Deif GPC-3, GPU-3, GPU-3 Hydro, PPU-3 Quick Start Manual

Page 1
DEIF A/S · Frisenborgvej 33 · DK-7800 Skive · Tel.: +45 9614 9614 · Fax: +45 9614 9615 · info@deif.com · www.deif.com
QUICK START GUIDE
Generator Paralleling Controller, GPC-3
Generator Protection Unit, GPU-3/GPU-3 Hydro
● What's in the delivery?
● Getting started
● The first steps
● PC utility software
Document no.: 4189340603B SW version: 3.0X.X or later
Page 2
1. General information
1.1. Warnings, legal information and safety..................................................................................................3
1.1.1. Warnings and notes ......................................................................................................................3
1.1.2. Legal information and disclaimer ..................................................................................................3
1.1.3. Safety issues ................................................................................................................................3
1.1.4. Electrostatic discharge awareness ...............................................................................................3
1.1.5. Factory settings ............................................................................................................................3
1.2. About the Quick Start Guide...................................................................................................................4
1.2.1. General purpose............................................................................................................................4
1.2.2. Intended users...............................................................................................................................4
1.2.3. Contents and overall structure ......................................................................................................4
2. What's in the delivery?
2.1. Standard delivery...................................................................................................................................5
2.2. Optional delivery.....................................................................................................................................6
3. Getting started
3.1. Connecting the devices..........................................................................................................................8
3.1.1. Connecting the display with the main unit.....................................................................................8
3.1.2. Connecting the power supply to the main unit...............................................................................9
3.1.3. Connecting the additional operator panel, AOP-1 (optional).........................................................9
3.1.4. Connecting the additional operator panel, AOP-2 (optional).......................................................10
3.2. Wiring...................................................................................................................................................11
3.2.1. Basic wiring for GPU-3 and GPU-3 Hydro...................................................................................11
3.2.2. Basic wiring for GPC-3 and PPU-3..............................................................................................13
4. The first steps
4.1. Basic AC values...................................................................................................................................15
4.2. Getting started with the DEIF utility software (USW)............................................................................17
4.2.1. Downloading the software...........................................................................................................17
4.2.2. Installation of USB drivers...........................................................................................................17
4.2.3. Getting connected........................................................................................................................18
4.2.4. Read parameters from the device...............................................................................................20
4.2.5. Basic configuration of a device using the utility software.............................................................20
5. Configuring the speed governor and AVR outputs
5.1. Settings for speed governor and AVR control......................................................................................22
ML-2 quick start guide 4189340603 UK
DEIF A/S Page 2 of 23
Page 3
1. General information
1.1 Warnings, legal information and safety
1.1.1 Warnings and notes
Throughout this document, a number of warnings and notes with helpful user information will be presented. To ensure that these are noticed, they will be highlighted as follows in order to separate them from the gener­al text.
Warnings
Warnings indicate a potentially dangerous situation, which could result in death, personal in­jury or damaged equipment, if certain guidelines are not followed.
Notes
Notes provide general information, which will be helpful for the reader to bear in mind.
1.1.2 Legal information and disclaimer
DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how to install or operate the engine/generator controlled by the Multi-line 2 unit, the company responsible for the installation or the operation of the set must be contacted.
The Multi-line 2 unit is not to be opened by unauthorised personnel. If opened anyway, the war­ranty will be lost.
Disclaimer
DEIF A/S reserves the right to change any of the contents of this document without prior notice.
1.1.3 Safety issues
Installing and operating the Multi-line 2 unit may imply work with dangerous currents and voltages. Therefore, the installation should only be carried out by authorised personnel who understand the risks involved in work­ing with live electrical equipment.
Be aware of the hazardous live currents and voltages. Do not touch any AC measurement in­puts as this could lead to injury or death.
1.1.4 Electrostatic discharge awareness
Sufficient care must be taken to protect the terminal against static discharges during the installation. Once the unit is installed and connected, these precautions are no longer necessary.
