2 Relay outputs, 2 Analog
outputs, 4 Digital inputs,
HMI connection, RS232,
RS485, RS422, Ethernet
›Easy USB programming
and data log retrieval via your PC
defineinstruments.com/workbench
1
Zen Datalogger
Data Logging Control Station
General Description
The Zen Datalogger is a stand-alone data
logging device. It has logging for up to 30
separate channels, including 16 on-board universal inputs.
Among the most exible data loggers on the
market, the Zen Datalogger is ideal for connecting to a mixture of analog and digital
sensors. The inputs are all individually isolated and EMC hardened, making it t for the
most demanding industrial environments.
Data is logged to a 1GB Micro SD card, for
easy data retrieval and transport.
Our free WorkBench soware enables easy
conguration of the unit, as well as download and display of logged data. Each unit
can be viewed by 8 simultaneous users over
the LAN.
The Zen Datalogger supports a range of
interface options including RS232, RS485,
RS422 and Ethernet, for simple integration
with PLCs and SCADA systems.
It can be set up as an analog multiplexer, utilizing the onboard dual analog outputs, or
as an alarm and control station, using the 16
inbuilt setpoints. These setpoints can trigger
up to 16 relay contacts if connected to the
optional ZEN-RIO (sold separately).
The setpoints can also trigger SMS and email
alarms if the unit is connected to an external
cellular modem and loaded with the modem
plugin (found in WorkBench).
For your safety and the prevention of damage to the Zen unit and other equipment
connected to it, please read complete instructions prior to installation and op-
eration of the Zen and carefully observe all safety regulations and instructions.
Consult this manual carefully in all cases where hazard symbols are marked on
your Zen unit.
Use of this instrument in a manner not specied by the manufacturer may compromise the protection provided by the instrument. This instrument should not be used
to directly drive valves, motors, or other actuators, unless equipped with appropriate safeguards.
It is the responsibility of the user to identify potential hazards that may arise in
the event of a fault to unit, and implement safeguards for the prevention of harm
to persons or equipment. The safety of any system incorporating this unit is the
responsibility of the assembler of the system.
Port 1 Comm
85–265V AC / 95–370V DC
24–48V AC / 17–72V DC
RS422/485
Ethernet Modbus
Symbol denitions
CAUTION
Risk of electric shock
Please refer to user manual.
CAUTION
Risk of danger
Please refer to user manual.
Both direct and alternating current.
Equipment protected throughout by
DOUBLE INSULATION or REINFORCED
INSULATION.
The Zen should be installed in a location that
does not exceed the maximum operating
temperature, and at a safe distance from
other devices that generate excessive heat.
The installation environment should provide
good air circulation to the unit.
The plastic casing and product label may be
cleaned, if required, using a so, damp cloth
and neutral soap product. Caution should
be exercised when cleaning the unit to
avoid water dripping inside, as this will
damage the internal circuits.
2.3 - Installation instructions
The Zen Datalogger is rated IP20, and should be mounted in an enclosure to protect the unit
from weather conditions and dust.
A - Installation in Enclosure (Fig 1)
Prepare an Enclosure (not supplied) as illustrated by mounting a DIN 35 rail, cable
glands, and any other required components.
If using a metal enclosure, the enclosure
must be earthed.
B - DIN Rail Mounting (Fig 2)
To clip the unit onto the DIN rail:
(1) Hook the lower part of the unit onto the
rail, and then
(2) Press down towards the rail until the red
hooks click into place
Leave at least 2" (5cm) clear above and below the unit, to allow room for airow and
wiring.
Fig 1
7
C - Wiring
Refer to Sections 6–7 in this manual.
D - Removal from DIN Rail (Fig 3)
To remove the unit from the DIN rail:
(1) Power down the unit
(2) Unplug the 'Input 4' and 'Port 1' connectors from the top of the Zen (the DIN clips
are behind these terminals)
(3) Gently pull the unit away from the rail
while levering one of the clips upward with
a screwdriver
(4) When one side is loosened, hold it slightly away from the rail to prevent the clip from
engaging again (pictured in Fig 3).
