Datasheet X24641S8I-2,5, X24641S8I-1,8, X24641S8I, X24641S8-2,5, X24641S8-1,8 Datasheet (XICOR)

...
Page 1
400 KHz 2-Wire Serial E
2
PROM
64K
Xicor, 1995, 1996 Patents Pending Characteristics subject to change without notice
7026 3/27/97 T0/C0/D0 SH
1
X24641
FUNCTIONAL DIAGRAM
FEATURES
1.8V to 3.6V, 2.5V to 5.5V and 4.5V to 5.5V Power Supply Operation
Low Power CMOS —Active Read Current Less Than 1mA —Active Write Current Less Than 3mA —Standby Current Less Than 1 µ A
400KHz Fast Mode 2-Wire Serial Interface —Down to 1.8V —Schmitt Trigger Input Noise Suppression —Output Slope Control for Ground Bounce
Noise Elimination
Internally Organized 8K x 8
32 Byte Page Write Mode —Minimizes T otal Write Time Per Byte
Hardware Write Protect
Bidirectional Data Transfer Protocol
Self-Timed Write Cycle —Typical Write Cycle Time of 5ms
High Reliability —Endurance: 1,000,000 Cycles —Data Retention: 100 Years
8-Lead SOIC
DESCRIPTION
The X24641 is a CMOS Serial E
2
PROM Memory, internally organized 8K x 8. The device features a serial interface and software protocol allowing opera­tion on a simple two wire bus. The bus operates at 400KHz all the way down to 1.8V.
Three device select inputs (S
0
–S
2
) allow up to eight
devices to share a common two wire bus . Hardware Write Protection is provided through a Write
Protect (WP) input pin on the X24641. When the WP pin is HIGH, the upper quadrant of the Serial E
2
PROM array is protected against any nonvolatile write attempts.
Xicor Serial E
2
PROM Memories are designed and tested for applications requiring extended endurance. Inherent data retention is greater than 100 years.
SERIAL E2PROM DATA AND ADDRESS (SDA)
SCL
S2 S1 S0
WP
COMMAND
DECODE
AND
CONTROL
LOGIC
DEVICE SELECT
LOGIC
WRITE
PROTECT
LOGIC
PAGE
DECODE
LOGIC
DATA REGISTER
Y DECODE LOGIC
E
2
PROM
WRITE VOLTAGE
CONTROL
7026 FM 01
ARRAY
8K x 8
Page 2
X24641
2
PIN DESCRIPTIONS Serial Clock (SCL)
The SCL input is used to clock all data into and out of the device.
Serial Data (SDA)
SDA is a bidirectional pin used to transfer data into and out of the device. It is an open drain output and may be wire-ORed with any number of open drain or open collector outputs.
An open drain output requires the use of a pull-up resistor. For selecting typical values, refer to the Pull­up resistor selection graph at the end of this data sheet.
Device Select (S
0
, S
1
, S
2
)
The device select inputs (S
0
, S
1
, S
2
) are used to set the first three bits of the 8-bit slave address. This allows up to eight devices to share a common bus. These inputs can be static or actively driven. If used statically they must be tied to V
SS
or V
CC
as appro­priate. If actively driven, they must be driven with CMOS levels .
Write Protect (WP)
The Write Protect input controls the Hardware Write Protect feature. When held LOW, Hardware Write Protection is disabled and the device can be written normally. When this input is held HIGH, Write Protec­tion is enabled, and nonvolatile writes are disabled to the upper quadrant of the E
2
PROM array.
PIN NAMES
7026 FRM T01
PIN CONFIGURATION
Symbol Description
S
0
, S
1
, S
2
Device Select Inputs SDA Serial Data SCL Serial Clock WP Write Protect V
SS
Ground V
CC
Supply Voltage
V
CC
WP SCL SDA
S
0
S
1
S
2
VSS
1 2 3 4
8 7 6 5
X24641
8-LEAD SOIC
7026 FM 02
Page 3
X24641
3
DEVICE OPERATION
The device supports a bidirectional, bus oriented protocol. The protocol defines any device that sends data onto the bus as a transmitter, and the receiving device as the receiver. The device controlling the transfer is a master and the device being controlled is the slave. The master will always initiate data trans­fers, and provide the clock for both transmit and receive operations. Therefore, the device will be considered a slave in all applications.