1.1.5 Factory settings
The Multi-line 2 unit is delivered from factory with certain factory settings. These are based on average values and are not necessarily the correct settings for matching the engine/generator set in question. Precautions must be taken to check the settings before running the engine/generator set.
ML-2 quick start guide 4189340603 UK
General information
DEIF A/S Page 3 of 23
Page 4
1.2 About the Quick Start Guide
1.2.1 General purpose
This Quick Start Guide mainly includes general product information, mounting instructions and wiring descrip­tions.
The general purpose of this document is to help the user with the first steps of installing and using the Multi­line 2 system.
Please make sure that you also read the Installation Instructions before starting to work with the Multi-line 2 unit and the genset to be controlled. Failure to do this could result in human injury or damage to the equipment.
1.2.2 Intended users
This Quick Start Guide is mainly intended for the panel builder in charge. On the basis of this document, the panel builder designer will give the electrician the information he needs in order to get started with the instal­lation. For detailed electrical drawings, please see the Installation Instructions.
1.2.3 Contents and overall structure
This document is divided into chapters, and in order to make the structure simple and easy to use, each chapter will begin from the top of a new page.
ML-2 quick start guide 4189340603 UK General information
DEIF A/S Page 4 of 23
Page 5
2. What's in the delivery?
2.1 Standard delivery
The main unit
Standard display unit, DU-2
Layout is option-dependent
Display cable, 3 m Installation instructions
ML-2 quick start guide 4189340603 UK What's in the delivery?
DEIF A/S Page 5 of 23
Page 6
2.2 Optional delivery
Display cable with plugs, 6 m (option J2) PC cable for option N programming -
Ethernet cable crossed (option J4)
Display cable with plugs, 1 m (option J6) PC cable for utility software (option J7)
ML-2 quick start guide 4189340603 UK What's in the delivery?
DEIF A/S Page 6 of 23
Page 7
Additional standard display, DU-2 (option X2)
Display unit, DU-2 DC/DC converter and 2 × CAN bus cable 3 m
Additional operator panel, AOP-1 (option X3)
AOP-1 0.5 m cable
Additional operator panel, AOP-2 (option X4)
AOP-2 DC/DC converter and 2 × CAN bus cable 3 m
ML-2 quick start guide 4189340603 UK What's in the delivery?
DEIF A/S Page 7 of 23
Page 8
3. Getting started
3.1 Connecting the devices
3.1.1 Connecting the display with the main unit
Connect the SUB-D display cable to the main unit and the display unit as shown in the picture below.
No use of tools or brute force when tightening finger-screws on display cable.
ML-2 quick start guide 4189340603 UK Getting started
DEIF A/S Page 8 of 23
Page 9
3.1.2 Connecting the power supply to the main unit
3
1
4
2
787776757473
96 979594929190 93
89888785 8683 8482818079
727169 70686765 66
62 6359 60 615856 575553 54 645251504947464443 45 4841403837 39 42
Service port Display
CAN B
CAN A
Power Self check ok Alarm inhibit
1. Terminal 1: +24 V
dc
2. Terminal 2: 0 V
dc
3. Option M4 - terminal 98: +24 V
dc
4. Option M4 - terminal 99: 0 V
dc
3.1.3 Connecting the additional operator panel, AOP-1 (optional)
Display unit DU-2
AOP-1
AOP-1 cable
0.5 m
ML-2 quick start guide 4189340603 UK Getting started
DEIF A/S Page 9 of 23
Page 10
3.1.4 Connecting the additional operator panel, AOP-2 (optional)
The CAN cable for the CAN bus communication between the display unit of main unit no. 1 and the AOP-2 has to be connected to the CAN port (CAN 2) of the display unit (DU-2) and the CAN port (CAN 1) of the AOP-2 as shown in the drawing below.
Standard display DU-2
OFF ON
App./Bootl.
End Res.
CAN 1
AOP-1
CAN 2
ML - 2
Green
Blue
DIN Rail
Additional Operator Panel AOP-2
OFF ON
App./Bootl.
End Res.
