To adjust the display brightness, press the and buttons together from the
main display. BRI appears on the display with the current brightness setting. Use the
and buttons to adjust the LED backlight, and then press to nish.
3
WIRING
3.1 - Pinouts
AB
D
E
C
Key
3.1A Relay Output (See 3.3)
3.1B Serial Port (See 3.5)
3.1C Analog Output (See 3.4)
3.1D Analog Input (See 3.2)
3.1E Function Pins (See 3.6)
3.1F Power Supply HV/LV
F
(See 3.7)
3.2 - Wire the analog input module
See 3.1D
IMPORTANT:
The analog input board for the PRO–CTR has adjustable headers for Sensor Type,
Noise Filtering, and Excitation Voltage. Unless you specied otherwise when you or-
dered your PRO–CTR, the headers will be set to:
›Sensor Type = NPN (for all counters)›Noise Filtering = Off (20kHz)›Excitation Voltage = 24V
If you need to change these settings, please follow the instructions in Section 4
BEFORE proceeding to wiring your sensor(s).
A If the meter is already installed, remove it from the panel, and unplug all plugs
from the back of the unit.
B Using a small screwdriver or similar implement,
press downward into one of the slots at the
rear of the case. This will disengage one of
the tabs which holds the back plate on, al-
lowing it to be gently levered away at
one corner.
C Holding the loosened corner open
with one hand, disengage the le-
ver on the opposite slot (Fig 1).
D You should now be able to remove the back plate. If it does not unclip easily,
you may need to disengage the two remaining tabs by repeating steps 4.2B–C
on the other side of the meter.
Fig 1
E Slide the analog input module out
of the meter case (Fig 2). (See 3.1D
to identify the input module.)
F Position the headers on the input
module as required for your sensor
type, referring to 4.1.
G Slide the input module back into
Fig 2
the meter case.
Make sure that it is sitting in the tracks on the le and right. Press rmly until the input module
is fully inserted and sits ush with the other boards that are visible from the back of the meter.
H Replace the back plate.
Begin by inserting the two lower tabs into the slots, and then position the upper tabs so that
they will not catch on the top lip of the meter case. Apply rm pressure until the back plate
clicks into place.
I Reconnect the plugs and return the meter to the panel installation.
` On a rising edge A signal when B is high` On a falling edge A signal when B is low
6.3 - Quad x4 Example: Sha Encoder
In this mode, the angular/linear resolution of the x1 mode is increased by 4. Depend-
ing on the direction of rotation, the A signal leads or lags the B signal.
Pulse Train Direction
Signal A
Signal B
Pulse Train Direction
Signal A
Signal B
Clockwise
Primary
Counter
With A and B
signals 90°
out-of-phase
Counter-clockwise
Primary
Counter
With A and B
signals 90°
out-of-phase
Primary counter decrements:
` On a rising edge A signal when B is low` On a rising edge B signal when A is high` On a falling edge A signal when B is high` On a falling edge B signal when A is low
Primary counter increments:
` On a rising edge A signal when B is high` On a rising edge B signal when A is low` On a falling edge A signal when B is low` On a falling edge B signal when A is high
6.4 - A+B
In this mode there is no xed relationship between signals A and B.
Primary
Counter
Signal A
Signal B
Primary counter increments:
` On a rising edge A signal` On a rising edge B signal
6.10 - RSOFST - Reset to oset and start A, B mode
In this mode the primary and secondary counters are reset to the values stored in
the meter's reset oset registers, and they continue counting aer being reset.
On a rising edge C signal:
BEGIN
COUNTING
Signal C
Primary
reset
oset
register
RESETRESET
Primary Counter
Reset to primary
reset oset value
BEGIN
COUNTING
Secondary
reset
oset
register
Secondary Counter
Reset to secondary
reset oset value
` Both counters begin counting
On a falling edge C signal:
` Primary counter is reset to the value stored in
primary reset offset register
` Secondary counter is reset to the value stored
in secondary reset offset register
` Both counters continue to count after being
reset
7
FEATURES
7.1 - Batching feature
The PRO–CTR has a Batching function, which is used to maintain the total count,
as well as the current Batch Value. The Batch Value is calculated using the following
formula:
Batch Value = Primary Count – Batch Tare
The Batch Tare value is reset to the Primary Count value via the setpoint reset func-
tion RST BT, which can be executed by setpoint logic (see 9.2M) or manually by
activating an appropriately congured user input pin (see 3.6 & 8.5). (Batch Tare is a
hidden register used only for this calculation.)