Clock and Data Conventions
Data states on the SDA line can change only during SCL LOW. SDA state changes during SCL HIGH are reserved for indicating start and stop conditions. Refer to Figures 1 and 2.
Start Condition
All commands are preceded by the start condition, which is a HIGH to LOW transition of SDA when SCL is HIGH. The device continuously monitors the SDA and SCL lines for the start condition and will not respond to any command until this condition has been met.
SCL
SDA
DATA STABLE DATA
CHANGE
7026 FM 03
SCL
SDA
START BIT STOP BIT
7026 FM 04
Figure 1. Data Validity
Figure 2. Definition of Start and Stop
Page 4
X24641
4
Figure 3. Acknowledge Response From Receiver
Stop Condition
All communications must be terminated by a stop condition, which is a LOW to HIGH transition of SDA when SCL is HIGH. The stop condition is also used to place the device into the standby power mode after a read sequence. A stop condition can only be issued after the transmitting device has released the bus .
Acknowledge
Acknowledge is a software con v ention used to indicate successful data transfer. The transmitting device, either master or slave, will release the bus after trans­mitting eight bits. During the ninth clock cycle the receiver will pull the SDA line LOW to acknowledge that it received the eight bits of data. Ref er to Figure 3.
The device will respond with an acknowledge after recognition of a start condition and its slave address. If both the device and a Write Operation have been selected, the device will respond with an acknowledge after the receipt of each subsequent byte.
In the read mode the device will transmit eight bits of data, release the SDA line and monitor the line for an acknowledge. If an acknowledge is detected and no stop condition is generated by the master, the device will continue to transmit data. If an acknowledge is not detected, the device will terminate further data trans­missions. The master must then issue a stop condition to return the device to the standby power mode and place the device into a known state.
SCL FROM
MASTER
DATA OUTPUT
FROM
TRANSMITTER
1
8 9
DATA
OUTPUT
FROM
RECEIVER
START
ACKNOWLEDGE
7026 FM 05
Page 5
X24641
5
Figure 4. Device Addressing
1
S1S0R/W
DEVICE
SELECT
0 1 0 S
2
DEVICE TYPE
IDENTIFIER
SLAVE ADDRESS BYTE
D7 D2 D1D6 D5 D4 D3
DATA BYTE
A2 A1 A0
A5
LOW ORDER ADDRESS
A4 A3
ADDRESS BYTE 0
0 A10 A9 A80
HIGH ORDER ADDRESS
A11
ADDRESS BYTE 1
0
A7 A6
D0
7026 FM 06
A12
DEVICE ADDRESSING
Following a start condition, the master must output the address of the slave it is accessing. The first four bits of the Slave Address Byte are the de vice type identifier bits. These must equal “1010”. The next 3 bits are the device select bits S
0
, S
1
, and S
2
. This allows up to 8 devices to share a single bus. These bits are compared to the S
0
, S
1
, and S
2
device select input pins. The last bit of the Slave Address Byte defines the operation to be performed. When the R/W bit is a one, then a Read Operation is selected. When it is zero then a Write Operation is selected. Refer to figure 4. After loading the Slave Address Byte from the SDA bus, the device compares the device type bits with the value “1010” and the device select bits with the status
of the device select input pins. If the compare is not successful, no acknowledge is output during the ninth clock cycle and the device returns to the standby mode.
The byte address is either supplied by the master or obtained from an internal counter, depending on the operation. When required, the master must supply the two Address Bytes as shown in figure 4.
The internal organization of the E
2
PROM array is 256 pages by 32 bytes per page. The page address is partially contained in the Address Byte 1 and par tially in bits 7 through 5 of the Address Byte 0. The specific byte address is contained in bits 4 through 0 of the Address Byte 0. Ref er to figure 4.
Page 6
X24641
6
Figure 5. Page Write Sequence
WRITE OPERATIONS Byte Write
For a Byte Write Operation, the device requires the Slave Address Byte, the Word Address Byte 1, and the Word Address Byte 0, which gives the master access to any one of the bytes in the array. Upon receipt of the Word Address Byte 0, the device responds with an acknowledge, and waits for the first eight bits of data. After receiving the 8 bits of the data byte, the device again responds with an acknowl­edge. The master then terminates the transfer by generating a stop condition, at which time the device begins the internal write cycle to the nonvolatile memory. While the internal write cycle is in progress the device inputs are disabled and the device will not respond to any requests from the master. The SDA pin is at high impedance. See figure 4.