CAN 1 CAN 2
Green
Blue
DIN Rail
5V DC
24V DC
+
-
+
-
White
Black
1
2
1
2
Twisted pair max. 200m
Cable shield
The AOP-2 can be placed up to 200 m from the main display. The AOP-2 requires a separate power supply unit, while the display receives the power supply through the display cable from the main unit.
For further information about the installation of multiple displays and AOP-2s, please refer to the document "Description of Option X".
ML-2 quick start guide 4189340603 UK Getting started
DEIF A/S Page 10 of 23
Page 11
3.2 Wiring
3.2.1 Basic wiring for GPU-3 and GPU-3 Hydro
AC wiring
L1 L2 L3
S1
S2
S1
S2
S1
S2
GB
U L1 U L2 U L3
U L3 U L2 U L1
73
74
75
76
77
78
79 81 83
85
87
89
787776757473 96 979594929190 9389888785 8683 8482818079
727169 70686765 66626359 60 615856 575553 54 645251504947464443 45 4841403837 39 42
Service port
Display
Power Self check ok Alarm inhibit
G
ML-2 quick start guide 4189340603 UK Getting started
DEIF A/S Page 11 of 23
Page 12
DC wiring
+ 24 VDC
0 VDC
Trip GB
12345
6
14
15
28
24
Remote alarm
acknowledge (pulse)
Alarm inhibit 1
Alarm
horn
Status OK
DC Main
supply
23
GB
L1 L2 L3
G
787776757473 96 979594929190 9389888785 8683 8482818079
727169 70686765 66626359 60 615856 575553 54 645251504947464443 45 4841403837 39 42
Service port
Display
Power Self check ok Alarm inhibit
ML-2 quick start guide 4189340603 UK Getting started
DEIF A/S Page 12 of 23
Page 13
3.2.2 Basic wiring for GPC-3 and PPU-3
AC wiring
L1 L2 L3
S1
S2
S1
S2
S1
S2
GB
U L1 U L2 U L3
U L3 U L2 U L1
73
74
75
76
77
78
79 81 83
85
87
89
787776757473 96 979594929190 9389888785 8683 8482818079
727169 70686765 6662 6359 60 615856 575553 54 645251504947464443 45 4841403837 39 42
Service port
Display
Power Self check ok Alarm inhibit
G
For further information, please refer to the document "Installation Instructions".
ML-2 quick start guide 4189340603 UK Getting started
DEIF A/S Page 13 of 23
Page 14
DC wiring
+ 24 VDC
0 VDC
Trip GB
12345
6
14
15
28
24
Remote alarm
acknowledge (pulse)
Alarm inhibit 1
Alarm
horn
Status OK
DC Main
supply
23
GB
L1 L2 L3
G
Up Down
Speed
governor
Breaker
feedback
26
27
GB
Closed
GB
Open
17
GB Close
787776757473 96 979594929190 9389888785 8683 8482818079
727169 70686765 66626359 60 615856 575553 54 645251504947464443 45 4841403837 39 42
Service port
Display
Power Self check ok Alarm inhibit
To other units
39 – Q load sharing 38 – Common 37 – P load sharing
25
Start
sync./ctrl.
Deload
66
65
68
67
ML-2 quick start guide 4189340603 UK Getting started
DEIF A/S Page 14 of 23
Page 15
4. The first steps
4.1 Basic AC values
This chapter guides you through the most essential parameters which have to be adjusted before you can start using the unit.
The set points can either be adjusted from the display unit or by using the DEIF utility software. The following examples will show how to adjust the parameters from the display unit.
All settings are reached by placing the cursor under SETUP (in the main page) and pressing ENTER.
Paralleling and Protection Unit
multi-line PPU
PPU V 3.00..0
SETUP MENU
SETUP V3 V2 V1
2010-01-02 12:42:55
Place the cursor under SYST and press ENTER.