The controller also includes a Batch Counter function associated with SP 1. The 'Batch
Count Modier' value (see 9.2P) is added to the Batch Count register each time SP 1 activates, allowing the user to count how many completed batches have been
If you are using a single display (PRO-CTR100), the menu title or text prompt will
scroll across the display, and toggle with the currently selected option. If you are
using a dual display (PRO-CTR200), the menu title or text prompt will scroll across the
bottom row, and the currently selected option will appear in the top row.
INPUT SETUP & CALIBRATION
8.1 - Enter CAL PIN number
A Enter the calibration mode by pressing the button.
_ _ _ ENTER CAL PIN NUMBER scrolls across the display, and 0 appears. Use the
and buttons to enter your security code (factory default 1). Then press
. If the correct PIN is entered, setup is started at 8.2.
If an incorrect PIN number is entered, _ _ _ INCORRECT PIN NUMBER – ACCESS DENIED scrolls across the display, and it returns to normal operating mode.
You will have the opportunity to change your PIN number at the end of this section
(8.8). If you have forgotten your PIN number, see Section 11.
8.2 - Counter setup
There are 3 counter inputs available on the input module:
›Count A input (drives the primary counter)›Count B input›Count C input
When the primary counter mode is set to AB IND (A & B independent) the A input
drives the primary counter and the B input drives the secondary counter. In other
count modes, the A and B inputs are both used to drive the primary counter, so the
B counter options are not available. IT IS THEREFORE ADVISABLE TO SET UP THE
A _ _ _ COUNTER SETUP scrolls across the display, and SKIP appears. Press to
skip to 8.3, or use the and buttons to select: PRM CT (primary counter),
B INPT (B input) or C INPT (C input), and then press to enter setup for the
selected counter.
¨ If you selected PRM CT or C INPT, continue to 8.2B now.¨ If you selected B INPT, skip to 8.2C now.
Note that the B INPT counter cannot be independently congured unless the count mode for
PRM CT is set to AB IND (see 8.2B). If you attempt to enter the B INPT counter setup when the
above condition has not been met, an error message will scroll across the display, and you will
not be allowed to continue.
B _ _ _ COUNT MODE scrolls across the display, and the current count mode ap-
pears. Use the and buttons to select an option from the list. (Options
will vary depending on which counter you are editing.) When you have made a
selection, press to accept and continue.
¨ If you are currently editing PRM CT, the menu options will be:
QUADX1, QUADX2, QUADX4, A+B, A–B, AB IND (AB independent) or
UP/DN (up/down).
¨ If you are currently editing C INPT, the menu options will be:
COUNT, RSOFAB (reset to oset A, B mode) or RSOFST (reset to oset
and start A, B mode).
For more information on count modes, please see Section 6.
C _ _ _ DECIMAL POINT POSITION scrolls across the display, and the current
decimal point position appears. Use the and buttons to select NO DP,
0.1, 0.12, 0.123, 0.1234 or 0.12345, and then press to accept and continue.
D _ _ _ PULSES PER UNIT OF MEASUREMENT scrolls across the display, and the
current number of pulses appears. Adjust this value using the
and but-
tons, and then press .
For example, if an encoder outputs 1,500 pulses/metre, set this value to 1500.
E _ _ _ ENTER DISPLAY VALUE FOR X PULSES scrolls across, and the current
display value appears. ('X' is the number of pulses selected in 8.2D.) Adjust this
value using the and buttons, and then press .
For example, if you selected 1,500 pulses in 8.2D, and 1,500 pulses = 1 metre, then enter 1
here. (Enter this value with reference to your decimal point position - the controller will automatically calculate the correct scale factor for you.)
F _ _ _ RESET AT POWER UP scrolls across the display, and the current setting
appears. Use the and buttons to select: NO (count value will be retained
at power up), ZERO (count value will be set to zero at power up), or LD VAL
(count value will be set to a user dened load value at power up - see 8.2G).