Page Write Operation
The device executes a thirty-two byte Page Write Operation. For a Page Write Operation, the device requires the Slave Address Byte, Address Byte 1, and Address Byte 0. Address Byte 0 must contain the first byte of the page to be written. Upon receipt of Address Byte 0, the device responds with an ackno wledge, and waits for the first eight bits of data. After receiving the 8 bits of the first data byte, the device again responds with an acknowledge. The device will respond with an acknowledge after the receipt of each of 31 more bytes. Each time the byte address is internally incre­mented by one, while page address remains constant. When the counter reaches the end of the page, the master terminates the data loading by issuing a stop condition, which causes the device to begin the nonvolatile write cycle. All inputs are disabled until completion of the nonvolatile write cycle. The SDA pin is at high impedance. Refer to figure 5 for the address, acknowledge, and data transf er sequence .
S T A R T
SLAVE
ADDRESS
S T O P
A C K
A C K
A C K
A C K
A C K
7012 ILL F08.1
DATA
(1)
SIGNALS FROM THE MASTER
SDA BUS
SIGNALS FROM THE SLAVE
DATA
(32)
ADDRESS
BYTE 1
ADDRESS
BYTE 0
1 0 1 0 0
S P
SIGNALS FROMTHE MASTER
SDA BUS
SIGNALS FROMTHE SLAVE
S
T A R
T
SLAVE
ADDRESS
S T O P
A C K
A C K
A C K
A C K
WORDADDRESS
BYTE 1
DATA
1 0 1 0 0
WORDADDRESS
BYTE 0
S P
7026 FM 07
SIGNALS FROMTHE MASTER
SDA BUS
SIGNALS FROMTHE SLAVE
S
T
A R
T
SLAVE
ADDRESS
S T O P
A C K
A C K
A C K
A C K
WORDADDRESS
BYTE 1
DATA
1 0 1 0 0
WORDADDRESS
BYTE 0
S P
7026 FM 07
Figure 4. Byte Write Sequence
Page 7
X24641
7
Acknowledge Polling
The maximum write cycle time can be significantly reduced using Acknowledge Polling. To initiate Acknowledge Polling, the master issues a star t condi­tion followed by the Slave Address Byte for a write or read operation. If the device is still busy with the nonvolatile write cycle, then no ACK will be returned. If the device has completed the nonvolatile write opera­tion, an ACK will be returned and the host can then proceed with the read or write operation. Refer to figure 6.
BYTE LOAD COMPLETED
BY ISSUING STOP.
ENTER ACK POLLING
ISSUE START
ISSUE SLAVE
ADDRESS BYTE
(READ OR PROGRAM)
ACK
RETURNED?
NONVOLATILE
WRITE
CYCLE COMPLETE.
CONTINUE
SEQUENCE?
CONTINUE NORMAL READ ORPROGRAM
COMMAND SEQUENCE
PROCEED
ISSUE STOP
NO
YES
YES
ISSUE STOP
NO
7026 FM 09
READ OPERATIONS
Read operations are initiated in the same manner as write operations with the exception that the R/W bit of the Slave Address Byte is set to one. There are three basic read operations: Current Address Reads, Random Reads, and Sequential Reads.
Current Address Read
Internally, the device contains an address counter that maintains the address of the last byte read or written, incremented by one. After a read operation from the last address in the array, the counter will “roll over” to the first address in the array. After a write operation to the last address in a given page, the counter will “roll over” to the first address of the same page.
Upon receipt of the Slave Address Byte with the R/W bit set to one, the device issues an acknowledge and then transmits the byte at the current address. The master terminates the read operation when it does not respond with an acknowledge during the ninth clock and then issues a stop condition. Refer to figure 7 for the address, acknowledge, and data transfer sequence.
It should be noted that the ninth clock cycle of the read operation is not a “don’t care.” To terminate a read operation, the master must either issue a stop condi­tion during the ninth cycle or hold SDA HIGH during the ninth clock cycle and then issue a stop condition.
