DATEL ACA5-20PC-9-DC3-RL, ACA5-20PC-9-DC3-RH, ACA5-20PC-9-DC3-GS, ACA5-20PC-9-DC2-RL, ACA5-20PC-9-DC1-RL Datasheet

...
DATEL, Inc., Mansfield, MA 02048 (USA) • Tel: (508)339-3000, (800)233-2765 Fax: (508)339-6356 E–mail: sales@datel.com • Internet: www.datel.com
ACA5-20PC Series
ACA5-20PC Series AC Ammeters are designed to scale and digitally display the output of standard, 5A-output current transformers (50:5A, 500:5A, 1000:5A, etc.). Simply pass the secondary/output wires of the "primary" CT through the ACA5-20PC's on-board CT, apply power to the meter, and you're instantly measuring ac currents over one of 14 ranges from 0-50A (with 100mA resolution) to 0-2000A (with 1A resolution). Because they accept outputs from previously installed high-current CT's, ACA5-20PC's can instantly bring modern digital precision to older ac ammeters.
The functionally complete ACA5-20PC ammeters incorporate scaling/interface circuitry to mate the on-board CT to a precision (3½ digit) A/D converter. The A/D's output directly drives the meters' large (0.37"/9.4mm digit height), easy-to-read, LED displays. All models employ auto-zero circuits, precision bandgap references, and super stable metal-film resistors for unsurpassed accuracy (±0.15%FS) and stability.
ACA5-20PC meters are either ac (120/220/277Vac @ 50/60Hz or 120Vac @ 400Hz) or dc (+5V, +5-40V, or +36-75V) powered. AC models can be powered by the same ac supply whose current they are monitoring. All ACA5-20PC's provide 2000Vdc isolation between the measured ac current and their power supply, and all models are UL/CSA recognized.
Each meter is housed in a subminiature, 1.38" x 0.88", epoxy-encapsulated package whose behind-the-panel installation depth is 2 inches. Display color options include standard red, high-intensity red, and standard green. Each meter is supplied with a plastic bezel assembly with sealing gaskets (DATEL DMS-BZL4).
Digital-Readout
LED-Display
50-2000A AC Ammeters
Figure 1. ACA5-20PC Series Simplified Schematic
Features
Scales and displays the output of 50:5A to
2000:5A current transformers
14 ranges (0-50 Amp to 0-2000 Amp)
3 LED options, 6 power options, 112 models
Functionally complete:
On-board 5A current transformers Scaling/interface circuitry Precision A/D converters Bright red or green LED displays
Subminiature, 1.38" x 0.88" package
Easy-to-read, 0.37"/9.4mm digits
AC powered models: 120Vac @ 400Hz,
120/220/277Vac @ 50/60Hz
AC models can be "self-powered"
DC powered models: +5V, +5-40V, +36-75V
2000V isolation; UL/CSA recognized
Digital replacements for analog ammeters
®
®
AC or DC
INPUT POWER
3½ DIGIT
A/D CONVERTER
+V –V
+
PRECISION FULL-WAVE
RECTIFIER
CAL.
BUILT-IN
0-5A CURRENT
TRANSFORMER
LED DISPLAY
POWER
CONVERTER
TB1
A B
+
(L1)
OUTPUT FROM 50:5A
TO 2000:5A EXTERNAL
CURRENT TRANSFORMER
E156931
Order on-line at www.datel.com
2
DATEL, Inc., Mansfield, MA 02048 (USA) • Tel: (508)339-3000, (800)233-2765 Fax: (508)339-6356 E–mail: sales@datel.com • Internet: www.datel.com
ACA5-20PC Series
5A INPUT, 3½ DIGIT, LED DISPLAY, AC AMMETERS
Performance/Functional Specifications
Typical at TA = + 25°C, unless otherwise noted.
Technical Notes
IMPORTANT! To ensure safe and reliable operation, ACA5-20PC ammeters must be installed and serviced by qualified technical personnel. Contact DATEL if there is any doubt regarding ammeter installation and/or operation.
1. Measurement Type: ACA5-20PC ac ammeters employ a full-wave-
rectified, average responding, rms-calibrated circuit to measure the stepped-down output of their built-in L1 current transformer (CT) . Stated accuracy specifications are measured using a sine-wave current at or close to the full-scale input level, at nominal line frequency.
