DCI C1103, C1203, C2106, C2206, C3210 Installation Manual

Compressor Installation Guide
C Series
COMPRESSOR
• C1103
• C1203
• C2106
• C2206
• C3210
Copyright © 2006 DCI. All Rights Reserved.
92094, Rev. D, 08/13
1 www.dcionline.com
www.dcionline.com
C - Series
Compressor
C Series Installation Guide
Compressor Model Specification
Oil-Less
# Heads
Tank
Power
Power
Model # # of Heads Tank Size Voltage Breaker Size Amps
C1103 1 Horizontal 20 gal. 115 20 Amps 13.4
C1203 1 Horizontal 20 gal. 230V 20 Amps 6.7
C2106 2 Horizontal 20 gal. 115V 30 Amps 26.8
C2206 2 Horizontal 20 gal. 230V 20 Amps 13.4
C3210 3 Horizontal 30 gal. 230V 30 Amps 20.1
All Voltage Ratings ± 5%.
NOTE: 1) All machines are of the 3 wire grounded system type.
2) Minimum Breaker size 30 amp & larger wire size #10 supply connection.
29.50"
33"
16"
39"
11.69"
23"
NOTE: Installation of this product should be undertaken only
If the product does not function as described in the start-up and
test procedures in this manual, call the number below for assistance.
NOTE: Air fl ow rates in excess of compressor ratings will result
Space Requirements
by qualifi ed service technicians.
This product has been factory-tested prior to shipment.
Technical Support: 1-800-624-2793
in reduced performance and possible overheating.
1.800.624.2793
46"
26"
1
C Series Installation Guide
Installation Kit
Compressor Installation Kit
Installation Kit
The C - Series is shipped with the following:
Lock Washer
Flat Washer
Antivibration Foot
Wire Nuts
Nut
Split Bushing
Conduit Connector
You must provide:
Fittings and bushings as required to connect the
exible hose to the on-site piping (the hose-end is 3/8 in. NPT “male”).
Earthquake restraints for securing the equipment
if required by local codes.
6 ft. Hose
2
www.dcionline.com
C Series Installation Guide
Site Requirements
Clearance Site Requirements
Adequate clearance as shown below for servicing and air circulation — room
temperature should be maintained between 40°F and 100°F when the motors are running.
A fl at, level fl oor that provides stable support.
Protection from the weather and direct sunlight.
A power source within 3 ft. of back-center that provides a dedicated,
breaker-protected circuit.
Compressor Site Requirements
WARNING! Fire Hazard! Running motors generate heat. Do not store fl ammable
liquids or objects such as clothing, mops, or brooms near or above the unit.
PLUMBING REQUIREMENTS
1. 1/2 in I.D. minimum pipe size.
2. Pipe connection is to be located within 3 ft of
center back of compressor.
3. Install per all Local and State plumbing codes.
ELECTRICAL REQUIREMENTS
1. 3 wire single phase 115 vac or 230 vac. All
voltage ratings ± 5%.
2. Green Wire is to be grounded to a suitable system ground.
3. Power supply must be on a dedicated circuit.
4. See data tag for appropriate breaker size.
5. Power supply connection is to be located
within 3 ft of center back of compressor.
6. Install per all local and State electrical codes.
1.800.624.2793
3
Loading...
+ 11 hidden pages