UL 7-6
6V 7AH
General
UL7-6
Specifications
Terminal Type
Container Material
Rated Capacity
Max Discharge Current
Internal Resistance
Discharge Characteristics
Design Floating Life at 20°C
Self Discharge
Physical Specification
Part Number:
Length:
Width:
Container Height:
Total Height (with terminal):
Approx Weight:
Nominal Voltage
Nominal Capacity (20HR)
Standard Terminal
Optional Terminal
Standard Option
Flame Retardant Option (FR)
7.00 AH/0.350A
6.51 AH/0.651A
5.95 AH/1.19A
5.37 AH/1.79A
4.40 AH/4.40A
105A (5s)
Approx 15mΩ
Operating Temp. Range
Nominal Operating Temp. Range
Cycle Use
Standby Use
Capacity affected by Temperature
5 Years
Ultracell batteries may be stored for up to 6 months at 25°C(°77F) and then a refresh charge is
required. For higher temperatures the time interval will be shorter.
6V
7AH
F1
F2
ABS
ABS (UL94:VO)
(20hr,1.80V/cell, 25°C / 77°F)
(10hr,1.80V/cell, 25°C / 77°F)
(5hr,1.75V/cell, 25°C / 77°F)
(3hr,1.75V/cell, 25°C / 77°F)
(1hr,1.60V/cell, 25°C / 77°F)
Discharge: -15 ~ 50°C (5 ~ 122°F)
Charge: 0 ~ 40°C (5 ~ 104°F)
Storage: -15 ~ 40°C (5 ~ 104°F)
25 ± 3°C (77 ± 5°F)
Inital Charging Current less than 2.1A.Voltage
7.2V ~ 7.5V at 25°C (77°F) Temp. Coefficient -15mV/°C
No limit on Initial Charging Current Voltage
6.75V ~ 6.9V at 25°C (77°F) Temp. Coefficient -10mV/°C
40°C (104°F) 103%
25°C (77°F) 100%
0°C (32°F) 86%
UL7-6
±
151
3
mm
(
±
34
3
mm
(
±
94
3
mm
(
±
100
3
mm
(
Approx 1.10 kg
5.94
1.34
3.70
3.94
inches
inches
inches
inches
)
)
)
)
Dimensions
F1 Terminal
3.2 [0.12 6]
6.35 [0.2 5]
Ultracell (UK) Ltd | Vesty Business Park | Vesty Road | Liverpool | L30 1NY | United Kingdom
Tel: +44 (0) 151 523 2777 Fax: +44 (0) 151 523 0855 Email: info@ultracell.co.uk
www.ultracell.co.uk
1
0. 8 [ 0. 03 1] 4.7 5 [ 0. 18 7]
100 1
94 1
151 1
ALL DATA IS SUBJECT TO CHANGE WITHOUT NOTICE
34 1
4. 5
ISO9001

Constant Current Discharge (Amperes) at 25 C (77 F )
0 0
F.V/Time
1.85V/cell
1.80V/cell
1.75V/cell
1.70V/cell
1.65V/cell
1.60V/cell
F.V/Time
1.85V/cell
1.80V/cell
1.75V/cell
1.70V/cell
1.65V/cell
1.60V/cell
5min
13.3 10.2 8.48 7.33 5.67 4.18 3.52 2.08 1.63 1.32 1.08 0.94 0.756 0.631 0.347
17.9 13.1 10.2 8.67 6.69 4.86 3.94 2.27 1.75 1.41 1.16 1.01 0.802 0.651 0.350
20.2 14.4 11.2 9.32 6.94 5.04 4.13 2.36 1.79 1.45 1.19 1.03 0.816 0.669 0.354
22.2 15.7 11.9 9.80 7.23 5.24 4.26 2.42 1.83 1.48 1.22 1.05 0.827 0.682 0.360
24.5 16.9 12.7 10.4 7.63 5.37 4.35 2.45 1.91 1.54 1.25 1.08 0.840 0.696 0.365
27.0 18.4 13.6 11.1 8.05 5.60 4.40 2.56 1.97 1.58 1.30 1.10 0.848 0.704 0.367
5min 10min 15min
24.4 18.9 15.8 13.8 10.8 8.03 6.79 4.04 3.18 2.59 2.12 1.84 1.492 1.250 0.686
32.4 23.9 18.9 16.1 12.6 9.26 7.57 4.38 3.40 2.75 2.26 1.97 1.578 1.286 0.692
35.7 25.8 20.3 17.2 12.9 9.52 7.8
