specied length of time (see 8.2G), which can be adjusted to suit the requirements
of externally connected devices.
When a setpoint is activated in volumetric pulse mode, the totalizer will reset using
the calculation: Total = Total – Setpoint Value, and then resume totalizing.
3
FRONT PANEL & DISPLAY
3.1 - Front panel
SPX
The SP LED's are used to
indicate active setpoints.
SP1 is used to indicate the
BCH SP. SP6 is perma-
nently disabled.
Used to access the Input
Setup & Calibration menu
(Section 7).
Used to save your settings and advance to the next step. It can also be cong-
ured to perform a user-selected custom function aer a long press (> 2secs)
from the main display (see 7.6B).
Typically used to scroll through options or increase values in the setup menu.
Pressing this button from the main display will show the current values for
Rate, Batch and Peak (see 3.3).
48mm
(1.89")
96mm (3.78")
Typically used to scroll through options or decrease values in the setup menu.
Pressing this button from the main display will show the current values for
Total, Batch Count, Inight Correction and Valley (see 3.3).
Used to access the Setpoint Setup menu (Section 8) and the Setpoint Direct
To adjust the display brightness, press the and buttons together from the
main display. BRI appears and toggles with the current setting. Use the and
buttons to adjust the LED backlight, and then press to return to the normal
operating mode.
3.3 - Up and down button shortcuts
Pressing the and buttons from the main operational display allows instant
access to a number of values held in the controller's memory. These variables will ap-
pear in the order shown in the table below, and will cycle continuously at each press
of the or button.
Press
at any time to return to normal operating mode. The PEAK, VALLEY, TO-
TAL and BT CNT values may be reset to zero by pressing the and buttons at
the same time while the variable is being displayed.
Up and down button shortcuts
RATEThe current ow rate input
BATCHThe batch value
PEAKThe maximum measured ow rate input since the instrument was turned on
or reset
TOTALThe totalizer value
BT CNTThe number of batches that have been processed (batch count)
INFLITInight correction oset: This value is calculated by the controller based on
the batch error (the dierence between the batch setpoint value and the
nal batch value) averaged over the last three batches, and the Inight Adjustment Delay time (selected in 8.2W)
VALLEYThe minimum measured ow rate input since the instrument was turned on
BEFORE YOU BEGIN WIRING, ensure that the unit is switched o and the power
supply is disconnected.
WIRING
4.1 - Pinouts
ABC
Key
4.1A Relay Output (See 4.3)
4.1B Serial Port (See 4.5)
4.1C Analog Output (See 4.4)
4.1D Analog Input (See 4.2)
4.1E Function Pins (See 4.6)
D
E
F
4.1F Power Supply (See 4.7)
4.2 - Wire the Analog Input ModuleSee 4.1D
IMPORTANT: The input module for this unit has four headers which are factory
congured to suit your application. The unit is congured for an NPN type sensor
by default.
¨ If you are using an NPN type sensor, you don't need to change anything.
¨ If you are using PNP, TTL, Namur, Tacho, or a Pushbutton switch, please
review your header configuration before continuing, referring to Section 6.
Then wire your input as required, referring to the diagrams on the following page.
A If the meter is already installed, remove it from the panel, and unplug all plugs
from the back of the unit.
B Using a small screwdriver or similar implement,
press downward into one of the slots at the
rear of the case. This will disengage one of
the tabs which holds the back plate on, al-
lowing it to be gently levered away at
one corner.
C Holding the loosened corner open
with one hand, disengage the le-
ver on the opposite slot (Fig 1).
D You should now be able to remove the back plate. If it does not unclip easily,
you may need to disengage the two remaining tabs by repeating steps 6.2B–C
on the other side of the meter.
FIG 1
E Slide the analog input module out
of the meter case (Fig 2). (See 4.1D
to identify the input module.)
F Position the headers on the input
module as required for your sensor
type, referring to 6.1.
