Deep Sea Electronics Plc DSE5320, DSE5310 Operating Manual

COMPLEX SOLUTIONS MADE SIMPLE.
DEEP SEA ELECTRONICS PLC
DSE5320
OPERATING MANUAL
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
2 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND
Sales Tel: +44 (0) 1723 890099 Sales Fax: +44 (0) 1723 893303
E-mail: sales@Deepseaplc.com
Website: www.deepseaplc.com
DSE Model 5320 Automatic Mains Failure Module Operators Manual © Deep Sea Electronics Plc
All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder except in accordance with the provisions of the Copyright, Designs and Patents Act 1988. Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to Deep Sea Electronics Plc at the address above.
Any reference to trademarked product names used within this publication is owned by their respective companies. Deep Sea Electronics Plc reserves the right to change the contents of this document without prior notice.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 3
TABLE OF CONTENTS
Section Page
1INTRODUCTION .............................................................................................. 5
2CLARIFICATION OF NOTATION USED WITHIN THIS PUBLICATION. ........ 5
3OPERATION .................................................................................................... 6
3.1 AUTOMATIC MODE OF OPERATION ............................................................................... 7
3.2 MANUAL OPERATION ....................................................................................................... 9
3.3 TEST OPERATION ............................................................................................................ 10
4PROTECTIONS .............................................................................................. 11
4.1 WARNINGS ....................................................................................................................... 12
4.2 ANALOGUE PRE-ALARMS ............................................................................................. 13
4.3 HIGH CURRENT WARNING ALARM ............................................................................... 15
4.4 SHUTDOWNS .................................................................................................................... 15
4.5 HIGH CURRENT SHUTDOWN ALARM ........................................................................... 18
4.6 ELECTRICAL TRIPS ......................................................................................................... 19
5DESCRIPTION OF CONTROLS .................................................................... 20
5.1 TYPICAL LCD DISPLAY SCREENS ................................................................................ 22
5.1.1 TYPICAL STATUS DISPLAY...................................................................................... 22
5.1.2 TYPICAL INSTRUMENT DISPLAY ............................................................................ 22
5.1.3 TYPICAL ALARM DISPLAY ....................................................................................... 22
5.1.4 TYPICAL EVENT DISPLAY ........................................................................................ 23
5.2 VIEWING THE INSTRUMENTS ........................................................................................ 23
5.2.1 INSTRUMENT PAGE CONTENT ............................................................................... 24
5.2.2 MANUALLY SELECTING AN INSTRUMENT ............................................................ 25
5.2.3 GSM MODEM STATUS .............................................................................................. 26
5.2.4 CAN ERROR MESSAGES ......................................................................................... 27
5.3 VIEWING THE EVENT LOG .............................................................................................. 27
5.4 USER CONFIGURABLE INDICATORS ........................................................................... 28
5.5 CONTROLS ....................................................................................................................... 28
6FRONT PANEL CONFIGURATION ............................................................... 29
6.1.1 ENTERING THE CONFIGURATION EDITOR PIN NUMBER ................................... 29
6.2 EDITING A VALUE ............................................................................................................ 31
6.2.1 LIST OF ADJUSTABLE PARAMETERS IN ‘MAIN CONFIGURATION EDITOR’ ...... 32
6.2.2 LIST OF ADJUSTABLE PARAMETERS IN ‘APPLICATION EDITOR’ ...................... 33
6.2.3 EDITING THE CURRENT DATE AND TIME ............................................................. 34
7INSTALLATION INSTRUCTIONS .................................................................. 36
7.1 PANEL CUT-OUT .............................................................................................................. 36
7.2 COOLING........................................................................................................................... 36
7.3 UNIT DIMENSIONS ........................................................................................................... 36
7.4 FRONT PANEL LAYOUT .................................................................................................. 37
7.5 REAR PANEL LAYOUT .................................................................................................... 37
8ELECTRICAL CONNECTIONS ...................................................................... 38
8.1 CONNECTION DETAILS................................................................................................... 38
8.1.1 PLUG “A” 8 WAY ........................................................................................................ 38
8.1.2 PLUG “B” 11 WAY ...................................................................................................... 39
8.1.3 PLUG “C” 3 WAY ........................................................................................................ 40
8.1.4 PLUG “D” 4 WAY ........................................................................................................ 40
8.1.5 PLUG “E” 8 WAY ........................................................................................................ 40
8.1.6 PLUG “F” 4 WAY ........................................................................................................ 41
8.1.7 PLUG “G” 5 WAY ........................................................................................................ 41
8.1.8 PLUG “H” 4 WAY ........................................................................................................ 41
8.1.9 PC CONFIGURATION INTERFACE CONNECTOR .................................................. 42
8.1.10EXPANSION OUTPUT CONNECTOR ....................................................................... 42
8.2 CONNECTOR FUNCTION DETAILS ................................................................................ 43
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
4 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
8.2.1 PLUG “A” 8 WAY ........................................................................................................ 43
8.2.2 PLUG “B” 11 WAY ...................................................................................................... 43
8.2.3 PLUG “C” 3 WAY ........................................................................................................ 44
8.2.4 PLUG “D” 4 WAY ........................................................................................................ 44
8.2.5 PLUG “E” 8 WAY ........................................................................................................ 44
8.2.6 PLUG “F” 4 WAY ......................................................................................................... 45
8.2.7 PLUG “G” 5 WAY ........................................................................................................ 45
8.2.8 PLUG “H” 4 WAY ........................................................................................................ 45
8.2.9 PURCHASING ADDITIONAL CONNECTOR PLUGS FROM DSE ............................ 45
9SPECIFICATION .............................................................................................46
10 COMMISSIONING .......................................................................................47
10.1.1PRE-COMMISSIONING .............................................................................................. 47
11 FAULT FINDING ..........................................................................................49
12 FACTORY DEFAULT CONFIGURATION ...................................................50
13 TYPICAL WIRING DIAGRAM ......................................................................54
14 APPENDIX ...................................................................................................55
14.1 ALTERNATIVE WIRING TOPOLOGIES ....................................................................... 55
14.1.13 PHASE, 3 WIRE ....................................................................................................... 55
14.1.21 PHASE, 2 WIRE ....................................................................................................... 56
14.1.32 PHASE, 3 WIRE ( 2 PHASE CENTRE TAP NEUTRAL) ......................................... 56
14.2 ICONS AND LCD IDENTIFICATION ............................................................................. 57
14.2.1PUSH BUTTONS ........................................................................................................ 57
14.2.2STATUS / MEASUREMENT UNITS ........................................................................... 57
14.2.3LED INDICATION ....................................................................................................... 57
14.3 5320 IDMT TRIPPING CURVES (TYPICAL) ................................................................. 58
14.4 SENDER WIRING RECOMMENDATIONS .................................................................... 59
14.4.1EARTH RETURN SENDERS ..................................................................................... 59
14.4.2INSULATED RETURN SENDERS ............................................................................. 59
14.4.3FUEL LEVEL SENDERS ............................................................................................ 59
14.5 CAN INTERFACE .......................................................................................................... 61
14.6 OUTPUT EXPANSION ................................................................................................... 61
14.6.1RELAY OUTPUT EXPANSION (157) ......................................................................... 61
14.6.2LED OUTPUT EXPANSION (548) .............................................................................. 61
14.7 INPUT EXPANSION ....................................................................................................... 61
14.8 COMMUNICATIONS OPTION CONNECTIONS ........................................................... 62
14.8.1DESCRIPTION ............................................................................................................ 62
14.8.2PC TO CONTROLLER (DIRECT) CONNECTION ..................................................... 62
14.8.3MODEM TO CONTROLLER CONNECTION ............................................................. 62
14.8.4RS485 LINK TO CONTROLLER ................................................................................ 63
14.8.5MODBUS™ ................................................................................................................. 64
14.9 ENCLOSURE CLASSIFICATIONS ............................................................................... 65
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 5
1 INTRODUCTION
The DSE 5320 automatic mains failure module has been primarily designed to monitor the mains (utility) supply, starting the generator automatically should it fall out of limits. Transfer of the load is automatic upon a mains supply failure. If required the generator and can be started and stopped manually, and if required, the user can transfer the load to the generator either manually (via external push-buttons) or automatically. The user also has the facility to view all the system operating parameters via the LCD display.
The DSE 5320 module monitors the mains (utility) supply indicating the status of the mains on the module’s integral LCD display. Additionally the module monitors the engine, indicating the operational status and fault conditions, automatically shutting down the engine and giving a true first up fault condition of an engine failure by a flashing COMMON AUDIBLE ALARM. The exact failure mode is indicated by text messages on the LCD display on the front panel.
The powerful microprocessor contained within the module allows for a range of complex features to be incorporated as standard:
Text based LCD display (supporting multiple languages).
Voltage, Current and Power monitoring.
Engine parameter monitoring.
Fully configurable inputs for use as alarms or a range of different functions.
Extensive range output functions using built in relay outputs or relay expansion available.
Selective operational sequences, timers and alarm trips can be altered by the customer via a PC using the 5xxx series configuration software and P810 interface. Additionally, a subset of this information can be adjusted from the module’s front panel configuration editor.
The module is housed in a robust plastic case for front panel mounting. Connections to the module are via locking plug and sockets.
2 CLARIFICATION OF NOTATION USED WITHIN THIS PUBLICATION.
NOTE:
Highlights an essential element of a procedure to ensure correctness.
CAUTION!
Indicates a procedure or practice which, if not strictly observed, could result in damage or destruction of equipment.
WARNING!
Indicates a procedure or practice which, could result in injury to personnel or loss of life if not followed correctly.
Compliant with BS EN 60950 Low Voltage Directive Compliant with BS EN 50081-2 EMC Directive Compliant with BS EN 50082-2 EMC Directive Indicates a function only applicable when the controller is configured for connection to a CAN (Controller Area Network) engine controller
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
6 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
3 OPERATION
The following description details the sequences followed by a module containing the standard ‘factory configuration’. Always refer to your configuration source for the exact sequences and timers observed by any
particular module in the field.
Deep Sea Electro nics
Model 5220
O
I
+
AUTO
i
Warming 10s L-N 240V 0A 50Hz L-L 415V 0kW
RUNNING IN AUTO
FIG 1
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 7
3.1 AUTOMATIC MODE OF OPERATION
NOTE:- If a digital input configured to panel lock is active, changing module modes will not be
possible. Viewing the instruments and iis NOT affected by panel lock. If panel lock is active the Panel lock indicator (if configured) illuminates.
This mode is activated by pressing the
pushbutton. An LED indicator beside the button confirms this
action. Should the mains (utility) supply fall outside the configurable limits for longer than the period of the mains transient
delay timer, the mains (utility) available GREEN indicator LED extinguishes. Additionally, while in AUTO mode, the remote start input (if configured) is monitored. If active, the Remote Start Active indicator (if configured) illuminates.
Whether the start sequence is initiated by mains (utility failure) or by remote start input, the following sequence is observed :
To allow for short term mains supply transient conditions or false remote start signals, the Start Delay timer is initiated. After this delay, if the pre-heat output option is selected then the pre-heat timer is initiated, and the corresponding auxiliary output (if configured) will energise.
NOTE:- If the mains supply returns within limits, ( or the Remote Start signal is removed if the start sequence was initiated by remote start) during the Start Delay timer, the unit will return to a stand-by state.
After the above delays the Fuel Solenoid (or enable ECU output if configured) is energised, then one second later, the Starter Motor is engaged.
NOTE:- If the unit has been configured for CAN, compatible ECU’s will receive the start command via CAN.
The engine is cranked for a pre-set time period. If the engine fails to fire during this cranking attempt then the starter motor is disengaged for the pre-set rest period. Should this sequence continue beyond the set number of attempts, the start sequence will be terminated and Fail to Start fault will be displayed.
Alarm
Shutdown Failed to start
When the engine fires, the starter motor is disengaged and locked out at a pre-set frequency from the alternator output. Alternatively a Magnetic Pickup mounted on the flywheel housing can be used for speed detection (This is selected by PC using the 5xxx series configuration software). Rising oil pressure can also be used to disconnect the starter motor, however it cannot be used for underspeed or overspeed detection.
NOTE:- If the unit has been configured for CAN, speed sensing is via CAN.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
8 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
After the starter motor has disengaged, the Safety On timer is activated, allowing Oil Pressure, High Engine Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the fault.
Once the engine is running, the Warm Up timer, if selected is initiated, allowing the engine to stabilise before accepting the load.
If an auxiliary output has been selected to give a load transfer signal, this would then activate.
