (φ1, φ
2
or φ3)
12
Uc Agreed supply voltage
Equations
Voltage
N
u
=
U
2 n
N
1=n
f
Phase voltage
N − 128 samples in one period (up to 65 Hz)
N − 128 samples in M
v
periods (above 65 Hz)
Example: 400 Hz → N = 7
( )
N
2
yn
xn
N
1
=n
xy
uu
=
U
Phase-to-phase voltage
ux, uy − phase voltages (Uf) N − a number of samples in a period
Current
N
=
i
I
2 n
N
1=n
RMS
Phase current
N 128 samples in a period (up to 65 Hz)
N − 128 samples in more periods (above 65
Hz)
( )
N
iii
=
2
n3n2n1
N
1=n
n
I
++
Neutral current
i − n sample of phase current (1, 2 or 3) N = 128 samples in a period (up to 65 Hz)
Page 50
MTR-3 Installation Instructions
DEIF A/S Page 50 of 51
Power
( )
=
×=
N
n
n
f
n
ff
iu
N
P
1
1
Active power by phases
N − a number of samples in a period n − sample number (0 ≤ n ≤ N)
f − phase designation
321t
PPPP ++=
Total active power
t − total power
1, 2, 3 − phase designation
( )
[ ]
( )
[ ]
( )
1SignQ360801
1SignQ1800
SignQ
f
f
f
=ϕ°°ϕ
+=ϕ°°ϕ
ϕ
Reactive power sign
Q
f
− reactive power (by phases)
φ − power angle
fff
IUS ×=
Apparent power by phases
Uf − phase voltage
If − phase current
321t
SSSS ++=
Total apparent power
Sf − apparent power by phases
( )
2
f
2 fff
PSSignQQ ×=
ϕ
Reactive power by phases (standard)
Sf − apparent power by phases
Pf − active power by phases
[ ]
( )
=
+
×=
N
n
Nn
f
n
ff
iu
N
Q
1
4/
1
Reactive power by phases (delayed current
method)
N − a number of samples in a period n − sample number (0 ≤ n ≤ N)
f − phase designation
321
t
Q
QQQ +
+=
Total reactive power
Qf − reactive power by phases
( )
[ ]
°°=ϕ
=ϕ
99,179,180
Q,P2tana
s
tts
Total power angle
Pt − total active power
St − total apparent power
S
P
PF =
Distortion factor
P − total active power
S − total apparent power
f
f
f
S
P
PF
=
Distortion factor
Pf − phase active power
Sf − phase apparent power
Page 51
MTR-3 Installation Instructions
DEIF A/S Page 51 of 51
THD
( )
100
I
In
%THDI
1
63
2n
2
f
=
=
Current THD
I
1
− value of first harmonic
n − number of harmonic
( )
100
U
Un
%THDU
1
63
2n
2
f
=
=
Phase voltage THD
U
1
− value of first harmonic
n − number of harmonic
( )
100
U
Un
%THDU
1
63
2n
2
ff
=
=
Phase-to-phase voltage THD
U
1
− value of first harmonic
n − number of harmonic
Energy
exponent price Tarif
10 Price in tariff Price =
Total exponent of tariff price and energy price in all tariffs
DEIF A/S reserves the right to change any of the above.
Loading...