G Slide the input module back into
the meter case.
Make sure that it is sitting in the tracks on the le and right. Press rmly until the input module
is fully inserted and sits ush with the other boards that are visible from the back of the meter.
H Replace the back plate.
Begin by inserting the two lower tabs into the slots, and then position the upper tabs so that
they will not catch on the top lip of the meter case. Apply rm pressure until the back plate
clicks into place.
I Reconnect the plugs and return the meter to the panel installation.
D _ _ _ K FACTOR RANGE scrolls across the bottom row and the current selection
appears in the top row. Use the
and buttons to select from: 99.9999,
999.999 or 9999.99, and then press .
E _ _ _ K FACTOR scrolls across the bottom row and the current value appears in
the top row. Use the
and buttons to enter the K factor from your ow
transducer manufacturer’s specications. Then press .
¨ Please skip to 7.2H now.
Pulses Calibration
F _ _ _ PULSES PER UNIT OF MEASUREMENT scrolls across the bottom row and
the current number of pulses appears in the top row. Adjust this value using the
and buttons, and then press .
For example, if a ow sensor outputs 50 pulses/unit of ow, set this value to 50. (Where 'unit
of ow' is your selected engineering unit i.e. Liters, Gallons etc.)
G _ _ _ ENTER DISPLAY VALUE FOR X PULSES (where 'X' is the number of pulses
selected above) scrolls across the bottom row. The current display value appears
in the top row. Adjust this value using the and buttons, and press .
¨ Please continue to 7.2H now.
If you selected 50 pulses above, and 50 pulses = 1 unit of ow, then enter 1 here. ('Unit of
ow' is your selected engineering unit i.e. Liters, Gallons etc.) The controller will automatically
calculate the correct scale factor for you.
H _ _ _ TIME PERIOD FOR RATE DISPLAY scrolls across the bottom row and the cur-
rent selection appears in the top row. Use the and buttons to select: SECS,
MINS or HOURS, and then press .
E.g. If the measurement units are liters, then rate can be viewed in L/sec, L/min or L/hr.
I _ _ _ RATE MULTIPLIER scrolls across the bottom row and the current multipli-
cation factor appears in the top row. This option adds a scale factor, to display
the rate in the required units. Use the and buttons to select: X0.0001,
X0.001, X0.01, X0.1, X1, X10, X100 or X1000. Then press .
J _ _ _ ROUNDING scrolls across the bottom row and the current display round-
ing appears in the top row. Using the
and buttons, select: NONE, 2, 5 or
10, and then press .
Rounding is quoted in display counts and is not inuenced by decimal point position. For
example, if your input signal is 5.3, the display will show: 5.3 (for rounding=NONE), 5.4 (for
rounding=2), 5.5 (for rounding=5) or 5.0 (for rounding=10).
K _ _ _ DISPLAY ZERO TIME scrolls across the bottom row and the current selec-
tion appears in the top row. This value controls how quickly the rate display
changes to zero. Use the and buttons to select either: 0.5SEC (for inputs
with >2 pulses/sec) or 100SEC (for slow inputs). Then press .
L _ _ _ AVE SAMPLES scrolls across the bottom row, and the currently selected av-
eraging appears in the top row. Using the
and buttons, alter the number
of input samples that the controller will average, and then press .
Your controller has input signal averaging, optimizing stable measurement.
If the change in input exceeds the averaging window value it will not average,
ensuring fast response when there are
large dierences between readings.
Increasing the number of AVE SAMPLES
will stabilise measurement, but it will
also slow down response rates.
Input exceeds
averaging window
Number
of samples
Averaging window
in displayed counts
M _ _ _ AVE WINDOW scrolls across the bottom row, and the currently selected
averaging window value appears in the top row. Using the and buttons,
alter the signal averaging window. Then press .