NOTE:-A load transfer will not be initiated until the Oil Pressure has risen. Thus preventing
excessive wear on the engine.
On the return of the mains supply, (or removal of the Remote Start signal if the set was started by remote signal) , the Stop delay timer is initiated, once it has timed out, the load Transfer signal is de-energised, removing the load. The Cooling timer is then initiated, allowing the engine a cooling down period off load before shutting down. Once the Cooling timer expires the Fuel Solenoid is de-energised, bringing the generator to a stop.
Should the mains supply fall outside limits again (or the Remote Start signal be re-activated) during the cooling down period, the set will return on load.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 9
3.2 MANUAL OPERATION
NOTE:- If a digital input configured to panel lock is active, changing module modes will not be
possible. Viewing the instruments and event logs iis NOT affected by panel lock. If panel lock is active the Panel lock indicator (if configured) illuminates.
To initiate a start sequence in MANUAL, press the pushbutton. When the controller is in the manual mode (indicated by an LED indicator beside the button), pressing the START (
I) button will initiate the start sequence.
NOTE:- There is no Start Delay in this mode of operation.
If the pre-heat output option is selected this timer is then initiated, and the auxiliary output selected is energised. After the above delay the Fuel Solenoid (or ECU output if configured) is energised, then one second later, the
Starter Motor is engaged.
NOTE:- If the unit has been configured for CAN, compatible ECU’s will receive the start command
via CAN.
The engine is cranked for a pre-set time period. If the engine fails to fire during this cranking attempt then the starter motor is disengaged for the pre-set rest period. Should this sequence continue beyond the set number of attempts, the start sequence will be terminated and Fail to Start will be displayed.
When the engine fires, the starter motor is disengaged and locked out at a pre-set frequency from the Alternator output. Alternatively a Magnetic Pickup mounted on the flywheel housing can be used for speed detection (This is selected by PC using the 5xxx series configuration software). Rising oil pressure can also be used to disconnect the starter motor, however it cannot be used for underspeed or overspeed detection.
NOTE:- If the unit has been configured for CAN, speed sensing is via CAN.
After the starter motor has disengaged, the Safety On timer is activated, allowing Oil Pressure, High Engine Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the fault.
Once the engine is running, the Warm Up timer, if selected, is initiated, allowing the engine to stabilise before it can be loaded.
The generator will run off load, unless the mains supply fails or a Remote Start on load signal is applied. If Close generator has been selected as a control source, the appropriate auxiliary output will then activate.
The generator will continue to run On load regardless of the state of the mains supply or remote start input until the Auto mode is selected. If Auto mode is selected, and the mains supply is healthy with the remote start on load signal not active, then the Remote Stop Delay Timer begins, after which, the load is disconnected. The generator will then run off load allowing the engine a cooling down period.
Selecting STOP (O) de-energises the FUEL SOLENOID, bringing the generator to a stop.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
10 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
3.3 TEST OPERATION
NOTE:- If a digital input configured to panel lock is active, changing module modes will not be
possible. Viewing the instruments and event logs iis NOT affected by panel lock. If panel lock is active the Panel lock indicator (if configured) illuminates.
To initiate a start sequence in TEST, press the pushbutton. When the controller is in the test mode (indicated by an LED indicator beside the button), pressing the START (
I) button will initiate the start sequence.
NOTE:- There is no Start Delay in this mode of operation.
If the pre-heat output option is selected this timer is then initiated, and the auxiliary output selected is energised. After the above delay the Fuel Solenoid (or ECU output if configured) is energised, then one second later, the
Starter Motor is engaged.
NOTE:- If the unit has been configured for CAN, compatible ECU’s will receive the start command
via CAN.
The engine is cranked for a pre-set time period. If the engine fails to fire during this cranking attempt then the starter motor is disengaged for the pre-set rest period. Should this sequence continue beyond the set number of attempts, the start sequence will be terminated and Fail to Start will be displayed.
Alarm
Shutdown Failed to start
When the engine fires, the starter motor is disengaged and locked out at a pre-set frequency from the Alternator output. Alternatively a Magnetic Pickup mounted on the flywheel housing can be used for speed detection (This is selected by PC using the 5300 series configuration software). Rising oil pressure can also be used to disconnect the starter motor, however it cannot be used for underspeed or overspeed detection.
NOTE:- If the unit has been configured for CAN, speed sensing is via CAN.
After the starter motor has disengaged, the Safety On timer is activated, allowing Oil Pressure, High Engine Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the fault.
Once the engine is running, the Warm Up timer, if selected, is initiated, allowing the engine to stabilise before it can be loaded.
The generator will continue to run On load regardless of the state of the mains supply or remote start input until the Auto mode is selected. If Auto mode is selected, and the mains supply is healthy with the remote start on load signal not active, then the Remote Stop Delay Timer begins, after which, the load is disconnected. The generator will then run off load allowing the engine a cooling down period.
Selecting STOP (O) removes the Close Generator output (if configured) and de-energises the FUEL SOLENOID, bringing the generator to a stop.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 11
4 PROTECTIONS
When an alarm is present the Audible Alarm will sound and the Common alarm LED if configured will illuminate.
The audible alarm can be silenced by pressing the ‘Mute’ button
The LCD display will jump from the ‘Information page’ to display the Alarm Page
Alarm
Warning Low oil pressure
The type of alarm. E.g.Shutdown or warning
The nature of alarm, e.g. Low oil pressure.
The LCD will display multiple alarms E.g. “High Engine Temperature shutdown”, “Emergency Stop” and “Low Coolant Warning” alarms have been triggered. These will automatically scroll round in the order that they occurred;
Running in auto
If no alarms are present the LCD will display this default page.
Generator on load L-N 230V 240A 50Hz L-L 400V 133kW
In the event of a warning alarm the LCD will display the appropriate text. If a shutdown then occurs the module will again display the appropriate text. Example:-
Alarm
Shutdown
High engine temperature
Followed by….
Alarm
Shutdown
Emergency stop
Followed by….
Alarm
Warning Low coolant level
The unit will scroll through all active alarms in a continuous loop.
Alarm
Shutdown High engine temperature
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
12 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
4.1 WARNINGS
Warnings are non-critical alarm conditions and do not affect the operation of the generator system, they serve to draw the operators attention to an undesirable condition.
In the event of an alarm the LCD will jump to the alarms page, and scroll through all active warnings and shutdowns.
BATTERY CHARGE FAILURE, will be displayed if the module does not detect a voltage from the warning light terminal on the auxiliary charge alternator.
Alarm
Warning Charge fail
BATTERY LOW VOLTAGE, will be displayed if the module detects that the plant DC supply has fallen below the low volts setting level. The Battery Low Voltage alarm is delayed by the Low DC Volts Delay timer.
Alarm
Warning Low battery volts
BATTERY HIGH VOLTAGE, will be displayed if the module detects that the plant DC supply has risen above the high volts setting level. The Battery High Voltage alarm is delayed by the High DC Volts Delay timer.
Alarm
Warning High battery volts
FAIL TO STOP, will be displayed if the module detects the engine is still running when the ‘Fail to stop timer’ expires.
Alarm
Fail to stop
NOTE:- ‘Fail to Stop’ could indicate a faulty oil pressure sender - If engine is at rest check oil sender
wiring and configuration.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 13
AUXILIARY INPUTS, auxiliary inputs can be user configured and will display the message as written by the user. Example
Alarm
Warning Bearing temp high
LOW FUEL LEVEL. will be displayed if the fuel level detected by the fuel level sender falls below the low fuel level setting.
Alarm
Warning Low fuel level
CAN ECU ERROR If the module is configured for CAN instruments and receives an “error” message from the engine control unit, ‘Can ECU error” is shown on the module’s display and a warning alarm is generated.
Example
Alarm
The display will alternate between the text display and the manufacturers error codes
Alarm
Can ECU error Exhaust high temperature
Can ECU error SPNnnnnnnn FMInnnnnnn
4.2 ANALOGUE PRE-ALARMS
The following alarms are termed ‘pre-alarms’ as they pre warn the operator of a potentially more serious alarm condition. For instance, if the engine temperature rises past the pre alarm level, a warning condition will occur to notify the operator. If the temperature falls below this level, then the alarm ceases, and the set will continue to run as normal. However if the temperature continues to rise until the coolant temperature trip point is reached, the warning is escalated and a high coolant temperature shutdown is initiated.
LOW OIL PRESSURE, if the module detects that the engine oil pressure has fallen below the low oil pressure pre­alarm setting level after the Safety On timer has expired, a warning will occur. Alarm Warning Low Oil Pressure will be displayed.
Alarm
Warning Low oil pressure
HIGH ENGINE TEMPERATURE if the module detects that the engine coolant temperature has exceeded the high engine temperature pre-alarm setting level after the Safety On timer has expired, a warning will occur. Alarm Warning High Coolant Temperature will be displayed.
Alarm
Warning High temperature
LOW ENGINE TEMPERATURE if the module detects that the engine coolant temperature has fallen below the low engine temperature pre-alarm setting level after the Safety On timer has expired, a warning will occur. Alarm Warning Low Coolant Temp will be displayed.
Alarm
Warning Low Coolant Temp
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
14 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
OVERSPEED, if the engine speed exceeds the pre-alarm trip a warning is initiated. Alarm Warning Overspeed will be displayed. It is an immediate warning.
Alarm
Warning Overspeed
UNDERSPEED, if the engine speed falls below the pre-set pre-alarm after the Safety On timer has expired, a warning is initiated. Alarm Warning Underspeed will be displayed.
Alarm
Warning Underspeed
GENERATOR HIGH FREQUENCY if the module detects a generator output frequency in excess of the pre-set pre-alarm, a warning is initiated. Alarm Warning High frequency will be displayed, it is an immediate warning.
Alarm
Warning Over frequency
GENERATOR LOW FREQUENCY if the module detects a generator output frequency below the pre-set pre-alarm after the Safety On timer has expired, a warning is initiated. Alarm Warning Low Frequency will be displayed
Alarm
Warning Under frequency
GENERATOR HIGH VOLTAGE if the module detects a generator output voltage in excess of the pre-set pre­alarm, a warning is initiated. Alarm Warning High voltage will be displayed, it is an immediate warning.
Alarm
Warning AC Overvolts
GENERATOR LOW VOLTAGE if the module detects a generator output voltage below the pre-set pre-alarm after the Safety On timer has expired, a warning is initiated. Alarm Warning Low Voltage will be displayed.
Alarm
Warning AC Undervolts
CAN ECU ERROR If the module is configured for CAN instruments and receives an “error” message from the engine control unit, ‘Can ECU error” is shown on the module’s display and a warning alarm is generated.
Example
Alarm
The display will alternate between the text display and the manufacturers error codes
Alarm
Can ECU error Exhaust high temperature
Can ECU error SPNnnnnnnn FMInnnnnnn
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 15
4.3 HIGH CURRENT WARNING ALARM
GENERATOR HIGH CURRENT, if the module detects a generator output current in excess of the pre-set trip a
warning is initiated. Alarm Warning High Current will be displayed. If this high current condition continues for an excess period of time, then the alarm is escalated to a shutdown condition. For further details of the high current alarm, please see High Current Shutdown Alarm.
Alarm
Warning High current
4.4 SHUTDOWNS
Shutdowns are latching and stop the Generator. The alarm must be cleared, and the fault removed to reset the module.
NOTE:- The alarm condition must be rectified before a reset will take place. If the alarm condition remains it will not be possible to reset the unit (The exception to this is the Low Oil Pressure alarm and similar ‘delayed alarms’, as the oil pressure will be low with the engine at rest).
FAIL TO START, if the engine does not fire after the pre-set number of attempts has been made a shutdown will be initiated. Alarm Shutdown Fail To Start will be displayed.
Alarm
Shutdown Failed to start
EMERGENCY STOP, removal of the Positive DC Supply from the Emergency Stop input initiates the following sequence, firstly it will initiate a controlled shutdown of the Generator and prevent any attempt to restart the Generator until the Emergency Stop push-button has been reset. Secondly it removes the Positive DC supply from both the Fuel Solenoid and Starter Solenoid.
Alarm Shutdown Emergency Stop will be displayed.
Alarm
Shutdown Emergency stop
NOTE:- The Emergency Stop Positive signal must be present otherwise the unit will shutdown.
LOW OIL PRESSURE, if the module detects that the engine oil pressure has fallen below the low oil pressure trip setting level after the Safety On timer has expired, a shutdown will occur. Alarm Shutdown Low Oil Pressure will be displayed.