Paralleling and Protection Unit
multi-line PPU
G 400 400 400V
SYSTEM SETUP
PROT CTRL I/O SYST
G f-L1 50.00Hz
ML-2 quick start guide 4189340603 UK The first steps
DEIF A/S Page 15 of 23
Page 16
Place the cursor under GEN and press ENTER.
Paralleling and Protection Unit
multi-line PPU
G 400 400 400V
GENERAL SETUP
GEN MAINS COMM
SYSTEM SETUP
Place the cursor under the setting you require and press ENTER.
Paralleling and Protection Unit
multi-line PPU
G 400 400 400V
Frequency 50.0HZ
F P I U Rpm Set
6000 Nom. Setting 1
Generator nominal settings 1
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
6000 Nominal settings 1
6001 Nom. set-
tings 1
Frequen-cy48.0 Hz
62.0 Hz
50.0 Hz Designer's Reference Handbook
The selection of nominal settings to be used is set in 6006. A binary input or selection in M-Logic can also be used.
The range of nom. volt­age and nom. power de­pends on the selected range in "9030 Scaling".
6002 Nom. set-
tings 1
Power 10 kW
20000 kW
480 kW
6003 Nom. set-
tings 1
Current 0 A
9000 A
867 A
6004 Nom. set-
tings 1
Voltage 100 V
25000 V
400 V
6005 Nom. set-
tings 1
RPM 100 RPM
4000 RPM
1500 RPM
6006 Nom. set-
tings 1
Set 1
4
1
To adjust the transformer settings, use the or push-button to get to the transformer page.
ML-2 quick start guide 4189340603 UK
The first steps
DEIF A/S Page 16 of 23
Page 17
VT and CT settings
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
6040 G transformer
6041 G transform-erU primary 100 V
25000 V
400 V Designer's
Reference Handbook
If no voltage transformer is present, the primary and secondary side val­ues are set to generator nominal value.
6042 G transform-erU secon-
dary
100 V 690 V
400 V
6043 G transform-erI primary 5 A
9000 A
1000 A
6044 G transform-erI secondary 1 A
5 A
5 A
6050 Busbar settings
6051 BB settings U primary 100 V
25000 V
400 V Designer's
Reference Handbook
If no voltage transformer is present, the primary and secondary side val­ues are set to generator nominal value
6052 BB settings U secon-
dary
100 V 690 V
400 V
6053 BB settings U BB nom. 100 V
25000 V
400 V
4.2 Getting started with the DEIF utility software (USW)
4.2.1 Downloading the software
1. Go to www.deif.com
2. Select Documentation & Software
3. Select Software download
4. In the dropdown menu, select Multi-line 2 utility software v.3.x
5. Fill in your e-mail address and click “Submit”
You will now receive an e-mail containing a link. Click the link and follow the instructions.
The USW is now installed on your computer.
4.2.2 Installation of USB drivers
On Windows Vista machines, the USB drivers are installed automatically.
This is the procedure on Windows XP machines:
When you connect the DEIF product, Windows XP will launch two "Hardware Wizards". Two drivers are in­stalled, so please let Windows execute both "Found new Hardware Wizard"s.
We recommend letting the Hardware Wizard install the software automatically by choosing the "Recommen­ded" option. If the "Advanced" option is chosen, the needed files are available from the USW3 installation folder (default: C:\Program Files\DEIF\USW3\) in the "USB driver files/source PreInstaller" folder.
Please select "Continue Anyway" if a "Hardware Installation" warning (see screenshot below) appears during the installation.
ML-2 quick start guide 4189340603 UK
The first steps
DEIF A/S Page 17 of 23
Page 18
4.2.3 Getting connected
Connect the service port to the USB on the computer (option J7 or option J3).
Click the Utility Software 3 icon on the desktop or in the Windows Start menu.
Desktop icon:
Quick launch and Start menu icon:
The below window appears.
ML-2 quick start guide 4189340603 UK The first steps
DEIF A/S Page 18 of 23
Page 19
Open the application settings by clicking this icon.
Open "Windows device man­ager".
Check the COM port used for communication, and make sure the settings correspond to the application settings.