Then press to accept and continue.
G _ _ _ LOAD VALUE scrolls across the display, and the load value appears. (This
value will loaded into the selected counter at power up when LD VAL is selected
in 8.2F.) Use the
and buttons to adjust your load value as desired, and
then press .
This value is also used for the C input reset functions RSOFAB (see 6.9) and RSOFST (see 6.10).
H _ _ _ COUNTER SETUP scrolls across the display, and SKIP appears. You are
now back at 8.2A. To set up another input channel, follow the instructions from
8.2A–H again. If you do not wish to set up another input channel, press now
to skip to 8.3.
8.3 - Rate display setup
A _ _ _ RATE DISPLAY SETUP scrolls across the display, and SKIP appears. Press
to skip to 8.4, or the button and then to ENTER.
The rate value is taken from the primary count input (signal A).
B _ _ _ DECIMAL POINT POSITION scrolls across the display, and the current
selection appears. Use the and buttons to select NO DP, 0.1 , 0 .12, 0.123,
0.1234 or 0.12345, and then press .
C _ _ _ ROUNDING scrolls across the display, and the currently selected rounding
setting appears. Using the
Then press .
Rounding is quoted in display counts and is not inuenced by decimal point position. For example, if your input signal is 5.3, the display will show: 5.3 (for rounding=None), 5.4 (for rounding=2), 5.5 (for rounding=5) or 5.0 (for rounding=10).
D _ _ _ TIME PERIOD FOR RATE DISPLAY scrolls across the display, and the
current selection appears. Use the and buttons to select: SECS,
MINS or HOURS, and then press .
This parameter allows you to view the eective rate over dierent time periods. For example, if
the measurement units are metres, then rate can be viewed in m/sec, m/min or m/hr.
The controller will automatically calculate the required scaling factors based on the input channel setup, so you must complete 'Counter Setup' (8.2) rst.
E _ _ _ RATE MULTIPLIER scrolls across the display, and the current multiplication
factor appears. This option adds a scale factor, to display the rate in the required
units. Use the and buttons to select: X0.0001, X0.001, X0.01, X 0 .1, X1,
X10, X100 or X1000. (To disable this feature select 'X1'.) Then press .
F _ _ _ LOW CUT scrolls across the display, and the current low cut value appears.
When the rate drops below the low cut value, it displays as zero. Use the
and buttons to adjust this value (or set the low cut value to '0' to disable this
feature). Then press .
G _ _ _ DISPLAY ZERO TIME scrolls across the display, and the current display zero
time appears. This controls how quickly the rate display changes to zero. Use
and buttons to select either: 100SEC (for slow inputs), or 0.5SEC (for
the
faster inputs with more than 2 pulses/second). Then press .
H _ _ _ AVE SAMPLES scrolls across the display, and the current averaging ap-
pears. Using the
and buttons, alter the number of rate samples that the
controller will average, and then press .
Your controller has input signal averaging, optimising stable measurement.
If the change in input exceeds the averaging window value it will not average, ensuring fast response when there are large
dierences between readings.
Increasing the number of AVE SAMPLES
will stabilise measurement, but it will also
slow down response rates.
I _ _ _ AVE WINDOW scrolls across the display, and the currently selected averag-
ing window value appears. Using the and buttons, alter the rate signal
averaging window, and then press .
If your input signal contains large noise spikes, then you can increase the size the of averaging window to ensure that these pulses are still averaged. However, increasing the averaging
window too far will reduce the ability of the controller to respond quickly to real changes in
input signal.
Setting the averaging window to zero will turn o the window mode and give continuous
averaging as per the selected averaging samples.
8.4 - Display setup
A _ _ _ DISPLAY SETUP scrolls across the display, and SKIP appears. Press to
skip to 8.5, or the button and then to ENTER.
B _ _ _ LINE 1 DISPLAY SOURCE scrolls across the display, and the currently se-
lected line 1 display source appears. (Line 1 is the main display for PRO-CTR100,
and the top row for PRO-CTR200). Using the
PRMCTR, B CNTR, C CNTR, RATE, BATCH or BCHCNT. Then press .
