6.2.2Deletion of the error display ..................................36
2
260216 - 7600717-001-06
Page 4
3
260216 - 7600717-001-06
Page 5
IniControl For C 330 / C 630 ECO
1Introduction
1.1Symbols used
1. Introduction
In these instructions, various danger levels are employed
to draw the user’s attention to particular information. In so
doing, we wish to safeguard the user’s safety, highlight
hazards and guarantee correct operation of the appliance.
DANGER
Risk of a dangerous situation causing serious
physical injury.
WARNING
1.2Liabilities
Risk of a dangerous situation causing slight
physical injury.
CAUTION
Risk of material damage.
Signals important information.
¼Signals a referral to other instructions or other pages
in the instructions.
1.2.1.Manufacturer’s liability
Our products are manufactured in compliance with the
requirements of the various applicable European
260216 - 7600717-001-06
Directives. They are therefore delivered with [ marking
and all relevant documentation.
4
Page 6
1. Introduction
IniControl For C 330 / C 630 ECO
In the interest of customers, we are continuously
endeavouring to make improvements in product quality.
All the specifications stated in this document are therefore
subject to change without notice.
Our liability as the manufacturer may not be invoked in the
following cases:
4 Failure to abide by the instructions on using the
appliance.
4 Faulty or insufficient maintenance of the appliance.
4 Failure to abide by the instructions on installing the
appliance.
1.2.2.Installer’s liability
The installer is responsible for the installation and
commissioning of the appliance. The installer must
respect the following instructions:
4 Read and follow the instructions given in the manuals
provided with the appliance.
4 Carry out installation in compliance with the prevailing
legislation and standards.
4 Perform the initial start up and carry out any checks
necessary.
4 Explain the installation to the user.
4 If a maintenance is necessary, warn the user of the
obligation to check the appliance and maintain it in
good working order.
4 Give all the instruction manuals to the user.
1.2.3.User’s liability
To guarantee optimum operation of the appliance, the
user must respect the following instructions:
4 Read and follow the instructions given in the manuals
provided with the appliance.
4 Call on qualified professionals to carry out installation
and initial start up.
4 Get your installer to explain your installation to you.
4 Ensure the Appliance is serviced in accordance with
the manufacturer’s instructions by a suitable qualified
person.
4 Keep the instruction manuals in good condition close
to the appliance.
5
260216 - 7600717-001-06
Page 7
IniControl For C 330 / C 630 ECO1. Introduction
This appliance is not intended to be used by persons
(including children) whose physcial, sensory or mental
capacity is impaired or persons with no experience or
knowledge, unless they have the benefit, through the
intermediary of a person responsible for their safety, of
supervision or prior instructions regarding use of the
appliance. Care should be taken to ensure that children
do not play with the appliance.
If the mains power lead is damaged it must be replaced
by the original manufacturer, the manufacturer’s dealer or
another competent person to prevent hazardous
situations.
1.3Certifications
This product complies to the requirements to the
european directives and following standards:
2. Safety instructions and recommendationsIniControl For C 330 / C 630 ECO
2Safety instructions and
recommendations
2.1Recommendations
WARNING
Any intervention on the appliance and heating equipment
must be carried out by a qualified engineer.
For a proper operating of the boiler, follow carefully the
instructions.
Keep this document close to the place where the boiler is
installed.
7
260216 - 7600717-001-06
Page 9
IniControl For C 330 / C 630 ECO3. Technical specifications
4 Installation, use and maintenance manual for the control panel
4.1.2.Accessories
Various options are available depending on the configuration of the
installation:
Control system options
Descriptionpackage
BUS connection cable (length 12 m)AD134
voice remote monitoring moduleAD152
OpenTherm interfaceAD287
Outside sensorFM46
RX11 cableAD124
Modulating room thermostatAD265
Radio-controlled modulating room thermostat AD266
Digital room thermostatAD137
Wireless settable ambient thermostatAD200
SCU-S05 PCB
SCU-S03 PCB
4.2Installing the outside sensor
4.2.1.Choice of the location
It is important to select a place that allows the sensor to measure the
outside conditions correctly and effectively.
Advised positions:
4 on one face of the area to be heated, on the north if possible
4 half way up the wall in the room to be heated
4 under the influence of meteorological variations
9
260216 - 7600717-001-06
Page 11
8800N001-C
8800N002-C
8800N003-C
2
IniControl For C 330 / C 630 ECO
4. Installation
4 protected from direct sunlight
4 easy to access
A
B
H
Z
Recommended position
Possible position
Inhabited height controlled by the sensor
Inhabited area controlled by the sensor
Positions to be avoided:
4 masked by a building element (balcony, roof, etc.)
4 close to a disruptive heat source (sun, chimney, ventilation grid,
etc.)
4.2.2.Connecting the outside sensor
Mount the sensor using the screws and dowels provided.
A
Z
Inserts
Ø4 wood screw
¼For the connection of the outside temperature sensor, refer to
the chapter "Electrical Connections".
4.3Fitting and connecting the control panel
260216 - 7600717-001-06
¼Refer to the boiler’s installation and service manual.
10
Page 12
M002709-C
1
3
2
On/off
OT
BL
RL
PCU
SCU-S05
PUMP
ECS S EXT S DE
2 1 21
M002710-C
5
6
7
8
9
0
1
2
3
4
6
7
8
5
1
2
4
4
3
On/off
OT
BL
RL
PCU
PUMP
OTH / MB
INTERFACE
OTH
9
10
11
12 13
4. InstallationIniControl For C 330 / C 630 ECO
4.4Electrical connections
4.4.1.Connecting a direct heating circuit
A
Connect the outside temperature sensor.
SCU-S05 PCB = Option
Z
E
Heating connection pump.
Connect a safety thermostat if the heating circuit is for
underfloor heating.
