Deif MIQ96-2 User Manual

Page 1
DEIF A/S
Multi-instrument type MIQ96-2
4189320013A
Limit switches
2 impulse outputs for kWh import, kvarh import
Customer specified display
DEIF A/S Tel.: (+45) 9614 9614 Frisenborgvej 33, DK-7800 Skive Fax: (+45) 9614 9615 Denmark E-mail: deif@deif.com
Page 2
1 Customer display
A customer specified display is available from software version 2.70. The customer display is placed between the menus “PF total/Frequency” and “Total energy” - see below.
6 parameters (3 in each window), chosen by the customer, can be shown at a time.
56
4 3
56
230.00 v
5000.0 mA
49.990 Hz f
56
U2
I3
558.00 kW+
4
300.00 var
3
485.90 VA
4 3
Menu 1 display Menu 2 display
P1
Q1
S1
56
1.1 How to set up the customer display
Press arrow up or arrow down until the menu “Setting” appears. Press “Enter” once or press arrow right until the menu “Password” appears.
Press arrow up or arrow down again until the menu “Display” appears, then press arrow right once, and the menu “Contrast” will appear.
Press arrow down once, and the menu for changing of the “Customer display” will appear.
Page 2 of 7 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com
Page 3
User’s manual (Appendix), multi-instrument MIQ96-2
CUSTOM 1: U2 I3 f
2. P1 Q1 S1
CUSTOM 1: U
2 I3 f
2. P1 Q1 S1 Set
When the “Enter” button is pressed, the display will go in “Set” mode, and the actual parameter that can be changed will be underlined.
Now arrow up or arrow down can be used to go to the wanted parameter. When the wanted parameter has been selected, press arrow right (“Enter”), and the next value can be changed.
When the “Customer display” is OK, press arrow right until “Set” disappears.
Now press arrow left (“Exit”) until the main menu appears, then use arrow up or
arrow down until “Customer display” is shown.
See abbreviation for each available parameter in the table below:
Pt Total active power P1 Phase 1 active power P2 Phase 2 active power P3 Phase 3 active power Qt Total reactive power Q1 Phase 1 reactive power Q2 Phase 2 reactive power Q3 Phase 3 reactive power It Total I (the sum of I1+I2+I3) I1 I1 I2 I2 I3 I3 UΥ Average voltage (star) U1 U1 U2 U2 U3 U3
4189320013A (UK)
Page 4
St Total apparent power S1 Phase 1 apparent power S2 Phase 2 apparent power S3 Phase 3 apparent power PFt Total power factor PF1 Power factor phase 1 PF2 Power factor phase 2 PF3 Power factor phase 3 f Frequency PAt Total power angle (atan2 (Pt, Qt)) A1 Power angle phase 1 A2 Power angle phase 2 A3 Power angle phase 3 In Neutral current A12 Angle between phase 1-2 A23 Angle between phase 2-3 A31 Angle between phase 3-1 U Average uxy (delta) U12 U between phase 12 U23 U between phase 23 U31 U between phase 31 MDP Dynamic demand value 1 (Pt) MDQ Dynamic demand value 2 (Qt) MDS Dynamic demand value 3 (St) MDI Dynamic demand value 4 (It) Tin Internal temperature in the MIQ96-2
2 Pulse output for kWh and kvarh
The pulse duration of the kWh (counters 1 and 3) and kvarh counters (counters 2 and
4) can be set between 10ms and 300ms.
2.1 How to change the pulse duration
Find the menu for “Outputs” under the menu “Setting” and press “Enter”.
Press “Enter” again, and the settings for output 1 will appear. Use arrow up or
arrow down to choose between output 1 and output 2.
Page 4 of 7 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com
Page 5
User’s manual (Appendix), multi-instrument MIQ96-2
The example below shows setting of the pulse duration for output 1.
OUT1: (200ms) 1P/Wh
Press ”Enter”, and ”SET” appears.
OUT1: (200ms) 1P/Wh SET
Press ”Enter”, and ”SET” appears for pulse duration. Change the value with arrow up or arrow down. To shift from one digit to another, use arrow left or arrow right.
Pulse: 200ms SET
Press ”Enter” until OUT1: (150ms) 1P/Wh appears again. Now choose number of pulses/Wh with arrow up or arrow down and press “Enter” to accept.
Pulse: (150ms) 1P/Wh SET
4189320013A (UK)
Page 6
3 Limit switches
Relays 1 and 2 can also be used as limit switches for stated parameters in the table in section 2.
3.1 How to set up a limit switch
Find the menu for “Outputs” under the menu “Setting” and press “Enter”.
Use arrow up or arrow down to choose between output 1 and output 2.
Press “Enter” again, and the settings for output 1 will appear. Use arrow up or
arrow down to choose between pulse output function or limit switch function.
OUT1: (200ms) 1P/Wh SET
LIMIT 1: 005s
ON : U1 < 190.00V OFF: U1 > 210.00V
SET
Press “Enter” for change of response/delay time - select with arrow up or arrow down.
Press “Enter” for change of parameter - select with arrow up or arrow down.
Press “Enter” for change of > or < - select with arrow up or arrow down.
Press “Enter” for determination of limit value ON - select with arrow up or arrow
down the percentage of nominal value.
Press “Enter” for determination of limit value OFF - select with arrow up or arrow down the percentage of nominal value.
When the limits have been set, the window below will be displayed.
LIMIT 1: 010s ON : U1 < 200.00V OFF: U1 > 230.00V
Page 6 of 7 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com
Page 7
User’s manual (Appendix), multi-instrument MIQ96-2
3.2 Function of limit set-up
Ex. 1
On: Off:
110V 200V 230V
LIMIT 1: 010s ON : U1 < 200.00V OFF: U1 > 230.00V
Ex. 2
On: Off:
110V 200V 230V
LIMIT 1: 010s ON : U1 > 230.00V OFF: U1 < 200.00V
Errors and changes excepted
4189320013A (UK)