See 7.1 for more information on the batching feature.
and buttons, select: NONE,
C The step that you proceed to now will depend on whether you have a single or
dual display PRO–CTR model:
¨ If your PRO–CTR has a single display (PRO-CTR100), skip the rest of this
section and proceed to 8.5 now.
¨ If your PRO–CTR has a dual display (PRO-CTR200), continue to 8.4D now.
D _ _ _ LINE 2 DISPLAY SOURCE scrolls across the bottom row and the currently
selected line 2 display source appears in the top row. (Line 2 is the bottom row
display for PRO-CTR200). Using the
and buttons, select: NONE, PRMCTR,
B CNTR, C CNTR, RATE, BATCH or BCHCNT. Then press .
See 7.1 for more information on the batching feature.
This section allows you to assign a custom function to the front panel button, or
the rear user input pins (see 3.6). The following functions are available:
User programmable input functions
NONENo action
RS PRMReset primary counter to load value
(8.2G)
RST BReset B counter to load value (8.2G)
RST CReset C counter to load value (8.2G)
RST BTReset batch value to zero
RSTBTCReset batch counter value to zero
* When a setpoint is congured for latching mode it will activate as normal and remain activated
until it is unlatched, either by setpoint logic or manually (as specied in this section). Refer to section
9.2F to congure setpoint latching.
UNLTCH Unlatch all setpoints*
UNLT 1Unlatch SP 1*
UNLT 2Unlatch SP 2*
UNLT 3Unlatch SP 3*
UNLT 4Unlatch SP 4*
A _ _ _ USER PROGRAMMABLE INPUT FUNCTIONS scrolls across the display,
and SKIP appears. Press to skip to 8.6, or the button and then to
ENTER input functions setup.
B _ _ _ PROGRAM BUTTON scrolls across the display, and the current function
appears. This species the operation to be executed when the
button is
pressed (for more than 2 seconds) from the main display. Referring to the table
above, use the and buttons to select a function, and then press .
C _ _ _ USER INPUT 1 scrolls across the display, and the current function appears.
This species the operation to be executed when the User 1 pin is activated
from the rear of the unit (see 3.6). Referring to the table above, use the
and
buttons to select a function, and then press .
D _ _ _ USER INPUT 2 scrolls across the display, and the current function appears.
This species the operation to be executed when the User 2 pin is activated
from the rear of the unit (see 3.6). Referring to the table above, use the
E _ _ _ USER INPUT 3 scrolls across the display, and the current function appears.
This species the operation to be executed when the User 3 pin is activated
from the rear of the unit (see 3.6). Referring to the table above, use the and
buttons to select a function, and then press .
8.6 - Analog output setup
N.B. All new units are calibrated before shipping. Recalibration is only necessary if settings
are wiped or the unit's accuracy requires verication aer a long period of use. e.g. 1 year.
A _ _ _ ANALOG OUTPUT SETUP scrolls across the display, and SKIP appears. If
your controller does not have analog output installed, (or you do not wish to
congure your analog output now), press to skip to 8.7.
Otherwise, press the
button and then to ENTER analog output setup.
B _ _ _ DATA SOURCE FOR ANALOG OUTPUT scrolls across the display, and
the current analog output data source appears. Use the
and buttons
to select an option from: NONE, PRMCTR, B CNTR, C CNTR, RATE, BATCH or
BCHCNT, and then press .
C _ _ _ LOW SCALE VALUE FOR ANALOG OUTPUT scrolls across the display, and
the currently selected low scale value appears. Use the
and buttons to
enter your cal low position, and then press .
This sets the display value for CAL LOW(as in 8.6F, below).
D _ _ _ HIGH SCALE VALUE FOR ANALOG OUTPUT scrolls across the display, and
the currently selected high scale value appears. Use the and buttons to
enter your cal high position, and then press .
This sets the display value for CAL HIGH (as in 8.6G, below).
E _ _ _ CALIBRATE ANALOG OUTPUT? scrolls across the display, and SKIP ap-
pears. To skip analog output calibration, press now and go to 8.7.