Meanwhile, lever the second clip upward as
you did with the rst.
The Zen has been designed to cope with
large EMC disturbances. This has been
achieved by continual testing and improvement of ltering and layout techniques over
many years.
The Zen meets CE noise requirements, and
even surpasses them in many tests. (For
full details and test results, see Appendix
A.) However in some applications with less
than optimum installations and large power
switching, the EMC performance of the Zen
can be further improved, by:
A Installing the unit in an earthed Metal
Enclosure. This is particularly useful
if the control box is mounted close to
large power switching devices like contactors. Every switching cycle there is a
possibility of generating a large amount
of near eld radiated noise. The Metal Enclosure, acting as a faraday cage,
will shunt this radiation to ground and
away from the Zen.
B Increasing the physical distance from
the power devices. For example, increasing the control box distance from
6" to 12" from the noise source will reduce the noise seen by the control box
by a factor of 4. (Probably the cheapest
and best results in this situation could
be obtained by adding RC snubbers to
the contactors or power switches.)
C Using shielded cable on sensitive input
and control signal lines. Good results
can be obtained by grounding the
shields to the metal enclosure close to
the entry point. All cables act as aerials and pick up unwanted R.F. radiated
signals and noise; the earthed shield
acts as a faraday cage around the cables, shunting the unwanted energy to
ground.
Shields can also help with capacitively
coupled noise typically found in circumstances when signal cable is laid on top
of noisy switching power cables. Of
course in this case you are better o to
keep separate signal and power lines.
D Laying cable on earthed cable trays
can also help reduce noise seen by the
Zen. This is particularly useful if there
are long cable runs, or the unit is close
to radiating sources such as two way
radios.
E The relay outputs of the Zen have built
in MOV's to help reduce EMI when
switching inductive loads. EMI can further be reduced at the load by adding
snubbers for AC signals or a yback diode for DC coils.
Dene WorkBench oers a comprehensive and yet simple-to-use setup tool for your Zen unit,
complete with data log extraction and visualization.
You must install WorkBench before connecting the Zen Datalogger to your computer. If
you have already connected using the Bridge Key, please disconnect before continuing.
A Download the latest version of WorkBench from
www.deneinstruments.com/workbench
B Extract the install le from the zip folder. Right-click on the zip folder and choose
'Extract All', (or extract the le using another extraction utility of your choice).
INSTALLING DEFINE WORKBENCH
C Double-click on the extracted .msi
install le. This will launch the
WorkBench installer.
Depending on your security settings,
a 'Security Warning' dialog may
appear. If you see the security
message, click 'Run'.
To program your Zen Datalogger, connect one end of the Interface Cable to
the programming port on the le side
of the Zen (see Fig 4), and the other
end to your Bridge Key.
Then plug the Bridge Key into your
computer's USB port (see Fig 5).
Supply Power
Supply power to the Zen Datalogger,
referring to 6.1 for wiring.
Bridge Key
Interface Cable
Zen Datalogger
Connect to your Zen in Dene WorkBench
Launch Dene WorkBench (see Section 3 for installation instructions), and select the 'Prog
Port' tab. If your Zen is powered up and connected via the Bridge Key, then the COM Port will
be detected automatically. Click 'Connect'.
Main Navigation, including channel sub-navigation. See 4.3 for more information.
Control Area
Main control area for conguring your
system. Any changes made in this area will
bring up the Apply Button (see below)
Connection Panel
Disconnect button
Connection status
Apply Button
Appears if you have made any changes in the
Control Area. WorkBench will not allow you to
browse to a new tab in the Main Navigation with
unapplied changes to your conguration.
Wiring diagrams, explanations
and helpful tips will automatically appear in this panel as
you congure the Zen.
4.3 - Main navigation
13
Overview
View basic device information including Serial Number and rmware version. Password
Protect your device, export a conguration
certicate and save/upload a conguration
le.
