Datasheet TIS600-172, TIS600-148SIG, TIS600-148, TIS600-148RED, TIS600-128 Datasheet (TRACO)

...
Page 1
http://www.tracopower.com Page 1
Industrial Power Supplies
TIS Series 75 - 600 Watt
Features
Switch mode power supplies for DIN-rail mounting
4 power ranges with 3, 6, 12 and 24 A output current (24 VDC models)
Selectable 115/ 230 VAC input Very low ripple and noise EMI complies with EN50081-2 and
EN50082-2 Conducted EMI to EN55011 class B For system operation available with
built-in functions:
RED: Redundancy module for N+1
systems with true current sharing.
SIG: Signal module with AC-Power-
fail, DC- OK Signal and external ON/OFF control
UDS: DC-UPS module for uninter-
ruptable battery backed-up power systems.
Worldwide Safety Approvals Easy snap-on mounting on DIN-rails
or chassis mounting 2 Year Product Warranty
The switching power supplies of the TIS series have been particular y de­signed for applications in industrial process control systems and machine tools. Excellent specifications and high immunity against electrical distur­bances guarantee reliable power for sensitive loads in rugged industrial environments. With help of optional function modules specific requirements for system applications can be met by a standard product. With the UDS module the power supplies can be extended to a perfect DC-UPS with auto­matic battery- backup. This function is ver y often required in applications where a time delayed shutdown of a system is necessary. To monitor and control the power supply a signal module can be installed. For parallel operation with active power sharing a redundancy option is available. This flexibility makes the TIS series power supplies a cost effective solution for many industrial applications.
Models
Ordercode Input Voltage Output Power Output Voltage Output Current
(includes terminal plugs) max. nom. max.
TIS 75-112
115 / 230 VAC
12 VDC 6.0 A
TIS 75-124
selectable
75 W 24 VDC 3.0 A
TIS 75-148 48 VDC 1.5 A
TIS 150-124 115 / 230 VAC
150 W
24 VDC 6.0 A
TIS 150-148 selectable 48 VDC 3.0 A TIS 300-124
115 / 230 VAC
24 VDC 12 A
TIS 300-148
selectable
300 W 48 VDC 6.0 A
TIS 300-172 72 VDC 4.2 A TIS 500-124 230 V AC 500 W 24 VDC 20 A TIS 600-124 24 VDC 24 A
TIS 600-128 115 / 230 VAC
600 W
28 VDC 22 A
TIS 600-148 selectable 48 VDC 12 A TIS 600-172 72 VDC 8.5 A
TIS 300-124 DCI 300 - 800 VDC 300 W 24 VDC 12 A
Page 2
http://www.tracopower.com Page 2
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
Industrial Power Supplies
TIS Series 75-600 Watt
Input Specifications
Input voltage range – TIS 75, TIS 150, TIS 300, TIS 600 93 132 VAC / 187 264 VAC
– TIS 500 187 – 264 VAC – TIS 300 DCI 300 – 800 VDC
Input frequency 47 – 63 Hz Input current at full load (typ.) 115 VAC 230 VAC
– TIS 75 1.7 A 0.9 A – TIS 150 3.0 A 1.7 A – TIS 300 5.4 A 3.3 A
– TIS 500 5.5 A – TIS 600 10.5 A 6.4 A
Inrush current (< 2 ms) 115 VAC 230 VAC – TIS 75 < 16.5 A < 33 A
– TIS 150 < 35 A < 70 A – TIS 300 < 35 A < 70 A
– TIS 500 < 70 A – TIS 600 < 70 A < 80 A
Output Specifications
Output voltage adj. range – 12 VDC models 12 14 VDC
– 24 VDC models 24 – 28 VDC – 28 VDC models 28 – 32 VDC – 48 VDC models 48 – 52 VDC (48 – 55 VDC on request)) – 72 VDC models 60 – 76 VDC
Regulation – Input variation ± 0.2 % max.
– Load variation (10–90%) – TIS 75, TIS 150 ± 1.0 % max.
– TIS 300, TIS 500, TIS 600 ± 0.3 % max.
(± 1.5 % in parallel operation) Ripple and Noise (20MHz Bandwidth) < 50 mV pk-pk Electronic shor t circuit protection current limitation at 110 % typ.
(constant current, automatic restart) Overvoltage protection, triggerpoint at 140 % typ. Vout nom. Hold-up time 115 VAC 230 VAC
– TIS 75 ... TIS 300 min. 25 ms min. 30 ms
– TIS 500 min. 40 ms – TIS 600 min. 15 ms min. 25 ms
Page 3
http://www.tracopower.com Page 3
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
General Specifications
Temperature ranges Operating (ambient temp.) 25 °C+70 °C max.
Derating above 50 °C 2% /°C Storage (non operating) 25 °C+ 85 °C
Humidity (non condensing) 95 % rel H max.