Factory analog output calibration is precisely set before shipping this instrument, and should not be adjusted unless advised by the manufacturer.
To calibrate your analog output now, connect a mA or volt meter across the
F _ _ _ CAL LOW ANALOG OUTPUT scrolls across the display and toggles with a
calibration number shown in internal units (around -16000). Press the or
buttons until the multimeter displays your target low output, then press .
G _ _ _ CAL HIGH ANALOG OUTPUT scrolls across the display and toggles with a
calibration number shown in internal units (around 30000). Press the
or
buttons until the multimeter displays your target high output, then press .
8.7 - Serial setup
A _ _ _ SERIAL SETUP scrolls across the display, and SKIP appears. If your control-
ler does not have a serial port installed, (or you do not wish to congure your
serial options now), please press to skip to 8.8.
Otherwise, press the
button and then to ENTER serial setup.
B _ _ _ SERIAL MODE scrolls across the display, and the currently selected serial
mode appears. Using the
and buttons, choose either: ASCII (custom),
MODBUS (RTU) or RNGR A (Ranger A), and then press .
See Appendix A [p32] for more information about the available serial modes.
¨ If you selected ASCII or MODBUS, skip to 8.7D now.
¨ If you selected RANGER A, continue to 8.7C now.
C _ _ _ SERIAL DATA SOURCE scrolls across the display, and the current Ranger A
serial data source appears. Use the
and buttons to select an option from:
PRMCTR, B CNTR, C CNTR, RATE, BATCH or BCHCNT, and then press .
D _ _ _ BAUD RATE scrolls across the display, and the current selection appears.
Use the
and buttons to select one of: 1200, 2400, 4800, 9600, 19200,
38400, 57600 or 115200 Then press .
E _ _ _ PARITY scrolls across the display, and the currently selected parity appears.
Using the
and buttons, select: NONE, ODD or EVEN, and then press .
F _ _ _ SERIAL ADDRESS scrolls across the display, and the serial address appears.
Use the
and buttons to alter the serial address, and then press .
Serial address is used to identify a particular device when used with other devices in a system.
(particularly to MODBUS mode when used on an RS485 serial network.) The serial address of
the controller must be set to match the serial address dened in the master device.
Refer to Appendix A [p32] for more information on serial modes and registers.
8.8 - Edit CAL PIN number
A _ _ _ EDIT CAL PIN NUMBER scrolls across the display, and SKIP appears. Press
to skip and return to the operational display, or the button and then
to ENTER and change your PIN number.
B _ _ _ ENTER NEW CAL PIN NUMBER scrolls across the display, and the current
PIN (default 1) appears. Using the
number. Then press to exit to the operational display.
and buttons, enter your new CAL PIN
9
The soware in your controller will allow you to congure 1 batch setpoint (SP 1)
and 3 standard setpoints (SP 2–4). SP 5 may be used as an LED indicator, if desired.
SP 6 is reserved.
Setpoints with no corresponding relay output hardware may be used as simple LED
indicators, if desired. In this case, features requiring relay output functionality will
continue to appear in the setup menu, but will be ignored by the controller.
SETPOINT SETUP
9.1 - Enter SP PIN number
A Enter setpoint setup mode by pressing and holding the button for 3 seconds.
_ _ _ ENTER SP PIN NUMBER scrolls across the display, and 0 appears. Use the
and buttons to enter your security code (factory default 1). Then press
. If the correct PIN is entered, setup is started at 9.2.
If an incorrect PIN number is entered, _ _ _ INCORRECT PIN NUMBER – ACCESS DENIED scrolls across the display, and it returns to normal operating mode.
You will have the opportunity to change your PIN number at the end of this section
(9.3). If you have forgotten your PIN number, see Section 11.
F _ _ _ SETPOINT TYPE scrolls across the display, and the setpoint type for the
selected setpoint appears. Using the and buttons, select: NORMAL,
TIMED or LATCHD (latched), and then press .
¨ If you selected TIMED or LATCHD, skip to 9.2I now.¨ If you selected NORMAL, continue to 9.2G now.
NORMAL: A normal setpoint will activate and deactivate using alarm or control logic regulated
within a hysteresis band (9.2G–H).