Alarm
Shutdown Low oil pressure
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
16 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
HIGH ENGINE TEMPERATURE if the module detects that the engine coolant temperature has exceeded the high engine temperature trip setting level after the Safety On timer has expired, a shutdown will occur. Alarm Shutdown High Engine Temperature will be displayed.
Alarm
Shutdown High temperature
OVERSPEED, if the engine speed exceeds the pre-set trip a shutdown is initiated. Alarm Shutdown Overspeed will be displayed. Overspeed is not delayed, it is an immediate shutdown.
Alarm
Shutdown Overspeed
NOTE:-During the start-up sequence the overspeed trip logic can be configured to allow an extra trip level margin. This is used to prevent nuisance tripping on start-up - Refer to the 5xxx series configuration software manual under heading ‘Overspeed Overshoot’ for details.
UNDERSPEED, if the engine speed falls below the pre-set trip after the Safety On timer has expired, a shutdown is initiated. Alarm Shutdown Underspeed will be displayed.
Alarm
Shutdown Underspeed
GENERATOR HIGH FREQUENCY if the module detects a generator output frequency in excess of the pre-set trip a shutdown is initiated. Alarm Shutdown High Frequency will be displayed, it is an immediate shutdown.
Alarm
Shutdown Over frequency
GENERATOR LOW FREQUENCY, if the module detects a generator output frequency below the pre-set trip after the Safety On timer has expired, a shutdown is initiated. Alarm Shutdown Low Frequency will be displayed.
Alarm
Shutdown Under frequency
GENERATOR HIGH VOLTAGE if the module detects a generator output voltage in excess of the pre-set trip a shutdown is initiated. Alarm Shutdown High Volts will be displayed, it is an immediate shutdown.
Alarm
Shutdown AC Overvolts
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 17
GENERATOR LOW VOLTAGE if the module detects a generator output voltage below the below the pre-set trip after the Safety On timer has expired, a shutdown is initiated. Alarm Shutdown Low Volts will be displayed.
Alarm
Shutdown AC Undervolts
OIL PRESSURE SENDER OPEN CIRCUIT, if the module detects a loss of signal from the oil pressure sender (open circuit) a shutdown is initiated. Alarm Shutdown Sender Fault will be displayed. Sender failure is not delayed, it is an immediate shutdown.
Alarm
Shutdown Oil pressure
sender fault
AUXILIARY INPUTS, if an auxiliary input has been configured as a shutdown the appropriate message will be displayed as configured by the user.
Alarm
Shutdown Bearing temp high
LOSS OF SPEED SIGNAL, if the speed sensing signal is lost during cranking, a shutdown is initiated. Alarm Shutdown Loss Of Speed Signal will be displayed.
Alarm
Shutdown Loss of speed
signal
NOTE:- This will only occur if the speed sensing signal is lost during cranking or during the safety on timer. If the signal is lost during normal operation the Generator will shutdown with an Under-speed alarm.
CAN DATA FAIL If the module is configured for CAN operation and does not detect data on the engine Can datalink, a shutdown will occur and ‘Can data fail’ is shown on the module’s display.
Alarm
Shutdown Can data fail
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
18 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
CAN ECU FAIL If the module is configured for CAN instruments and receives a “fail” message from the engine control unit, the engine is shutdown and ‘Can ECU fail” is shown on the module’s display.
Example
Alarm
The display will alternate between the text display and the manufacturers error codes
Alarm
Can ECU fail Fuel pressure low
Can ECU fail SPNnnnnnnn FMInnnnnnn
NOTE:- If the CAN message is a manufacturers specific code, it may not be displayed as text. If this is the case the display will show the generic manufacturers code only, which must be cross­referenced with the engine manufacturers literature. Please contact the engine manufacturer for further assistance.
Example
Alarm
Can ECU fail SPNnnnnn
FMInnnn
4.5 HIGH CURRENT SHUTDOWN ALARM
GENERATOR HIGH CURRENT, if the module detects a generator output current in excess of the pre-set trip a
warning is initiated. This warning will continue for a period of time depending upon the level of overload that the generator is subjected to, and the configuration setting for Generator High Current in the 5xxx series configuration software.
Alarm
Shutdown High current trip
For instance the factory default settings for Generator High Current allow for a loading of the generator to 110% for one hour. That is to say if the generator load level exceeds the trip point by 10%, a warning alarm will occur while the overload condition exists. If the load level does not drop to normal levels within one hour, the set is stopped, the 5320 module displaying either shutdown alarm or electrical trip alarm depending upon module configuration.
NOTE:- Higher overload levels will result in a faster acting shutdown condition. For instance with the factory default configuration, an overload level twice that of the trip level ( typically 200%) will result in a Generator High Current shutdown condition after 36 seconds. For details of the relationship between the overload and the shutdown time, please see the Appendix section of this manual.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 19
4.6 ELECTRICAL TRIPS
Electrical trips are latching and stop the Generator but in a controlled manner. On initiation of the electrical trip condition the module will de-energise the ‘Close Generator’ Output to remove the load from the generator. Once this has occurred the module will start the Cooling timer and allow the engine to cool off-load before shutting down the engine. The alarm must be accepted and cleared, and the fault removed to reset the module.
AUXILIARY INPUTS, if an auxiliary input has been configured as an electrical trip the appropriate message will be displayed as configured by the user.
Example
Alarm
Electrical trip
Phase rotation
GENERATOR HIGH CURRENT. If the module detects a generator output current in excess of the pre-set trip a warning is initiated. If this high current condition continues for an excess period of time, then the alarm is escalated to either a shutdown or electrical trip condition (depending upon module configuration). For further details of the high current alarm, please see High Current Shutdown Alarm.
Alarm
Electrical trip
High current
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
20 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
5 DESCRIPTION OF CONTROLS
The following section details the function and meaning of the various controls on the module.
Scroll Down Next page Configurable LEDs
Deep Sea Electro nics
Model 5 220
O
I
+
AUTO
i
Warming 10s L-N 240V 0A 50Hz L-L 415V 0kW
RUNNING IN AUTO
Stop Manual Test Auto Mute/Lamp
Test
Start
FIG 2A
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 21
Deep Sea Electro nics
Model 5 220
O
I
+
AUTO
i
Warming 10s L-N 240V 0A 50Hz L-L 415V 0kW
RUNNING IN AUTO
Mains Indication LED. Lit when The Mains Is
Healthy
Close Mains Output LED. On When The
Mains Is Required To
Be On Load
Close Generator
Output LED. On When
The Generator Is
Required To Be On
Load
Generator available LED. On When The
Generator Is Available
For Loading.
NOTE:- “Generator on load” and “Mains on Load” LEDs have two modes of operation depending
upon the configuration of the controllers digital inputs.
1) Digital input configured for “Generator closed auxiliary” – The LED will be lit when the generator
closed auxiliary input is active – The LED shows the state of the auxiliary contact.
2) There is NO input configured for “Generator closed auxiliary” (factory default setting) – The LED will
be lit when the 5320 gives the loading signal to the generator – The LED shows the state of the 5320’s loading request.
3) Digital input configured for “Mains closed auxiliary” – The LED will be lit when the mains closed
auxiliary input is active – The LED shows the state of the auxiliary contact.
4) There is NO input configured for “Mains closed auxiliary” (factory default setting) – The LED will be
lit when the 5320 gives the loading signal to the mains – The LED shows the state of the 5320’s loading request.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
22 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
5.1 TYPICAL LCD DISPLAY SCREENS
5.1.1 TYPICAL STATUS DISPLAY
Waiting in auto
Indicates that the module is in Automatic, and that the mains is on load (closed). The unit will respond to either a mains failure or an active remote start.
Mains on load
Starting in auto 10s
Indicates that the module is in automatic and that a start sequence has been initiated, either by a mains failure. The module is attempting to crank the generator.
Mains on load Cranking attempt 1
Running in auto
Indicates that the module is in Automatic, and that the generator is running on load. This default screen also indicates the average line to neutral voltage, highest of the 3 phase currents, generator frequency, average line to line voltage and total kilo Watts.
Generator on load L-N 230V 240A 50Hz L-L 400V 133kW
5.1.2 TYPICAL INSTRUMENT DISPLAY
Coolant temperature
The display of coolant temperature in both degrees centigrade and Fahrenheit.
60 ºC 140 ºF
Oil pressure
The display of engine oil pressure in Bar, Pounds Per Square Inch and kilo Pascal.
6 Bar 87 PSI 600 kPa
Generator Amps
The display of all three generator line currents.
L1 L2 L3
238 241 241
5.1.3 TYPICAL ALARM DISPLAY
Alarm
The module is warning that the engine oil pressure has fallen below a pre set level. The generator is not shutdown.
Warning Low oil pressure
Alarm
The oil pressure has fallen below a second pre set value and has shutdown the generator.
Shutdown Low oil pressure
Alarm
The module is warning that the battery volts is below a pre set value.
Warning Low battery Volts
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 23
5.1.4 TYPICAL EVENT DISPLAY
Event log 21:15:00
On the 10
th
September 2005 at 21:15 the unit detected that the oil pressure was below the pre-set trip level, and has shutdown the generator.
10th September 2005 Low oil pressure
Shutdown
Event log 20:10:00
On the 8
th
September 2005 at 20:10. The emergency stop button
was pressed and the generator was shutdown.
8th September 2005 Emergency stop
Shutdown
Event log 08:46:00
On the 7
th
September 2005 at 08:46 the unit detected that the generator out put volts exceeded pre-set trip level, and has shutdown the generator.
7th September 2005 Over Volts
Shutdown
5.2 VIEWING THE INSTRUMENTS
It is possible to manually scroll to display the different pages of information by repeatedly operating the next page
i
button.
Page order:-
Status display
Instrument display
Alarms display
Event log
It is possible to manually scroll to display the different instruments by repeatedly operating the next page button
. Once selected the instrument will remain on the LCD display until the user selects a different
instrument or after a period of inactivity for the duration of the configurable Page Timer, the module will revert to the default display.
Alternatively, to autoscroll through all instruments on the currently selected page, press and hold the scroll button.
To disable autoscroll, press and hold the scroll
button, or select another page with the page select i button.
When autoscroll is disabled, the display will automatically return to the Status/Alarms page if no buttons are pressed for the duration of the configurable Page Timer.
If an alarm becomes active while viewing instruments, the Status/Alarms page will be automatically displayed to draw the operator’s attention to the alarm condition.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
24 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
5.2.1 INSTRUMENT PAGE CONTENT
Engine speed
Oil Pressure
Coolant temperature
Engine Hours Run
DC Battery Voltage
Charge alternator voltage
Modem status (GSM)
Generator AC Voltage Line-Neutral
Generator AC Voltage Line-Line
Generator Line Current
(Displays load current when CTs are located in the load feed, and the module is suitably configured). (Displays mains load when CTs are located in the load feed, and the module is suitably configured).
Generator Output
Number of starts
Fuel level (%)
Mains (Utility) AC Voltage Line-Neutral
Mains (Utility) AC Voltage Line-Line
Mains (Utility) Frequency (Hz)
If enhanced instrumentation is selected, the following instrumentation will become available, if supported by the engine manufacturer.
Engine oil temperature
Inlet manifold temperature
Coolant pressure
Fuel pressure
Fuel consumption
Total fuel used
Turbo pressure
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 25
5.2.2 MANUALLY SELECTING AN INSTRUMENT
Default display
Running in auto
Generator on load L-N 230V 240A 50Hz
L-L 400V 133kW
Pressing the DOWN button the LCD will then show Engine speed
Engine speed
1500 RPM 50 Hz
Pressing the DOWN button the LCD will then show Oil pressure
Oil pressure
6 Bar 87 PSI 600 KPa
Pressing the
button again will scroll through each individual instrument eventually returning to the original
instrument displayed.
NOTE:-Once selected the instrument will remain on the LCD display until the user selects a different instrument or after a period of inactivity for the duration of the configurable Page Timer, the module will revert to the initial display.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
26 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
5.2.3 GSM MODEM STATUS
When configured and connected to a GSM Modem for cellular network communications, the GSM MODEM STATUS screen shows the following information.
Modem Status
The modem is reset by the 5300 series controller.
Resetting modem
Modem Status
Modem initialising strings are sent to the modem (as set in the Edit Config | Comms tab of the configuration software.
Initialising modem…
Modem Status
The modem has been initialised and is ready to answer.
Ready to answer
If the module does not detect that the modem is operating correctly, this procedure begins again from Resetting modem and will continue to repeat until the modem operation is detected correctly.