If your input signal contains large noise spikes, you can increase the size of the averaging window to ensure that these are still averaged. However, increasing the window size too far will
reduce the ability of the controller to respond quickly to real changes in input signal. Setting
AVE WINDOW to 0 will give continuous averaging as per the selected averaging samples.
A _ _ _ TOTALIZER SETUP scrolls across the bottom row and SKIP appears in the
top row. Press to skip to 7.4, or the button and then to ENTER.
B _ _ _ DECIMAL POINT POSITION scrolls across the bottom row and the current
selection appears in the top row. Use the
0.1, 0.12, 0.123, 0.1234 or 0.12345, and then press .
C _ _ _ RESOLUTION scrolls across the bottom row and the currently selected
totalizer resolution appears in the top row. Use the
X1, 10^3 (103), or 10^6 (106), and then press .
D _ _ _ RESET AT POWER UP scrolls across the bottom row and the current setting
appears in the top row. Use the
ous totalizer value at power up), ZERO (reset totalizer to zero at power up), or
LD VAL (reset totalizer to custom load value (see 7.3E) at power up). Press .
E _ _ _ LOAD VALUE scrolls across the bottom row and the current totalizer load
value appears in the top row. Use the
required, and then press .
This value will be loaded into the totalizer at power up, if LD VAL is selected in 7.3D above.
It will also be loaded into the totalizer if either TOT=LV or T&B=LV is executed via a user programmable input function (see 7.6).
and buttons to select: NO (retain previ-
and buttons to select NO DP,
and buttons to select:
and buttons to adjust this value if
7.4 - Batching Setup
A _ _ _ BATCHING SETUP scrolls across the bottom row and SKIP appears in the
top row. Press to skip to 7.5, or the button and then to ENTER.
B _ _ _ RESET AT POWER UP scrolls across the bottom row and the current set-
ting appears in the top row. Use the
previous batch value at power up), ZERO (reset batch value to zero at power
up), or LD VAL (reset batch to custom load value (see 7.4C) at power up). Then
C _ _ _ LOAD VALUE scrolls across the bottom row and the currently selected
batch load value appears in the top row. Use the and buttons to adjust
this value if required, and then press .
This value will be loaded into the batch register at power up, if LD VAL is selected in 7.4B
above. It will also be loaded into the batch register if either BCH=LV or T&B=LV is executed via
a user programmable input function (see 7.6).
7.5 - Display Setup
A _ _ _ DISPLAY SETUP scrolls across the bottom row and SKIP appears in the
top row. Press to skip to 7.6, or the button and then to ENTER setup.
B _ _ _ LINE 1 DISPLAY SOURCE scrolls across the bottom row and the currently
selected line 1 (top row) display source appears in the top row. Use the
buttons to select: NONE, RATE, TOTAL, BATCH, BCHCNT, or BCH SP, and
then press .
C _ _ _ LINE 2 DISPLAY SOURCE scrolls across the bottom row and the currently
selected line 2 (bottom row) display source appears in the top row. Use the
and buttons to select: NONE, RATE, TOTAL, BATCH, BCHCNT, or BCH SP,
and then press .
and
7.6 - User Programmable Input Functions
This section allows you to assign a custom function to the front panel button, or
the rear user input pins (see 4.6). The following functions are available:
NONENo action
TOT=0Reset totalizer to zero
TOT=LVReset totalizer to totalizer load value (dened in 7.3E)
BCH=0Reset batch value to zero
BCH=LVReset batch value to batch load value (dened in 7.4C)
T&B=0Reset totalizer & batch to zero
T&B=LVReset totalizer & batch to load values (dened in 7.3E & 7.4C)
HALT BHalt the batch in progress (not available on User Input 2)
HOLDHold all counts (available on User Input 2 only)
In this mode, activating User Input 2 will stop the batch process (turn the
batching relay o), and will hold the current total and batch values until
the pin is deactivated. Any pulses on the input will be ignored while the
User Input 2 pin is activated. Deactivating User Input 2 will restart the
batching process (turn the batching relay on again), and the total and
batch values will continue counting from the previously held values.