TIMED: A timed setpoint will activate as normal, and remain active for a user dened time
period (9.2K), aer which it will deactivate automatically.
LATCHD: A latched setpoint will activate as normal, and remain active until it is unlatched either by setpoint logic (9.2M), or manually using a user programmable shortcut (8.5).
G _ _ _ HYSTERESIS TYPE scrolls across the display, and the hysteresis type for the
selected setpoint appears. Using the and buttons, select either ALARM
or CNTRL (control), and then press .
ALARM - SETPOINT VALUE controls setpoint
activation point. HYSTERESIS VALUE con-
trols setpoint deactivation point.
CNTRL - SETPOINT VALUE controls setpoint
deactivation point. HYSTERESIS VALUE con-
trols setpoint reactivation point.
Hysteresis
band
Hysteresis
band
Energised Below
Hysteresis
band
Hysteresis
band
Energised Below
H _ _ _ HYSTERESIS VALUE scrolls across the display, and the hysteresis value for
the selected setpoint appears. Use the and buttons to adjust this value if
required, and then press .
The HYSTERESIS VALUE denes the separation band between setpoint activation and deacti-
vation, and will operate as per the HYSTERESIS TYPE setting selected in 9.2G.
I _ _ _ MAKE DELAY scrolls across the display, and the current make delay time
for the selected setpoint appears. This is the time delay between setpoint acti-
vation, and when the relay turns on. Adjust this value in 0.1 second increments
using the and buttons, and then press .
¨ If your Setpoint Type = NORMAL, proceed to 9.2J now.¨ If your Setpoint Type = TIMED, skip to 9.2K now.¨ If your Setpoint Type = LATCHD, skip to 9.2L now.
J _ _ _ BREAK DELAY scrolls across the display, and the current break delay value
for the selected setpoint appears. This is the time delay between setpoint de-
activation, and when the relay turns o. Adjust this value in 0.1 second incre-
ments using the and buttons, and then press .
¨ Please skip to 9.2L now.
K _ _ _ ON TIME scrolls across the display, and the current selection appears. This
denes the time that a 'Timed' relay (see 9.2F) remains energised. Adjust this
value in 0.1 second increments using the
and buttons, and then press .
L _ _ _ STARTUP INHIBIT scrolls across the display, and the current selection
appears. Use the
select NO or YES. Then press .
This option can be used with setpoints which may
be active initially at power up. Setting STARTUP INHIBIT to YES will cause a relay to remain o (deenergised) at power up until it has rst reached its
inactive state. It will then function normally.
and buttons to
Startup
inhibit
(Energised below)
M _ _ _ RESET ACTION scrolls across the display, and the current selection ap-
pears. This parameter species the action to be executed when the 'Reset Edge'
(9.2O) occurs. Use the and buttons to select: NONE, RS PRM (reset primary counter), RST B (reset B counter), RST C (reset C counter), RST BT (reset
batch), RSTBTC (reset batch count) or UNLTCH (unlatch all setpoints). Then
press to accept.
¨ If you selected NONE, then the step that you proceed to now will depend
on which setpoint you are editing (your selection in 9.2A):
` SP 1 = Skip to 9.2O now.` SP2–4 = Skip to 9.2Q now.
¨ If you selected RS PRM, RST B, RST C or RSTBTC, continue to 9.2N now.¨ If you selected RST BT or UNLTCH, skip to 9.2O now.
See 7.1 for more information on the batching feature.
N _ _ _ RESET VALUE scrolls across the display, and the current reset value ap-
pears. Use the and buttons to adjust the value which will be loaded
into the destination register selected in 'Reset Action' (9.2M) when the selected
O _ _ _ RESET EDGE scrolls across the display, and the current selection appears.
The denes the reset edge which must occur in order to trigger the 'Reset Action' selected in 9.2M. Use the and buttons to select: NONE, MAKE
(make edge, relay energises), BREAK (break edge, relay de-energises) or BOTH
(make and break edges). Then press to accept and continue.
¨ If you are currently editing SP 1, continue to 9.2P now.¨ If you are currently editing SP 2–4, skip to 9.2Q now.