Modem Status
The modem has been initialised and is ready to answer. OK shows The SIM card is inserted but there is no signal
Ready to answer OK
Modem Status
The modem has been initialised and is ready to answer. The SIM card is inserted, the signal is received full strength and the operator name is shown.
NOTE:- Operator name is not available in all GSM areas.
Ready to answer OK
ORANGE UK
Modem Status
The modem has been initialised and is ready to answer. The SIM card is inserted, the signal is received but is low and the operator name is shown.
NOTE:- Operator name is not available in all GSM areas.
Ready to answer OK
ORANGE UK
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 27
5.2.4 CAN ERROR MESSAGES
On CAN enabled 53xx controllers connected to a suitable CAN ECU, alarm status messages are transmitted to the 53xx controller and displayed on the alarms page.
Alarm
Here the ECU code is interpreted by the module, which displays the warning as text. An error is like a warning, and does not shutdown the generator. The display will alternate between the text display and the manufacturers error codes
Alarm
CAN ECU error Exhaust hi temp
CAN ECU error SPNnnnnn FMInnnnn
Alarm
A CAN ECU fail is a shutdown and the module stops the generator. The display will alternate between the text display and the manufacturers error codes
Alarm
CAN ECU fail Fuel pressure low
CAN ECU fail SPNnnnnn FMInnnnn
Alarm
Where the module does not recognise the ECU error / fail code the SPN and FMI codes are displayed. These codes then have to be cross referenced with engine manufactures literature to determine the exact problem.
CAN ECU error SPNnnnnn
FMInnnnn
NOTE:- For details on these code meanings, refer to the ECU instructions provided by the engine
manufacturer, or contact the engine manufacturer for further assistance.
NOTE:- For further details on connection to electronic engines please refer to the CAN and DSE
wiring manual.
5.3 VIEWING THE EVENT LOG
The 53xx modules maintains a log of the last 30 shutdown alarms and mains fail/returns to enable the operator or engineer to view the past alarms history. Only shutdown and electrical trip alarms are logged; warning alarms are not logged. Once the log is full (30 events, any subsequent shutdown alarms or mains fail/returns will overwrite the oldest entry in the log. Hence the log will always contain the 30 most recent shutdown alarms. The alarm is logged, along with the date and time of the event in the format shown in this example.
Event log 21:15:00
10th September 2005 Low oil pressure Shutdown
To view the event log, repeatedly press the next page button
i
the LCD screen displays Event log.
Press down
to view the next most recent shutdown alarm:
Continuing to press down
will cycle through the past alarms until all 15 logged alarms have been viewed,
after which the most recent alarm will again be showed and the cycle will begin again. To exit the event log and return to viewing the instruments, press the next page
i
button.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
28 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
5.4 USER CONFIGURABLE INDICATORS
These LEDs can be configured by the user to indicate any one of 100+ different functions based around the following:-
Indications - Monitoring of a digital input and indicating associated functioning user’s equipment - Such as Battery Charger On or Louves Open, etc.
WARNINGS And SHUTDOWNS - Specific indication of a particular warning or shutdown condition, backed up by LCD indication - Such as Low Oil Pressure Shutdown, Low Coolant level, etc.
Status Indications - Indication of specific functions or sequences derived from the modules operating state - Such as Safety On, Pre-heating, Panel Locked, Generator Available, etc.
5.5 CONTROLS
Stop / Reset
This button places the module into its Stop/reset mode. This will clear any alarm conditions for which the triggering criteria have been removed. If the engine is running and this position is selected, the module will automatically instruct the changeover device to un-load the generator (‘Close Generator becomes inactive (if used)). The fuel supply will be removed and engine will be brought to a standstill. Should a remote start signal be present, or a mains fail occurs, while operating in this mode, a remote start will not
occur. Manual This mode is used to allow manual control of the generator functions. Once in Manual mode the module will respond to the start (I) button and start the engine and run off load. If the engine is running off-load in the Manual mode and a remote start signal becomes present, or the mains fails, the module will automatically instruct the changeover device to place the generator on load (‘Close Generator’) becomes active (if used)). Should the remote start signal then be removed, or the mains returns, the generator will remain on load until either the ‘STOP/RESET’ or ‘AUTO’ positions is selected. Auto This button places the module into its ‘Automatic’ mode. This mode allows the module to control the function of the generator automatically. The module will monitor the remote start input and the mains supply. If the remote start input is active, or the mains fails, the set will be automatically started and placed on load (‘Close Generator’ becomes active if used). If the starting signal is removed, or the mains returns, the module will automatically transfer the load from the generator and shut the set down observing the stop delay timer and cooling timer as necessary. The module will then await the next start event. For further details please see the more detailed description of ‘Auto Operation’ earlier in this manual. Test This button places the module into its ‘Test’ mode. This mode allows the operator to perform an ‘on
load’ test of the system. Once in Test mode the module will respond to the start
I
button and start the engine, and run on load (‘Close Generator’ becomes active if used). The generator will continue to run on load until Auto mode is selected. Then, If the starting signal is removed and the mains is healthy, the module will automatically transfer the load from the generator and shut the set down observing the stop delay timer and cooling timer as necessary. The module will then await the next start event. For further details please see the more detailed description of ‘Test Operation’ earlier in this manual.
Start
This button is only active in MANUAL
or TEST mode. Pressing this button in manual or test
mode will start the engine and run off load (manual) or on load (test). Pressing this button in STOP/RESET mode will turn on the CAN engine ECU (when correctly configured and fitted to a compatible engine ECU)
I
Mute / Lamp Test
This button silences the audible alarm if it is sounding and illuminates all of the LEDs. If there is no audible alarm this button will only illuminate all the LEDs. When correctly configured and fitted to a compatible engine ECU, pressing this button in
STOP/RESET mode after pressing the START
I
button (to power the ECU) will cancel any
“passive” alarms on the engine ECU.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 29
6 FRONT PANEL CONFIGURATION
This configuration mode allows the operator limited customising of the way the module operates.
Operation Detail
To enter the ‘configuration mode’ press both the INFO and
STOP buttons together.
+
6.1.1 ENTERING THE CONFIGURATION EDITOR PIN NUMBER
The configuration editor contains two sections.
Main configuration editor (for ‘site adjustable’ or ‘commissioning’ parameters)
Application editor (to allow installation engineers to make application changes).
The ‘Application Editor’ is designed to allow the module to be configured for different applications without needing to re-configure the module settings. This makes it particularly suitable for applications where the generator would be used in a number of different roles, specifically in Rental or mobile type applications.
If the module PIN number has been set, the PIN number request is then shown. The configuration cannot be viewed or changed until the PIN number is correctly entered.
Enter either the ‘main’ PIN or the application PIN. If no PIN has been set, then skip to the next section.
NOTE:- The ‘Application Editor’ must be enabled first in order to make it accessible from the module’s fascia. This is done by setting a PIN (number) for the module’s main front panel editor, using the 5xxx for Windows™ PC configuration software.
Deep Sea Electronics
Model 5220
O
I
+
AUTO
i
Warming 10s L-N 240V 0A 50Hz L-L 415V 0kW
RUNNING INAUTO
- button + button
9 button
The configuration editor contains two sections.
Main configuration editor (for ‘site adjustable’ or ‘commissioning’ parameters)
Application editor (to allow installation engineers to make application changes).
The ‘Application Editor’ is designed to allow the module to be configured for different applications without needing to re-configure the module settings. This makes it particularly suitable for applications where the generator would be used in a number of different roles, specifically in Rental or mobile type applications.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
30 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
If the module PIN number has been set, the PIN number request is then shown. The configuration cannot be viewed or changed until the PIN number is correctly entered.
Enter either the ‘main’ PIN or the application PIN. If no PIN has been set, then skip to the next section.
NOTE:- The ‘Application Editor’ must be enabled first in order to make it accessible from the module’s fascia. This is done by setting a PIN (number) for the module’s main front panel editor, using the 5xxx for Windows™ PC configuration software.
Enter pin
The first * is flashing. Press + or – buttons to adjust it to the correct value for the first digit of the PIN number. Press
9 when the first digit is correctly entered.
The entered digit will turn back to a * to maintain security.
****
Enter pin
The second * is now flashing. Press + or – buttons to adjust it to the correct value for the second digit of the PIN number. Press
9 when the second digit is correctly entered.
The entered digit will turn back to a * to maintain security.
****
Enter pin
The third * is now flashing. Press + or – buttons to adjust it to the correct value for the third digit of the PIN number. Press
9 when the third digit is correctly entered.
The entered digit will turn back to a * to maintain security.
****
Enter pin
The fourth * is now flashing. Press + or – buttons to adjust it to the correct value for the fourth digit of the PIN number. Press
9 when the fourth digit is correctly entered.
****
NOTE:- When 9 is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct, the editor is automatically exited. To retry you must re-enter the editor as described above.
Oil pressure pre-alarm
If the Configuration PIN has been entered successfully (or the PIN number has not been set in the module) the first configurable parameter is displayed :
2 Bar 30 PSI 200 kPa
NOTE:- To exit the front panel configuration editor at any time, press the Stop/Reset button. Ensure you have saved any changes you have made by pressing the 9 button first.
NOTE:- When the editor is visible, it is automatically exited after 5 minutes of inactivity to ensure security.
NOTE:- If the Application Menu PIN is entered, then only the Application Menu is displayed. If the Full Configuration PIN is entered, the entire configuration menu is displayed including the Application Menu.
NOTE:- The PIN number is automatically reset when the editor is exited (manually or automatically) to ensure security.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 31
6.2 EDITING A VALUE
Oil pressure pre-alarm
Press the Stop/Reset and Info i buttons simultaneously. If the module PIN number has been set, the PIN number request is then shown.
The configuration cannot be viewed or changed until the PIN number is correctly entered. (see the section ACCESSING THE FRONT PANEL CONFIGURATION EDITOR)
Press the + button until the desired page is shown. EG oil pressure pre-alarm.
2 Bar 30 PSI 200 kPa
Oil pressure pre-alarm
To edit the oil pressure pre-alarm, press the 9 button, the pressure will start to flash. Pressing the
+ or buttons will adjust the parameter to the desired value.
In this example, the 30 PSI will be adjusted, and the bar/kPA units will automatically show their respective values.
2 Bar 30 PSI 200 kPa
Oil pressure pre-alarm
Press the 9 button to ‘save’ the value. The value will stop flashing to confirm
that it has been saved.
3 Bar 45 PSI 300 kPa
Oil pressure shutdown
To select another value to edit, press the + button.
1 Bar 15 PSI 100 kPa
NOTE:- To exit the front panel configuration editor at any time, press the Stop/Reset button.
Ensure you have saved any changes y ou have made by pressing the 9 button first.