FROM THE
S T A R T
SLAVE
ADDRESS
S T O P
A C K
DATA
SIGNALS FROM THE MASTER
SDA BUS
SIGNALS SLAVE
1S P0 1 0 1
7026 FM 10
Figure 6. Acknowledge Polling Sequence
Figure 7. Current Address Read Sequence
Page 8
X24641
8
Random Read
Random read operation allows the master to access any memory location in the array. Prior to issuing the Slave Address Byte with the R/W
bit set to one, the master must first perform a “Dummy” write operation. The master issues the start condition and the Slave Address Byte with the R/W bit low, receives an acknowledge, then issues Address Byte 1, receives another acknowledge, then issues Address Byte 0 containing the address of the byte to be read. After the device acknowledges receipt of Address Byte 0, the master issues another start condition and the Slave Address Byte with the R/W
bit set to one. This is followed b y an ac kno wledge and then eight bits of data from the device. The master terminates the read oper­ation by not responding with an acknowledge and then issuing a stop condition. Refer to figure 8 for the address, acknowledge, and data tr ansf er sequence.
The device will perform a similar operation called “Set Current Address” if a stop is issued instead of the second start shown in figure 9. The device will go into standby mode after the stop and all bus activity will be ignored until a start is detected. The effect of this oper­ation is that the new address is loaded into the address counter, b ut no data is output by the de vice .
The next Current Address Read operation will read from the newly loaded address.
Sequential Read
Sequential reads can be initiated as either a current address read or random read. The first byte is trans­mitted as with the other modes; however, the master now responds with an acknowledge, indicating it requires additional data. The device continues to output data for each acknowledge received. The master terminates the read operation by not responding with an acknowledge and then issuing a stop condition.
The data output is sequential, with the data from address n followed by the data from address n + 1. The address counter for read operations increments through all byte addresses, allowing the entire memory contents to be read during one operation. At the end of the address space the counter “rolls over” to address 0000h and the device continues to output data for each acknowledge received. Refer to figure 9 for the acknowledge and data transfer sequence.
SLAVE
ADDRESS
S
S T O P
A C K
A C K
A C K
A C K
DATA
(1)
DATA
(2)
SIGNALS FROM THE MASTER
SDA BUS
SIGNALS FROM THE SLAVE
DATA (n–1)
DATA
(n)
1 P
7026 FM 12
SIGNALS FROMTHE MASTER
SDA BUS
SIGNALS FROMTHE SLAVE
S T A R
T
SLAVE
ADDRESS
S T O P
A C K
A C K
A C K
ADDRESS
BYTE 1
SLAVE
ADDRESS
0
ADDRESS
BYTE 0
S T A R
T
1
DATA
A C K
S PS1 0 1 0
7026 FM 11
Figure 8. Random Read Sequence
Figure 9. Sequential Read Sequence
Page 9
X24641
9
ABSOLUTE MAXIMUM RATINGS*
Temperature under Bias
X24641.......................................–65 ° C to +135 ° C
Storage Temperature........................–65 ° C to +150 ° C
Voltage on any Pin with
Respect to V
SS
....................................–1V to +7V
D.C. Output Current..............................................5mA
Lead Temperature
(Soldering, 10 seconds) ..............................300 ° C
*COMMENT
Stresses above those listed under “Absolute Maximum Ratings” may cause per manent damage to the device. This is a stress rating only and the functional operation of the device at these or any other conditions above those indicated in the operational sections of this specification is not implied. Exposure to absolute maximum rating conditions for extended periods may affect device reliability.
D.C. OPERATING CHARACTERISTICS
7026 FRM T06.1
CAPACITANCE T
A
= +25 ° C, f = 1MHz, V
CC
= 5V
7026 FRM T07
Notes: (1) Must perform a stop command prior to measurement.
(2) V
IL
min. and V
IH
max. are f or ref erence only and are not 100% tested.
(3) This parameter is periodically sampled and not 100% tested.
