n
Performances in hot mode with outside air temperature
at +7°C and outlet water temperature at +35°C (in
accordance with EN 14511–2)
AWHP 4 MR 6 MR -2 8 MR-2 11 MR-2 11 TR-2 16 MR-2 16 TR-2 22 TR 27 TR
Calorific output - A7/W35 kW 3.72 5.87 8.26 10.56 10.56 14.19 14.19 19.40 24.4
COP hot - A7/W35
4.15 4.18 4.27 4.18 4.18 4.22 4.15 3.94 3.90
Absorbed electrical power - A7/W35 kWe 0.90 1.41 1.93 2.53 2.53 3.36 3.42 4.92 6.25
Nominal amperage - A7/W35 A 4.11 6.57 8.99 11.81 3.80 16.17 5.40 7.75 9.86
n
Performances in hot mode with outside air temperature
at +2°C and outlet water temperature at +35°C (in
accordance with EN 14511–2)
AWHP
4 MR 6 MR -2 8 MR-2 11 MR-2 11 TR-2 16 MR-2 16 TR-2 22 TR 27 TR
Calorific output - A2/W35 kW 3.76 3.87 5.93 10.19 10.19 11.38 11.38 12.10 14.70
COP hot - A2/W35
3.32 3.26 3.12 3.20 3.20 3.22 3.22 3.10 3.10
Absorbed electrical power - A2/W35 kWe 1.13 1.19 1.90 3.19 3.19 3.53 3.53 3.91 4.70
Nominal amperage - A2/W35 A 6.1 6.1 8.2 10.7 6.2 14.6 8.4 9.7 11.8
n
Performances in cold mode with outside air
temperature at +35°C and outlet water temperature at
+7°C (in accordance with EN 14511–2)
AWHP
4 MR 6 MR -2 8 MR-2 11 MR-2 11 TR-2 16 MR-2 16 TR-2 22 TR 27 TR
Cooling output kW 2.27 3.13 4.98 7.43 7.43 7.19 7.19 / /
EER
3.28 3.14 2.7 3.34 3.34 3.58 3.58 / /
Frigorific output range kW 1,12-4 1,12-4,5 2-6,6 3,2-9,1 3,2-9,1 4,1-12,5 4,1-12,5 6,2-15,2 7,6-18,7
Absorbed electrical power kWe 0.69 1.0 1.85 2.22 2.22 2.01 2.01 / /
n
Performances in cold mode with outside air
temperature at +35°C and outlet water temperature at
+18°C (in accordance with EN 14511–2)
AWHP
4 MR 6 MR -2 8 MR-2 11 MR-2 11 TR-2 16 MR-2 16 TR-2 22 TR 27 TR
Cooling output kW 3.84 4.69 7.90 11.16 11.16 14.46 14.46 17.65 22.2
EER
4.83 4.09 3.99 4.68 4.68 4.43 4.43 3.80 3.80
Frigorific output range kW 1,7-4,5 1,7-4,5 2,6-9,5 4,6-14 4,6-14 5,8-16 5,8-16 9-22,4 11,2-28
Absorbed electrical power kWe 0.72 1.15 2.0 2.35 2.35 3.65 3.65 4.65 5.84
3. Technical specifications AWHP-2 MIT-IN-2 iSystem
15