Continuing to press the + or – buttons will cycle through the adjustable parameters in the order shown overleaf:
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
32 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
6.2.1 LIST OF ADJUSTABLE PARAMETERS IN ‘MAIN CONFIGURATION EDITOR’
Sectio
n Param
eter
Di
splay shows
Values
Input settings
Low Oil Pressure warning
Oil pressure pre-alarm
0-4bar (1.17bar)
Low Oil Pressure shutdown
Oil pressure shutdown
0-4bar (1.03bar)
High Temperature warning
Coolant temp pre-alarm
80-140°C (110°C)
High Temperature shutdown
Coolant temp shutdown
80-140°C (120°C)
Low Coolant Temperature
Low Coolant Temperature
65-136°C (65°C)
Timers
Mains transient delay
Mains transient delay
0-10s (2s)
Generator transient delay
Gen transient delay
0 -10s (0s)
Start delay
Start delay
0 -60m (5s)
Return delay
Return delay
0 -60m (30s)
Preheat
Preheat
0 -60m (5s)
Crank attempt
Cranking time
0 -60s (10s)
Crank rest
Crank rest
0-60s (10s)
Safety delay
Safety on
0-30s (10s)
Overspeed overshoot
Overspeed overshoot
0-10s (0s)
Warming up
Warm up
0-60m (0s)
Transfer delay
Transfer delay
0-10m (1s)
Cooling run
Cooling
0-60m (60s)
Fail to stop delay
Fail to stop
0-30s (30s)
Low battery volts delay
Battery low delay
0-10m (30s)
High battery volts delay
Battery high delay
0-10m (30s)
Mains (utility)
Mains Low Voltage
Mains undervolt trip
50-360V ph-N (184V)
Mains High Voltage
Mains overvolt trip
50-360V ph-N (276V)
Mains Low Frequency
Mains low frequency trip
0 -75Hz (45Hz)
Mains High Frequency
Mains high frequency trip
0 -75Hz (55Hz)
Generator
Generator Under voltage shutdown
Gen low voltage shutdown
50-360V ph-N (184V)
Generator Under voltage prealarm
Gen low voltage pre-alarm
50-360V ph-N (196V)
Generator Over voltage prealarm
Gen high voltage pre-alarm
50-360V ph-N (253V)
Generator Over voltage shutdown
Gen high voltage shutdown
50-360V ph-N (265V)
Generator Under frequency shutdown
Gen low frequency shutdown
0 -75Hz (40Hz)
Generator Under frequency prealarm
Gen low frequency pre-alarm
0 -75Hz (42Hz)
Generator Over frequency prealarm
Gen high frequency pre-alarm
0 -75Hz (55Hz)
Generator Over frequency shutdown
Gen high frequency shutdown
0 -75Hz (57Hz)
Generator delayed overcurrent
Delayed high current
50-120% (100%)
Engine
Underspeed (RPM) shutdown
Underspeed shutdown
0-6000RPM (1270)
Underspeed (RPM) warning
Underspeed pre-alarm
0-6000RPM (1350)
Overspeed (RPM) warning
Overspeed pre-alarm
0-6000RPM (1650)
Overspeed (RPM) shutdown
Overspeed shutdown
0-6000RPM (1710)
Overspeed overshoot %
Overspeed overshoot percent
0-10 (0%)
Low DC Voltage
Battery low warning
0-24V (8V)
High DC Voltage
Battery high warning
0-24V (33V)
Charge Alternator Failure
Charge fail warning
0-24V (6V)
Display
Language
Language
ENGLISH
, OTHER
(see note below)
Application
Engine speed selection
Alternative Frequency
Disable, Enable
Volts selection
Alternative Voltage
Disable, Enable
Wiring topography
AC System
3 phase 4 wire
Single phase, 2 wire 3 phase, 3 wire 2 phase 3 wire (L1 & L2) 2 ph
ase 3
wire (L1 & L3)
Full load current rating
Generator Full Load
5A - 6000A (500A)
Droop
Disable, Enable
Droop %
0% - 5%
LCD Contrast
Contrast
|
Date/Time
Date and Time
dd mmm yyyy hh:m m
NOTE:- Display language selection via the modules front panel configuration editor is between English and a PC configurable language. This ‘other’ language is configurable using the 5xxx PC configuration software in conjunction with the P810 interface.
NOTE:- Droop percent is only applicable to CAN controlled engines when CAN is enabled in the 5300 series controller.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 33
6.2.2 LIST OF ADJUSTABLE PARAMETERS IN ‘APPLICATION EDITOR’
Sectio
n Param
eter
Di
splay shows
Values
Application
Engine speed selection
Alternative Frequency
Disable, Enable
Volts selection
Alternative Voltage
Disable, Enable
Wiring topography
AC System
3 phase 4 wire
Single phase, 2 wire 3 phase, 3 wire 2 phase 3 wire (L1 & L2) 2 ph
ase 3
wire (L1 & L3)
Full load current rating
Generator Full Load
5A - 6000A (500A)
Droop
Disable, Enable
Droop %
0% - 5%
LCD Contrast
Contrast
|
Date/Time
Date and Time
dd mmm yyyy hh:m m
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
34 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
6.2.3 EDITING THE CURRENT DATE AND TIME
The date and time can be set either using the 5xxx series configuration or the front panel configuration editer.
NOTE:- The 5320 controller maintains the current date and time so long as it is connected to a DC supply within the operating range. Disconnection of the supply will result in the date and time being frozen until the module’s power is reapplied. When this occurs, the date and time will resume operation from the time the power was disconnected. If this occurs you can use the front panel configuration editor to correct the date and time or reset it using the 5xxx series configuration software.
NOTE:- The calendar is used by the 5320’s run scheduler and the event log.
Date and time
Press the Stop/Reset and Info i buttons simultaneously. If the module PIN number has been set, the PIN number request is then shown.
The configuration cannot be viewed or changed until the PIN number is correctly entered. (see the section ACCESSING THE FRONT PANEL CONFIGURATION EDITOR)
Press the + button until the desired page is shown. Date and time
19 Sep 2005 10:00
Date and time
To edit the Date and time, press the 9 button, the minutes will start to flash. Pressing the
+ or buttons will adjust the minutes to the desired value.
19 Sep 2005 10:00
Date and time
Press the button to ‘save’ the value, and select the hours for adjustment.
The hours will start to flash. Pressing the
+ or buttons will adjust the hours to the desired value.
19 Sep 2005 10:00
Date and time
Press the button to ‘save’ the value, and select the day for adjustment.
The day will start to flash. Pressing the
+ or buttons will adjust the day to the desired value.
19 Sep 2005 10:00
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 35
Date and time
Press the button to ‘save’ the value, and select the month for adjustment.
The month will start to flash. Pressing the
+ or buttons will adjust the month to the desired value.
19 Sep 2005 10:00
Date and time
Press the button to ‘save’ the value, and select the year for adjustment.
The year will start to flash. Pressing the
+ or buttons will adjust the year to the desired value.
19 Sep 2005 10:00
Date and time
Press the 9 button to ‘save’ the values.
19 Sep 2005 10:00
NOTE:- To exit the front panel configuration editor at any time, press the Stop/Reset button.
Ensure you have saved any changes y ou have made by pressing the 9 button first.
Continuing to press the + or – buttons will cycle through the adjustable parameters in the order shown overleaf:
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
36 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
7 INSTALLATION INSTRUCTIONS
The model DSE 5320 Module has been designed for front panel mounting. Fixing is by 4 clips for easy assembly.
7.1 PANEL CUT-OUT
220.00mm (8.7”)
FIG 3
Maximum panel thickness – 8mm (0.3”) In conditions of excessive vibration the module should be mounted on suitable anti-vibration mountings.
7.2 COOLING
The module has been designed to operate over a wide temperature range -30 to +70º C. Allowances should be made for the temperature rise within the control panel enclosure. Care should be taken
NOT to mount possible
heat sources near the module unless adequate ventilation is provided. The relative humidity inside the control panel enclosure should not exceed
95%.
7.3 UNIT DIMENSIONS
Panel cutout 220mm x 160mm ( 8.7” x 6.3”)
FIG 4
160.00mm (6.3”)
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 37
7.4 FRONT PANEL LAYOUT
Deep Sea Electronics
Model 5220
O
I
+
AUTO
i
Warming 10s L-N 240V 0A 50Hz L-L 415V 0kW
RUNNING IN AUTO
FIG 5
7.5 REAR PANEL LAYOUT
FIG 6
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
38 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
8 ELECTRICAL CONNECTIONS
Connections to the Module are via plug and sockets.
8.1 CONNECTION DETAILS
The following describes the connections and recommended cable sizes to the 8 plugs and sockets on the rear of the Module. See rear panel layout
FIG 6.
8.1.1 PLUG “A” 8 WAY
PIN
No
DESCRIPTION CABLE
SIZE
NOTES
1 DC Plant Supply Input
(Negative)
2.5mm²
AWG 13
2 DC Plant Supply Input
(Positive)
2.5mm²
AWG 13
(Recommended Maximum Fuse 21A)
3 Emergency Stop Input 2.5mm²
AWG 13
Plant Supply Positive. Also supplies fuel & start outputs. (Recommended Maximum Fuse 32A)
4 Fuel relay Output 2.5mm²
AWG 13
Plant Supply Positive from pin 3. 16 Amp rated.
5 Start relay Output 2.5mm²
AWG 13
Plant Supply Positive from pin 3. 16 Amp rated.
6 Auxiliary Output relay 1 1.0mm²
AWG 18
Plant Supply Positive. 5 Amp rated.
7 Auxiliary Output relay 2 1.0mm²
AWG 18
Plant Supply Positive. 5 Amp rated.
8 Auxiliary Output relay 3 1.0mm²
AWG 18
Plant Supply Positive. 5 Amp rated.
NOTE:- When the module is configured for CAN operation, FUEL, START and AUXILIARY output
requirements may be different. Refer to CAN and DSE Wiring for further information.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 39
8.1.2 PLUG “B” 11 WAY
PIN
No
DESCRIPTION CABLE
SIZE
NOTES
9 Charge fail / excite 2.5mm²
AWG 13
Do not connect to ground (battery –ve)
10 Auxiliary input 1 0.5mm²
AWG 20
Switch to Negative
11 Auxiliary input 2 0.5mm²
AWG 20
Switch to Negative
12 Auxiliary input 3 0.5mm²
AWG 20
Switch to Negative
13 Auxiliary input 4 0.5mm²
AWG 20
Switch to Negative
14 Auxiliary input 5 0.5mm²
AWG 20
Switch to Negative
15 Auxiliary input 6 0.5mm²
AWG 20
Switch to Negative
16 Functional Earth 2.5mm²
AWG 13
Connect to a good clean earth point
17 Magnetic pickup Positiv e 0.5mm²
AWG 20
Connect to Magnetic Pickup device
18 Magnetic pickup Negativ e 0.5mm²
AWG 20
Connect to Magnetic Pickup device
19 Not connected -
NOTE:- Ensure magnetic pickup screen is connected to ground at one end only.
NOTE:- When the module is configured for CAN operation, terminals 17 & 18 should be left
unconnected. Engine speed is transmitted to the 53xx controller on the CAN link.
NOTE:- When the module is configured for CAN operation, FUEL, START and AUXILIARY output
requirements may be different. Refer to CAN and DSE Wiring for further information.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
40 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
8.1.3 PLUG “C” 3 WAY
PIN
No
DESCRIPTION CABLE
SIZE
NOTES
20 CAN port Common 0.5mm²
AWG 20
Use only 120Ω CAN approved cable
21 CAN port H 0.5mm²
AWG 20
Use only 120Ω CAN approved cable
22 CAN port L 0.5mm²
AWG 20
Use only 120Ω CAN approved cable
NOTE: - Screened 120Ω impedance cable specified for use with CAN must be used. DSE stock and supply Belden cable 9841 which is a high quality 120Ω impedance cable suitable for CAN use (DSE part number 016-030)
8.1.4 PLUG “D” 4 WAY
PIN
No
DESCRIPTION CABLE
SIZE
NOTES
23 RS485 port Common 0.5mm²
AWG 20
Use only 120Ω RS485 approved cable
24 RS485 port B 0.5mm²
AWG 20
Use only 120Ω RS485 approved cable
25 RS485 port A 0.5mm²
AWG 20
Use only 120Ω RS485 approved cable
26 Not connected -
NOTE: - Screened 120Ω impedance cable specified for use with RS485 must be used. DSE stock and supply Belden cable 9841 which is a high quality 120Ω impedance cable suitable for RS485 use (DSE part number 016-030)
8.1.5 PLUG “E” 8 WAY
PIN
No
DESCRIPTION CABLE
SIZE
NOTES
27 Mains loading relay 1.0mm²
AWG 18
Connect to mains contactor coil
28 Mains loading relay 1.0mm²
AWG 18
Connect to mains contactor feed supply
29 Generator loading relay 1.0mm²
AWG 18
Connect to generator contactor coil
30 Generator loading relay 1.0mm²
AWG 18
Connect to generator contactor feed supply
31 Mains (utility) L1 voltage
monitoring input
1.0mm²
AWG 18
Connect to mains L1 (AC) (Recommend 2A fuse)
32 Mains (utility) L2 voltage
monitoring input
1.0mm²
AWG 18
Connect to mains L2 (AC) (Recommend 2A fuse)
33 Mains (utility) L3 voltage
monitoring input
1.0mm²
AWG 18
Connect to mains L3 (AC) (Recommend 2A fuse)
34 Mains (utility)Neutral input 1.0mm²
AWG 18
Connect to mains Neutral (AC)
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 41
8.1.6 PLUG “F” 4 WAY
PIN
No
DESCRIPTION CABLE
SIZE
NOTES
35 Generator L1 v oltage
monitoring input
1.0mm²
AWG 18
Connect to generator L1 output (AC) (Recommend 2A fuse)
36 Generator L2 v oltage
monitoring input
1.0mm²
AWG 18
Connect to generator L2 output (AC) (Recommend 2A fuse)
37 Generator L3 v oltage
monitoring input
1.0mm²
AWG 18
Connect to generator L3 output (AC) (Recommend 2A fuse)
38 Generator Neutral input 1.0mm²
AWG 18
Connect to generator Neutral terminal (AC)
8.1.7 PLUG “G” 5 WAY
PIN
No
DESCRIPTION CABLE
SIZE
NOTES
39 CT Secondary for L1 2.5mm²
AWG 13
Connect to secondary of L1 monitoring CT
40 CT Secondary for L2 2.5mm²
AWG 13
Connect to secondary of L2 monitoring CT
41 CT Secondary for L3 2.5mm²
AWG 13
Connect to secondary of L3 monitoring CT
42 CT secondary common 2.5mm²
AWG 13
Connect to secondary of all monitoring CT’s
43 Not connected -
8.1.8 PLUG “H” 4 WAY
PIN
No
DESCRIPTION CABLE
SIZE
NOTES
44 Oil Pressure Input 0.5mm²
AWG 20
Connect to Oil pressure sender
45 Coolant Temperature
Input
0.5mm²
AWG 20
Connect to Coolant Temperature sender
46 Fuel Level input 0.5mm²
AWG 20
Connect to Fuel Level sender
47 Sender Common Return 0.5mm²
AWG 20
Return feed for senders*.
