If your controller has serial port tted, wire it as
shown in the applicable diagram.
›S2R: RS232, RJ11 terminal
N/C
D -D +
SGND
N/C
SGND
+5V DC (option)
RXD
TXD
›S4S: RS485, screw terminal
3.6 - Wire the function pinsSee 3.1E
Connect external switches as shown to enable a
function to be executed when its switch is activated.
›Valley Clears the Valley reading (also see 2.3)
›HoldHolds the current display value
›TestResets the meter
›Peak Clears the Peak reading (also see 2.3)
COM
3.7 - Wire the power supply See 3.1F
DO NOT connect your low voltage controller to mains power.
Wire the power supply as shown
below. Compare the label on
the unit with the connector:
›Orange = HV (85–265V AC,
95–370V DC)
High
voltage
(HV)
+DC
Live
AC
−DC
Neutral
AC
Low
voltage
(LV)
+DC
Live
AC
›Black = LV (15–48V AC,
10–72V DC)
HV power
supply
Once you have completed the
wiring process it is safe to switch
on your power supply. Ensure that your display is functioning before you proceed.
E _ _ _ DISPLAY TEMPERATURE UNITS scrolls across the bottom row, and the
current selection appears in the top row. Use the and buttons to select
either YES or NO, and then press .
If you select YES, then C or F (as selected in 5.2D) will appear aer the last digit
of the temperature value on the main display.
Note that activating this feature will eectively limit your temperature display range to 5 digits
(9999.9), because the last character is used for the units.
F _ _ _ DISPLAY HUMIDITY UNITS scrolls across the bottom row, and the current
selection appears in the top row. Use the
and buttons to select either
YES or NO, and then press .
If you select YES, then the percent symbol (
%) will appear aer the last digit of
the humidity value on the main display.
5.3 - Calibration
Your TEX-DEW200 is factory calibrated for 0–100°C (32–212°F). In many cases you
will not need to calibrate again.
A _ _ _ CALIBRATE scrolls across the bottom row, and SKIP appears in the top
row. Press
channel to calibrate: RH (relative humidity), RM TMP (room temperature), or
WT TMP (wet bulb temperature). Press to continue.
¨ If you selected RM TMP or WT TMP, complete steps 5.3B–F now.
¨ If you selected RH, complete steps 5.3G–H now.
¨ If you selected SKIP, skip to 5.4 now.
Temperature calibration
B _ _ _ APPLY LOW INPUT AND WAIT FOR STABLE READING scrolls across the
bottom row, and the current input signal appears in the top row. Apply the low
input signal and wait for the reading to stabilise. Then press
If averaging has been applied to the selected channel (see 5.4), it may take 20–30 seconds or
longer for the reading to stabilise.
now to skip to 5.4, or use the and buttons to select a
A _ _ _ AVERAGING SETUP scrolls across the bottom row, and SKIP appears in
the top row. Press to skip to 5.5, or use the and buttons to select a
channel to congure: RH (relative humidity), RM TMP (room temperature), or
WT TMP (wet bulb temperature). Press to continue.
B _ _ _ AVE SAMPLES scrolls across the bottom row, and the current selection
appears in the top row. Using the
and buttons, alter the number of input
samples that the controller will average for the selected channel. Then press .
Increasing the number of samples will stabilise measurement, but it will also slow down response rates. A typical value is 4.
C _ _ _ AVE WINDOW scrolls across the bottom row, and the currently selected
averaging window value appears in the top row. Using the and buttons,
alter the signal averaging window for the selected channel. Then press .
If your input signal contains large noise spikes, you can increase the size of the averaging window to ensure that these are still averaged. However, increasing the window size too far will
reduce the ability of the controller to respond quickly to real changes in input signal. Setting
AVE WINDOW to 0 will give continuous averaging as per the selected averaging samples. A
typical value is 10% of your system capacity.
D _ _ _ AVERAGING SETUP scrolls across the bottom row, and SKIP appears in
the top row. You are now back at 5.4A. Press now to skip to 5.5, or repeat
5.4A–D to congure averaging for a dierent channel.
N.B. All new units are calibrated before shipping. Recalibration is only necessary if settings
are wiped or the unit's accuracy requires verication aer a long period of use. e.g. 1 year.