CONT BContinue with the current batch (not available on User Input 2)
HOLD BHold the batch count (available on User Input 2 only)
In this mode, activating User Input 2 will stop the batch process (turn the
batching relay o), and will hold the current batch value until the pin is deactivated. While User Input 2 is activated, the total value will continue to
count input pulses, but the batch value will be held. Deactivating User Input 2 will restart the batching process (turn the batching relay on again),
and the batch value will continue counting from its previously held value.
UNLTCHUnlatch all setpoints (see 2.1 and 8.2I for information on latched setpoints)
UNLT BUnlatch BCH SP (see 2.1 and 8.2I for information on latched setpoints)
UNLT 2/3/4/5 Unlatch SP 2/3/4/5 (see 2.1 and 8.2I for information on latched setpoints)
A _ _ _ USER PROGRAMMABLE INPUT FUNCTIONS scrolls across the bottom
row and SKIP appears in the top row. Press to skip to 7.7, or the button
and then to ENTER input functions setup.
B _ _ _ PROGRAM BUTTON scrolls across the bottom row and the current func-
tion appears in the top row. This species the operation to be executed when
the
button is pressed (for more than 2 seconds) from the main display. Re-
ferring to the table above, use the and buttons to select a function, and
then press .
C _ _ _ USER INPUT 1 scrolls across the bottom row and the current function
appears in the top row. This species the operation to be executed when the
User 1 pin is activated from the rear of the unit (see 4.6). Referring to the table
above, use the
and buttons to select a function, and then press .
D _ _ _ USER INPUT 2 scrolls across the bottom row and the current function
appears in the top row. This species the operation to be executed when the
User 2 pin is activated from the rear of the unit (see 4.6). Referring to the table
and buttons to select a function, and then press .
21
Note that User Input 2 has unique additional options, including HOLD (Hold all counts) and
HOLD B (Hold batch count). See the table above for more information.
E _ _ _ USER INPUT 3 scrolls across the bottom row and the current function
appears in the top row. This species the operation to be executed when the
User 3 pin is activated from the rear of the unit (see 4.6). Referring to the table
above, use the and buttons to select a function, and then press .
7.7 - Analog Output Setup
N.B. All new units are calibrated before shipping. Recalibration is only necessary if settings
are wiped or the unit's accuracy requires verication aer a long period of use. e.g. 1 year.
A _ _ _ ANALOG OUTPUT SETUP scrolls across the bottom row and SKIP appears
in the top row. If your controller does not have analog output installed, (or you
do not wish to congure your analog output now), press to skip to 7.8.
Otherwise, press the
button and then to ENTER analog output setup.
B _ _ _ DATA SOURCE FOR ANALOG OUTPUT scrolls across the bottom row and
the current analog output data source appears in the top row. Use the
and
buttons to select an option from: NONE, RATE, TOTAL, BATCH or BCHCNT,
and then press .
C _ _ _ LOW SCALE VALUE FOR ANALOG OUTPUT scrolls across the bottom row
and the currently selected low scale value appears in the top row. Use the
and buttons to enter your cal low position, and then press .
This sets the display value for CAL LOW (as in 7.7F, below).
D _ _ _ HIGH SCALE VALUE FOR ANALOG OUTPUT scrolls across the bottom row
and the currently selected high scale value appears in the top row. Use the
and buttons to enter your cal high position, and then press .
This sets the display value for CAL HIGH (as in 7.7G, below).
E _ _ _ CALIBRATE ANALOG OUTPUT? scrolls across the bottom row and SKIP
appears in the top row. If you do not wish to calibrate your analog output then
press now to skip to 7.8.
Factory analog output calibration is precisely set before shipping this instrument, and should not be adjusted unless advised by the manufacturer.