4Remove the bridge.
4Connect the wires from the safety thermostat to the
connector.
4.4.2.Connection in cascade (with OpenTherm
AD287) option
11
A
Z
E
R
Master boiler (DIEMATIC iSystem)
Secondary boiler (DIEMATIC iSystem or IniControl)
Secondary boiler (DIEMATIC iSystem or IniControl)
Cable BUS
260216 - 7600717-001-06
Page 13
IniControl For C 330 / C 630 ECO4. Installation
T
Y
U
I
O
P
a
z
e
Boiler pump
Low loss header
Cascade outlet sensor
Connect the sensor to the terminal block S SYST on the
master boiler.
Boiler power supply - 230 V
Connection cable linking the Opentherm from the PCU to
the Opentherm on the interface
OpenTherm (AD287) interface board to be fitted in the
boiler control panel
Encoding wheel used to set the addresses of the slave
boilers. Set to 1 on boiler 2 - Set to 2 on boiler 3 - etc.
BUS cable to the master boiler
BUS cable to the slave boilers
260216 - 7600717-001-06
12
Page 14
-
)
L
m
rrr
ddd
T
y
1
2
SERVICE
°C°Fh
barPsi
% rpm
kW uA
x10 l/min
°CSt:
M002715-A
t
h
j
AB
EF
CD
5. CommissioningIniControl For C 330 / C 630 ECO
5Commissioning
5.1Control panel
For operation of the boiler C 630 ECO: Each module has
its own instrument panel.
5.1.1.Description of the keys
13
A
B
C
D
E
F
Return button j, Escape G or Manual reset t
Heating temperature button d or [-]
DHW temperature button r or [+]S [Enter] Key
) [Chimney-sweeping] keys
Press keys A and B simultaneously
f [Menu] keys
Press keys C and D simultaneously
260216 - 7600717-001-06
Page 15
-
)
L
m
r
r
r
d
d
d
T
y
1
2
SERVICE
°C°Fh
barPsi
% rpm
kW uA
x10 l/min
°CSt:
M002716-A
t
h
j
-
)
L
m
rrr
d
d
d
T
y
1
2
SERVICE
°C°Fh
barPsi
% rpm
kW uA
x10 l/min
°CSt:
M002717-A
t
h
j
-
)
L
m
m
r
r
ddd
T
y
g
1
2
SERVICE
°C°Fh
barPsi
% rpm
kW uA
x10 l/min
°CSt:
M002735-A
t
h
j
-
)
L
m
rrr
ddd
T
y
1
2
SERVICE
°C°Fh
barPsi
% rpm
kW uA
x10 l/min
°CSt:
M002719-A
t
h
j
IniControl For C 330 / C 630 ECO5. Commissioning
5.1.2.Description of the display
Key functions
n
G
t
d
[-]
r
[+]
®
Operating modes
n
d
D
r
S
Back to the previous level without saving the
modifications made
Manual reset
Central heating function:
Access to the max. heating temperature parameter.
To reduce a value
DHW function:
Access to sanitary hot water temperature parameter.
To increase a value
Access the selected menu or confirm a value modification
State heating pump
Heating programme deactivated:
The heating function is deactivated
State DHW pump
DHW off
260216 - 7600717-001-06
m
m
g
Flame output level
n
e
r
t
y
Manual mode
The DHW function is in economic mode (deactivated)
Boiler protection is active
Low output level 0 - 25 %
Average output level 25 - 50 %
High output level 50 - 75 %
Output level 75 - 100 %
14
Page 16
-
)
L
m
rrr
ddd
T
y
1
2
SERVICE
°C°Fh
barPsi
% rpm
kW uA
x10 l/min
°CSt:
M002720-A
t
h
j
-
)
L
m
rrr
ddd
T
y
1
2
SERVICE
°C°Fh
barPsi
% rpm
kW uA
x10 l/min
°CSt:
M002721-A
t
h
j
5. Commissioning
System pressure
n
IniControl For C 330 / C 630 ECO
bar
Other information
n
"
!
)
-
K
Pressure indicator:
The symbol is displayed next to the installation’s pressure
value. If no water pressure sensor is connected, -.appears on the display
User menu:
Parameters at user level can be changed
Information menu:
Reading the various current values
Chimney-sweeping position:
Forced full or part load for CO2 measurement
Service menu:
Parameters at installer level can be changed
Display with the symbols:
$ + K + Z (Maintenance message)
\
a
I
M
a
5.2Switch on the instrument panel
The instrument panel IniControl is ready for use, as soon as the
power to the boiler is switched on.
Hour counter menu:
Readout of the operating hours, number of successful
starts and hours on mains supply
Blocking:
After 5 resets in under 1 hour, the appliance should be
switched off and switched on again before resetting
Outside temperature sensor present
The symbol is displayed when the boiler pump is
operating
Defect:
Boiler indicates a fault. This is indicated by an E code
and a flashing display
For operation of the boiler C630 Eco: The features and
instructions described are for each boiler module.
15
1. Open the gas valve on the boiler.
2. Turn on the boiler using the on/off switch.
3. Set the controls (thermostats, control system) so that they request
heat.
260216 - 7600717-001-06
Page 17
IniControl For C 330 / C 630 ECO
5. Commissioning
4. The start-up cycle begins and cannot be interrupted. During the
start-up cycle, the display shows the following information:
A short test where all segments of the display are visible.
fK[xx
pK[xx
: Software version
: Parameter version
The version numbers are displayed alternately.
By pressing the S key for a short time, the current operating status
is shown on the display:
Heat demand Heat demand stopped
1: Fan ON5: Burner stop
": Boiler is igniting 6: Post-circulation of the pump
3: Heating System 0: Standby
In STAND-BY, the display normally shows the water pressure next to
0 (only when the hydraulic pressure sensor is connected) and the
symbols d and H.