A _ _ _ ANALOGUE O/P SETUP scrolls across the bottom row, and SKIP appears
in the top row. Press to skip to 5.6, or use the and buttons to select an
analog output channel to congure: either RH (relative humidity), or RM TMP
(room temperature). Press to continue.
B _ _ _ LOW SCALE VALUE FOR ANALOGUE O/P scrolls across the bottom row,
and the currently selected low scale display value appears in the top row. Use
and buttons to enter your cal low position, and then press .
the
C _ _ _ HIGH SCALE VALUE FOR ANALOGUE O/P scrolls across the display and
toggles with a calibration number shown in internal units (around 30000). Press
the
then press .
D _ _ _ CALIBRATE ANALOGUE O/P? scrolls across the bottom row, and SKIP ap-
pears in the top row. Use the
then press . You should not need to calibrate your output (see top)
or buttons, until the multimeter displays your target high output,
and buttons to select SKIP or ENTER, and
¨ If you selected SKIP, skip to 5.5G now.
¨ If you selected ENTER, connect a mA meter across the analog output
connector (see 3.3), and then continue to 5.5E.
E _ _ _ CAL LOW ANALOGUE O/P scrolls across the display and toggles with a
calibration number shown in internal units (around -16000). Press the
or
buttons until the multimeter displays your target low output (e.g. 4mA), then
press .
F _ _ _ CAL HIGH ANALOGUE OUTPUT scrolls across the display and toggles with
a calibration number shown in internal units (around 30000). Press the
or
buttons, until the multimeter displays your target high output, then press .
G _ _ _ ANALOGUE O/P SETUP scrolls across the bottom row, and SKIP appears
A _ _ _ SERIAL SETUP scrolls across the bottom row, and SKIP appears in the top
row. If your controller does not have a serial port installed, (or you do not wish
to congure your serial options now), please press to skip to 5.7.
Otherwise, press the
button and then to ENTER serial setup.
B _ _ _ SERIAL MODE scrolls across the bottom row, and the current serial mode
appears in the top row. Use the
and buttons to choose between: ASCII
(custom), MODBUS (RTU), or RNGR A (Ranger A). Then press .
ASCII is a simple custom protocol that allows connection to various PC conguration tools.
MODBUS is an industry standard RTU slave mode that allows connection to a wide range of
devices, such as PC’s or PLC’s.
RNGR A is a continuous output, used to drive remote displays and other instruments in the
Rinstrum™ range. (Ranger is a trade name belonging to Rinstrum Pty Ltd.)
See Appendix A for more information about the available serial modes.
C _ _ _ BAUD RATE scrolls across the bottom row, and the current selection ap-
pears in the top row. Use the and buttons to select one of: 300, 600, 1200, 2400, 4800, 9600, 19200 or 38400. Then press
.
D _ _ _ PARITY scrolls across the bottom row, and the currently selected parity
appears in the top row. Using the
and buttons, select: NONE, ODD or
EVEN, and then press .
E _ _ _ SERIAL ADDRESS scrolls across the bottom row, and the currently selected
serial address appears in the top row. Use the
and buttons to alter the
serial address, and then press .
The serial address parameter is used to identify a particular device when it is used with other
devices in a system. (It applies particularly to MODBUS mode when used on an RS485 serial
network.) The serial address of the controller must be set to match the serial address dened
in the master device.
Refer to Appendix A for more information on serial modes and registers.
A Enter setpoint setup mode by pressing and holding the button for 3 seconds.
_ _ _ ENTER SP PIN NUMBER scrolls across the bottom row, and 0 appears in
the top row. Use the
default 1). Then press . If the correct PIN is entered, setup is started at 6.3.
If an incorrect PIN number is entered, _ _ _ _ INCORRECT PIN NUMBER – ACCESS DENIED scrolls across the display and it returns to normal operating
mode.
You will have the opportunity to change your PIN number at the end of this section
(6.3). If you have forgotten your PIN number, see Section 8.
and buttons to enter your security code (factory
6.2 - Setpoint setup
The soware in your controller will allow you to congure up to 4 setpoints,
however full functionality is only supported when relay output hardware installed.
(Setpoints with no corresponding relay output hardware may be used as simple LED
indicators, if desired. In this case, features requiring relay output functionality will
continue to appear in the setup menu, but will be ignored by the controller.)