Temperature coefficient 0.02 % / °C Switching frequency 80 kHz typ. (Pulswidth modulation) Efficiency TIS 75 ... TIS 300 85 % typ.
TIS 500 90 % typ. TIS 600 88 % typ.
Isolation according to EN 60950, UL 1950, UL 508C Reliability, calculated MTBF (MIL-HDBK-217 E) – TIS 75 /150 450000 h @ +25°C/ 420000 h @ +25°C
TIS 300 /500 360000 h @ +25°C/ 340000 h @ +25°C TIS 600 300000 h @ +25°C
Safety standards IEC 60950, EN 60950 (SELV),
UL/cUL 1950, UL 508C
Safety approvals UL/cUL 1950 recognized, File E18138
UL/cUL 508C listed, File E210002 UL/cuL 1604 listed, File E213613
(Class I,Division
2, Groups A, B, C and D hazardous locations)
CB-Scheme
Electromagnetic compatibility (EMC), Emissions EN 50081-1 / EN 50081-2 – Conducted RI suppression on input EN 55011 class B, EN 55022 class B,
FCC part 15, level B
Radiated RI suppression EN 55011 class A, EN 55022 class A,
FCC part 15, level A
Electromagnetic compatibility (EMC), Immunity EN 50082-2
– Electrostatic discharge (ESD) IEC / EN 61000-4-2 4 kV / 8 kV – Radiated RF field immunity IEC / EN 61000-4-3 10 V / m – Electrical fast transient / burst immunity IEC / EN 61000-4-4 2 kV – Surge immunity IEC / EN 61000-4-5 2 kV / 4 kV
– Immunity to conducted RF disturbances IEC / EN 61000-4-6 10 V – Power frequency field immunity IEC / EN 61000-4-8 30 A / m
Safety class Degree of Protection 1 (IEC 536) Case protection IP 20 (IEC 529) Environment – Vibration IEC 60068-2-6,1 gn, 200 sweeps, each axis
– Shock IEC 60068-2-27, 15 gn, 11 ms, each axis Enclosure material Aluminium (chassis) / stainless steel (cover) Mounting (snap-on with selflocking spring) for 35 mm DIN-rails as per EN 50022 Connection Plugable screw terminals (plugs included)
(TIS 600: screw terminal blocks)
Industrial Power Supplies
TIS Series 75-600 Watt
Page 4
http://www.tracopower.com Page 4
Specifications can be changed without notice
Optional Mounting Systems Dimensions mm (inches)Power Supplies with Redundancy Function
With this option a parallel operation of up to 5 units is possible. Decoupling diodes and current share lines allow to build true N +1 redundant systems with active current sharing for all units. This function also includes an alarm relay to signal a single unit failure. This option is available for TIS 150 W, TIS 300 W and TIS 600 W models. Please note: A combination with other options is not possible.
Models
Ordercode Input Voltage Output Power Output Voltage Output Current
(includes terminal plugs) max. nom. max.
TIS 150-124 RED 115 / 230 VAC
150 W
24 VDC 6.0 A
TIS 150-148 RED selectable 18 VDC 12 A TIS 300-124 RED 115 / 230 VAC
300 W
24 VDC 12 A
TIS 300-148 RED selectable 48 VDC 6.0 A TIS 600-124 RED 115 / 230 VAC
600 W
24 VDC 24 A
TIS 600-148 RED selectable 48 VDC 12 A
Industrial Power Supplies
TIS Series 75-600 Watt
Specifications
Raiting per relay contact 60 VDC /0.36 A max.
I-Sense
Regulator
L
Con1 Pin3
N
115/230VAC
Con1 Pin1
AC
Con1 Pin2
DC
Common
Unit OK
Unit OK
Con3 - Pin1
Bus Indicator
Con2 - Pin1/2
Con2 - Pin3/4
V-Sense
+Vout
Current Share­line
Unit OK
Con3 - Pin4
Con3 - Pin3 Con3 - Pin2
-Vout
24/48VDC
Page 5
http://www.tracopower.com Page 5
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
Power Supplies with Powerfail Functions
These models provide 3 functions required in many process control system applications:
AC-Power fail signal (relay contact)
DC-OK signal (relay contact)
Remote ON/OFF
Models
Ordercode Input Voltage Output Power Output Voltage Output Current
(includes terminal plugs) max. nom. max.