Limits
Symbol Parameter Min. Max. Units Test Conditions
I
CC1
V
CC
Supply Current (Read) 1 mA SCL = VCC X 0.1/VCC X 0.9 Levels
@ 400KHz, SDA = Open, All Other Inputs =
V
SS
or VCC – 0.3V
I
CC2
VCC Supply Current (Write)
3 mA
I
SB1
(1)
VCC Standby Current 3 µA SCL = SDA = VCC – 0.3V,
All Other Inputs =
V
SS
or VCC – 0.3V,
V
CC
= 5V ± 10%
I
SB2
(1)
VCC Standby Current 1 µA SCL = SDA = VCC – 0.1V,
All Other Inputs =
V
SS
or VCC – 0.1V,
V
CC
= 1.8V
I
LI
Input Leakage Current 10 µA VIN = VSS to V
CC
I
LO
Output Leakage Current 10 µA V
OUT
= VSS to V
CC
V
lL
(2)
Input LOW Voltage –0.5 VCC x 0.3 V
V
IH
(2)
Input HIGH Voltage VCC x 0.7 VCC + 0.5 V
V
OL
Output LOW Voltage 0.4 V IOL = 3mA
V
hys
(3)
Hysteresis of Schmitt Trigger Inputs
V
CC
x 0.05 V
Symbol Parameter Max. Units Test Conditions
C
I/O
(3)
Input/Output Capacitance (SDA) 8 pF V
I/O
= 0V
C
IN
(3)
Input Capacitance (S0, S1, S2, SCL,WP) 6 pF VIN = 0V
RECOMMENDED OPERATING CONDITIONS
7026 FRM T04
Temperature Min. Max.
Commercial 0°C +70°C
Industrial –40°C +85°C
7026 FRM T05
Supply Voltage Limits
X24641 4.5V to 5.5V X24641–2.5 2.5V to 5.5V X24641–1.8 1.8V to 3.6V
Page 10
X24641
10
A.C. OPERATING CHARACTERISTICS (Over the recommended operating conditions, unless otherwise specified.) Read & Program Cycle Limits
7026 FRM T09
POWER-UP TIMING
(4)
7026 FRM T10
Notes: (4) t
PUR
and t
PUW
are the delays required from the time VCC is stable until the specified operation can be initiated. These par ameters
are periodically sampled and not 100% tested. (5) Cb = total capacitance of one bus line in pF (6) tAA = 1.1µs Max below VCC = 2.5V.
Symbol Parameter Min. Max. Units
f
SCL
SCL Clock Frequency 0 400 KHz
T
I
Noise Suppression Time Constant at SCL, SDA Inputs
50 ns
t
AA
(6)
SCL LOW to SDA Data Out Valid 0.1 0.9 µs
t
BUF
Time the Bus Must Be Free Before a New Transmission Can Start
1.2 µs
t
HD:STA
Start Condition Hold Time 0.6 µs
t
LOW
Clock LOW Period 1.2 µs
t
HIGH
Clock HIGH Period 0.6 µs
t
SU:STA
Start Condition Setup Time (for a Repeated Start Condition)
0.6 µs
t
HD:DAT
Data In Hold Time 0 µs
t
SU:DAT
Data In Setup Time 100 ns
t
R
SDA and SCL Rise Time
20+0.1XC
b
(5)
300 ns
t
F
SDA and SCL Fall Time
20+0.1XC
b
(5)
300 ns
t
SU:STO
Stop Condition Setup Time 0.6 µs
t
DH
Data Out Hold Time 50 ns
t
OF
Output Fall Time 20 + 0.1C
b
(5)
250 ns
Symbol Parameter Max. Units
t
PUR
Power-up to Read Operation 1 ms
t
PUW
Power-up to Write Operation 5 ms
A.C. CONDITIONS OF TEST
7026 FRM T08
Input Pulse Levels VCC x 0.1 to VCC x 0.9 Input Rise and
Fall Times 10ns Input and Output
Timing Levels
V
CC
X 0.5
EQUIVALENT A.C. LOAD CIRCUIT
5V
1.53K
100pF
OUTPUT
7026 FM 13
Page 11
X24641
11
SYMBOL TABLE
WAVEFORM INPUTS OUTPUTS
Must be steady
Will be steady
May change from Low to High
Will change from Low to High
May change from High to Low
Will change from High to Low
Don’t Care: Changes Allowed
Changing: State Not Known
N/A Center Line
is High Impedance
7026 FM 17
The program cycle time is the time from a valid stop condition of a program sequence to the end of the inter nal erase/program cycle. During the program cycle, the X24641 bus interface circuits are disabled, SDA is allowed to remain HIGH, and the device does not respond to its slav e address.
Bus Timing
t
SU:STA
t
HD:STAtHD:DAT
t
SU:DAT
t
LOW
t
SU:STO
t
R
t
BUF
SCL
SDA IN
SDA OUT
t
DH
t
AA
t
F
t
HIGH
7026 FM 14
Program Cycle Limits
7026 FRM T11
Symbol Parameter Min. Typ.