Error during the start-up procedure:
4 No information is shown on the display:
- Check the mains supply voltage
- Check the main fuses
- Check the fuses on the control panel:
(F1 = 2 AT, F2 = 8 AT)
- Check the connection of the mains lead to the connector in the
instrument box
4 A fault is indicated on the display by the fault symbol a and a
flashing fault code.
- The meaning of the error codes is given in the error table.
- Press for 3 seconds on key J to restart the boiler.
5.3Reading out measured values
5.3.1.Reading out measured values
The following current values can be read off the information menu
Q:
4 5200 = Fan speed.
4 5201 = Fan speed Set point.
4 5203 = Burner flame signal.
4 5204 = Gas valve open (1) or closed (0).
4 5205 = GpS connected.
4 5206 = Ignition phase.
4 5207 = Ionization current.
4 5208 = Heat output requested.
4 5209 = Release input.
For operation of the boiler C630 Eco: The features and
instructions described are for each boiler module.
The boiler control panel is set for the most common heating
systems. With these settings, practically all heating systems operate
correctly. The user or installer can optimise the parameters according
to own preferences.
For the settings of the C630 Eco boiler: The parameters
and settings described are for each boiler module. Each
parameter changing must therefore be done identical on
each module.
5.4.2.Parameter descriptions
Boiler type C 330 ECO
n
Factory setting
Parameter
p1
p2
p3
p4
p5
p17
p18
p19
p20
p21
(1) Do not modify these factory settings unless absolutely necessary. E.g. to adapt the boiler to: G20 (Gas H)
DescriptionAdjustment range
Flow temperature: T
Post-circulation of the pump
Boiler regulation
Display screen
Brightness of display lighting
Maximum fan speed
Minimum fan speed
offset Minimum fan speed
Start speed
Maximum flow temperature
of system
SET
20 to 90 °C
1 to 98 minutes
99 minutes = continuous
0 = Heating deactivated
1 = Heating activated
0 = Simple
1 = Comprehensive
2 = Automatic switching to simple after 3
minutes
3 = Automatic switching to simple after 3
minutes; Key blocking is active
0 = Dimmed
1 = Bright
G25 (Gas L)
(x100 rpm)
G20 (Gas H)
(x100 rpm)
G25 (Gas L)
(x100 rpm)
G20 (Gas H)
(x100 rpm)
Do not modify
(x1 rpm)
Do not modify
(x100 rpm)
0 to 90 °C909090909090
(1)
(1)
C 330 ECO
280 350 430 500 570 650
808080808080
535635384342
525535384341
14159101110
14159101110
252513141414
555555
111111
222222
111111
0505050050
19
260216 - 7600717-001-06
Page 21
IniControl For C 330 / C 630 ECO5. Commissioning
Factory setting
ParameterDescriptionAdjustment range
C 330 ECO
280 350 430 500 570 650
Heat curve set point
(Maximum outside
p22
temperature)
0 to 30 °C202020202020
(Only with an outside
temperature sensor)
Heat curve set point
p23
(Flow temperature)
(Only with an outside
0 to 90 °C202020202020
temperature sensor)
Heat curve set point
(Minimum outside
p24
temperature)
-30 to 0 °C-15 -15 -15 -15 -15 -15
(Only with an outside
temperature sensor)
Antifreeze temperature
p25
(Only with an outside
from - 30 to 0°C- 10 - 10 - 10 - 10 - 10 - 10
temperature sensor)
p26
p27
Fault relay function X4
(If connected)
Fault relay function X5
(If connected)
0 = Operation signal
1 = Alarm signal
0 = Operation signal
1 = Alarm signal
000000
111111
Minimum water pressure
p28
Wps
(Only with the hydraulic
0 - 3 bar (MPa) (x 0,1bar (MPa))
0 = Not connected
000000
pressure sensor connected)
p29
Minimum gas pressure
check Gps
0 = Not connected
1 = Connected
000000
Hydraulic valve running time
p30
HdV
0 to 255 seconds000000
(If connected)
Flue gas damper running
p31
time FgV
0 to 255 seconds000000
(If connected)
p32
p33
p34
Release waiting time0 to 255 seconds000000
Gas valve leak proving
system CCE
( If connected)
Live/neutral inversion
0 = Not connected
1 = Connected
0 = Off
1 = On
000000
000000
1 = Shutdown without frost-protection
p35
Shutdown input function
2 = Shutdown with frost protection
111111
3 = Lock-out with frost protection (Pump only)
0 =0-10 V Wilo control PCB
p36
From Analogue output (0 10V)
SCU-S05 control PCB
1 = 0-10 V Grundfoss control PCB
2 = PWM pump
3 = Heat output feedback
000000
4 = Temperature feedback
From Analogue input
p37
(0-10V)
SCU-S05 control PCB
p38
p39
p40
(1) Do not modify these factory settings unless absolutely necessary. E.g. to adapt the boiler to: G20 (Gas H)
Boiler inertiaDo not modify666666
Display units
Maintenance message
0 =OpenTherm regulator
1 = Analogue temperature-based control (°C)
2 = Analogue heat output-based control (%)
0 = À/ bar
1 = F / PSI
0 = Service messages off
1 = Service messages on
000000
000000
000000
260216 - 7600717-001-06
20
Page 22
5. CommissioningIniControl For C 330 / C 630 ECO
Factory setting
ParameterDescriptionAdjustment range
C 330 ECO
280 350 430 500 570 650
p41
p42
Service operating hours
Service burning hours
( x 100)
Do not modify
( x 100)
Do not modify
175 175 175 175 175 175
303030303030
Setting the pump speed
p43
(Minimum pump speed for
2 - 10 (x 10%)222222
central heating operation)
