Mounting
To obtain optimum cooling it is imperative to comply with the specified installation
position, where the input terminals (L1, L2, L3, PE or L1, N, PE) are placed at the top
and the output terminals (+/-) at the bottom.
Distance
:
Above and below the DCP2 100 mm
To each side 30 mm
The permissible ambient temperature must not be exceeded:
-10...70°C (operating, free convection)
-25...85°C (storage)
Connection
:
See the cover of the unit (imprint). The phase sequence is indifferent.
Protection
:
Units supplied by 1 x 230V AC are internally protected by a fuse and can be
connected directly to line.
The power cords for 3 x 400/480V AC units must be protected by a three-pole C-fuse
or a three-pole motor circuit breaker (only DCP2-2420 and DCP2-2440). Operating
with a disconnected phase is not permissible.
Fuse
: DCP2-1205, -2405:
5 x 20 mm T3.15A/250V internal
DCP2-1210, -2410, -2410/115V:
5 x 20 mm T6.3A/250V internal
DCP2-2420:
5 x 20 mm T10A/250V internal
DCP2-2420, -2440:
Three poles, C-fuse or motor circuit breaker
Switch - external (setting 3A)
CE marking
All variants of the DCP2 are CE marked to the EMC Directive and the Low Voltage
Directive. However, the following comments concerning EN 61000-3-2 (limits for
harmonic current emissions) apply and must be observed upon installation of the 10A
and 20A variants:
If the 10A and 20A variants are used as part of an apparatus which has a rated AC
power of 1kW or more, there is no requirement for compliance with EN 61000-3-2.
If the 10A and 20A variants are used as part of an apparatus which has a rated AC
power less than 1kW , compliance with EN 61000-3-2 must be ensured by the maker
of the apparatus. In this case the maker of the apparatus containing the DCP2 must