Ports
This tab is only visible if you are connected to
your Zen via the USB Programming Port. It
enables you to congure a range of settings
for Port 1 and Port 2 (baud rate, parity, Tx
delay etc.).
Once your ports are set up, you will be able
to congure to your Zen in WorkBench via
Port 1 or Port 2 instead of the USB programming port - perfect for adjusting settings
once your unit is installed.
Inputs
Set up and scale the 16 isolated input channels. Includes integrated wiring diagrams
and examples.
Digital Inputs
Set up the four digital inputs and view their
live status.
Totalizers
Congure up to 10 totalizers using either an
input channel or a digital input as the source.
Setpoints
Congure up to 16 setpoints which can be
activated by an input, a digital input or a
totalizer. Congure alarms or control functions by selecting from a variety of pre-programmed modes, complete with detailed
explanations.
Relays
Congure the two relay outputs. These may
be driven from one or more setpoints, or directly from one of the digital input pins.
Logging
Congure your data logging options. Select
the logging interval, set the time, and select
which channels will be logged. (See Section
5 for more on Data Logging.)
Data Viewer
View and analyze your live data and download it to your computer. (See Section 5 for
more on Data Logging.)
Plugins
Plugins are small programs which are loaded
into the Zen to expand its functionality or
simplify its use. Plugins are optional and in
many cases they may not be needed. Note
that only one plugin can be installed on your
Zen at a time.
Retransmission
Congure up the two analog outputs to
operate independently, or in cooperation
with the digital inputs as an intelligent
multiplexer.
The Zen Datalogger is supplied with a 1GB Micro SD card, which is the default storage location
for logged data. The Micro SD card can hold up to 7.8 million data samples - enough for nearly
15 years' data logging at 1 sample per minute.
If you remove the Micro SD card to download data from it (see 5.5), the Zen will continue
to log data to its onboard memory. The onboard memory capacity is 32MB (31,744 data
samples) - enough for 22 days' data logging at 1 sample per minute.
Logged data which has been temporarily saved to the onboard memory will be automatically
transferred to the Micro SD card as soon as it is inserted again. (This process can take some
time, depending on how much data needs to be transferred. You will not be able to safely
remove the Micro SD card again [as in 5.5] until the transfer has completed.)
NOTE
Please use the supplied 1GB Micro SD card. Commercially available Micro SD cards
with a capacity higher than 1GB are not supported by the Zen Datalogger.
5.2 - Data logging setup
To set your Data Logging preferences,
connect to your Zen using Dene
WorkBench (see Section 4), and click on the
"Logging" tab.
From there you can:
›Specify what to do when the data
logging capacity is reached (either
overwrite old data, or stop logging)
›Set your logging interval in hours,
minutes and seconds
›Delete your Data Log›Set the clock›Select which channels to log (up to 30
channels, which may include a mixture
of Inputs, Digital Inputs, Totalizers and
Auxiliary inputs)
The Zen Datalogger has 3 LED indicators which provide
information on the status of the data log.
A INTERNAL / SD CARD
These LED's indicate which memory location is currently being used to store logged data:
›If the 'SD CARD', LED is lit, then data is being
saved to the Micro SD card.
›If the 'INTERNAL' LED is lit, the data is being
saved to the onboard memory.
B PRESS BEFORE REMOVING SD
This button must be pressed BEFORE removing the Micro SD card. (Please see 5.5 for
more information on safely removing the Micro SD card.)
C SAFE
If this LED is lit, then it is safe to remove your SD card from the Zen's Micro SD slot.
Fig 6
5.4 - Using the Data Viewer
Dene WorkBench "Data Viewer" enables you to view your logged data and visualize it in the
form of a Multi-Channel Graph (Fig 7), Tiled Graphs (Fig 8), a Distribution Graph (Fig 9), or as
Tabulated Data (Fig 10).
A variety of settings enable you to specify the range of viewable data, and congure your
graph axes and labels. You can also export logged data to CSV format for further processing
using Excel.