P _ _ _ BATCH COUNT MODIFIER scrolls across the display, and the current value
appears. Use the
and buttons to adjust this value if desired, and then
press .
A positive number will cause the batch count register to be incremented by that amount each
time the selected reset edge is triggered. Likewise, a negative number will cause the batch
count register to be decremented. Setting this value to zero will disable this feature.
See 7.1 for more information on the batching feature.
Q _ _ _ USER ACCESS? scrolls across the display, and the direct access permission
setting for the selected setpoint appears. Use the and to select either
OFF or ON, and then press .
When enabled, this option allows the selected setpoint's value to be edited directly aer pressing the button, without needing to enter a PIN number or go through all of the other
options. Each setpoint can individually have this option enabled or disabled. See Section 10.
R _ _ _ EDIT SETPOINT scrolls across the display, and SKIP appears. You are now
back at 9.2A. To edit another setpoint, follow the instructions from 9.2A–R
again. If you do not wish to edit another setpoint, press now to skip to 9.3.
9.3 - Edit SP PIN number
A _ _ _ EDIT SP PIN NUMBER scrolls across the display, and SKIP appears. Press
to skip and return to the operational display, or the button and then
to ENTER and change your PIN number.
B _ _ _ ENTER NEW SP PIN NUMBER scrolls across the display, and the current
PIN (default 1) appears. Using the
number. Then press to exit to the operational display.
Start - Use 'S' for the start character of a command string (not case sensitive). This
must be the rst character in the string.
Controller Address - Use an ASCII number from '1' to '255' for the controller address.
If the character following the start character is not an ASCII number, then address '0' is assumed. All controllers respond to address '0'.
Read/Write Command - Use ASCII 'R' for read, 'U' for unformatted read, or 'W' for
write (not case sensitive). Any other character aborts the operation.
In Custom ASCII mode, data is normally read as formatted data (which includes decimals and
any text characters that may be selected to show units). However it is also possible to read unformatted data by using a 'U' in the read command. There is no unformatted write command,
as when writing to xed point registers, any decimal point and text characters are ignored.
Register Address - The register address for the read/write operation will be an ASCII
number from '1' to '65535'. This character must be specied for a write com-
mand, but may be omitted for a read command, (in which case the controller
will respond with the data value currently on the display).
Separator Character - The separator character can be either a space or a comma,
and is used to separate the register address from the data value.
Data Value - Must be an ASCII number. The absolute limits for this number are
-1000000 to 1000000, but please note that not all registers will accept this range.
Message Terminator - This is the last character, and must be either a '$' (dollar) or
an '*' (asterisk). Neither of these characters should be used elsewhere in the
message string. If '$' is used, a 50ms minimum delay is inserted before a reply is
sent. If '*' is used, a 2ms minimum delay is inserted before a reply is sent.
Custom ASCII Read/Write Examples
ExampleDescription
SR$Read display value from all controllers, 50ms delay.
S15R$Read display value from controller address 15, 50ms delay.
S3U40*Read unformatted data in channel 4 from controller address 3, 2ms delay.
S2W2 -10000$Write -10000 to the display register of controller address 2, 50ms delay.
SWT CHAN_1$Write ASCII text string Chan_1 to channel 1 text register, 50ms delay.
Custom ASCII Registers - Active for models with relay output installed
8 Bit Unsigned
8207Baud rate
8211Serial address
8215Serial mode
16 Bit Unsigned
4181Hysteresis SP 1 (Batch SP)
4182–4185Hysteresis SP 2–5
4197Make delay SP 1 (Batch SP)
4198–4201Make delay SP 2–5
4213Break delay SP 1 (Batch SP)
4214-4217Break delay SP 2–5
5173Batch count increment
24 Bit Signed (2 x 16 Bit)
2509Load value (Primary)
2511Load value (B counter)
2513Load value (C counter)
32 Bit Signed (2 x 16 Bit)
7Batch result
9Rate
13Primary counter
15B counter
11C counter
37Batch tare
39Batch count
57Peak
59Valley
111Setpoint 1 (Batch setpoint)
113Setpoint 2
115Setpoint 3
117Setpoint 4
119Setpoint 5
239Alarm status
Controller Response - Aer the controller has completed a read or write instruction,