Datexel DAT 3016 User Manual

Thermocouple RS485 Converter 4 channel Phone: +1 561 779 5660 E-mail : Info@datexel.com - Web Site www.datexel.com
4 channel Thermocouple to RS485
Converter
DDAAT T 33016
016
FEATURES
- Field-Bus remote data acquisition
- Modbus Slave device on RS-485
- Modbus RTU/ Modbus ASCII protocol
- 4 channels input
- Input configurable for Tc J, K, R, S, B, E, T, N and voltage up to ± 1V
- Watch-Dog Alarm
- Remotely Configurable
- 2000 Vac 3-ways Galvanic Isolation
- High Accuracy
- UL / CE mark
- DIN rail mounting in compliance with EN-50022
(1) Referred to input Span (di fference between max. and min.
Values)
(2) A pull-up resistor ( 10MW) is connected to +1V (brea k sensor)
GENERAL DESCRIPTION
The DAT 3016 device is able to acquire up to 4 analogue input signals. The data are transmitted with MODBUS RTU/MODBUS ASCII protocol on the RS-485 network (RS-232 interface is available). It is possible to connect on input thermocouples or voltage signals up to ± 1V . The Cold Junction compensation for thermocouples is internally performed. The device guarantees high accuracy and stable measure versus time and temperature. To ensure the plant safety, two Watch-Dog timer alarms are provided. The isolation between the parts of circuit removes eventual ground-loop effects, allowing the use of the device even in the heavy environmental conditions. The DAT 3016 is in compliance with the Directive UL 61010-1 for US market and with the Directive CSA C22.2 No 61010-1 for the Canadian market. The device is housed in a rough self-extinguishing plastic container which, thanks to its thin profile of 17.5mm only, allows a high density mounting on EN-50022 standard DIN rail.
COMMUNICATION PROTOCOLS
The DAT3016 is designed to work with the MODBUS RTU/MODBUS ASCII protocol: standard protocol in field-bus; allows to directly interface DAT3000 series devices to the larger part of PLCs and SCADA applications available on the market. For the protocol instructions, refer to the User Guide of the device.
USER INSTRUCTIONS
Before to install the device, please read the “Installation Instruction” section. If the module configuration is unknown, with device powered off, connect the INIT terminal to the GND terminal (ground), at the next power on the device will be auto-configured in the default settings (refer to the User Guide of the device). Connect power supply, serial bus and analogue inputs as shown in the “Wiring” section. The “PWR” LED state depends on the working condition of the device: see the "Light Signalling" section to verify the device working state. To perform configuration and calibration operations, read the instructions in the User Guide of the device. To simplify handling or replacing of the device, it is possible to remove the wired terminals even with the device powered.
TECHNICAL SPECIFICATIONS (Typical @ 25 °C and in the nominal conditions)
Input Accuracy (1)
mV/Tc the higher of
± 0.05% or 5 uV(1)
Linearity (1)
mV ± 0.1% f.s. (1) Tc ± 0.2% f.s. (1)
Cold Junction Compensation ± 0.5 °C
Input Impedance
mV, Tc >/= 1 MW (2)
Thermal drift
Full Scale ± 0.005 % / °C (1)
CJC Thermal drift
Full Scale ± 0.02 %/ °C
Lead wire resistance influence
mV, Tc < 0.8 uV/Ohm (1)
Sample time 0.5 ÷ 1 sec.
Data Transmission
Baud Rate 38.4 Kbps Max. distance 1.2 Km – 4000 ft
Warm-up time 3 min.
Voltage
25 mV -25 mV +25 mV 100 mV -100 mV +100 mV 250 mV -250 mV +250 mV 1000 mV -1000 mV +1000 mV
Thermocouple
J -210 °C +1200 °C K -210 °C +1372 °C R -50 °C +1767 °C S -50 °C +1767 °C B +400 °C +1825 °C E -210 °C +1000 °C T -210 °C +400 °C N -210 °C +1300 °C
Input type Min Max
INPUT
MECHANICAL SPECIFICATIONS
Material Self-extinguish plastic IP Code IP20 Wiring wires with diameter
0.8÷2.1 mm2 /AWG 14-18 Tightening Torque 0.5 N m Mounting in compliance with DIN rail
standard EN-50022
Weight about 150 g.