Setting the pump speed
p44
(Maximum pump speed for
6 - 10 (x 10%)101010101010
central heating operation)
p45
Zd
df and dV
ΔTModulate down10 to 30 °C252525252525
Detection of connected
SCUs
Factory setting
0 = No detection
1 = Detection
To restore the factory settings or when
replacing the main PCB, enter the values dF
and dU from the type plate in parameters
000000
XXXXXX
YYYYYY
df and dV
(1) Do not modify these factory settings unless absolutely necessary. E.g. to adapt the boiler to: G20 (Gas H)
Boiler type C 630 ECO
n
Factory setting
Parameter
DescriptionAdjustment range
C 630 ECO
560 700 860 1000 1140 1300
p1
p2
p3
Flow temperature: T
Post-circulation of the
pump
Boiler regulation
SET
20 to 90 °C
1 to 98 minutes
99 minutes = continuous
0 = Heating deactivated
1 = Heating activated
808080808080
555555
111111
0 = Simple
1 = Comprehensive
p4
Display screen
2 = Automatic switching to simple after 3
minutes
222222
3 = Automatic switching to simple after 3
minutes; Key blocking is active
p5
p17
p18
p19
p20
p21
(1) Do not modify these factory settings unless absolutely necessary. E.g. to adapt the boiler to: G20 (Gas H)
Brightness of display
lighting
Maximum fan speed
Minimum fan speed
offset Minimum fan speed
Start speed
Maximum flow temperature
of system
0 = Dimmed
1 = Bright
G25 (Gas L)
(x100 rpm)
G20 (Gas H)
(x100 rpm)
G25 (Gas L)
(x100 rpm)
G20 (Gas H)
(x100 rpm)
Do not modify
(x1 rpm)
Do not modify
(x100 rpm)
(1)
(1)
111111
535635384342
525535384341
191813121413
191813121413
050050050
252514141516
0 to 90 °C909090909090
21
260216 - 7600717-001-06
Page 23
IniControl For C 330 / C 630 ECO5. Commissioning
Factory setting
ParameterDescriptionAdjustment range
C 630 ECO
560 700 860 1000 1140 1300
Heat curve set point
(Maximum outside
p22
temperature)
0 to 30 °C202020202020
(Only with an outside
temperature sensor)
Heat curve set point
p23
(Flow temperature)
(Only with an outside
0 to 90 °C202020202020
temperature sensor)
Heat curve set point
(Minimum outside
p24
temperature)
-30 to 0 °C-15 -15 -15-15-15-15
(Only with an outside
temperature sensor)
Antifreeze temperature
p25
(Only with an outside
from - 30 to 0°C- 10 - 10 - 10 - 10- 10- 10
temperature sensor)
p26
p27
Fault relay function X4
(If connected)
Fault relay function X5
(If connected)
0 = Operation signal
1 = Alarm signal
0 = Operation signal
1 = Alarm signal
000000
111111
Minimum water pressure
p28
Wps
(Only with the hydraulic
pressure sensor
0 - 3 bar (MPa) (x 0,1bar (MPa))
0 = Not connected
000000
connected)
p29
Minimum gas pressure
check Gps
0 = Not connected
1 = Connected
000000
Hydraulic valve running
p30
time HdV
0 to 255 seconds000000
(If connected)
Flue gas damper running
p31
time FgV
0 to 255 seconds000000
(If connected)
p32
p33
p34
Release waiting time0 to 255 seconds000000
Gas valve leak proving
system CCE
Live/neutral inversion
0 = Not connected
1 = Connected
0 = Off
1 = On
000000
000000
1 = Shutdown without frost-protection
p35
Shutdown input function
2 = Shutdown with frost protection
3 = Lock-out with frost protection (Pump
111111
only)
0 =0-10 V Wilo control PCB
p36
From Analogue output (0 10V)
SCU-S05 control PCB
1 = 0-10 V Grundfoss control PCB
2 = PWM pump
3 = Heat output feedback
000000
4 = Temperature feedback
From Analogue input
p37
(0-10V)
SCU-S05 control PCB
p38
p39
(1) Do not modify these factory settings unless absolutely necessary. E.g. to adapt the boiler to: G20 (Gas H)
Boiler inertiaDo not modify666666
Display units
0 =OpenTherm regulator
1 = Analogue temperature-based control
(°C)
2 = Analogue heat output-based control (%)
0 = À/ bar
1 = F / PSI
000000
000000
260216 - 7600717-001-06
22
Page 24
5. CommissioningIniControl For C 330 / C 630 ECO
Factory setting
ParameterDescriptionAdjustment range
p40
p41
p42
p43
p44
p45
Zd
df and dV
(1) Do not modify these factory settings unless absolutely necessary. E.g. to adapt the boiler to: G20 (Gas H)
Maintenance message
Service operating hours
Service burning hours
Setting the pump speed
(Minimum pump speed for
central heating operation)
Setting the pump speed
(Maximum pump speed for
central heating operation)
ΔTModulate down10 to 30 °C252525252525
Detection of connected
SCUs
Factory setting
0 = Service messages off
1 = Service messages on
( x 100)
Do not modify
( x 100)
Do not modify
2 - 10 (x 10%)222222
6 - 10 (x 10%)101010101010
0 = No detection
1 = Detection
To restore the factory settings or when
replacing the main PCB, enter the values
dF and dU from the type plate in parameters
df and dV
C 630 ECO
560 700 860 1000 1140 1300
000000
175 175 175 175175175
303030303030
000000
XXXXXX
YYYYY
Y
5.4.3.Modification of the user-level parameters
Parameters p001 to p007 can be changed by the user.
CAUTION
Modification of the factory settings may be detrimental to
the functioning of the appliance.
23
260216 - 7600717-001-06
Page 25
)
r
d
bar
C003050-A
t
h
j
h
j
1x
2x
IniControl For C 330 / C 630 ECO5. Commissioning
1. Press the two keys f simultaneously and then key [+] until the
symbol W flashes on the menu bar.