Fig 9 - Distribution Graph Fig 10 - Tabulated Data
Downloading logged data
When you connect to your Zen Datalogger in Dene WorkBench and click on the "Data Viewer"
tab, you will have immediate access to any data which has previously been downloaded from
the Zen unit.
Additionally, the graph will show preview content for any data that has not yet been downloaded (this is built using 100 samples from your actual data). To view the complete
data set, you must download the data log.
Downloading the data log has the additional benet of enabling 'oine' viewing, making it
possible to view your data in Dene WorkBench without connecting to your Zen. Regularly
downloading your data log will also ensure that your data history is maintained, in the unlikely
event that the size of your data log exceeds the capacity of the Micro SD Card.
There are two methods for downloading logged data to your PC:
A While connected to your Zen unit, click the "Download NEW
Samples" button.
This button appears in the top right-hand corner of the Data Viewer
window, along with the number of samples to be downloaded. If there are only a mod-
erate number of new samples to be downloaded, then this method is ideal.
However please note that this method can take considerable time if there are a large
number of samples to be downloaded. In this case it is recommended that you download data from the Micro SD Card, as explained below.
B Without connecting to your Zen unit, safely remove the SD Card (see 5.5) and import
its contents to WorkBench.
This is the recommended method for downloading a large data log, because transfer of
data is not impeded by distance, or by the speed of your serial or ethernet connection.
This method also enables you to download the data log without being connected to a
live unit. Please see 5.5 for further instructions.
5.5 - Importing logged data from the Micro SD card
The Micro SD card can be removed from the Zen unit and read using a stan-
dard SD card reader, enabling fast, simple and portable data log retrieval.
To do this, you must rst unmount the Micro SD card by pressing the
button marked 'PRESS BEFORE REMOVING SD'.
This disengages the Micro SD card from the data logging process, causing
any subsequent data samples to be logged to the unit's onboard memory.
(When the Micro SD card is inserted again, any samples that have been logged
to the unit's onboard memory will be transferred to the Micro SD card.)
IMPORTANT
Please read and follow these instructions to remove the Micro SD Card from the Zen
unit. Incorrect removal of the Micro SD could corrupt your data log.
A Press the button marked 'PRESS BEFORE REMOVING SD' (see 5.3B).
B Wait for the green 'SAFE' LED to come on. When the 'SAFE' light is on, remove the SD
card from the Zen unit. Open the rubber ap marked 'DATA' which is located just above
the Display terminal on the lower le-hand side of the unit. Press the SD card to eject it.
C Insert the SD card into your computer's card reader.
D Launch Dene WorkBench and click on the "Data Viewer" tab. (Note that you do not
need to connect to your Zen Datalogger.)
E The 'Data Source' dialog will pop up automatically. Click "SD Card Import" and then
follow the steps in the images below to import the data from your Micro SD card.
F When you have nished importing the data, return the Micro SD card to the Zen Data-
logger. (You do not need to follow any special process to re-insert the SD card).
INTERNAL ON = Using onboard memory for datalog storage
6.2 - LED indicators
The Zen Datalogger has 15 LED indicators on the top label which provide information about
the unit's status, as further explained below:
SD CARD ON = Using Micro SD card for datalog storage
SAFE ON = Safe to remove Micro SD card
ON = Relay Energised
OFF = Relay De-energised
ON = Power is supplied to the unit
FLASHING = Normal operation
ON = Error (contact manufacturer)
6.3 - Analog output
The two Analog Outputs (A–B) can be wired as shown (right) and
congured and scaled in Dene WorkBench from the 'Retransmis-sion' tab.
The Zen Datalogger can also be congured as an Intelligent Multiplexer from the 'Retransmission' tab (see Section 8) - in this case the
Digital Inputs are disabled.
ON = Digital Input Active
OFF = Digital Input Inactive
The two Relay Outputs (A–B) can be wired as shown (right) and
congured in Dene WorkBench from the "Relays" tab. Each Relay
Output has LED indication on top of the unit to indicate when the
relay is energized.