NOTE*:- If using single terminal senders refer to connection diagram. If using earth return type senders connect return terminals to pin 47 and also connect pin 47 to earth. This is detailed in the Appendix section entitled “Sender wiring recommendations” elsewhere in this manual.
NOTE:- When the module is configured for CAN operation, terminals 44 & 45 should be left unconnected. Engine oil pressure and coolant temperature is transmitted to the 53xx controller on the CAN link.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
42 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
8.1.9 PC CONFIGURATION INTERFACE CONNECTOR
8-way connector allows connection to PC via the 810 configuration interface. Module can then be re-configured utilising the
5xxx series configuration
software.
8.1.10 EXPANSION OUTPUT CONNECTOR
The expansion connector allows connection to the 157 relay expansion module or to the 548 LED Remote annunciator module.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 43
8.2 CONNECTOR FUNCTION DETAILS
The following describes the functions of the 8 connectors on the rear of the module. See rear panel layout FIG 5.
8.2.1 PLUG “A” 8 WAY
PIN
No
DESCRIPTION
1 DC Supply System negative input. (Battery Negative). 2 DC Supply System positive input. (Battery Positive). 3 Emergency Stop input. Internally linked to Starter and Fuel outputs. If this input is not
connected to positive the module will be locked out, and if the engine is running it will shutdown immediately. The Positive Supply is also removed from Starter and Fuel outputs, therefore only a single pole Emergency Shutdown button is required.
4 Fuel Relay output. Plant Supply Positive from pin 3. Used to control the fuel solenoid or
engine fuel control system. 5 Starter Relay output. Plant Supply Positive from pin 3. Used to control the Starter Motor. 6 Auxiliary Relay output 1. Plant Supply Positive. Configurable output, see Calibration Manual
for options available. 7 Auxiliary Relay output 2. Plant Supply Positive. Configurable output, see Calibration Manual
for options available. 8 Auxiliary Relay output 3. Plant Supply Positive. Configurable output, see Calibration Manual
for options available.
8.2.2 PLUG “B” 11 WAY
PIN
No
DESCRIPTION
9 Charge Fail input / Excitation output. Supplies excitation to the Plant Battery Charging
Alternator, also an input for the Charge Fail detection circuitry.
10 Auxiliary input 1. This is a negative switched configurable input, see Calibration Manual for
options available. It is possible to configure the input to be a normally closed signal or a
normally open signal.
11 Auxiliary input 2. This is a negative switched configurable input, see Calibration Manual for
options available. It is possible to configure the input to be a normally closed signal or a
normally open signal.
12 Auxiliary input 3. This is a negative switched configurable input, see Calibration Manual for
options available. It is possible to configure the input to be a normally closed signal or a
normally open signal.
13 Auxiliary input 4. This is a negative switched configurable input, see Calibration Manual for
options available. It is possible to configure the input to be a normally closed signal or a
normally open signal.
14 Auxiliary input 5. This is a negative switched configurable input, see Calibration Manual for
options available. It is possible to configure the input to be a normally closed signal or a
normally open signal.
15 Auxiliary input 6. This is a negative switched configurable input, see Calibration Manual for
options available. It is possible to configure the input to be a normally closed signal or a
normally open signal.
16 Functional Earth - Ensure connection to a good clean earth point. 17 Magnetic Input Positiv e. An AC signal from the magnetic pickup Positive for speed sensing. 18 Magnetic Input Negativ e. An AC signal from the magnetic pickup Negative for speed
sensing.
19 Not connected
NOTE:- Ensure magnetic pickup screen is connected to ground at one end only.
NOTE:- When the module is configured for CAN operation, terminals 17 & 18 should be left
unconnected. Engine speed is transmitted to the 53xx controller on the CAN link.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
44 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
8.2.3 PLUG “C” 3 WAY
PIN
No
DESCRIPTION
20
CAN port Common. Do not connect this terminal to earth. Use only screened 120Ω cable approved specifically for use in CAN applications.
21
CAN port H. Use only screened 120Ω cable approved specifically for use in CAN applications.
22
CAN port L. Use only screened 120Ω cable approved specifically for use in CAN applications.
NOTE: - Screened 120Ω impedance cable specified for use with CAN must be used. DSE stock and supply Belden cable 9841 which is a high quality 120Ω impedance cable suitable for CAN use (DSE part number 016-030)
8.2.4 PLUG “D” 4 WAY
PIN
No
DESCRIPTION
23 RS485 port Common 24
RS485 port B. Use only screened 120Ω cable approved specifically for use in RS485 applications.
25
RS485 port A. Use only screened 120Ω cable approved specifically for use in RS485 applications.
26 Not used. Do not connect to this terminal.
NOTE: - Screened 120Ω impedance cable specified for use with RS485 must be used. DSE stock and supply Belden cable 9841 which is a high quality 120Ω impedance cable suitable for RS485 use (DSE part number 016-030)
8.2.5 PLUG “E” 8 WAY
PIN No DESCRIPTION
27 Mains loading relay, normally closed. Volts free contact to terminal 28. 28 Mains loading relay, normally closed. Volts free contact to terminal 27. 29 Generator loading relay, normally open. Volts free contact to terminal 30. 30 Generator loading relay, normally open. Volts free contact to terminal 29. 31 Mains L1 voltage monitoring input. Connect to mains L1 supply 32 Mains L2 voltage monitoring input. Connect to mains L2 supply. If using single phase AC system
do not connect to this terminal.
33 Mains L3 voltage monitoring input. Connect to mains L3 supply. If using single phase or two
phase AC system do not connect to this terminal.
34 Mains Neutral input. Connect to mains N supply. If using 3phase 3wire AC system, do not
connect to this terminal.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 45
8.2.6 PLUG “F” 4 WAY
PIN
No
DESCRIPTION
35 Generator L1 sensing input. Connect to alternator L1 output. 36 Generator L2 sensing input. Connect to alternator L2 output. If using single phase only do not
connect this terminal.
37 Generator L3 sensing input. Connect to alternator L3 output. If using single phase only do not
connect this terminal.
38 Generator N sensing input. Connect to alternator N output.
8.2.7 PLUG “G” 5 WAY
PIN No DESCRIPTION
39 Generator L1 current transformer connection. 40 Generator L2 current transformer connection. If single phase is used do not connect this pin. 41 Generator L3 current transformer connection. If single phase is used do not connect this pin. 42 Generator current transformer common connection and CT earth connection. 43 Not used. Do not connect to this terminal.
8.2.8 PLUG “H” 4 WAY
PIN
No
DESCRIPTION
44 Oil Pressure sensing input. Connect to resistive type oil pressure sender. Refer to connection
diagram for details.
45 Coolant Temperature sensing input. Connect to resistive type coolant temperature sender.
Refer to connection diagram for details.
46 Fuel Level sensing input. Connect to resistive type fuel level sender. Refer to connection
diagram for details.
47 Sender Common connection. Return feed from sender units - refer to connection diagram for
details.
NOTE:- When the module is configured for CAN operation, terminals 44 & 45 should be left unconnected. Engine oil pressure and coolant temperature is transmitted to the 53xx controller on the CAN link.
8.2.9 PURCHASING ADDITIONAL CONNECTOR PLUGS FROM DSE
If you require additional plugs from DSE, please contact our Sales department using the part numbers below.
5320 Terminal Connector Plug description DSE Part number
1-8 A BL08 8way 5.08mm spacing connector plug 007-125
9-19 B BL11 11way 5.08mm spacing connector plug 007-135 20-22 C BL03 3way 3.81mm spacing connector plug 007-409 23-26 D BL04 4way 3.81mm spacing connector plug 007-408 27-34 E BL08 8way 10.16mm spacing connector plug 007-410 35-38 F BL04 4way 10.16mm spacing connector plug 007-003 39-43 G BL05 5way 5.08mm spacing connector plug 007-329 44-47 H BL04 4way 5.08mm spacing connector plug 007-100
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
46 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
9 SPECIFICATION
DC Supply Continuous voltage rating :
8V to 35V
Cranking dip protection :
Able to survive 0V for 50mS, providing supply was at least 10V before dropout and supply recovers to 5V. This is achieved without the need for internal batteries
Charge Fail/ Excitation:
0V to 35V fixed power source 25W
Max. Standby Current:
375mA at 12V. 200mA at 24V.
Max. Sleep Mode Current: 86mA at 12V. 50mA at 24V
Max. Operating Current:
460mA at 12V. 245mA at 24V
Alternator Input Range:
5V - 277(ph-N) (+20%) 50Hz - 60Hz (Minimum 15V AC Ph-N)
Accuracy:
1% of full scale Average sensing
Supported topologies:
3 Phase 4wire Single phase 2 wire 3 phase 3 wire 2 Phase 3 wire L1 & L2 2 Phase 3 wire L1 & L3
Mains Input Range:
15V - 277(ph-N) (+20%) 50Hz - 60Hz
Accuracy:
1% of full scale Average sensing
Supported topologies:
3 Phase 4wire Single phase 2 wire 3 phase 3 wire 2 Phase 3 wire L1 & L2 2 Phase 3 wire L1 & L3
CT’s Burden:
0.5VA
Primary rating:
1A - 6000A (user selectable)
Secondary rating:
1A or 5A secondary (user selectable)
Accuracy of measurement:
1% of full load rating (when using 0.5% or better CTs with 5A secondary winding) Lower class CTs will reduce the overall accuracy of the reading.
Recommendations:
Class 1 required for instrumentation Protection class required if using for protection.
Magnetic Pickup Voltage range :
+/- 0.5V minimum (during cranking) to 70V Peak
Frequency range:
10,000 Hz (max)
Relay outputs Fuel:
16 Amp DC at supply voltage
Start:
16 Amp DC at supply voltage
Auxiliary outputs 1,2,3:
5 Amp DC at supply voltage
Dimensions Overall:
240mm x 172 mm x 57mm (9 ½“ x 6 ¾” x 2 ¼”)
Panel cut-out:
220mm x 160mm ( 8.7” x 6.3”) Max panel thickness 8mm ( 0.3”)
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 47
Electrical Safety /Electromagnetic Compatibility
BS EN 60950 Safety of information technology equipment, including electrical business equipment BS EN 61000-6-2 EMC Generic Emission Standard (Industrial) BS EN 61000-6-4 EMC Generic Emission Standard (Industrial)
Environmental BS EN 60068-2-1 Cold Temperature
-30°C BS EN 60068-2-2 Hot Temperature +70°C BS2011-2-1 Humidity 93% RH@40°C for 48 Hours BS EN 60068-2-6 Vibration
10 sweeps at 1 octave/minute in each of 3 major axes 5Hz to 8Hz @ +/-7.5mm constant displacement 8Hz to 500Hz @ 2gn constant acceleration
BS EN 60068-2-27 Shock 3 Half sine shocks in each of 3 major axes 15gn amplitude, 11mS duration
BS EN 60529 Degrees of protection provided by enclosures: IP55 (Front of module when module is installed into the control panel with the optional sealing
gasket). IP42 (front of module when module is installed into the control panel WITHOUT being sealed to the panel)
NEMA Rating (Approximate) 12 (Front of module when module is installed into the control panel with the optional sealing
gasket). 2 (front of module when module is installed into the control panel WITHOUT being sealed to the panel)
Product Certification
C
US
European CE approved.
UL approved
C-UL / CSA approved.
Russia and other CIS
countries approved
BS EN 2002/95/EC
Restriction of Hazardous
Substances
(RoHS)
BS EN 2002/96/EC
Waste Electrical and
Electronic Equipment (WEEE)
Relevant Company Certification
BS EN ISO 9001:2000
Applicable to Design,
marketing, assembly, service
and repair of electronic control
modules
In line with our policy of continual development, Deep Sea Electronics, reserve the right to change specification without notice.