2. Select the users menu using the key S.
p[001
is displayed
with 1 flashing.
3. Press the S key a second time. The value
°C appears and
80
flashes (for example).
4. Change the value by pressing the [-] or [+] key. In this example
using key [-] to
5. Confirm the value with the S key.
flashing.
1
60
°C.
p[001
is displayed with
6. Press the j key 2 times to return to the current operating mode.
The parameters
same way as
p001
p002
to
p007
are changed in the
. After step 2, use the [+] key to
move to the required parameter.
5.4.4.Modification of the installer-level
parameters
Parameters p017 to c0nf must only be modified by a
qualified professional. To prevent unwanted settings, some
parameter settings can only be changed after the special access code
0012 is entered.
CAUTION
Modification of the factory settings may be detrimental to
the functioning of the appliance.
260216 - 7600717-001-06
24
Page 26
C003059-A
h
j
-
3x
2x
C003060-A
3x
...x
...x
2x
-
h
j
5. Commissioning
IniControl For C 330 / C 630 ECO
1. Press the two keys f simultaneously and then key [+] until the
symbol - flashes on the menu bar.
2.
Select the fitter menu using the ® key.
c0de
appears on the
display.
3. Use keys [-] or [+] to input the installer code
4. Confirm using key S.
p[001
is displayed with 1 flashing.
5. Press the S key a second time. The value
0012
75
.
°C appears and
flashes (for example).
6. Change the value by pressing the [-] or [+] key. In this example
using key [-] to
7. Confirm the value with the S key:
flashing.
1
60
°C.
p[001
is displayed with
8. If necessary, set other parameters by selecting them using the
[-] or [+] keys.
9. Press the j key 2 times to return to the current operating mode.
The boiler also returns to operating status if no keys are
pressed for 3 minutes.
5.4.5.Setting the maximum heat input for central
heating operation
The speed can be changed using parameter p17. To do this,
proceed as follows:
1. Press the two keys f simultaneously and then key [+] until the
symbol - flashes on the menu bar.
2. Select the installers menu using the key S.
c0de
on the display.
3. Use keys [-] or [+] to input the installer code
4. Confirm using key S.
5. Press the [+] key to go to parameter
is displayed with 1 flashing.
p[1
p[17
0012
.
6. Confirm using key S.
7. Press the [+] key to increase the speed from
(see the graphs for the associated heat output).
50
8. Confirm the value with the S key.
46
9. Press the j key 2 times to return to the current operating mode.
appears
.
to, for example,
25
260216 - 7600717-001-06
Page 27
C003062-A
3x
...x
-
IniControl For C 330 / C 630 ECO
5. Commissioning
5.4.6.Return to the factory settings Reset Param
1. Press the two keys f simultaneously and then key [+] until the
symbol - flashes on the menu bar.
2. Select the installers menu using the key S.
c0de
on the display.
3. Use keys [-] or [+] to input the installer code
4. Confirm using key S.
5. Press the [+] key several times.
Cn1
6. Press the S key.
flashing.
Cn[x
is displayed with 1 flashing.
p[1
p[Cnnf
is displayed with x flashing. This is
0012
is displayed with
the current value of X for CN1. Check this against the value of X
on the type plate.
7. Enter the value of X shown on the type plate using the [-] or [+]
key.
8. Confirm the value with the S key,
Cn[y
is displayed with
flashing. This is the current value of Y for CN2. Check this against
the value of Y on the type plate.
9. Enter the value of Y shown on the type plate using the [-] or [+]
key.
10.Confirm the value with the j key. The factory settings are reset.
11.The display returns to the current operating mode.
appears
.
y
5.4.7.Carrying out an auto-detect
After removing a control PCB, an auto-detect must be carried out. To
do this, proceed as follows:
1. Press the two keys f simultaneously and then key [+] until the
symbol - flashes on the menu bar.
2. Select the installers menu using the key S.
c0de
on the display.
3. Use keys [-] or [+] to input the installer code
4. Confirm using key S.
5. Press the [+] key several times.
is displayed with 1 flashing.
p[1
p[Zd
0012
is displayed with
flashing.
6. Confirm using key j. Auto-detect is carried out.
7. The display returns to the current operating mode.
appears
.
Zd
260216 - 7600717-001-06
26
Page 28
L000168-A
2x
2x
bar
h
j
)
r
d
bar
t
h
j
5. CommissioningIniControl For C 330 / C 630 ECO
5.4.8.Setting the manual mode
In some cases it may be necessary to switch the boiler to manual
operation, For example, if the controller has not yet been
connected. The boiler can be switched to automatic or manual
operation under the symbol E. To do this, proceed as follows:
1. Press the two keys f simultaneously and then key [+] until the
symbol E flashes on the menu bar.
2. Press the S key:
or
The text
sensor is connected). The flow temperature is determined by the
internal heating curve.
or
The value of the minimum flow temperature.
3. Press the [-] or [+] key to increase this value temporarily in manual
operation.
4. Confirm the value with the S key. The boiler is now set to manual
operation.
5. Press the
mode.
with the current water pressure (only if an outside
Zv
key 2 times to return to the current operating
>
27
260216 - 7600717-001-06
Page 29
IniControl For C 330 / C 630 ECO6. Troubleshooting
6Troubleshooting
6.1Shutdowns and lock-outs
For operation of the boiler C 630 ECO:
The features and instructions described are for each boiler
module.
6.1.1.General
The boiler is fitted with an electronic regulation and control unit. The
heart of the control system is a microprocessor, the Comfort
a failure is signalled, the boiler stops or becomes locked.