(7)
Max. Units
T
WR
(8)
Program Cycle Time 5 10 ms
SCL
SDA 8th BIT
WORD n
ACK
t
WR
STOP
CONDITION
START
CONDITION
7026 FM 15
Guidelines for Calculating Typical Values of Bus Pull-Up Resistors
120 100
80
40
60
20
20 40 60 80
100 120
0
0
RESISTANCE (K)
BUS CAPACITANCE (pF)
MIN. RESISTANCE
MAX. RESISTANCE
R
MAX
=
C
BUS
t
R
R
MIN
=
I
OL MIN
V
CC MAX
=1.8K
7026 FM 16
Bus Timing
Notes: (7) Typical values are f or TA = 25°C and nominal supply voltage (5V).
(8) tWR is the minimum cycle time to be allowed from the system perspective unless polling techniques are used. It is the maximum
time the device requires to automatically complete the nonvolatile write operation.
Page 12
X24641
12
PACKAGING INFORMATION
0.150 (3.80)
0.158 (4.00)
0.228 (5.80)
0.244 (6.20)
0.014 (0.35)
0.019 (0.49)
PIN 1
PIN 1 INDEX
0.010 (0.25)
0.020 (0.50)
0.050 (1.27)
0.188 (4.78)
0.197 (5.00)
0.004 (0.19)
0.010 (0.25)
0.053 (1.35)
0.069 (1.75)
(4X) 7°
0.016 (0.410)
0.037 (0.937)
0.0075 (0.19)
0.010 (0.25)
0° – 8°
X 45°
8-LEAD PLASTIC SMALL OUTLINE GULL WING PACKAGE TYPE S
NOTE:ALL DIMENSIONS IN INCHES (IN PARENTHESES IN MILLIMETERS)
0.250"
0.050" TYPICAL
0.050" TYPICAL
0.030"
TYPICAL
8 PLACESFOOTPRINT
7026 FM 19
Page 13
X24641
13
ORDERING INFORMATION
Part Mark Convention
Device
X24641 X X -X
X24641 X
X
LIMITED WARRANTY
Devices sold by Xicor, Inc. are covered by the warranty and patent indemnification provisions appearing in its Terms of Sale only. Xicor, Inc. makes no warranty, express, statutory, implied, or by description regarding the information set forth herein or regarding the freedom of the described devices from patent infringement. Xicor, Inc. makes no warranty of merchantability or fitness for any purpose. Xicor, Inc. reserves the right to discontinue production and change specifications and prices at any time and without notice.
Xicor, Inc. assumes no responsibility for the use of any circuitry other than circuitry embodied in a Xicor, Inc. product. No other circuits, patents, licenses are implied.
U.S. PATENTS
Xicor products are covered by one or more of the following U.S. Patents: 4,263,664; 4,274,012; 4,300,212; 4,314,265; 4,326,134; 4,393,481; 4,404,475; 4,450,402; 4,486,769; 4,488,060; 4,520,461; 4,533,846; 4,599,706; 4,617,652; 4,668,932; 4,752,912; 4,829, 482; 4,874, 967; 4,883, 976. Foreign patents and additional patents pending.
LIFE RELA TED POLICY
In situations where semiconductor component failure may endanger life, system designers using this product should design the system with appropriate error detection and correction, redundancy and back-up features to prev ent such an occurence.
Xicor's products are not authorized for use in critical components in life support devices or systems.
1. Life support devices or systems are devices or systems which, (a) are intended for surgical implant into the body, or (b) support or sustain life, and whose failure to perform, when properly used in accordance with instr uctions for use provided in the labeling, can be reasonably expected to result in a significant injury to the user.
2. A critical component is any component of a life support device or system whose failure to perform can be reasonably e xpected to cause the failure of the life support device or system, or to affect its saf ety or eff ectiv eness .
VCC Range
Blank = 5V ±10%
2.5 = 2.5V to 5.5V
Temperature Range
Blank = 0°C to +70°C I = –40°C to +85°C
Package X24641
Blank = 8-Lead SOIC
Blank = 4.5V to 5.5V, 0°C to +70°C I = 4.5V to 5.5V, –40°C to +85°C AE = 2.5V to 5.5V, 0°C to +70°C AF = 2.5V to 5.5V, –40°C to +85°C
S8= 8-Lead SOIC
1.8 = 1.8V to 3.6V
AG = 1.8V to 3.6V, 0°C to +70°C AH = 1.8V to 3.6V, –40°C to +85°C
Loading...