F _ _ _ SERIAL ADDRESS scrolls across the bottom row and the currently selected
serial address appears in the top row. Use the and buttons to alter the
serial address, and then press .
The serial address parameter is used to identify a particular device when it is used with other
devices in a system. (It applies particularly to MODBUS mode when used on an RS485 serial
network.) The serial address of the controller must be set to match the serial address dened
in the master device.
Refer to Appendix A for more information on serial modes and registers.
7.9 - Edit F1 PIN Number
A _ _ _ EDIT F1 PIN NUMBER scrolls across the bottom row and SKIP appears in
the top row. Press to skip and return to the operational display, or the
button and then to ENTER and change your PIN number.
B _ _ _ ENTER NEW F1 PIN NUMBER scrolls across the bottom row and the cur-
rent PIN (default 1) appears in the top row. Using the
your new F1 PIN number. Then press to exit to the operational display.
and buttons, enter
8
The soware in your controller will allow you to congure 1 batch setpoint (SP 1/
BCH SP) and up to 4 standard setpoints (SP 2–5). SP 6 is permanently deactivated.
For the rst 5 setpoints, full functionality is only supported when relay output
hardware installed.
(Setpoints with no corresponding relay output hardware may be used as simple LED
indicators, if desired. In this case, features requiring relay output functionality will
continue to appear in the setup menu, but will be ignored by the controller.)
SETPOINT SETUP
8.1 - Enter F2 PIN Number
A Enter setpoint setup mode by pressing and holding the button for 3 seconds.
_ _ _ ENTER F2 PIN NUMBER scrolls across the bottom row and 0 appears in the
top row. Use the
1). Then press . If the correct PIN is entered, setup is started at 8.2.
and buttons to enter your security code (factory default
If an incorrect PIN number is entered, _ _ _ INCORRECT PIN NUMBER – ACCESS DENIED scrolls across the display and it returns to normal operating mode.
You will have the opportunity to change your PIN number at the end of this section
(8.3). If you have forgotten your PIN number, see Section 10.
8.2 - Setpoint Setup
A _ _ _ EDIT SETPOINT scrolls across the bottom row and SKIP appears in the
top row. Press now to skip to 8.3, or use the and buttons to select a
setpoint to edit: BCH SP (batch setpoint/SP 1), SP 2, SP 3, SP 4, or SP 5. Then
press .
B _ _ _ SP VALUE scrolls across the bottom row, and the current value for the
selected setpoint appears in the top row. Using the
the display value at which the selected setpoint will activate, and then press .
C The step that you proceed to now will depend on which setpoint you are editing
(selected in 8.2A):
and buttons, adjust
¨ If you are currently editing BCH SP, skip to 8.2E now.¨ If you are currently editing SP 2-5, continue to 8.2D now.
D _ _ _ TRACK BATCH SP scrolls across the bottom row, and the tracking setting
for the selected setpoint appears in the top row. Using the
select OFF or ON, and then press .
¨ If you selected OFF, continue to 8.2E now.¨ If you selected ON, the step that you proceed to now will depend on the
Setpoint Source (8.2E) previously configured for your Batch Setpoint:
` BCH SP source = TOTAL: Skip to 8.2F now.` BCH SP source = RATE, BATCH, or BCHCNT: Skip to 8.2H now.
A setpoint with TRACK BATCH SP enabled will track the setpoint value of BCH SP, with the
setpoint value of the tracking setpoint becoming an oset value.
E _ _ _ SETPOINT SOURCE scrolls across the bottom row and the activation source
for the selected setpoint appears in the top row. Use the and buttons to
choose RATE, TOTAL, BATCH, or BCHCNT and then press .
¨ If you selected RATE, BATCH, or BCHCNT, skip to 8.2H now.¨ If you selected TOTAL, continue to 8.2F now.