Click the "Connect" icon.
You are now online with the unit.
ML-2 quick start guide 4189340603 UK
The first steps
DEIF A/S Page 19 of 23
Page 20
4.2.4 Read parameters from the device
Open the "Parameters" list.
Click the "Read parameters from the device" icon.
After retrieving all the parameters, the device is ready to be configured.
4.2.5 Basic configuration of a device using the utility software
When the parameters have been uploaded, the options below will be available.
Click the "Gen" tab.
The parameters can be configured as follows:
Click a parameter and the dialogue box below will appear.
ML-2 quick start guide 4189340603 UK
The first steps
DEIF A/S Page 20 of 23
Page 21
Click this or use the bar to adjust the setpoint, then click "Write" and "OK".
The parameter setpoint has now been changed and downloaded to the device.
For further information, please refer to the General Guidelines for Commissioning.
ML-2 quick start guide 4189340603 UK The first steps
DEIF A/S Page 21 of 23
Page 22
5. Configuring the speed governor and AVR out­puts
5.1 Settings for speed governor and AVR control
Dependent on the hardware configuration, relays or analogue outputs can be used for speed governor and AVR control.
The settings used for this are the following:
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
2600 Relay control
2601 Relay
control
GOV ON time
10 ms 6500 ms
500 ms Designer’s
Reference Handbook
GPU: Option G2
This menu is only availa­ble if "Relay" is selected in menu 2781.
Normally used: Relay 65 for increase and relay 67 for decrease.
2602 Relay
control
GOV peri­od time
50 ms 32500 ms
2500 ms
2603 Relay
control
Increase relay
Not used Option­dep.
Relay 65
2604 Relay
control
Decrease relay
Not used Option­dep.
Relay 67
2720 Relay control (AVR)
2721 Relay
control
AVR ON time
10 ms 3000 ms
100 ms Option:
AVR control (D1)
Relay outputs for voltage/ var/power factor control. This menu is only availa­ble if "Relay" is selected in menu 2782.
Normally used: Relay 69 for increase and relay 71 for decrease
2722 Relay
control
AVR per time
50 ms 1500 ms
500 ms
2723 Relay
control
U in­crease
Not used Option­dep.
Relay 69
2724 Relay
control
U de­crease
Not used Option­dep.
Relay 71
2780 Regulator output
2781 Reg.
output
GOV Relay
EIC
Relay Designer’s
Reference Handbook
GPU: Option G2
Selection of the speed output: Relay, analogue or engine interface com­munication. Analogue and EIC are option-de­pendent.
ML-2 quick start guide 4189340603 UK Configuring the speed governor and AVR
outputs
DEIF A/S Page 22 of 23
Page 23
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
2782 Reg.
output
AVR Relay
Analogue
Relay Option:
AVR control (D1)
Generator voltage control based on relay or ana­logue output signals. An­alogue selection is only available if option E1, E2, EF2, EF4 or F2 is present.
5980 Governor output
5981 Gover-
nor out­put
Output A Disabled
AO66 AO71
Disa­bled
Option E andFNormally used: Analogue
output 66
5990 AVR output
5991 AVR out-
put
Output A Disabled
AO66 AO71
Disa­bled
Option D Normally used: Analogue
output 71
AVR control requires option D1.
Analogue outputs require option E1, E2, EF2, EF4 or EF5.
For further information, please refer to the document "General Guidelines for Commissioning".
For further information, please check the following documents:
GPC-3 Designer’s Reference Handbook Document no. 4189340587 GPU-3 Designer’s Reference Handbook Document no. 4189340584 GPU-3 Hydro Designer’s Reference Handbook Document no. 4189340588 PPU-3 Designer’s Reference Handbook Document no. 4189340583 GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Installation Instructions Document no. 4189340582 GPC-3/GPU-3/GPU-3 Hydro/PPU-3 Operator’s Manual Document no. 4189340579
ML-2 quick start guide 4189340603 UK Configuring the speed governor and AVR
outputs
DEIF A/S Page 23 of 23