Both relays are normally open, and share a common. Each can be congured for a ‘Closed’ or ‘Open’ triggered state (e.g. for fail safe operation). These settings are retained in soware on power down, but the
relays are de-energized.
Connection example for relay outputs
21
B
A
COM
Power Supply
Note 1 30V AC/DC, 1A maximum contact rating.
COM
Note 2 For individual relay outputs (i.e.
not sharing a common) and/or a con-
A
tact rating of 250V AC, use ZEN-RIO,
which can provide 16 Relay Outputs.
Cooling
B
6.5 - Digital inputs
The Zen Datalogger has four Digital Inputs (A–D), each with LED indication on top of the unit.
The digital inputs can be congured and scaled using Dene WorkBench from the "Digital
Inputs" tab, as per the list below:
›Status (active/inactive - can be read by a SCADA
system as a general digital input)
›Counter (up to 10KHz, or 100Hz Debounced)›Frequency (up to 10KHz)›Flow count (up to 10KHz)›Flow rate (up to 10KHz)›RPM (up to 10KHz)
The Zen Datalogger can also be congured as an Intelligent Multiplexer from the 'Retransmission' tab (see Section 8) - in this case the Digital Inputs are disabled.
Note 2 Do not t the 4K7 resistor for
3-Wire PNP transducers.
D
23
6.6 - Port 1
Port 1 on the Zen Datalogger can be purchased with an auto-detecting RS485/RS422 port
(order code '-RS'), or as an Ethernet Modbus terminal (order code '-EMOD'). If you have the
auto-detecting RS port, refer to the diagrams below for wiring.
RS485
NC
NC
COM
Tx+
Tx−
RS422
Rx−
Rx+
COM
Tx+
Tx−
NOTE
Pins marked 'NC' MUST be le disconnected to ensure correct auto-detection of
your comm type.
6.7 - Port 2
Port 2 can be wired for either RS232
or RS485 serial connection, as shown
(right).
NOTE
Pins marked 'NC' MUST be
le disconnected to ensure
correct auto-detection of
your comm type.
Risk of electric shock. Dangerous and lethal voltages may be present on the input termi-
nals. Please take appropriate precautions to ensure safety.
CAUTION
Risk of danger. The sensor input can potentially oat to dangerous and unexpected volt-
ages depending on what external circuit it is connected to. Appropriate considerations
must be given to the potential of the sensor input with respect to earth common.
7.1 - Current input
Range 0–20mA, 4–20mA
Input impedance 45Ω
Maximum over-range protected by PTC
to 24V DC
Accuracy 0.1% FSO max
0/4–20mA DC is the most commonly used analog signal in industry, and is universally accepted.
As a current loop, it is unaected by voltage drops in cables, and can be transmitted over long
distances without signal degradation.
If you are connecting other instruments in a loop
with a Zen mA input, a fail-safe has been added to
prevent the external loop from being interrupted in
the event of a power loss to the Zen.
To activate the fail-safe for an input channel, turn
on the micro switch above the input terminal. You
will need to remove the input connector to see the
switch, and use a small screwdriver to turn it on.
NOTE
The Fail-Safe Micro Switch is only compatible with mA inputs.
For the accurate operation of this instrument, it is critical that the micro switch be
set to the OFF position for all other input types.
Connection example for 2, 3 & 4 wire mA output transmitters
+24V Supply
Fail-safe Micro Switch
25
2-Wire
Transmitter
Output +
Output −
Output +
Output −
Power
Supply
3-Wire
Transmitter
4-Wire
Transmitter
Note 1 All analog inputs are isolated to
other channels and all other voltages.
They also have built in over voltage protection to 24V, protecting the unit if the
24V supply is inadvertently connected to
the unit when congured for mA input.
Note 2 All cables must be screened, with
screen earthed at one end only.