10 COMMISSIONING
10.1.1 PRE-COMMISSIONING
Before the system is started, it is recommended that the following checks are made:-
10.1. The unit is adequately cooled and all the wiring to the module is of a standard and rating compatible with the system.
10.2. The unit
DC supply is fused and connected to the battery and that it is of the correct polarity.
10.3. The Emergency Stop input is wired to an external normally closed switch connected to
DC positive.
NOTE:- If Emergency Stop feature is not required link this input to the DC Positive. The module will
not operate unless either the Emergency Stop is fitted correctly OR Pin 3 is connected to DC positive.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
48 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
10.4. To check the start cycle operation take appropriate measures to prevent the engine from starting (disable the operation of the fuel solenoid). After a visual inspection to ensure it is safe to proceed, connect the battery supply. Select
“MANUAL”, the unit start sequence will commence.
10.5. The starter will engage and operate for the pre-set crank period. After the starter motor has attempted to start the engine for the pre-set number of attempts the
LCD will display ‘Failed to start. Select the
STOP/RESET position to reset the unit.
10.6. Restore the engine to operational status (reconnect the fuel solenoid), again select
“MANUAL”, this time the
engine should start and the starter motor should disengage automatically. If not then check that the engine is fully operational (fuel available, etc.) and that the fuel solenoid is operating. The engine should now run up to operating speed. If not, and an alarm is present, check the alarm condition for validity, then check input wiring. The engine should continue to run for an indefinite period. It will be possible at this time to view the engine and alternator parameters - refer to the ‘Description of Controls’ section of this manual.
10.7. Select
“AUTO” on the front panel, the engine will run for the pre-set cooling down period, then stop. The
generator should stay in the standby mode. If not check that there is not a signal present on the
Remote
start
input and that the mains (utility) supply is healthy and available.
10.8. Initiate an automatic start by supplying the remote start signal or failing the mains (utility) supply. The start sequence will commence and the engine will run up to operational speed. Once the generator is available a load transfer will take place, the Generator will accept the load. If not, check the wiring to the Generator Contactor Coil
(if used). Check the Warming timer has timed out.
10.9. Remove the remote start signal and/or ensure the mains (utility) supply is healthy, the return sequence will start. After the pre-set time period, the load will be removed from the generator. The generator will then run for the pre-set cooling down period, then shutdown into it’s standby mode.
10.10. Set the modules internal clock/calendar to ensure correct operation of the scheduler and event logging functions. For details of this procedure see section entitled
Front Panel Configuration – Editing the date and
time.
10.11. If despite repeated checking of the connections between the
5320 and the customer’s system, satisfactory
operation cannot be achieved, then the customer is requested to contact the factory for further advice on:-
INTERNATIONAL TEL: +44 (0) 1723 890099 INTERNATIONAL FAX: +44 (0) 1723 893303
E-mail:
Support@Deepseaplc.com
Website :
www.deepseaplc.com
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 49
11 FAULT FINDING
SYMPTOM POSSIBLE REMEDY
Unit is inoperative Check the battery and wiring to the unit. Check the DC supply. Check the DC
fuse.
Unit shuts down Check DC supply voltage is not above 35 Volts or below 9 Volts
Check the operating temperature is not above 70 °C. Check the DC fuse.
Unit locks out on Emergency Stop If an Emergency Stop Switch is not fitted, ensure that a positive is connected
to the Emergency Stop input. Check emergency stop switch is functioning
correctly. Check Wiring is not open circuit. Intermittent Magnetic Pick-up sensor fault
Ensure that Magnetic pick-up screen is only connected at one end, if
connected at both ends, this enables the screen to act as an aerial and will
pick up random voltages. Low oil Pressure fault operates after engine has fired
Check engine oil pressure. Check oil pressure switch/sender and wiring.
Check configured polarity (if applicable) is correct (i.e. Normally Open or
Normally Closed) or that sender is compatible with the 5320 Module and is
correctly configured. High engine temperature fault operates after engine has fired.
Check engine temperature. Check switch/sender and wiring. Check
configured polarity (if applicable) is correct (i.e. Normally Open or Normally
Closed) or that sender is compatible with the 5320 Module. Shutdown fault operates Check relevant switch and wiring of fault indicated on LCD display. Check
configuration of input. Warning fault operates Check relevant switch and wiring of fault indicated on LCD display. Check
configuration of input. Fail to Start is activated after pre­set number of attempts to start
Check wiring of fuel solenoid. Check fuel. Check battery supply. Check battery
supply is present on the Fuel output of the module. Check the speed sensing
signal is present on the 5320 inputs. Refer to engine manual. Continuous starting of generator when in
AUTO
Check that mains (utility) supply is healthy and check that it’s protection fuses
are in place and are not blown
Check that there is no signal present on the “Remote Start” input. Check
configured polarity is correct. Generator fails to start on receipt of Remote Start signal or mains (utility) supply failure.
Check Start Delay timer has timed out.
If remote start fault, check signal is on “Remote Start” input. Confirm input is
configured to be used as “Remote Start”. Pre-heat inoperative Check wiring to engine heater plugs. Check battery supply. Check battery
supply is present on the Pre-heat output of module. Check pre-heat has been
selected in your configuration. Starter motor inoperative Check wiring to starter solenoid. Check battery supply. Check battery supply
is present on the Starter output of module. Ensure that the Emergency Stop
input is at Positive. Engine runs but generator will not take load
Check Warm up timer has timed out. Ensure generator load inhibit signal is
not present on the module inputs. Check connections to the switching device. Incorrect reading on Engine gauges
Check engine is operating correctly. Check sender and wiring paying
particular attention to the wiring to terminal 47 (refer to appendix). Check that
sender is compatible with the 5320 Module and is correctly configured.
NOTE:- The above fault finding is provided as a guide check-list only. As it is possible for the module to be configured to provide a wide range of different features always refer to the source of your module configuration if in doubt.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
50 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
12 FACTORY DEFAULT CONFIGURATION
In the tables below, the icon
# indicates an item that can be adjusted from the module’s front panel editor.
Absence of the
# icon beside an item means that adjustment of this parameter is only possible using the 5xxx
series configuration software in conjunction with the P810 interface. For further details on adjustment from the front panel editor, see the section entitled “Front panel configuration” elsewhere within this manual.
Module settings Value
Base module 5320 automatic mains failure module
Miscellaneous settings Value
Two lines of text (Configuration description)
Blank
Alternator fitted Yes Poles 4 Magnetic pickup fitted No CAN enabled No AC System 3 phase, 4 wire VT Ratio Disabled Mains failure detection Enabled Number of start attempts 3 Enable fast loading feature No Immediate mains dropout Disabled Sleep in STOP mode No All warnings are latched No
Input settings – Analogue | Oil pressure Value
Low oil pressure input type VDO 10 bar Trip Return
Low oil pressure pre-alarm
#
1.17 Bar 17.0 PSI 1.24 Bar 18.0 PSI
Low oil pressure shutdown
#
1.03 Bar 14.9 PSI N/A
Input settings – Analogue | Coolant temp
Value
High coolant temp input type VDO 120 degrees C
Trip Return
High coolant temp pre-alarm
#
115°C 239°F 110°C 230°F
High coolant temp shutdown
#
120°C 248°F N/A
Low coolant temp pre-alarm
#
65°C 149°F 66°C 151°F
Input settings – Analogue | Fuel level Value
Fuel level input type Not Used
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 51
Input settings - Digital Value
1 Remote start Close to activate 2 Lamp test Close to activate 3 User configured Close to activate, Warning Active from safety on 4 User configured Close to activate, Shutdown Always active 5 User configured Close to activate, Shutdown Active from safety on 6 User configured Close to activate, Electrical trip Always active
NOTE:- Inputs set to ‘User configured’ have an extra text box to allow the user to type in a
description.
Output settings – Relay Value
1 Energise Preheat (during pre-heat timer) 2 Energise Common alarm 3 Energise System in auto mode 4 Energise Close generator 5 De-energise Close mains
Output settings – Expansion A Value
1 Energise System in auto mode 2 Energise Fail to start 3 Energise Generator available 4 Energise Delayed alarms armed 5 Energise Combined under / over freq. Shutdown 6 Energise Combined under / over voltage shutdown 7 Energise Cooling timer in progress 8 Energise Mains failure
Output settings – Expansion B Value
1 Energise Output not used 2 Energise Output not used 3 Energise Output not used 4 Energise Output not used 5 Energise Output not used 6 Energise Output not used 7 Energise Output not used 8 Energise Output not used
LED indicator settings Value
1 Lit Remote start on load 2 Lit Lamp Test 3 Lit System In Auto 4 Lit Common alarm
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
52 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
Timer settings Value
Mains transient delay
#
2s
Start delay
#
5s
Pre-heat
#
0s
Cranking time
#
10s
Crank rest time
#
10s Smoke limit 0s Smoke limit off 0s Safety on delay
#
10s Overspeed overshoot
#
2s Warming up time
#
0s Transfer time
#
0.7s Breaker close pulse 0.5s Breaker trip pulse 0.5s Return delay
#
30s
Cooling time
#
1m ETS solenoid hold 0s Fail to stop delay
#
30s Generator transient delay
#
1s Battery low volts delay
#
1m Battery high volts delay
#
1m LCD page timer 5m
Mains (utility) settings – Voltage/frequency Trip Return
Under volts trip
#
184V AC 207V AC
Over volts trip
#
276V AC 253V AC
Under frequency trip
#
45.0 Hz 48.0 Hz
Over frequency trip
#
55.0 Hz 52.0 Hz
Generator settings – Voltage/frequency Trip Return
Under volts trip
#
184V AC N/A
Under volts pre-alarm
#
196V AC 207V AC
Over volts pre-alarm
#
265V AC 253V AC
Over volts trip
#
276V AC N/A
Under frequency trip
#
40.0 Hz N/A
Under frequency pre-alarm
#
42.0 Hz 45.0 Hz
Over frequency pre-alarm
#
55.0 Hz 52.0 Hz
Over frequency trip
#
57.0 Hz N/A
Droop
#
Disabled N/A
Droop %
#
0.0% N/A
Loading Voltage 207V Ph-N Loading Frequency 45 Hz Alternative Voltage
#
230v norm / 115v alt Disabled on module
Alternative frequency
#
50Hz norm / 60Hz alt Disabled on module
Generator settings – Current/power Value
Generator CT primary 600A Generator CT secondary 5A CT location Generator Only Generator full load rating
#
500A
Delayed High Current
#
100% ( 500A )
Trip Curve 36
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 53
Engine settings – Crank disconnect Value
Crank disconnect on generator frequency 21.0Hz Crank disconnect oil pressure <Disabled> Check oil pressure prior to starting Yes
Engine settings – speed Value
Underspeed trip
#
1250 RPM Disabled
Underspeed prealarm
#
1350 RPM Disabled
Overspeed prealarm
#
1650 RPM Disabled
Overspeed trip
#
1750 RPM Disabled
Overspeed overshoot
#
0% Disabled
Plant battery settings Trip Return
Under volts warning
#
8.0V DC 9.0V DC
Over volts warning
#
33.0V DC 32.0V DC
Charge alternator warning
#
6.0V DC N/A
Exercise scheduler settings Value
Enable exercise scheduler No
Comms Value
Site identity Genset ID Modem mode No modem Modem init (not auto answer) E0S7=60S0=0&S0&C1&D3 Modem init (auto answer) E0S7=60S0=2&S0&C1&D3 Modem Hang H0 Master inactivity timeout 5s Slave ID 10 (Default) Baud Rate 19200 (Default)
Languages Value
Fixed Languages
#
English (UK)
User configured languages Not used
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
54 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
13 TYPICAL WIRING DIAGRAM
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 55
14 APPENDIX
14.1 ALTERNATIVE WIRING TOPOLOGIES
The 53xx series controllers can support many different wiring topologies (AC systems) to suit the many systems in use worldwide. The ‘Typical connection diagram’ details how to connect the module when used in a 3 phase, 4 wire system (3 phase star connected alternators). Changes to this typical wiring diagram for other AC systems are detailed below.
NOTE:- The factory default configuration for the 5320 module is for use with the 3 phase, 4 wire AC system. If another system is to be used, the controller must be reconfigured using the 5xxx series configuration software.
14.1.1 3 PHASE, 3 WIRE
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
56 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
14.1.2 1 PHASE, 2 WIRE
Single phase alternator with neutral conductor.