F _ _ _ VOLUMETRIC PULSE scrolls across the bottom row and the current selec-
tion appears in the top row. Use the
and buttons to select OFF or ON,
and then press .
¨ If you selected OFF, skip to 8.2H now.¨ If you selected ON, continue to 8.2G now.
This function outputs a pulse on the relay when Total ≥ Setpoint Value. This will activate the
selected relay for a specied length of time (see 8.2G), which can be adjusted in 0.1 second
increments to suit the requirements of externally connected devices. This function is useful for
feeding volume information to other equipment.
When the selected setpoint is activated in volumetric pulse mode, the totalizer will reset using
the calculation: Total = Total – Setpoint Value, and then resume totalizing.
G _ _ _ PULSE TIME scrolls across the bottom row and current selection appears
in the top row. Pulse reset requires a minimum of 0.1 seconds. Use the and
buttons to select your pulse time (up to 10.0 seconds), and then press .
¨ All remaining setpoint parameters will be configured automatically by the
controller. Please skip to 8.2X now.
A combination of high input rates and low setpoint values may exceed this limitation, resulting in missed output pulses.
H _ _ _ SP ACTIVATION scrolls across the bottom row, and the current activation
for the selected setpoint appears in the top row. Using the and buttons,
select the relay activation to operate ABOVE or BELOW the setpoint value, and
then press .
ABOVE: Relay turns on above the setpoint value and o below it. BELOW: Relay turns on
below the setpoint value and o above it.
I _ _ _ SETPOINT TYPE scrolls across the bottom row, and the setpoint type for
the selected setpoint appears in the top row. Using the and buttons,
select: NORMAL, TIMED or LATCHD (latched), and then press .
¨ If you selected TIMED or LATCHD, skip to 8.2L now.¨ If you selected NORMAL, continue to 8.2J now.
NORMAL: A normal setpoint will activate and deactivate using alarm or control logic regu-
lated within a hysteresis band (8.2J–K). TIMED: A timed setpoint will activate as normal, and
remain active for a user dened time period (8.2O), aer which it will deactivate automatically. LATCHD: A latched setpoint will activate as normal, and remain active until it is unlatched
either by setpoint logic (8.2Q), or manually using a user programmable shortcut (7.6).
J _ _ _ HYSTERESIS TYPE scrolls across the bottom row, and the hysteresis type
for the selected setpoint appears in the top row. Using the and buttons,
select either ALARM or CNTRL (control), and then press .
ALARM - SETPOINT VALUE controls setpoint activation point. HYSTERESIS VALUE
controls setpoint deactivation point.
CNTRL - SETPOINT VALUE controls setpoint
deactivation point. HYSTERESIS VALUE con-
trols setpoint reactivation point.
Hysteresis
band
Hysteresis
band
Energised Below
Hysteresis
band
Hysteresis
band
Energised Below
K _ _ _ HYSTERESIS VALUE scrolls across the bottom row, and the hysteresis value
for the selected setpoint appears in the top row. Use the
and buttons to
adjust this value if required, and then press .
The HYSTERESIS VALUE denes the separation band between setpoint activation and deac-
tivation, and will operate as per the HYSTERESIS TYPE setting selected in 8.2J.
L _ _ _ MAKE DELAY scrolls across the bottom row, and the current make delay
time for the selected setpoint appears in the top row. This is the time delay be-
tween setpoint activation, and when the relay turns on. Adjust this value in 0.1
second increments using the and buttons, and then press .
M The step that you proceed to now will depend on the Setpoint Type that you
selected in 8.2I:
¨ If your Setpoint Type = NORMAL, proceed to 8.2N now.¨ If your Setpoint Type = TIMED, skip to 8.2O now.¨ If your Setpoint Type = LATCHD, skip to 8.2P now.
N _ _ _ BREAK DELAY scrolls across the bottom row, and the current break delay
value for the selected setpoint appears in the top row. This is the time delay
between setpoint de-activation, and when the relay turns o. Adjust this value
in 0.1 second increments using the and buttons, and then press .