B+
Input
Channel
B–
B+
Input
Channel
B–
B+
Input
Channel
B–
Note 3 Do not run input cables in close
vicinity to noisy power supplies, contactors or motor cables. The best practice is
to run input cables on a separate earthed
cable tray. This will minimise RFI eects,
of which magnitude cannot be easily
predicted.
The Zen Datalogger accepts both voltage and millivolt inputs. Along with the standard 0–10V
DC range, a variety of other ranges are provided to suit a various applications. These can all be
selected using the WorkBench soware and easily scaled into engineering units.
The ±200mV DC and -200mV to 1V DC ranges are ideal for low signal applications, such as
measuring large DC currents using external current shunts, or interfacing to sensors with low
voltage output. A 0–18V general purpose voltage range is also provided.
Connection Example for Millivolt & Voltage Inputs for 2, 3 & 4 Wire
Transmitters
+24V Supply
2-Wire
Transmitter
B+
B–
27
Input
Channel
Output +
Output −
Output +
Output −
Power
Supply
3-Wire
Transmitter
4-Wire
Transmitter
Note 1 Each voltage input must not see
more than 18V peak between the negative and the input, otherwise permanent
damage may occur.
Note 2 All cables must be screened, with
screen earthed at one end only.
B+
Input
Channel
B–
B+
Input
Channel
B–
Note 3 Do not run input cables in close
vicinity to noisy power supplies, contactors or motor cables. The best practice is
to run input cables on a separate earthed
cable tray. This will minimise RFI eects,
of which magnitude cannot be easily
predicted.
The RTD (standing for Resistance Temperature Device) is highly stable
and accurate, and is fast becoming the most popular temperature
sensor in industry.Oen referred to as Pt100 and Pt1000, the Pt represents platinum (the dominant metal in its construction), and 100/1000
is the resistance in ohms at 0°C.
Supported RTD types/ranges
Pt100/Pt1000 (0.02°F/0.01°C res)-328 to 572°F (-200 to 300°C)
Pt100/Pt1000 (0.1°F/0.1°C res)-328 to 1472°F (-200 to 800°C)
Note 1 All RTD inputs are isolated from
each other.
Note 2 All RTD cables must be screened,
with screen earthed at one end only. All
three wires must be the same resistance
(i.e. the same type and size).
Note 3 To minimise lead resistance errors,
3-wire RTD’s should be used. Oset errors
for 2-wire RTD’s may be compensated for
in the soware.
Note 4 Do not run input cables in close
vicinity to noisy power supplies, contactors or motor cables. The best practice is
to run input cables on a separate earthed
cable tray. This will minimise RFI eects,
of which magnitude cannot be easily
predicted.
Thermocouple types B, E, J, K, N, R, S or
T type (see table below for ranges)
Cold junction compensation 14 to 140°F
(–10 to 60°C)
CJC dri <0.02°C/°C typical for all inputs
The thermocouple
is one of the most
common temperature sensors used in
industry. It relies on
the Seebeck coecient
between dissimilar
metals. The thermocouple type is selected
with reference to the
application temperature range and environment, with J and K
type being the most common.
Connection Example for
Thermocouple Inputs
B+
B–
B+
B–
B+
B–
Note 1 All thermocouple inputs are isolated from each other. There is no need to
buy expensive isolated thermocouples.
Thermocouple
Input
Channel
Input
Channel
Input
Channel
Sensor open Upscale
TC lead resistance 100Ω max
Input impedance >500KΩ
Accuracy 0.1% of FSO ±1°C typical
Supported thermocouple types/ranges
B 32 to 3272°F(0 to 1800°C)
E-328 to 1292°F(-200 to 700°C)
J-328 to 1832°F(-200 to 1000°C)
K-328 to 2300°F(-200 to 1260°C)
N-328 to 2372°F(-200 to 1300°C)
R32 to 3092°F(0 to 1700°C)
S32 to 3092°F(0 to 1700°C)
T-328 to 752°F(-200 to 400°C)
Note 2 For accurate thermocouple mea-
surements (especially at low temperatures) the top cover must always be tted.
