Datel DMS-PS-CM User Manual

C
®
US E156931
Universal Input
TB4
F1
1A/250V
TB1
LDO
Regulator
DC/DC
Converter
IN
OUT
GND
AC(L)
AC(N)
FG
+
V1
TB2
+
V2
LDO
Regulator
DC/DC
Converter
AC/DC Converter
Drive
Circuitry
(Auxilliary)
(Auxilliary)
(Main)
IN
OUT
GND
TB3
+
V3
+
+
+
+
+
+
+
+
+
**
*
**
**
Used only on dual and triple-output models
*Not used on single-output models
85-264V 50/60Hz
+
85-264Vac or 110-340Vdc
FEATURES
n
Up to 80% efficient single, dual, and triple-
output model
nIndividual, fully-isolated outputs:
3000Vac on main 4000V double-isolation on auxiliaries
nAvailable with +5V, +12V, and +24V outputs
nLow noise: 40mVp-pk on main, 8mVp-pk on
auxiliaries; Ideal for sensitive instrumentation
nUniversal input: 85-264Vac @ 47-63Hz or
110-340Vdc
nChoice of 5, 10, or 16W models for minimal
system power-consumption
nStandby power consumption as low as 0.6W
n Short-circuit protection on all outputs;
OVP on main output
nBuilt-in ac mains fuse & ‘Power On’ indicator
n5W models operate up to 5 LED-display DPM’s
nVibration-resistant, chassis-mount
modular packages
nEMC compliant; UL/CSA recognized
nLow cost!
High Efficiency, AC/DC Instrumentation Power
Supplies with Individually Isolated Outputs
Murata Power Solution’s DMS-PS-CM Series of high-efficiency, chassis mount AC/DC power supplies feature low noise (40mV on main, 8mV on auxiliaries), fully-isolated +24, +12V, and +5V outputs, making them perfect for powering today’s complex instrumenta­tion. A high-current main output is isolated from the AC line by 3000Vac. In dual- and triple-output models, the low-current auxiliary outputs are isolated from the main output by 1000Vdc, and from each other by 2000Vdc, effectively providing double isolation from the AC line! This unprecedented isolation elimi­nates ground loop problems in complex, multiple-instrument applications.
Full-load efficiencies of up to 80% and output-power ratings of 5, 10 or 16 Watts, combine to ensure minimal ac power con­sumption. For intermittent use or low-power applications, the 5-Watt model’s no-load quiescent consumption with a nominal 120Vac input is a mere 0.6 Watts---that’s nearly seven times less than a standard 4W
DMS-PS-CM Series
night light! These low cost, high-efficiency power supplies can significantly reduce long-term electricity costs in low (<5Watts) to medium (<16Watts) power applications.
All DMS-PSX-CM power supplies fea­ture universal inputs of 85-264Vac 50/60Hz, built-in line fuses, and on-board ‘Power On’ LED indicators. At full rated load, hold-up time is typically 20ms at 120Vac, and 80ms at 230Vac. All outputs provide indefinite short-circuit protection and, for added reli­ability, the main high-current output also includes overvoltage protection. A rugged, vibration-proof, chassis mount package incorporates large, shock-resistant terminal blocks for all I/O connections.
Multiple outputs, low noise, low cost, high efficiency, double isolation, and rugged construction combine to make DMS-PSX­CM Series AC/DC power supplies the ideal choice for powering today’s sensitive instrumentation, and any electronic device that requires a reliable dc voltage!