¨ Please skip to 8.2P now.
O _ _ _ ON TIME scrolls across the bottom row, and the current selection appears
in the top row. This denes the time that a Timed relay (see 8.2I) remains ener-
gized. Adjust this value in 0.1 second increments using the
and buttons,
and then press .
P _ _ _ STARTUP INHIBIT scrolls across the bottom row, and the current selection
appears in the top row. Use the
and then press
This option can be used with setpoints which may
be active initially at power up.
Setting STARTUP INHIBIT to YES will cause a relay to remain o (de-energized) at power up until
it has rst reached its inactive state. It will then
function normally.
.
and buttons to select either NO or YES,
Startup
inhibit
(Energised below)
Q _ _ _ RESET ACTION scrolls across the bottom row, and the current selection
appears in the top row. This parameter species the action to be executed when
the Reset Edge (8.2S) occurs. Use the and buttons to select: NONE, RS TOT (reset total), RS BAT (reset batch), RS BCT (reset batch count) or UNLTCH
(unlatch all setpoints). Then press to accept.
¨ If you selected NONE, then the step that you proceed to now will depend
on which setpoint you are editing (your selection in 8.2A):
` BCH SP = Skip to 8.2S now.` SP2–5 = Skip to 8.2X now.
¨ If you selected RS TOT or RS BCT, continue to 8.2R now.¨ If you selected RS BAT or UNLTCH, skip to 8.2S now.
R _ _ _ RESET VALUE scrolls across the bottom row, and the current reset value
appears in the top row. Use the
and buttons to adjust the value which
will be loaded into the destination register selected in 8.2Q (Reset Action) when
the selected Reset Edge (8.2S) occurs. Then press to accept.
S _ _ _ RESET EDGE scrolls across the bottom row, and the current selection ap-
pears in the top row. The denes the reset edge which must occur in order to
trigger the Reset Action selected in 8.2Q. Use the and buttons to select:
NONE, MAKE (make edge, relay energizes), BREAK (break edge, relay de-ener-
gizes) or BOTH (make and break edges). Then press to accept and continue.
T The step that you proceed to now will depend on which setpoint you are editing
(selected in 8.2A):
¨ If you are currently editing BCH SP, continue to 8.2U now.¨ If you are currently editing SP 2–5, skip to 8.2X now.
U _ _ _ BATCH COUNT MODIFIER scrolls across the bottom row and the current
value appears in the top row. Use the
and buttons to adjust this value if
desired, and then press .
A positive number will cause the batch count register to be incremented by that amount each
time the selected reset edge is triggered. Likewise, a negative number will cause the batch
count register to be decremented. Setting this value to zero will disable this feature.
V _ _ _ INFLIGHT CORRECTION scrolls across the bottom row and the current
option appears in the top row. This function is used to correct for overrun errors
caused by pipes/valves etc. Use the and buttons to turn this feature ON
or OFF, and then press .
¨ If you selected ON, continue to 8.2W now.¨ If you selected OFF, skip to 8.2X now.
When INFLIGHT CORRECTION is turned ON, the batch error (the dierence between the
batch setpoint value and the nal batch value) is averaged over the last 3 batches. When a
batch has nished, the controller waits for the INFLIGHT ADJUSTMENT DELAY time (see
8.2W), and then calculates a new inight correction oset for the next batch.
During the next batch, the eective BCH SP value is modied to include the calculated Correction Oset value, in an attempt to compensate for errors. (Correction Oset cannot be
greater than 50% of the setpoint value).
W _ _ _ INFLIGHT ADJUSTMENT DELAY IN SECONDS? scrolls across the bot-
tom row, and the current value appears in the top row. This function is used to
specify the time delay (in seconds) between the batching relay turning o, and
the inight correction calculation being made (see 8.2V). Use the and to
X _ _ _ USER ACCESS? scrolls across the bottom row, and the direct access permis-
sion setting for the selected setpoint appears in the top row. Use the and
to select either OFF or ON, and then press .