TIS 150-124 SIG 115 / 230 VAC
150 W
24 VDC 6.0 A
TIS 150-148 SIG selectable 48 VDC 3.0 A TIS 300-124 SIG 115 / 230 VAC
300 W
24 VDC 12 A
TIS 300-148 SIG selectable 48 VDC 6.0 A TIS 600-124 SIG 115 / 230 VAC
600 W
24 VDC 24 A
TIS 600-148 SIG selectable 48 VDC 12 A
Industrial Power Supplies
TIS Series 75-600 Watt
Specifications
DC-OK signal trigger point Models with 24 Vout > 22.8 VDC ± 0.5 V relay B closed (pin 4 pin 3)
Models with 48 Vout > 45.6 VDC ± 1.0 V relay B closed (pin 4 – pin 3)
AC-Powerfail signal Vin < 93 resp. < 187 VAC relay A closed (pin 7 – pin 6) Raiting per relay contact 60 VDC /0.36 A max.
Remote
ON/OFF
L
115/230VAC
Con1 Pin1
N
Con1 Pin2
Con1 Pin3
AC
DC
Mains
Fail
Detection
Mains OK
Remote
ON/OFF
+Vout
Con2 - Pin3/4
-Vout
24/48VDC
Common AC-Powerfail
Con3 - Pin2
Con3 - Pin7 Con3 - Pin6
Con2 - Pin1/2
Output OK
DC-OK
Detection
DC-OK
Common DC-OK
DC-OK
Con3 - Pin5 Con3 - Pin4 Con3 - Pin3
+
-
Con3 - Pin1
(Relay A)
(Relay B)
Page 6
http://www.tracopower.com Page 6
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
DC-UPS-System
In addition to the standard power supply function, these models include a professional battery management system to charge and monitor an external batter y. In case of a power failure the battery is switched automatically and without any interruption to the DC-output. If mains power is available again, the battery is switched off. The hold-up time is limited only by battery capacity and load. Charge current and voltage can be adjusted to values as required by battery type. Power fail and low battery alarm signals
Models
Ordercode Input Voltage Output Power Output Voltage Output Current
(includes terminal plugs) max. nom. max.
TIS 300-124 UDS
115 / 230 VAC
300 W 24 VDC 12 A
selectable
TIS 600-124 UDS
115 / 230 VAC
600 W 24 VDC 24 A
selectable
Industrial Power Supplies
TIS Series 75-600 Watt
are available via two independent relay contacts. During normal operation the battery status is monitored by periodically loading the battery for shor t time. If a cell resistance is high, there is a relay alarm available. The battery is fully protected under any operational conditions. The power supply is short circuit protected even in battery­backup operation, however for safety reason the battery should be fused with a fast blow fuse. Battery mode can be activated by connection of Pin 7 and 8.
Complete external battery modules (3.2 Ah or 7 Ah standard) with lead batteries are available on request.
Page 7
http://www.tracopower.com Page 7
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
DC-UPS-System
Industrial Power Supplies
TIS Series 75-600 Watt
Specifications
Charging current (factory set) TIS 300-124 UDS 1.2 A
TIS 600-124 UDS 2.4 A
Adjustment range of charging current TIS 300-124 UDS 0.15...1.5 A
TIS 600-124 UDS 0.25...2.5 A
Holding current for charging battery atvoltage 27.3 VDC < 50 mA Overload at short circuit during batter y operation system switches of f AC-Powerfail signal Vin < 93 resp. < 187 VAC relay A closed (pin 2 – pin 3) Low battery signal Battery voltage below 22 V relay B closed (pin 5 – pin 6)
Raiting per relay contact 60 VDC /0.36 A max. During battery charge operation output current reduction by 1.4 x battery charge current
Battery
ON/OFF
Con4 Pin7
L
115/230VAC
Con1 Pin1
Con4 Pin8
N
Con1 Pin2
Battery -
Battery +
Con1 Pin3
Con3 - Pin1
Con3 - Pin2
AC
DC
Mains
Fail
Detection
Battery
Test
Battery OK
Battery Low / failure Common
Low Battery
Con4 - Pin4
AC-Powerfail
Con4 - Pin6 Con4 - Pin5
Battery Switch
Logic
I
Battery Charger
V
+Vout
Con2 - Pin3/4
-Vout
24VDC
Common AC-Power OK
AC-Powerfail
Con4 - Pin3 Con4 - Pin2 Con4 - Pin1
Con2 - Pin1/2
Output OK
VBat>18V
Bat ON/OFF
Mains Fail
(Relay B)
(Relay A)
Page 8
http://www.tracopower.com Page 8
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
Battery-Pack for DC-UPS Systems
The Battery Pack contains high quality, maintenance free lead-acid batteries with 3.2 Ah resp. 7.0 Ah capacity. The batteries are fixed together with a re-settable electronic fuse on a solid mounting frame. Together with power supply models TIS 300-124 UDS or TIS 600-124 UDS the battery pack provides a complete and reliable DC-UPS system. Backup time is depending on load current and battery capacity.
Models
Ordercode Battery Voltage Batter y Capacity Permissable Charge
(25°C, 20h-rate) Current max.