Avoid dras and temperature dierences
across terminals. Once installation is complete, close the cabinet door and allow
the cabinet to reach equilibrium. This may
take several hours. Place all thermocouple
probes into a calibrated thermal bath at
temperature of interest. Any osets can
be zeroed out in the soware.
Note 3 All thermocouples are referenced
to a combination of four CJC temperature sensors on the main Zen board. This
minimizes errors caused by the mounting
orientation of the Zen unit, and temperature dierences in enclosures. However,
for high accuracy applications it is still
Note 4 All cables must be screened, with
screen earthed at one end only.
Note 5 When thermocouple inputs are selected, an upscale resistor is automatically
connected to the T/C + input, resulting in
an overow condition for open or broken
sensors.
7.5 - Digital pulse
Frequency range 0–2500.0Hz
Fast counter range 0–2500.0Hz
Sensors Open collector (NPN, PNP), TTL
or Clean Contact
The Zen's 16 universal input terminals accept
digital inputs from NPN, PNP or TTL sensors
as well as Clean Contacts. Pulses up to 2.5kHz
can be counted (except for the debounced
counter, which has a range of 0–50Hz).
A variety of operating modes are soware
programmable to suit your application.
Note 4 Do not run input cables in close
vicinity to noisy power supplies, contactors or motor cables. The best practice is
to run input cables on a separate earthed
cable tray. This will minimise RFI eects,
of which magnitude cannot be easily
predicted.
Frequency resolution 0.1Hz
Debounce counter range 0–50Hz max
Counter register output 32 bit
Accuracy ±0.5%
Soware programmable modes include:
›General counter›General debounced counter (ideal for
mechanical relay contacts which are
subject to bouncing)
each other. Inputs from various sources
can be connected without fear of crating unwanted and troublesome ground
loops.
Note 2 Soware selectable functions
include: frequency to 2kHz, debounced
counter for contact closures to 100Hz
maximum, fast counter to 20KHz.
Note 3 All cables must be screened, with
screen earthed at one end only.
Note 4 Do not run input cables in close
vicinity to noisy power supplies, contactors or motor cables. The best practice is
to run input cables on a separate earthed
cable tray. This will minimise RFI eects,
of which magnitude cannot be easily
predicted.
Field prog span 0.1–100%
Linearity and repeatability
<±0.05% FSO typical
Response time 100msec
Temperature dri <50ppm/°C
A 3 wire potentiometer is typically used to measure position. A low or
high potentiometer range can be programmed to your unit using the
WorkBench soware.
These ranges must be calibrated using the two point calibration method.
8.1 - Connecting to a PLC as an intelligent multiplexer
the Zen Datalogger can easily be congured as an intelligent multiplexer via the 'Retransmission' tab in Dene WorkBench. To do this, select 'Multiplexer (Binary)' as the Retransmission
Mode and wire the unit as shown below.
Specications
Settling time before reading 100msec
min. Multiple readings with averaging
recommended. (Longer times may be
required for longer cable lengths and
higher resolution.)
Binary signal magnitude 5–30V DC
Cycle time 4sec min to cycle through all 16
inputs
Resolution 15 bits, 16,000 steps typical
NOTE
Multiplexer Mode uses both the Retransmission Outputs and the Digital Inputs.
Digital Inputs can no longer be congured independently via the 'Digital Inputs' tab.
The Binary Channel selection is PLC RTX, and
uses the four digital inputs (A–D), as shown
below:
›DI Com = CS Com›DI A = Bin 1›DI B = Bin 2›DI C = Bin 4›DI D = Bin 8
A binary value of ‘0’ indicates no voltage on
the terminal, while a value of ‘1’ indicates
5–30V DC on the terminal.
DI A
BIN 1
DI B
BIN 2
00001
10002
01003
11004
00105
10106
01107
11108
00019
100110
010111
110112
001113
101114
011115
111116
DI C
BIN 4
DI D
BIN 8
Retrans.