2. Calibration: Periodic recalibration of ACA5-20PC ammeters is not required under normal, indoor operating environments. If user calibration is necessary, it should be performed by qualified technical personnel. Calibration is performed with potentially lethal voltages applied to the ACA5-20PC and its associated wiring, with the specified full-scale current flowing through the ammeter’s built-in current transformer. A plastic, fully-insulated adjusting tool must be used to access the recessed calibration potentiometer located on the back of the meter (see Mechanical Specifications). Contact DATEL if additional information is required regarding calibration, setup, or any other technical issue pertaining to ACA5-20PC ammeters.
3. Wire Gauges and Fusing: Wires specified in the Functional Specifications section must be used for making connections to ACA5­20PC Series ammeters. All power-supply and load wiring must be rated for the supply voltages and currents they will conduct and must comply with any code or application-mandated requirements pertaining to the user’s specific installation.
Rated Full-Scale Current Min. Typ. Max. Units All Models 5.0 Amps Overcurrent Rating 1.5 x rated full-scale current Performance Sampling Rate 2.5 samples per second Accuracy ±0.15%FS ±6 counts Measurement Type Sine wave input, full-wave
averaging, rms calibrated
Temperature Drift (0 to +60°C) ±0.2 ±0.4 Counts/°C Zero-Current Reading -001 000 001 Counts Dielectric Withstanding Voltage 2000 Vdc Power Supply Voltage
ACA5-20PC-X-AC1-XX 85 120 264 Vac@47-99Hz ACA5-20PC-X-AC2-XX 85 120 140 Vac@350-450Hz ACA5-20PC-X-AC3-XX 240 264 310 Vac@47-99Hz ACA5-20PC-X-DC1-XX +4.75 +40 Vdc ACA5-20PC-X-DC2-XX +36 +75 Vdc ACA5-20PC-X-DC3-XX +4.75 +5.25 Vdc
Power Supply Current
ACA5-20PC-X-AC1,3-XX 30 50 mA@47-99Hz ACA5-20PC-X-AC2-XX 30 50 mA@350-450Hz ACA5-20PC-X-DC1,2-XX +8 +12 mAdc ACA5-20PC-X-DC3-XX +80 +120 mAdc
Power Supply Terminal Block Wire Size & Type 16-22AWG (solid or stranded) Insulation Strip Length 0.25 inches Screw Tightening Torque 3.6 pound-inches (0.4Nm) Maximum Rated Voltage 310Vac Display Display Type and Size 3½ digit LED, 0.37"/9.4mm digit height Overrange Indication "1___" Display Reading/Decimal Point Model dependent. See Ordering Info. Physical/Environmental Operating Temperature 0 +60 °C Storage Temperature –40 +75 °C Humidity (non-condensing) 0 95 % Case Material Polycarbonate Dimensions 1.38"W x 0.88"H Depth is model
dependent (see Mechanical Specifications)
Weight (all models) 1.1 ounces (31 grams)
The specified Full-Scale Current is the current carried by the single wire passing through the
center hole of the ACA5-20PC's on-board CT. It is not the load current ultimately being measured. the Overcurrent Rating is a continuous rating that applies to the Full-Scale Current. It does not apply to any circuitry external to the meter.
Listed accuracy specifications apply over the range of the Rated Full-Scale Current over
frequencies of 45-450Hz.
Maximum reverse polarity protection on "DC1" models is –40Vdc, and –50Vdc on "DC2"
models. "DC3" models provide no reverse polarity protection.
All specified maximum power supply currents are steady-state. AC-powered models can
draw larger surges at initial turn on.
Ordering Information
Order on-line at www.datel.com
ACA5 - 20PC - 1 - AC1 - RL
1 = 50.0A 2 = 75.0A 3 = 100.0A 4 = 150.0A 5 = 199.9A 6 = 250A 7 = 300A 8 = 400A 9 = 500A 10 = 600A 11 = 750A 12 = 1000A 13 = 1500A 14 = 1999A
RL = Red Standard RH = High-Intensity Red* GS = Green Standard*
AC1 = 85-264Vac@50/60Hz AC2 = 85-140Vac@400Hz AC3 = 240-310Vac@50/60Hz DC1 = +5-40Vdc DC2 = +36-75Vdc DC3 = +5Vdc
Input Range:
LED Color:
Power Supply:
*
Available on "DC3" +5V
powered models only
Accessories: DMS-20-CP Panel cutout punch
A DMS-BZL4 bezel assembly with sealing gasket is supplied with each ammeter.