14.1.3 2 PHASE, 3 WIRE ( 2 PHASE CENTRE TAP NEUTRAL)
The alternator is 2 phase star connected. The live phases are separated by 180°
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 57
14.2 ICONS AND LCD IDENTIFICATION
14.2.1 PUSH BUTTONS
Display Description Display Description Display Description
Stop/Reset
i
Page scroll Auto mode
Scroll
Test mode
I
Start (when in
Manual or Test
mode)
Mute
Manual mode
14.2.2 STATUS / MEASUREMENT UNITS
Display Description Display Description Display Description
L1
Phase
L2
Phase
L3
Phase
L1- N
Phase - Neutral
L2- N
Phase - Neutral
L3- N
Phase -Neutral
L1-L2
Phase - Phase
L2-L3
Phase - Phase
L3-L1
Phase - Phase
BAR
Pressure
KPa
KPa Oil Pressure
Units
PSI
Pressure
V
Voltage
o
F
Temperature
Hz
Frequency
A
Amperes
o
C
Temperature
RPM
Speed
kW
KiloWatts
kVA
Apparent power
KW divided by
kVA
14.2.3 LED INDICATION
Display Description Display Description
Generator available
Mains available
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
58 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
14.3 5320 IDMT TRIPPING CURVES (TYPICAL)
5320 Delayed over-current protection
1
10
100
1000
10000
100000
1000000
123
Current as a multiple of the trip-point setting (tripping curve = 36)
Tripping time in seconds
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 59
14.4 SENDER WIRING RECOMMENDATIONS
14.4.1 EARTH RETURN SENDERS
Connection Name Terminal Number
Oil pressure Sender 44
Coolant temperature
sender
45
Fuel level sender 46
Sender common 47
NOTE:- . It is important that terminal 47 ( sender common ) is soundly connected to an earth point on the ENGINE BLOCK, not within the control panel, and must be a sound electrical connection to the sender bodies.
NOTE:- . If you use PTFE insulating tape on the sender thread when using earth return senders, ensure you do not insulate the entire thread as this will prevent the sender body from being earthed via the engine block.
14.4.2 INSULATED RETURN SENDERS
Connection Name Terminal Number
Oil pressure Sender 44
Coolant temperature
sender
45
Fuel level sender 46
Sender common 47
NOTE:- . It is important that terminal 47 ( sender common ) is soundly connected to an earth point on the ENGINE BLOCK, not within the control panel .
14.4.3 FUEL LEVEL SENDERS
53xx
53xx
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
60 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
The resistive fuel level senders supported by the 5300 series controllers are devices that translate fuel level into resistance. A change in fuel level translates directly to a change in the resistance of the sender. In the case of a parallel sided fuel tank, an accurate measure of the fuel level can easily be made, however as shown in the example below, this is not the case with non-parallel sided fuel tanks. Therefore it is recommended that only parallel sided fuel tanks are used to ensure correct fuel level detection.
The fuel sender measures the distance between the top of the tank and the fuel level. Typically, they use a ball float. In this example, the distance between the top of the tank and the level of the fuel is 50% of the height of the tank. The fuel level sender will report the tank correctly as being 50% full.
For a parallel-sided tank like this one, 50% distance between the top of the tank and the level of the fuel will occur when the tank is 50% full of fuel. In this example, the distance between the top of the tank and the level of the fuel is again 50% of the height of the tank, the fuel level sender will report the tank as being 50% full.
However, as the bottom of the tank is curved, the actual amount of fuel in the tank is only about 40%. The fuel sender is incorrectly reporting the amount of remaining fuel.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 61
14.5 CAN INTERFACE
Modules are fitted with the CAN interface as standard and are capable of receiving engine data from engine
CAN controllers compliant with the CAN standard. CAN enabled engine controllers monitor the engines operating parameters such as engine speed, oil pressure, engine temperature (among others) in order to closely monitor and control the engine. The data that is gathered by the engine controller is then transmitted on an industry standard communications interface (CAN). This allows generator controllers such as the DSE 53xx range to access these engine parameters with no physical connection to the sensor device.
NOTE:- For further details for connections to Can enabled engines refer to the manual Can and DSE
Wiring Part No. 057-004
14.6 OUTPUT EXPANSION
There are several methods of output expansion available for the 5xxx module:-
14.6.1 RELAY OUTPUT EXPANSION (157)
An expansion module is available, which connects to the configuration socket and enables the 5xxx to use eight additional relays on the 157 relay module, providing Volt-free contacts for customer connection. A maximum of 2 off 157 relay modules can be connected, there are identified as ‘A’ and ‘B’ and give a total of 16 extra relay outputs.
Refer to technical data sheet on the 157 relay module for further details.
14.6.2 LED OUTPUT EXPANSION (548)
An expansion module is available, which connects to the configuration socket, and enables the 5xxx to use eight additional LED’s on the 548 module, providing remote LED’s indication up to 50 metres away. A maximum of 2 off 548 LED modules can be connected, there are identified as ‘A’ and ‘B’ and give a total of 16 extra LED outputs.
It is possible to use a mix of 157 and 548 modules to give both relay and LED expansion if required (Please refer to our Technical Support department for details.).
14.7 INPUT EXPANSION
It is possible to increase the number of monitored inputs available by utilising either :
¾ DSE P130 input expansion ¾ 54x Protection Expansion/Annunciator.
Please refer to the relevant product documentation for further details.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
62 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
14.8 COMMUNICATIONS OPTION CONNECTIONS
14.8.1 DESCRIPTION
The 5xxx series configuration software allows the 5320 controller to communicate with a PC. The computer can be connected to the module either directly (P810 shown to the right), via a modem (RS232)* or via an RS485 link**.
The operator is then able to remotely control the module, starting or stopping the generator, selecting operating modes, etc. The various operating parameters (such as output volts, oil pressure, etc.) on the remote generator can also be viewed.
The information contained in this manual should be read in conjunction with the appropriate module documentation. This manual only details the operation of the communications software and how it should be used. The operation of the module is detailed in its own relevant manual.
NOTE: - *If modem communications is a requirement, then it is important to order the correct 5320 module with the RS232 communications board fitted. This provides a 9-way D-type connector suitable for connection to the modem. Please refer to the
comms
section of this manual for details of how the
system should be configured.
**If RS485 communications is required, then it is important to order the correct 5320 module with the RS485 communications board fitted. This provides a 3-way terminal block for connection of the RS485 link.
14.8.2 PC TO CONTROLLER (DIRECT) CONNECTION
To connect a 5320 to a modem the following items are required: -
Any 5320 Module (RS232 or RS485)
5xxx series configuration software (Supplied on DSE software
CD).
P810 interface (USB or RS232 as required)
14.8.3 MODEM TO CONTROLLER CONNECTION
To connect a 5320 to a modem the following items are required: -
5320 Module with RS232 Communications Interface
Compatible RS232 Modem (PSTN or GSM)
Suitable connection leads
Power supply for the modem
5xxx series configuration software (Supplied on DSE software CD).
Access to a PSTN Line or GSM network.
CAUTION! - The modem must be powered from a suitably stabilised supply, preferably supplied with the modem (see below). Failure to ensure continuity of supply will result in communication difficulties at such times as Mains failure or during cranking. An uninterruptible power supply arrangement is recommended (AC or DC depending on modem power requirement).
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 63
14.8.4 RS485 LINK TO CONTROLLER
The RS485 enabled 5320 modules are able to communicate with a PC or other RS485 enabled device over a standard RS485 connection. Typical uses of RS485 are:
Direct connection to a remote PC running the 5xxx series configuration software. RS485 is capable of
communication over a distance of 1.2km where suitable 120
Ω RS485 cable is installed.
Connection to a building management to allow mains, generator and engine parameters/alarm conditions to be
displayed along with information from other devices (air conditioning, fire alarm system etc).
NOTE: - The RS485 system will comprise of one MODBUS master (typically a PC) and up to 31 MODBUS slaves. The 5320 modules are always MODBUS slave devices. To ensure correct operation a suitable 120Ω terminal resistor must be fitted to each end of the RS485 connection bus.
Caution! - The A and B lines of the 485 network should be terminated at each end with a 120Ω resistor.
Some RS485 devices (PC cards in particular) are already fitted with a terminating resistor. However if they are not installed as an ‘end of line’ device then such terminating resistors must be removed. Other RS485 devices may be fitted with a ‘switchable’ resistor, again this must be switched out if the device is not installed as an ‘end of line’ device.
Typical connections of RS485 PC system (master) to RS485 DSE controller (slave)
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
64 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
TYPICAL BUILDING MANAGEMENT SCHEME USING RS485 MONITORING
CAUTION! -. RS485 cabling must be 120Ω impedance cable, specified for use with RS485. 120Ω terminating resistors must be fitted to the first and last devices on the bus. Some PC RS485 cards are already fitted with this resistor, and in this case should not be fitted externally. If in doubt, consult the supplier of your PC RS485 card. If the 5320 controller is the ‘last’ device on the bus, then it’s RS485 connection must be suitably terminated with a 120Ω resistor as detailed in the specification laid out in the RS485 standard.
Recommended cable BELDEN 9841 120Ω RS485 cable. DSE part number 016-030.
NOTE: - The RS485 output uses ‘MODBUS’ protocol. It is possible to use third party software to monitor and control the 5320 module via this protocol. Please refer to Deep Sea Electronics Plc for details.
14.8.5 MODBUS™
The RS485 output uses Modbus™ communications protocol. This uses a master-slave technique to communicate. Only the Master can initiate a packet transaction, called a ‘query’. When appropriate the slave (5320 Module) responds to the query and provides the information requested by the master.
All supported data can be read and written as specified in the register table (documentation is available from Deep Sea Electronics Plc.).
When the 5320 Module receives a query it will respond by either supplying the requested register data or performing the requested action. A slave device (the 5320 module) will never initiate communications on the Modbus™ link. The 5320 can only be configured as a slave device. The Master can only query individual slaves. Refer to the Modbus™ protocol document for more details.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM 65
14.9 ENCLOSURE CLASSIFICATIONS
IP CLASSIFICATIONS
BS EN 60529 Degrees of protection provided by enclosures
First Digit
Second digit
Protection against contact and ingress of solid objects Protection against ingress of water 0 No protection 0 No protection
1 Protected against ingress solid objects with a
diameter of more than 50 mm. No protection against deliberate access, e.g. with a hand, but large surfaces of the body are prevented from approach.
1 Protection against dripping water falling vertically. No
harmful effect must be produced (vertically falling drops).
2 Protected against penetration by solid objects with a
diameter of more than 12 mm. Fingers or similar objects prevented from approach.
2 Protection against dripping water falling vertically.
There must be no harmful effect when the equipment (enclosure) is tilted at an angle up to 15° from its normal position (drops falling at an angle).
3 Protected against ingress of solid objects with a
diameter of more than 2.5 mm. Tools, wires etc. with a thickness of more than 2.5 mm are prevented from approach.
3 Protection against water falling at any angle up to 60°
from the vertical. There must be no harmful effect (spray water).
4 Protected against ingress of solid objects with a
diameter of more than 1 mm. Tools, wires etc. with a thickness of more than 1 mm are prevented from approach.
4 Protection against water splashed against the
equipment (enclosure) from any direction. There must be no harmful effect (splashing water).
5 Protected against harmful dust deposits. Ingress of
dust is not totally prevented but the dust must not enter in sufficient quantity to interface with satisfactory operation of the equipment. Complete protection against contact.
5 Protection against water projected from a nozzle
against the equipment (enclosure) from any direction. There must be no harmful effect (water jet).
6 Protection against ingress of dust (dust tight).
Complete protection against contact.
6 Protection against heavy seas or powerful water jets.
Water must not enter the equipment (enclosure) in harmful quantities (splashing over).
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
66 Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
NEMA CLASSIFICATIONS
NOTE: - There is no direct equivalence between IP / NEMA ratings. IP figures shown are approximate only.
1
IP30
Provides a degree of protection against contact with the enclosure equipment and against a limited amount of falling dirt.
2
IP31
Provides a degree of protection against limited amounts of falling water and dirt.
3
IP64
Provides a degree of protection against windblown dust, rain and sleet; undamaged by the formation of ice on the enclosure.
3R
IP32
Provides a degree of protection against rain and sleet:; undamaged by the formation of ice on the enclosure.
4 (X)
IP66
Provides a degree of protection against splashing water, windblown dust and rain, hose directed water; undamaged by the formation of ice on the enclosure. (Resist corrosion).
12/12K
IP65
Provides a degree of protection against dust, falling dirt and dripping non corrosive liquids.
13
IP65
Provides a degree of protection against dust and spraying of water, oil and non corrosive coolants.
CALL US TODAY 1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
Loading...