or
110-340Vdc
MPM_DMS-PS-CM_B01 Page 1 of 8
Figure 1. Simplified Schematic
Figure 1. DMS-PS-CM Series Simplified Schematic
www.murata-ps.com Technical enquiries email: sales@murata-ps.com, tel: +1 508 339 3000
Performance/Functional Specifications
Typical at TA = +25°C and VIN = 85-264V @47-63Hz
DMS-PS-CM Series
High Efficiency, AC/DC Instrumentation Power
Supplies with Individually Isolated Outputs
AC Input
Input Voltage Range, All models 85-264V @47-63Hz
Input Current (115V/230V, typ.):
5-Watt Models 0.15A/0.07A
10-Watt Models 0.3A/0.13A
16-Watt Models 0.33A/0.16A
Inrush Current (All models, typical peak):
@115Vac 14.1A
@230Vac 32.5A
Isolation (Min.):
Output V1 to AC Input 3000Vac
Outputs V2 & V3 to AC Input 3000Vac + 1000Vdc
AC Input to Frame Ground 1500Vac
Output V1 to Frame Ground 500Vac
Outputs V2 & V3 to Frame Ground 500Vac + 1000Vdc
Outputs V2 & V3 to Output V1 1000Vdc
Output V2 to Output V3 2000Vdc
Frame Ground Leakage Current (Max.):
@115Vac 0.5mA
@230Vac 3.5mA
Switching Frequency (Typical):
V1 (5W and 10W models) 75kHz
V1 (16W models) 83kHz
V2 & V3 (All models) 100kHz
Line Fuse (Built-in) 1A/250Vac, 5 x 20mm, meeting
IEC60127-2, sheet 3 specification for time lag fuses
(slow-blow)
AC Mains Terminal Block (TB4):
Wire Size & Type 14-20AWG (2.5 to 0.5mm2),
solid or stranded
Insulation Strip Length 0.25 inches (6.4mm)
Screw Tightening Torque 4.4 pound-inches (0.5Nm)
Rated Voltage 630V (VDE 0110-V. Group 2);
250V (VDE 0110-V. Group 3)
EMI (All models) Meets CISPR Pub. 22 & FCC
Class B
Safety Approvals Pending
DC Outputs
Line Regulation (All outputs) ±0.1% (max)
Load Regulation:
V1 (All models) ±2%
V2 & V3 (All models) ±0.2% (max)
Output Accuracy (Max.):
V1 (All models) ±2.0%
V2 & V3 (All models) ±2.5%
Hold-Up Time (47-63Hz):
@115Vac 20mSec. typ.
@230Vac 80mSec. typ.
Noise & Ripple
(All models, 20MHz bandwidth): See Noise & Ripple graphs
V1 40mVp-pk (typ.)
V2 & V3 8mVp-pk (typ.)
Transient Response See Transient Response graphs
DC Outputs (continued)
Efficiency (Typ.@ 120Vac, full load):
Single Output Models 75%
Dual Output Models 73%
Triple Output Models 71%
DC-Output Terminal Blocks (TB1, TB2, TB3):
Wire Size &Type 16-20AWG (1.5 to 0.5mm2),
solid or stranded
Insulation Strip Length 0.25 inches (6.4mm)
Screw Tightening Torque 3.6 pound-inches (0.4Nm)
Short Circuit Protection (All outputs) Foldback, self-recovering
Overvoltage Protection V1 (max.) 134% x Vout
Environmental
Operating Temperature 0 to +50°C @ full rated power;
–25 to +70°C @ 50% rated power (see Figure 3)
Storage Temperature –40 to +85°C
Cooling Free air convection with derating
(see Figure 3 and Technical
Notes)
Humidity (Non-condensing) 0 to 85%
Physical
Dimensions See Mechanical Specifications
Weight:
5 Watt Models 5.8 ounces (165 grams)
10 Watt Models 6.9 ounces (195 grams)
16 Watt Models 7.9 ounces (223 grams)
Case Materials:
Outer Case ABS, UL94 5VA
DC/DC Modules Phenolic, UL94 V-0
AC/DC Modules Plastic, UL94 V-1
All models will also operate from a regulated and filtered 110 to 340Vdc input.
Unless otherwise specified, load regulation is measured with the output under
test undergoing a load change of 100% to 50% at nominal line input and, when applicable, with all other outputs operating at 50% of rated load.
Transient response is defined as the output returning to within its specified
tolerance in 10ms or less, following a 90% load change.
Technical enquiries email: sales@murata-ps.com, tel: +1 508 339 3000www.murata-ps.com
MPM_DMS-PS-CM_B01 Page 2 of 8
0.25"
(6.4mm)
DMS-PS-CM Series
High Efficiency, AC/DC Instrumentation Power
Supplies with Individually Isolated Outputs
Ordering Information and Selection Guide
MPS Part No. Rated Power Efficiency V1 Output V2 Output V3 Output
DMS-PS1-CM 5 Watts 75% 5Vdc/1A
DMS-PS2-CM 5 Watts 73% 5Vdc/0.65A 4.85Vdc/0.2A
DMS-PS3-CM 5 Watts 71% 5Vdc/0.35A 4.85Vdc/0.2A 4.85Vdc/0.2A
DMS-PS4-CM 10 Watts 80% 24Vdc/0.45A
DMS-PS5-CM 10 Watts 75% 24Vdc/0.35A 4.85Vdc/0.2A
DMS-PS6-CM 10 Watts 73% 24Vdc/0.30A 4.85Vdc/0.2A 4.85Vdc/0.2A
DMS-PS7-CM 16 Watts 82% 24Vdc/0.70A
DMS-PS8-CM 16 Watts 76% 24Vdc/0.60A 4.85Vdc/0.2A
DMS-PS9-CM 16 Watts 74% 24Vdc/0.55A 4.85Vdc/0.2A 4.85Vdc/0.2A
DMS-PS10-CM 16 Watts 82% 12Vdc/1.35A
Efficiency typical @120V/60Hz
TECHNICAL NOTES
IMPORTANT! To ensure safe and reliable operation, DMS-PS-CM
power supplies must be installed and serviced by qualified
personnel. Contact Murata Power Solutions if there is any doubt
regarding their installation and/or operation. Please read all of the
following technical and application notes BEFORE installing or
making connections to DMS-PS-CM power supplies.