Shutdown
code
5v[0
5v[1
5v[2
5v[3
5v[4
(1) These lock-outs are not stored in the fault memory
DescriptionProbable causesChecking / solution
Parameter error
Maximum flow temperature
exceeded
Maximum increase of the flow
temperature has been exceeded
Maximum heat exchanger
temperature exceeded
Maximum heat exchanger
temperature increase has been
exceeded
■ Blocking(Control stop)
A (temporary) blocking mode is a boiler operating function caused by
an unusual situation. In this case, the display gives a code of blocking
(code 5t[9). The boiler control will try to re-start several times.
The shutdown codes can be read out as follows
The boiler starts up again automatically when the reason
for the blocking has been removed.
The PSU PCB is incorrectly
configured
The water flow in the
installation is insufficient
The water flow in the
installation is insufficient
Sensor error
The water flow in the
installation is insufficient
The water flow in the
installation is insufficient
Sensor error
4Reset df and dV
4Restore parameters with Recom
4Check the circulation (direction, pump,
valves)
4Check the circulation (direction, pump,
valves)
4Check the water pressure
4Check the cleanliness of the heat
exchanger
4Check that the sensors are operating
correctly
4Check whether the boiler sensor has been
correctly fitted
4Check the circulation (direction, pump,
valves)
4Check the circulation (direction, pump,
valves)
4Check the water pressure
4Check the cleanliness of the heat
exchanger
4Check that the sensors are operating
correctly
4Check whether the boiler sensor has been
correctly fitted
260216 - 7600717-001-06
28
Page 30
6. TroubleshootingIniControl For C 330 / C 630 ECO
Shutdown
DescriptionProbable causesChecking / solution
code
The maximum difference
5v[5
between the exchanger
temperature and the return
temperature has been exceeded
The maximum difference
between the boiler temperature
and the exchanger temperature
has been exceeded
5v[6
Maximum difference between the
flow and return temperature
exceeded
5v[7
The RL inlet on the PCU PCB
5v[8
5v[9
terminal block is open
Phase and neutral of mains
supply mixed up
The BL inlet on the PCU PCB
5v[10
terminal block is open
5v[11
5v[13
5v[14
5v[15
5v[16
5v[17
(1) These lock-outs are not stored in the fault memory
Communication error with the
SCU PCB
The water pressure is lower than
0,8 bar
Gas pressure too low
The SU PCB is not recognisedWrong SU PCB for this
(1)
The parameters saved on the
(1)
PCU PCB are impaired
The water flow in the
installation is insufficient
Sensor error
The water flow in the
installation is insufficient
Sensor error
The water flow in the
installation is insufficient
Sensor error
Parameter error
Bad connection
4Mains supply
incorrectly wired
4Floating or 2 phase
network
The contact connected to
the BL inlet is open
Parameter error
Bad connection
Bad connection
SCU PCB not installed in
the boiler
Not enough water in the
circuit
4Incorrect setting of the
gas pressure switch on
the SCU PCB
4Gas pressure too low
4Wiring fault
4Pressure switch is not
or badly fitted
4Gas valve defect
boiler
Parameter error on the
PCU PCB
4Check the circulation (direction, pump,
valves)
4Check the water pressure
4Check the cleanliness of the heat
exchanger
4Check that the sensors are operating
correctly
4Check whether the boiler sensor has been
correctly fitted
4Check the circulation (direction, pump,
valves)
4Check the water pressure
4Check the cleanliness of the heat
exchanger
4Check that the sensors are operating
correctly
4Check whether the boiler sensor has been
correctly fitted
4Check the circulation (direction, pump,
valves)
4Check the water pressure
4Check the cleanliness of the heat
exchanger
4Check that the sensors are operating
correctly
4Check whether the boiler sensor has been
correctly fitted
4Reset df and dV
4Restore parameters with Recom
4Check the wiring
4Invert phase and neutral
4Set parameter p34 to 0
4Check the contact on the BL inlet
4Check the parameter IN.BL
4Check the wiring
4Check the wiring
4Install an SCU PCB
4Top up the installation with water
4Check that the gas valve is fully opened
4Checking the gas supply pressure
4Check whether the gas pressure control
system has been correctly fitted
4Replace the gas pressure control system
if need be
4Check the gas valve and replace if
necessary
4Replace the SU PCB
4Replace the PCU PCB
29
260216 - 7600717-001-06
Page 31
IniControl For C 330 / C 630 ECO6. Troubleshooting
Shutdown
code
5v[18
5v[19
5v[20
5v[21
5v[22
5v[25
(1) These lock-outs are not stored in the fault memory
DescriptionProbable causesChecking / solution
The PSU PCB is not recognised Wrong PSU PCB for this
(1)
The boiler has not been
(1)
configured
Communication error between
(1)
the PCU and SU PCBs
No flame during operationNo ionization current
No flame during operation
Internal error on the SU PCB
boiler
The PSU PCB has been
changed
Bad connection
No ionization current
4Replace the PSU PCB
4Reset df and dV
4Restore parameters with Recom
4Check that the SU PCB has been correctly
put in place on the PCU PCB
4Replace the SU PCB
4Purge the gas supply to remove air
4Check that the gas valve is fully opened
4Check the supply pressure
4Check the operation and setting of the gas
valve unit
4Check that the air inlet and flue gas
discharge flues are not blocked
4Check that there is no recirculation of flue
gases
4Purge the gas supply to remove air
4Check that the gas valve is fully opened
4Check the supply pressure
4Check the operation and setting of the gas
valve unit
4Check that the air inlet and flue gas
discharge flues are not blocked
4Check that there is no recirculation of flue
gases
4Replace the SU PCB
Error
code
e[00
e[01
■ Blockage(Fault)
If the blocking conditions still exist after several start up attempts, the
boiler will switch into locking mode (fault). The display shows :
In a red flashing display:
4 The symbol c
4 The symbol J
4 The fault code (for example e[01)
4 Press the J key for 2 seconds. If the error code continues to
display, search for the cause in the error table and apply the
solution.
