This button is used to
access the Input Setup & Calibration menu (Section 5).
This button is used to save
your settings and advance
to the next step in the setup process.
This button is typically used to scroll through options or increase values in the
setup menu. Pressing this button from the main display will show the current values
for PWR (power) AMP (current), PEAK or P.F. (power factor). See 2.4 for more
information.
This button is typically used to scroll through options or decrease values in the
setup menu. Pressing this button from the main display will show the current values
for ENRG (energy), FREQ (frequency), VLTS (voltage) or VALY (valley). See 2.4 for
more information.
48mm
(1.89")
96mm (3.78")
This button is used to access the Setpoint Setup menu (Section 6) and the
Setpoint Direct Access menu (Section 7).
2.2 - Display brightness
To adjust the display brightness, press the and buttons together from the
main display. BRI appears and toggles with the current setting. Use the and
buttons to adjust the LED backlight, and then press to nish.
D _ _ _ AVE SAMPLES scrolls across the display and toggles with the currently
selected averaging. Using the and buttons, alter the number of input
samples that the controller will average, and then press .
Increasing the number of samples will stabilise measurement, but it will also slow down response rates.
E _ _ _ AVE WINDOW scrolls across the display and toggles with the currently
selected averaging window value. Using the and buttons, alter the signal
averaging window. Then press .
If your input signal contains large noise spikes, you can increase the size of the averaging window to ensure that these are still averaged. However, increasing the window size too far will
reduce the ability of the controller to respond quickly to real changes in input signal. Setting
AVE WINDOWto 0 will give continuous averaging as per the selected averaging samples.
F _ _ _ INPUT SETUP scrolls across the display and toggles with SKIP. You are now
back at 5.2A. To edit dierent input type, follow the instructions from 5.2A–F
again. If you do not wish to edit another input type, press now to skip to 5.3.
5.3 - Energy setup
The energy function allows you to see the total amount of energy that has been
used in W/hr, kW/hr or MW/hr.
A _ _ _ ENERGY SETUP scrolls across the display and toggles with SKIP. Press
to skip to 5.4, or the button and then to ENTR (enter) energy setup.
B _ _ _ RESOLUTION scrolls across the display and toggles with the currently se-
lected energy resolution. Using the and buttons, select: W, KW or MW,
and then press .
` If the resolution was set successfully, setup will proceed to 5.3C.n _ _ _ SCALING ERROR - CHANGE ENERGY SETTINGS!
If you see this message, then the combination of settings that you have
selected in Power Resolution (5.2B) and Energy Resolution (5.3B) will
produce values which are too large for the controller to process or display.
To correct this, modify the settings in 5.2B or 5.3B.
C _ _ _ CUTOFF scrolls across the display and toggles with the currently selected
power cuto value. When the power input value falls below the cuto value,
the energy register will stop accumulating power, and will pause until the input
power is greater than or equal to the cuto value again.
Use the
and buttons to adjust this value as required, and then press .
D _ _ _ ROLL OVER scrolls across the display and toggles with the current setting.
If rollover is ON, then when the energy value exceeds 9,999, the display will roll
to 0 and continue accumulating. If rollover is OFF, then the display will read
OVER in this situation. Use the
and buttons to turn the rollover feature
OFF or ON, and then press .
Note that the ROLL OVER feature does not produce any output pulse or other indication when
it rolls over. (An output pulse can be activated on a setpoint with its data source set to Energy.
See 6.2F for more information, and to enable this feature.)
5.4 - Display setup
A _ _ _ DISPLAY SETUP scrolls across the display and toggles with SKIP. Press
to skip to 5.5, or the button and then to ENTR (enter) display setup.
B _ _ _ DISPLAY SOURCE scrolls across the display and toggles with the current
display source. Use the
age), PWR (power), FREQ (frequency), ENRG (energy) or P.F. (power factor).
error is that the controller could not detect any change in input signal during
calibration. Check your signal and connections, and repeat the procedure.
Manual calibration
F _ _ _ ENTER DISPLAY VALUE AT FULL SCALE CURRENT scrolls across the dis-
play and toggles with the current selection. Use the
and buttons to enter
a display value for the full scale current input (typically 5A). Then press .
Manual calibration is now complete. You will be directed back to the opera-
tional display. (To proceed to step 5.6, you must select SKIP at 5.5A.)
Current Transformer calibration
G _ _ _ ENTER CT INPUT CURRENT scrolls across the display and toggles with the
currently selected CT input value. Adjust this value using the
and but-
tons, and then press .
H _ _ _ ENTER CT OUTPUT CURRENT scrolls across the display and toggles with
the currently selected CT output value. Adjust this value using the
and
buttons, and then press .
CT calibration is now complete. You will be directed back to the operational
display. (To proceed to step 5.6, you must select SKIP at 5.5A.)