Warnings (Marking)
Caution, unit may become hot in normal operation, thereby creat­ing a potential burn hazard. Disconnect ac mains and then allow unit to cool before servicing. Reference document: IEC 417, No. 5041.
Dangerous, potentially lethal voltages are present during normal operation. Disconnect ac mains before servicing. Reference document: IEC 417, No. 5036.
Caution, refer to accompanying documents for more informa­tion. Reference document: ISO 3864, No. B.3.1.
1. Shock Hazard: DMS-PS-CM Series power supplies feature touch-proof
terminals blocks and fully-isolated plastic construction, thereby greatly reduc-
ing the risk of electrical shock. However, these are mains-powered devices
whose operation is derived from hazardous and potentially lethal voltages.
All service and installation must be performed by qualified personnel, with
the ac supply voltage de-energized. Before making connections to any of
the unit’s terminal blocks, use a digital voltmeter to verify that the ac supply is
de-energized (off).
2. AC Supply Fuse (F1): All DMS-PS-CM Series power supplies are equipped
with a built-in 1A/250V time-lag fuse. Replacement fuses must be of the
same type and rating; please refer to the Functional Specifications section
of this datasheet for more information. F1 is conservatively rated in order
to reduce nuisance tripping which might occur during power-up or output
overload conditions. However, F1 is primarily intended to provide protection in
the event of catastrophic failure in the DMS-PS-CM’s ac/dc converter.
3. Fuse Replacement: If any dc-output drops to zero volts, and no fault
conditions exist within the external load circuitry or the ac mains, F1 may
have failed. F1 is located on the circuit (etch) side of the pc-board. Fuse
replacement is performed by first de-energizing and then disconnecting
the ac mains from TB4. Next, disconnect all load wiring from TB1, TB2,
and TB3. Lastly, remove the four screws that secure the pc-board to the
plastic case. After making sure that the new fuse is securely attached to its
mounting clips, re-assemble the unit using all four screws. Reconnect all
input and output wiring and re-apply ac power.
If the unit still does not operate properly, and the ac supply at TB4 is
measured to be within its specified operating range, the power supply
is defective and must be replaced. Except for F1, DMS-PS-CM supplies
contain no other user-serviceable components.
4. Wire Gauges and Fusing: All wiring connected to the DMS-PS-CM’s
terminal blocks must meet the requirements specified in the Functional
Specifications section. All ac supply and load wiring must be rated for the
voltages and currents they will conduct and must comply with any code
or application-mandated requirements pertaining to the user’s specific
installation. Applications subject to vibration should include adequate strain
reliefs on both input and output wiring. Install the strain reliefs within 2-3
inches (5-7.5cm) of the terminal blocks.
It is recommended that all wiring be rated for 600V and 105°C operation
(UL1015 type, for example). Also, wire insulation must be stripped to within
±10% of the dimensions shown in Figure 2. All wires must be inserted
into their respective terminal blocks such that the screw terminal does not
pinch their insulation. No more than two wires should be connected to
any single terminal on TB1 through TB4. If two wires are attached to a
single terminal, be sure to use only two 20AWG (0.5mm2) wires on TB1,
TB2, and TB3, and only two 18 or 20AWG (0.75 or 0.5mm2) wires on TB4.
Figure 2. Insulation Strip Length
Technical enquiries email: sales@murata-ps.com, tel: +1 508 339 3000www.murata-ps.com
MPM_DMS-PS-CM_B01 Page 3 of 8
Loading...
+ 5 hidden pages