The code is important for the correct and rapid diagnosis
of the type of failure and for any technical assistance that
may be needed.
DescriptionProbable causesChecking / solution
PSU PCB not connectedBad connection
PSU PCB faulty
The safety parameters are
incorrect
Bad connection
PSU PCB faulty
4Check the wiring between the PCU and PSU PCBs
4Replace the PSU PCB
4Check the wiring between the PCU and PSU PCBs
4Replace the PSU PCB
260216 - 7600717-001-06
30
Page 32
6. TroubleshootingIniControl For C 330 / C 630 ECO
Error
code
e[02
e[03
e[04
e[05
e[06
e[07
DescriptionProbable causesChecking / solution
The exchanger sensor is short
circuited
Bad connection
4Check the wiring between the PCU PCB and the
sensor
4Check that the SU PCB is correctly in place
4Check that the sensor has been correctly fitted
Sensor fault
4Check the Ohmic value of the sensor
4Replace the sensor if necessary
The exchanger sensor is on an
open circuit
Bad connection
4Check the wiring between the PCU PCB and the
sensor
4Check that the SU PCB is correctly in place
4Check that the sensor has been correctly fitted
Sensor fault
4Check the Ohmic value of the sensor
4Replace the sensor if necessary
Temperature of heat exchanger
too low
Bad connection
4Check the wiring between the PCU PCB and the
sensor
4Check that the SU PCB is correctly in place
4Check that the sensor has been correctly fitted
Sensor fault
4Check the Ohmic value of the sensor
4Replace the sensor if necessary
No water circulation
4Vent the air in the heating system
4Check the circulation (direction, pump, valves)
4Check the water pressure
4Check the cleanliness of the heat exchanger
Exchanger temperature too highBad connection
4Check the wiring between the PCU PCB and the
sensor
4Check that the SU PCB is correctly in place
4Check that the sensor has been correctly fitted
Sensor fault
4Check the Ohmic value of the sensor
4Replace the sensor if necessary
No water circulation
4Vent the air in the heating system
4Check the circulation (direction, pump, valves)
4Check the water pressure
4Check the cleanliness of the heat exchanger
The return temperature sensor has
short-circuited
Bad connection
4Check the wiring between the PCU PCB and the
sensor
4Check that the SU PCB is correctly in place
4Check that the sensor has been correctly fitted
Sensor fault
4Check the Ohmic value of the sensor
4Replace the sensor if necessary
The return temperature sensor is
on an open circuit
Bad connection
4Check the wiring between the PCU PCB and the
sensor
4Check that the SU PCB is correctly in place
4Check that the sensor has been correctly fitted
Sensor fault
4Check the Ohmic value of the sensor
4Replace the sensor if necessary
31
260216 - 7600717-001-06
Page 33
IniControl For C 330 / C 630 ECO6. Troubleshooting
Error
code
e[08
e[09
e[10
e[11
DescriptionProbable causesChecking / solution
Return temperature too lowBad connection
4Check the wiring between the PCU PCB and the
sensor
4Check that the SU PCB is correctly in place
4Check that the sensor has been correctly fitted
Sensor fault
4Check the Ohmic value of the sensor
4Replace the sensor if necessary
No water circulation
4Vent the air in the heating system
4Check the circulation (direction, pump, valves)
4Check the water pressure
4Check the cleanliness of the heat exchanger
Return temperature too highBad connection
4Check the wiring between the PCU PCB and the
sensor
4Check that the SU PCB is correctly in place
4Check that the sensor has been correctly fitted
Sensor fault
4Check the Ohmic value of the sensor
4Replace the sensor if necessary
No water circulation
4Vent the air in the heating system
4Check the circulation (direction, pump, valves)
4Check the water pressure
4Check the cleanliness of the heat exchanger
Difference insufficient between the
exchanger temperature and the
return temperature
Sensor fault
Bad connection
No water circulation
4Check the Ohmic value of the sensor
4Replace the sensor if necessary
4Check that the sensor has been correctly fitted
4Vent the air in the heating system
4Check the circulation (direction, pump, valves)
4Check the water pressure
4Check the cleanliness of the heat exchanger
Difference between the return
temperature and the exchanger
temperature too big
Sensor fault
Bad connection
No water circulation
4Check the Ohmic value of the sensor
4Replace the sensor if necessary
4Check that the sensor has been correctly fitted
4Vent the air in the heating system
4Check the circulation (direction, pump, valves)
4Check the water pressure
4Check the cleanliness of the heat exchanger
260216 - 7600717-001-06
32
Page 34
6. TroubleshootingIniControl For C 330 / C 630 ECO
Error
code
e[12
e[14
e[15
e[16
DescriptionProbable causesChecking / solution
4Check that the air inlet and flue gas discharge flues
are not blocked
4Check that condensate has been removed and the
cleanliness of the siphon
4Check the cleanliness of the heat exchanger (Flue
4Maximum boiler temperature
exceeded (STB thermostat
maximum)
4Air differential pressure switch
has been triggered
4Air inlet or flue
gas discharge
blocked
4Bad connection
4No water
circulation
4Failure of the
safety device
4Sensor not or
badly connected
gas dimensions)
4Check the wiring between the PCU PCB and the
STB
4Check that the SU PCB is correctly in place
4Check the electrical continuity of the STB
4Check whether the STB has been correctly fitted
4Check that the sensor has been correctly fitted
4Check for correct operation
4Remove the air from the installation
4Check the circulation (direction, pump, valves)
4Check the water pressure
4Check the cleanliness of the heat exchanger
4Check that the heating pump is operating correctly
4Check the wiring between the PCU PCB and the
ignition transformer
4Check that the SU PCB is correctly in place
No ignition