When enabled, this option allows the selected setpoint's value to be edited directly aer
pressing the button, without needing to enter a PIN number or go through all of the other
options. Each setpoint can individually have this option enabled or disabled. See Section 9.
Y _ _ _ EDIT SETPOINT scrolls across the bottom row and SKIP appears in the top
row. You are now back at 8.2A. To edit another setpoint, follow the instructions
from 8.2A–Y again. If you do not wish to edit another setpoint, press now
to skip to 8.3.
8.3 - Edit F2 PIN Number
A _ _ _ EDIT F2 PIN NUMBER scrolls across the bottom row and SKIP appears in
the top row. Press to skip and return to the operational display, or the
button and then to ENTER and change your PIN number.
B _ _ _ ENTER NEW F2 PIN scrolls across the bottom row, and the current PIN
(default 1) appears in the top row. Using the
new F2 PIN number. Then press to exit to the operational display.
Start - Use 'S' for the start character of a command string (not case sensitive). This
must be the rst character in the string.
Controller Address - Use an ASCII number from '1' to '255' for the controller address.
If the character following the start character is not an ASCII number, then address '0' is assumed. All controllers respond to address '0'.
Read/Write Command - Use ASCII 'R' for read, 'U' for unformatted read, or 'W' for
write (not case sensitive). Any other character aborts the operation.
In Custom ASCII mode, data is normally read as formatted data (which includes decimals and
any text characters that may be selected to show units). However it is also possible to read unformatted data by using a 'U' in the read command. There is no unformatted write command,
as when writing to xed point registers, any decimal point and text characters are ignored.
Register Address - The register address for the read/write operation will be an ASCII
number from '1' to '65535'. This character must be specied for a write com-
mand, but may be omitted for a read command, (in which case the controller
will respond with the data value currently on the display).
Separator Character - The separator character can be either a space or a comma,
and is used to separate the register address from the data value.
Data Value - Must be an ASCII number. The absolute limits for this number are
-1000000 to 1000000, but please note that not all registers will accept this range.
Message Terminator - This is the last character, and must be either a '$' (dollar) or
an '*' (asterisk). Neither of these characters should be used elsewhere in the
message string. If '$' is used, a 50ms minimum delay is inserted before a reply is
sent. If '*' is used, a 2ms minimum delay is inserted before a reply is sent.
Custom ASCII Read/Write Examples
ExampleDescription
SR$Read display value from all controllers, 50ms delay.
S15R$Read display value from controller address 15, 50ms delay.
S3U40*Read unformatted data in channel 4 from controller address 3, 2ms delay.
S2W2 -10000$Write -10000 to the display register of controller address 2, 50ms delay.
SWT CHAN_1$Write ASCII text string Chan_1 to channel 1 text register, 50ms delay.
Custom ASCII Registers
8 Bit Unsigned
48207Baud rate
48211Serial address
48215Serial mode
16 Bit Unsigned
65Hysteresis BCH SP (SP 1)
66–69Hysteresis SP 2–5
71Make delay BCH SP (SP 1)
72–75Make delay SP 2–5
4213Break delay BCH SP (SP 1)
4214-4217Break delay SP 2–5
5173Batch count increment
32 Bit Signed (2 x 16 Bit)
9Rate
11Total
13Batch result
15Batch count
81Batch tare
57Peak
59Valley
6Batch setpoint (SP 1)
7Setpoint 2
8Setpoint 3
9Setpoint 4
10Setpoint 5
239Alarm status
24 Bit Signed (2 x 16 Bit)
2509Load value (Total)
2511Load value (Batch)
Controller Response - Aer the controller has completed a read or write instruction,
it responds by sending a carriage return/line feed (CR/LF) back to the host. If