Channel
Notes & Recommendations
›Analog Output A is used to retransmit the input process values 1–16, and Analog Output
B is used to retransmit the controller setpoints 1–16.
›The input and output always share the same range. E.g. If Input 1 is ranged 32–212°F
(0–100°C) and retransmission Channel 1 is selected on DI A–D, then AO A and AO B are
both transmitted as 4–20mA = 32–212°F (0–100°C). Similarly, if Input 2 is ranged for
32–482°F (0–250°C), then AO A and AO B are transmitted as 32–482°F (0–250°C).
›If AO A process value or AO B setpoint are transmitted to an indicator, then all the inputs
must be ranged the same, (unless the indicator is ranged to 0–100%).
›In the PLC RTX modes, AO B always retransmits the controller setpoint regardless of
whether the controller is enabled or not.
›The PLC RTX modes can operate simultaneously with the Scada Comms, allowing a PLC
to read back data that the Scada will be showing.
›If multiple Zen units are wired to the same PLC, then it is recommended that the analog
Note 1 In this conguration the DI Com
and digital inputs are isolated from the
inputs and outputs. The 24V external
power supply can therefore be used to
power transmitters connected to the Zen's
inputs.
Note 2 Each digital input draws 10mA at
24V DC.
Zen
AO Com
AO 1
DI Com
DI 1
DI 2
DI 3
DI 4
Note 3 All cables must be screened,with
screen earthed at one end only.
Note 4 There is no limit to the number of
Zens that can be connected, except that
the power supply and open collector outputs must be able to handle the load.
Below is a list of the commonly used Zen Datalogger registers. For a full register list, please see
the Zen Registers document, available at: deneinstruments.com/zen-registers
Your Zen Datalogger has been fully calibrated at the factory, and can be recalibrated in soware using Dene WorkBench (see Section 4). Scaling to convert the input signal to a desired
display value is also done using WorkBench
If your Zen unit appears to be behaving incorrectly or inaccurately, refer to troubleshooting
before attempting to calibrate it. When recalibration is required (generally every 2 years), it
should only be performed by qualied technicians using appropriate equipment.
Calibration does not change any user programmed parameters. However, it may aect the
accuracy of the input signal values previously stored.
9.2 - Troubleshooting
IssueResolution
Input signal is not reading
correctly
Auto-detecting RS Port is
not working
Beat light stays ON for
more than 1 minute
Cannot power up unitCheck the power supply connections and supply range. (The
Ethernet device does not
appear on the network
when trying to connect in
WorkBench
Check positioning of fail-safe micro switch
The fail-safe micro switch should be switched o for all input
types except mA. See 7.1 to conrm.
Ensure that any terminal connections marked 'NC' are le
open - otherwise the Zen will not be able to auto-detect
your serial type.
This indicates an error. Please return the Zen RTU to the
manufacturer for analysis and repair.
polarity on the power input is irrelevant.)
Repower the device aer you plug in the ethernet cable to
ensure that it appears on the network.
For further assistance, please contact technical support using the contact details listed at the
end of this document.
Meets Criterion A
Meets Criterion A
Meets Criterion A
39
Performance Criteria
Performance Criterion A
During the test, normal performance within the specication limits.
Performance Criterion B
During testing, temporary degradation, or loss of performance or function which is
self-recovering.
Performance Criterion C
During testing, temporary degradation, or loss of function or performance which requires
operator intervention or system reset occurs.
*Note 1: EN61326-1 calls for a Criterion B pass; unit exceeds this by meeting Criterion A.
B
The FM1602 display can be purchased separately to enable fast, eld viewing of your input
channel data, without connecting to WorkBench. The display is congured to function with
your Zen Datalogger automatically, with no setup required.
Simply connect the HMI ribbon cable to your Zen's display port (shown in 6.1). The FM1602
will immediately display the current values for input channels 1 and 2 (pictured below).
To view other input channels, press the
the next data pair.