4Check the ionization/ignition electrode
4Check the earthing
4SU PCB faulty: Change the PCB
4Vent the gas flues
4Check that the gas valve is fully opened
4Checking the gas supply pressure
5 burner start-up failures
Ignition arc, but no
flame formation
4Check the operation and setting of the gas valve
unit
4Check that the air inlet and flue gas discharge flues
are not blocked
4Check the wiring on the gas valve unit
4SU PCB faulty: Change the PCB
4Check that the gas valve is fully opened
Presence of the flame
but insufficient
ionization (<3 µA)
4Checking the gas supply pressure
4Check the ionization/ignition electrode
4Check the earthing
4Check the wiring on the ionization/ignition
electrode
The cyclical leak proofing kit (CCE)
has detected a leak
Reset the box
4Check that the gas valve is fully opened
4Checking the gas supply pressure
4Check the gas valve and replace if necessary
Detection of a parasite flameIonization current
4Check the ionization/ignition electrode
present even though
there is no flame
Ignition transformer
defective
Gas valve defect
The burner remains
4Check the gas valve and replace if necessary
4Set the CO
2
very hot: CO2 too high
33
260216 - 7600717-001-06
Page 35
IniControl For C 330 / C 630 ECO6. Troubleshooting
Error
code
e[17
e[32
e[33
e[34
e[35
e[36
e[37
e[38
e[39
DescriptionProbable causesChecking / solution
Problem on the gas valveBad connection
4Check the wiring between the PCU PCB and the
gas valve
4Check that the SU PCB is correctly in place
The boiler flow sensor has shortcircuited
SU PCB faulty
Bad connection
4Inspect the SU PCB and replace it if need be
4Check the wiring between the PCU PCB and the
sensor
4Check that the SU PCB is correctly in place
4Check that the sensor has been correctly fitted
Sensor fault
4Check the Ohmic value of the sensor
4Replace the sensor if necessary
The boiler flow sensor is on an
open circuit
Bad connection
4Check the wiring between the PCU PCB and the
sensor
4Check that the SU PCB is correctly in place
4Check that the sensor has been correctly fitted
Sensor fault
4Check the Ohmic value of the sensor
4Replace the sensor if necessary
The fan is not running at the right
speed
Bad connection
Fan defective
4Check the wiring between the PCU PCB and the
fan
4Check for adequate draw on the chimney
connection
4Replace the fan if need be
Bad connection
Sensor fault
Flow and return reversed
Water circulation
4Check that the sensor has been correctly fitted
4Check the Ohmic value of the sensors
4Replace the sensor if necessary
4Check the circulation (direction, pump, valves)
direction reversed
The flame went out more than 5
times in 24 hours while the burner
was operating
No ionization current
4Purge the gas supply to remove air
4Check that the gas valve is fully opened
4Checking the gas supply pressure
4Check the operation and setting of the gas valve
unit
4Check that the air inlet and flue gas discharge flues
are not blocked
4Check that there is no recirculation of flue gases
Communication failure with the
SU PCB
Bad connection
4Check whether the SU PCB has been correctly
fitted into the connector on the PCU PCB
4Change the SU PCB
Bad connection
Communication error with the
SCU PCB
SCU PCB not
4Check the wiring between the PCU and SCU PCBs
4Reset df and dV
4Restore parameters with Recom
4Replace the SCU PCB
connected or faulty
Shutdown input in locked-out
mode
Bad connection
External cause
Parameter incorrectly
4Check the wiring
4Check the device connected to the BL contact
4Check the parameter IN.BL
set
260216 - 7600717-001-06
34
Page 36
L000169-A
4x
2x
h
j
h
j
h
j
6. TroubleshootingIniControl For C 330 / C 630 ECO
6.2Error memory
The boiler control is equipped with an error memory. The last 16 errors
encountered are recorded in this memory.
In addition to the error codes, the following data are also saved:
4 Number of times that the error occured: (MK[xx).
4 Boiler operating mode selected (5t[xx).
4 The flow temperature (t1[xx) and the return temperature
(t2[xx) when the error occured.
To view the error memory, you first have to enter access code
0012.
6.2.1.Error readout memorised
1. Press the two keys f simultaneously and then key [+] until the
symbol a flashes on the menu bar.
2. Select the installers menu using the key S.
c0de
on the display.
3. Use keys [-] or [+] to input the installer code
4. Press the S key.
er[xx
appears on the display.
0012
5. The fault list or shutdown list can be displayed by pressing the
[-] or [+] key.
6. Confirm using key S.
er[xx
is displayed with
flashing = Last error which occured, For example
7. Use the [-] or [+] key to scroll through the faults or shutdowns.
8. Press the S key to display the details of the faults or shutdowns.
9. Press the j key to interrupt the display cycle.
displayed with
flashing = Last error which occured.
xx
er[xx
10.Press the j key to show the fault list or shutdown list.
11.Press 2 times on the key j to exit the error memory.
xx
K2
appears
.
.
is
35
260216 - 7600717-001-06
Page 37
L000170-A
3x
4x
h
j
IniControl For C 330 / C 630 ECO6. Troubleshooting
6.2.2.Deletion of the error display
1. Press the two keys f simultaneously and then key [+] until the
symbol a flashes on the menu bar.
2. Select the installers menu using the key S.
c0de
on the display.
3. Use keys [-] or [+] to input the installer code
4. Press the S key.
er[xx
appears on the display.
0012
5. The fault list or shutdown list can be displayed by pressing the
[-] or [+] key.
6. Confirm using key S.
er[xx
7. Press the [+] key several times until
is displayed with
er[cl
is displayed on the
screen.
8. Press the S key.
cl[0
is displayed with 0 flashing.
9. Press key [+] to modify the value to 1.
10.Press the S key to delete the errors from the error memory.
11.Press 3 times on the key j to exit the error memory.