38.2 27.5 21.4 17.9 13.4 9.86 8.10 4.63 3.54 2.87 2.37 2.05 1.622 1.345 0.710
41.6 29.4 22.6 18.9 14.0 10.0 8.23 4.67 3.67 2.96 2.43 2.09 1.644 1.370 0.719
44.8 31.2 23.8 19.9 14.7 10.4 8.26 4.85 3.76 3.04 2.50 2.13 1.656 1.383 0.722
10min
Discharge Characteristics
6V
Battery
V
6.5
6.0
5.5
5.0
4.5
Terminal Voltage( V)
4.0
6
2
1
4
15min 30min
20min
Constant Power Discharge (Watts) at 25 C (77 F )
20min
Tem pe ra ture:2 5 C( 77F)
0.6 28C
1C
3C
2C
Min
8
10
Dis charge T ime
60
40
20
0.4 C
45min
1h 2h
3h
4h
5h
6h
8h
10h
20h
0 0
30min
45min
1h 2h
3h
4h
5h
6h
8h
10h
20h
8 4.53 3.45 2.80 2.31 2.02 1.602 1.319 0.698
Float Charging Characteristics
Cha rging
0 0
0.0 5C
0.0 93C
0.2 07C
6
10
2
4
20
8
H
Cha rge
Volume
%
120
110
100
90
80
70
60
50
40
30
20
10
0
0.25
0.20
0.15
0.10
0.05
Curre nt
(XC A)
0
0 8
4
0.10 CA- 2.25 V/cell te mperature25 C
Cha rged Vo lume
(C ons tan t 2.2 5v/ce ll)
Afte r 50 % D is cha rge
Afte r 10 0% D is ch arg e
Ch arg ing C urr en t
20
16
12 24
Cha rging Time(h ours)
Ch arg e Vo ltage
32 36
28
Cha rging
Voltage
0
(V)
7.5
7.0
6.5
6.0
5.5
40
Temperature Effects in Relation to Battery Capacity
120
100
80
60
40
C a pac ity %
20
0
-10
-20
0.0 5C A
0.1 CA
0.2 CA
1.0 CA
2.0 CA
10
0
Tempera ture( C)
3.0 CA
30
20
0
40
Cycle Life in Relation to Depth of Discharge
Testi ng cond ition
Dis charg ing:c urrent 0. 17C (FV 1.7 V/cel l);
Cha rging :curr ent 0.2 5C max, voltag e 2.45V /cell ;
Cha rging volume :125% o f disch arged capacity.
120
100
80
60
40
Cap city( %)
20
100%
50%
DOD
DOD
0
0 200 400 600 800 100 0 1200
Num ber of Cycles
30%
DOD
Ambient Termperature:
o o
25 C (77 F)
Effect of Temperature on Long Term Float Life
10
8
6
5
4
3
2
1
Life expectancy(year)
50
0.5
20
68
30
86
Battery temperature
Charging voltage :
40
104
2.25V/cell
50
122
0
C
O
F
Self Discharge Characteristics
100
80
60
40
20
Remaining Capacity (%)
0
0 2
No supplementary required
A
(Carryout supplementary charge before use if 100% capacity is required.)
Supplementary charge required before use. Optional charging way as below:
1. Charged for above 3 days at limited current 0.25CA and constant voltage 2.25V/cell.
B
2. Charged for above 20 hours at limited current 0.25CA and constant voltage 2.25Vcell.
3. Charged for 8 ~ 10 hours at limited current 0.05 CA.
Supplementary charge may often fail to recover the capacity.
C
The battery should never be left standing till this is reached.
0
40 C
6
4
Storage Time (Months)
8
30 C
0
A
10 C
0
25 C
0
10
B
C
12
2
Ultracell (UK) Ltd | Vesty Business Park | Vesty Road | Liverpool | L30 1NY | United Kingdom
Tel: +44 (0) 151 523 2777 Fax: +44 (0) 151 523 0855 Email: info@ultracell.co.uk
www.ultracell.co.uk
ALL DATA IS SUBJECT TO CHANGE WITHOUT NOTICE
ISO9001