5.6 - Analog output setup
N.B. All new units are calibrated before shipping. Recalibration is only necessary if settings
are wiped or the unit's accuracy requires verication aer a long period of use. e.g. 1 year.
A _ _ _ ANALOG OUTPUT SETUP scrolls across the display and toggles with SKIP.
If your controller does not have analog output installed, (or you do not wish to
congure your analog output now), press to skip to 5.7. Otherwise, press
the button and then to ENTER analog output setup.
B _ _ _ DATA SOURCE scrolls across the display and toggles with the current analog
output data source. Use the
rent), VLT S (voltage), PWR (power), FREQ (frequency), ENRG (energy), or P.F.
The soware in your controller will allow you to congure up to 4 setpoints,
however full functionality is only supported when relay output hardware installed.
(Setpoints with no corresponding relay output hardware may be used as simple LED
indicators, if desired. In this case, features requiring relay output functionality will
continue to appear in the setup menu, but will be ignored by the controller.)
SETPOINT SETUP
6.1 - Enter Setpoint PIN number
A Enter setpoint setup mode by pressing and holding the button for 3 seconds.
_ _ _ ENTER SP PIN NUMBER scrolls across the display and toggles with 0.
Use the
Then press . If the correct PIN is entered, setup is started at 6.2.
If an incorrect PIN number is entered, _ _ _ INCORRECT PIN NUMBER - ACCESS
DENIED scrolls across the display and it returns to normal operating mode.
You will have the opportunity to change your PIN number at the end of this section
(6.3). If you have forgotten your PIN number, see Section 8.
and buttons to enter your security code (factory default '1').
6.2 - Setpoint setup
A _ _ _ EDIT SETPOINT scrolls across the display and toggles with SKIP. Press
now to skip to 6.3, or use the and buttons to select a setpoint to edit,
and then press .
B _ _ _ SP VALUE scrolls across the display and toggles with the current value for
the selected setpoint. Using the
which the selected setpoint will activate, and then press .
G _ _ _ PULSE WIDTH scrolls across the display and toggles with the current pulse
width. Use the and buttons to adjust the pulse width from 0.1 to 10
seconds, and then press .
¨ Please skip steps 6.2H−K, and proceed to 6.2L now.
Current, Voltage, Power, Frequency, or Power Factor Setpoints
H _ _ _ SP ACTIVATION scrolls across the display and toggles with the current
activation for the selected setpoint. Using the
and buttons, select the
relay activation to operate ABVE (above) or BLW (below) the setpoint value,
and then press .
ABVE: Relay turns on above the setpoint value and o below it.
BLW: Relay turns on below the setpoint value and o above it.
I _ _ _ SP TYPE scrolls across the display and toggles with the current setting for
the selected setpoint. Using the and buttons, select either ALM (alarm)
or CTRL (control), and then press .
ALM - SETPOINT VALUE controls setpoint
activation point. HYSTERESIS VALUE con-
trols setpoint deactivation point.
CTRL - SETPOINT VALUE controls setpoint
deactivation point. HYSTERESIS VALUE con-
trols setpoint reactivation point.
Hysteresis
band
Hysteresis
band
Energised Below
Hysteresis
band
Hysteresis
band
Energised Below
J _ _ _ HYSTERESIS VALUE scrolls across the display and toggles with the hyster-
esis value for the selected setpoint. Use the and buttons to adjust this
value if required, and then press .
The HYSTERESIS VALUE denes the separation band between setpoint activation and deacti-
vation, and will operate as per the SP TYPE setting selected in 6.2I.
K _ _ _ MAKE DELAY scrolls across the display and toggles with the current make
delay time for the selected setpoint. This is the time delay between setpoint ac-
tivation, and when the relay turns on. Adjust this value in 0.1 second increments
L _ _ _ USER ACCESS? scrolls across the display and toggles with the direct access
permission setting for the selected setpoint. Use the and to select either
OFF or ON, and then press .
When enabled, this option allows the selected setpoint's value to be edited directly aer pressing the button, without needing to enter a PIN number or go through all of the other options. Each setpoint can individually have this option enabled or disabled. See Section 7.
M _ _ _ EDIT SETPOINT scrolls across the display and toggles with SKIP. You are
now back at 6.2A. To edit another setpoint, follow the instructions from 6.2A–M
again. If you do not wish to edit another setpoint, press now to skip to 6.3.
6.3 - Edit SP PIN number
A _ _ _ EDIT SP PIN NUMBER scrolls across the display and toggles with SKIP.
Press to skip and return to the operational display, or the button and
then to ENTER and change your PIN number.
B _ _ _ ENTER NEW SP PIN NUMBER scrolls across the display and toggles with
the current PIN (default 1). Using the
number. Then press to exit to the operational display.