ISOLATION
Input – RS485 2000 Vac 50 Hz, 1 min. Supply – Input 2000 Vac 50 Hz, 1 min. Supply – RS485 2000 Vac 50 Hz, 1 min.
POWER SUPPLY
Power supply voltage 10 .. 30 Vdc Reverse polarity protection 60 Vdc max
Current consumption 30 mA max.
ENVIRONMENTAL CONDITIONS
Operative Temperature -10°C .. +60°C UL Operative Temperature -10°C .. +40°C Storage Temperature -40°C.. +85°C Humidity (not condensed) 0 .. 90 % Maximum Altitude 2000 m Installation Indoor Category of installation II Pollution Degree 2
CERTIFICATIONS EMC ( for industrial environments)
Immunity EN 61000-6-2 Emission EN 61000-6-4
UL
US Standard UL 61010-1 Canadian Standard CSA C22.2 No 61010-1 CCN NRAQ/NRAQ7 Typology Open Type device Classification Industrial Control
Equipment
File Number E352854
Datexel s.r.l. reserves its right to modify the characteristics of its products totally or in part without warning at any time.
ED.03.15 REV.01
V+
D-
D+
V-
RS-485
SHIELD
INPUT #0
INIT
INPUT #1
INPUT #3
INPUT #2
A
BCD
I
J
1
3456728
+
-
10÷30 Vdc
J
I
-V
+V
GND
D -
D +
(-)
(+)
A
C
B
120
20
17.5
1 0 0
Voltage
2
1
INPUT 0
+
4
3
INPUT 1
+
6
5
INPUT 2
+
8
7
INPUT 3
+
Thermocouple
2
1
INPUT 0
+
4
3
INPUT 1
6
5
INPUT 2
8
7
INPUT 3
+ + +
= Ref.2 4 6 8
GND
TX
RX
RS-232
RX
TX
E
C
F
GND
INSTALLATION INSTRUCTIONS
The DAT 3016 is suitable for fitting to DIN rails in the vertical position. For optimum operation and long life follow these instructions:
When the devices are installed side by side it may be necessary to separate them by at least 5 mm in the following case:
- If panel temperature exceeds 45°C and at least one of the overload conditions exist.
Make sure that sufficient air flow is provided for the device avoiding to place raceways or other objects which could obstruct the ventilation slits. Moreover it is suggested to avoid that devices are mounted above appliances generating heat; their ideal place should be in the lower part of the panel. Install the device in a place without vibrations.
Moreover it is suggested to avoid routing conductors near power signal cables (motors, induction ovens, inverters etc...) and to use shielded cable for connecting signals.
CABLING
LIGHT SIGNALLING
LED
COLOUR
STATE
DESCRIPTION
PWR
GREEN
ON
OFF
FAST BLINK
1 second BLINK
Device powered
Device not powered / W rong RS-485 cabling.
Communication in progres s (blink frequency depends to baud-rat e)
Watch-Dog Al arm condition
MECHANICAL DIMENSIONS (mm)
WIRING
ANALOG INPUT
NOTE: input channels are not isolated between them.
RS-485 NETWORK RS-232 NETWORK
RS-485 network
POWER SUPPLY (*)
INIT
ON: short-circuit to GND
D
C
GND
INIT
HOW TO ORDER
In the order phase, it is mandatory to specify the interface type (RS485 or RS232) . DAT3016 can be supplied with the configuration specified by the customer.
ORDER CODE:
DAT 3016 / 485 / Tc K
Input typeInterface type 485 : RS-485 232 : RS-232
= Requested
= Optional
(*) Note: for UL installation the device must be powered using a power supply unit classified NEC class 2 or SELV
POWER SUPPLY
SERIAL BUS
ANALOGUE INPUTS
ISOLATION STRUCTURE