A _ _ _ EDIT SETPOINT scrolls across the bottom row, and SKIP appears in the
top row. Press
setpoint to edit, and then press .
B _ _ _ SP VALUE scrolls across the bottom row, and the current value for the
selected setpoint appears in the top row. Using the
the display value at which the selected setpoint will activate, and then press .
The units for the SP VALUE will always correspond with your chosen SP SOURCE.
I.e. If you select 50.0% as your SP VALUE in this step, and then you choose RM TEMP as your SP SOURCE in 6.2C, your SP VALUE will be automatically changed to 50.0°C/F.
now to skip to 6.3, or use the and buttons to select a
and buttons, adjust
17
Energised Above
Energised Above
C _ _ _ SP SOURCE scrolls across the bottom row, and the current selection ap-
pears in the top row. Use the and buttons to select RH (relative humidity)
or RM TMP (room temperature), and then press .
D _ _ _ SP ACTIVATION scrolls across the bottom row, and the activation for the
selected setpoint appears in the top row. Using the
and buttons, set the
relay activation to operate ABOVE or BELOW the setpoint value, and press .
ABOVE: Relay turns on above the setpoint value and o below it. BELOW: Relay turns on be-
low the setpoint value and o above it.
E _ _ _ SP TYPE scrolls across the bottom row, and the current type for the se-
lected setpoint appears in the top row. Using the and buttons, select
either ALARM or CNTRL (control), and then press .
ALARM - SP VALUE controls setpoint activation point. HYSTERESIS VALUE controls set-
point deactivation point.
CNTRL - SP VALUE controls setpoint deactivation point. HYSTERESIS VALUE controls set-
point reactivation point.
Hysteresis
band
Hysteresis
band
Energised Below
Hysteresis
band
Hysteresis
band
Energised Below
F _ _ _ HYSTERESIS VALUE scrolls across the bottom row, and the hysteresis value
for the selected setpoint appears in the top row. Use the and buttons to
adjust this value if required, and then press .
The HYSTERESIS VALUE denes the separation band between setpoint activation and deacti-
vation, and will operate as per the SP TYPE setting selected in 6.2E.
G _ _ _ MAKE DELAY scrolls across the bottom row, and the make delay time for
the selected setpoint appears in the top row. This is the time delay between
setpoint activation, and when the relay turns on. Adjust this value in 0.1 second
increments using the and buttons, and then press .
H _ _ _ OPEN ACCESS TO SP VALUE scrolls across the bottom row, and the open
access permission setting for the selected setpoint appears in the top row. Use
and to select either OFF or ON, and then press .
the
When enabled, this option allows the selected setpoint's value to be edited directly aer pressing the button, without needing to enter a PIN number or go through all of the other options. Each setpoint can individually have this option enabled or disabled. See Section 7.
Start - Use 'S' for the start character of a command string (not case sensitive). This
must be the rst character in the string.
Controller Address - Use an ASCII number from '1' to '255' for the controller address.
If the character following the start character is not an ASCII number, then address '0' is assumed. All controllers respond to address '0'.
Read/Write Command - Use ASCII 'R' for read, 'U' for unformatted read, or 'W' for
write (not case sensitive). Any other character aborts the operation.
In Custom ASCII mode, data is normally read as formatted data (which includes decimals and
any text characters that may be selected to show units). However it is also possible to read unformatted data by using a 'U' in the read command. There is no unformatted write command,
as when writing to xed point registers, any decimal point and text characters are ignored.
Register Address - The register address for the read/write operation will be an ASCII
number from '1' to '65535'. This character must be specied for a write com-
mand, but may be omitted for a read command, (in which case the controller
will respond with the data value currently on the display).
Separator Character - The separator character can be either a space or a comma,
and is used to separate the register address from the data value.
Data Value - Must be an ASCII number. The absolute limits for this number are
–
1000000 to +1000000, but note that not all registers will accept this range.
Message Terminator - This is the last character, and must be either a '$' (dollar) or an
'*' (asterisk). Neither of these characters should be used elsewhere in the message string. If '$' is used, a 50ms minimum delay is inserted before a reply is sent.
If '*' is used, a 2ms minimum delay is inserted before a reply is sent.