For flat surface mounting in a Type 1 enclosure to meet UL requirements
240.0mm x 181.1mm x 41.7mm (9.4” x 7.1” x 1.6”)
220mm x 160mm (8.7” x 6.3”)
ACCESSING THE FRONT PANEL CONFIGURATION EDITOR.
Ensure the engine is at rest and the module is in STOP mode by pressing the Stop/Reset
• Press the Stop/Reset and Info
If a module security PIN has been set, the PIN number request is then
shown :
• Press the button the first digit will flash
when the first digit is c
show ‘#’ for security.
•
Repeat this process for the other digits o
f the PIN number. You can press
back to adjust one of the previous digits.
•
When
is pressed after editing the final
not correct, you must re-enter the PIN.
If the PIN has been successfully entered (or the module PIN has not been
enabled), the editor is displayed :
• Enter the editor as described above.
• Press the or
to cycle to the section you wish to view/change.
to cycle to the parameter
within the section you have chosen.
• To edit the parameter, press
to enter edit mode. The parameter begins to flash to indicate that
you are editing the value.
• Press the up or down buttons to
change the parameter to the required value.
• Press to save the value
• To exit the editor at any time, press and hold the
DEE P S E A E L E C T R O N I C S
0 IN ST AL L AT IO N IN S TR UC T IO NS
NOTE: When the editor is visible, it is automatically exited after 5
NOTE: When the editor is visible, it is automatically exited after 5 NOTE: When the editor is visible, it is automatically exited after 5
NOTE: When the editor is visible, it is automatically exited after 5
ensure security.
ensure security.ensure security.
ensure security.
NOTE:
NOTE: NOTE:
NOTE:
The PIN number is automatically reset when the editor is exited (manually or
The PIN number is automatically reset when the editor is exited (manually or The PIN number is automatically reset when the editor is exited (manually or
The PIN number is automatically reset when the editor is exited (manually or
automatically) to ensure security.
automatically) to ensure security.automatically) to ensure security.
automatically) to ensure security.
NOTE:
NOTE: NOTE:
NOTE:
More comprehensive module configuration is possible using the
More comprehensive module configuration is possible using the More comprehensive module configuration is possible using the
More comprehensive module configuration is possible using the
configurati
configuraticonfigurati
configuration software
on softwareon software
on software.
. .
.
Please contact us for further details
Please contact us for further detailsPlease contact us for further details
Please contact us for further details
NOTE: The contents of the tables overleaf may differ depending on the actual module
NOTE: The contents of the tables overleaf may differ depending on the actual module NOTE: The contents of the tables overleaf may differ depending on the actual module
NOTE: The contents of the tables overleaf may differ depending on the actual module
configuration.
configuration. configuration.
configuration.
enable the pin to be entered.
(left) if you need to move
ceases flashing to indicate that it has been saved.
minutes of inactivity to
minutes of inactivity to minutes of inactivity to
minutes of inactivity to
86
8686
86xx series PC
xx series PC xx series PC
xx series PC

ADJUSTABLE PARAMETERS
Front Panel Configuration Editor
Section Parameter as shown on display Values
Engine Crank Duration
10s
Engine Crank Rest Time
10s
Engine Safety On Delay
10s
Engine Smoke Limiting Off
0s
Engine Speed Overshoot Delay
0s
Engine Failed To Stop
30s
Battery Under Voltage Warning Delay
1m
Battery Over Voltage Warning Delay
1m
Return Delay
30s
Generator Transient Delay
0s
Mains Transient Delay
2s
Mains transfer time
0.7s
Mains Under Voltage Alarm
184V
Mains Over Voltage Alarm
277V
Mains Under Frequency Alarm
45Hz
Mains over Frequency Alarm
55Hz
Mains Transient Delay
2s
Under Voltage Shutdown
184v
Under Voltage Pre-Alarm
196v
Nominal Voltage 230v
Over Voltage Pre-Alarm 265v
Over Voltage Shutdown 277v
Under Frequency Shutdown 40Hz
Under Frequency Pre-Alarm 42Hz
Nominal frequency 50Hz
Over Frequency Pre-Alarm 54Hz
Over Frequency Shutdown 57Hz
Full Load Rating 500A
kW Overload Trip 100%
Delayed Over current Active
Delayed Over Current 100%
AC System 3 Phase 4 Wire
CT Primary 600A Power Cycle After Exit
CT Secondary 5A Power Cycle After Exit
Short Circuit Trip 200%
Earth CT Primary 500A
Earth Fault Trip Active
Earth Fault Trip 10%
Transient Delay 0s
Gen Reverse Power Delay 2s
Full kW rating 345kW
Full kVAr rating 258kVAr
Load Ramp Rate 3%
Gen Reverse Power 35kW
Insufficient Capacity Delay 1s
Insufficient Capacity action None
Reactive Load CTL mode VAr fixed export
Load Parallel Power 50%
Load Power Factor 1.00pf 0 KVAr 0%
Oil Pressure Low shutdown 1.03bar
Oil Pressure Low Pre-Alarm 1.24bar
Coolant Temp High Pre-Alarm 90ºC
Coolant Temp High Electrical Trip 92ºC (When Enabled)
Coolant Temp High Shutdown 95ºC
Start Delay Off load 5s
Start Delay on load 5s
Start Delay Telemetry 5s
Pre Heat Timer 0s
Crank Duration 10s
Crank rest Time 10s
Safety On Delay 10s
Smoke Limiting 0s
Smoke limiting off 0s
Warm Up Time 0s
Cool Down Time 1m
Speed Overshoot Delay 0s
Speed Overshoot 0%
Fail To Stop Delay 30s
Battery Under Volts Warning Active
Battery Under Volts Warning Delay 1m
Configuration Editor (continued)
Section Parameter as shown on display Values
Battery Under Volts Warning 10v
Battery Over Volts Warning Active
Battery Over Volts Warning Delay 1m
Battery Over Volts Warning 30v
Charge Alternator Failure Warning Active
Charge Alternator Failure Warning
Charge Alternator Warning Delay
Charge Alternator Failure Shutdown
Charge Alternator Failure Shutdown
4.0v (When Enabled)
Charge Alternator Shutdown Delay
5s (When Enabled)
Droop %
Active, Inactive. Electronic engines only when
droop is enabled.
Scheduler
Active, Inactive
Schedule On Load
Active , Inactive (Only Available When
Scheduler Is Active)
Schedule Period
Weekly, Monthly (Only Available When
Scheduler Is Active)
Schedule Time & Date Selection (1-16)
Press to begin editing then or
when selecting the different
parameters in the scheduler.
ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
• The ‘running’ editor can be entered while the engine is running. All protections remain active if the
engine is running while the running editor is entered.
• Press and hold the button to enter the running editor.
ADJUSTABLE PARAMETERS (Running editor)
• Enter the editor as described above.
• Press the up or down buttons to cycle to the section you wish to view/change.
• To Edit the parameter press the button to enter edit mode. The parameter begins to flash to
indicate that you are editing the value.
• Press the up
or down
buttons to change the parameter to the required value.
• Press the button to save the value. The parameter ceases flashing to indicate that it has been
saved.
• To exit the editor at any time , press and hold the button.
Running Editor
Section Parameter as shown on display Factory Settings
Load parallel power
0-100% (50)
Override starting alarms
Inactive, Active
Voltage adjust (manual mode only engine running breaker open)
0-100 % (0)
Frequency adjust (manual mode only engine running breaker open)
0-100 % (0)
Auxiliary Mains Fail Out of sync reset
Inactive Active
Mains decoupling test mode (Stop mode only)
Inactive Active