TIS 24-32 AP 24 VDC 3.2 Ah 1.2 A TIS 24-70 AP 24 VDC 7.0 Ah 2.4 A
Industrial Power Supplies
TIS Series 75-600 Watt
Specifications
Max. charge voltage 27...27.6 VDC Temperature coefficient – 36mV /°C Temperature range at charge operation – 15 °C...+50 °C
at load operation 20 °C...+60 °C Storage 20 °C...+60 °C
Average lifetime on standby operation at tA =20 °C 4...5 years
Cable length 1.0 m Cable diameter TIS 24-32 AP 2.5 mm2 (AWG 12)
TIS 24-70 AP 4.0 mm2 (AWG 11)
Weight TIS 24-32 AP 4.6 kg (10.1 lb)
TIS 24-70 AP 5.9 kg (13.0 lb)
Recommended combinations – TIS 24-32 AP TIS 300-124 UDS
(power supplies) TIS 24-70 AP TIS 600-124 UDS
Page 9
http://www.tracopower.com Page 9
Specifications can be changed without notice
Optional Mounting Systems Dimensions mm (inches)
W eight: TIS 75 0.48 kg
(1.06 lb)
TIS 150 0.80 kg (1.76 lb)
TIS 75
TIS 150
Industrial Power Supplies
TIS Series 75-600 Watt
Tolerances: ±0.5 mm (±0.02)
TIS 300
W eight: TIS 300 1.4 kg
(3.09 lb)
adj
114.6
(4.51)
56.7
(2.23)
90
(3.54)
45
(1.77)
6.8
(0.27)
53.7
(2.11)
56.7
(2.23)
OUTPUT
Output
O K
Industrial Switching
Power Supply
TIS-75-124
24VDC / 3 A
CAUTION
Do notopen. Risk ofhigh voltage. Read instructionmanual. Check lineselection switch before connection.
Nom. Voltage: 24 VDC Nom. Current: 3 A
Output
+
INPUT
Nom. Freq.: 50/60Hz Nom. Voltage: 115/230VAC Nom. Current: 1,7/0,9 A
N
L
114.6 (4.51)
53.7
(2.11)
6.8
(0.27)
56.7 (2.23)
56.7 (2.23)
157 (6.18)
80 (3.15)
38.5
(1.52)
Output
O K
Industrial Switching
Power Supply
TIS150-124
24VDC / 6 A
Input
Nom. Freq.: 50/60Hz Nom. Voltage: 115/230VAC Nom. Current: 3,7/1,7 A
N
L
Nom. Voltage: 24 VDC Nom. Current: 6 A
Output
+
CAUTION
Do notopen. Risk ofhigh voltage. Read instructionmanual.
Check lineselection switch beforeconnection.
Output
O K
114.6 (4.51)
53.7
(2.11)
6.8
(0.27)
83 (3.27)
38.5
(1.52)
130 (5.12)
83 (3.27)
207 (8.15)
Industrial Switching
Power Supply
TIS 300-124
24VDC / 12A
Input
Nom. Freq.: 50/60Hz Nom. Voltage: 115/230VAC Nom. Current: 5,4/3,3 A
N
L
+
Nom. Voltage: 24 VDC Nom. Current: 12 A
Output
+
CAUTION
Do notopen. Risk ofhigh voltage. Read instructionmanual.
Check lineselection switch beforeconnection.
Page 10
http://www.tracopower.com Page 10
Specifications can be changed without notice
Optional Mounting Systems Dimensions mm (inches)
Industrial Power Supplies
TIS Series 75-600 Watt
Tolerances: ±0.5 mm (±0.02)
TIS 500
TIS 600
Weight: TIS 600 2.0 kg
(4.41 lb)
Weight: TIS 500 1.9 kg
(4.19 lb)
Industrial Switching
Power Supply
TIS 500-124
24VDC / 20A
+
Nom. Voltage: 24VDC Nom. Current: 20 A
Output
Input
Nom. Freq.: 50/60Hz Nom. Voltage: 230 VAC Nom. Current: 5,3 A
N
L
+
CAUTION
Do notopen. Risk ofhigh voltage. Read instructionmanual.
75
(2.95)
6.8
(0.27)
83
(3.27)
83
(3.27)
130
(5.12)
220
(8.66)
130
(5.12)
46
(1.81)
Industrial Switching
Power Supply
TIS 600-124
24VDC / 24A
+
Nom. Voltage: 72 VDC Nom. Current: 8 A
Output
Input
Nom. Freq.: 50/60Hz Nom. Voltage: 115/230VAC Nom. Current: 10,5/6,4 A
N
L
+
CAUTION
Do notopen. Risk ofhigh voltage. Read instructionmanual. Check lineselection switch beforeconnection.
6.8
(0.27)
177.2
(6.98)
82.8
(3.26)
32
(1.26)
120.2
(4.73)
82.6
(3.25)
179
(7.05)
243
(9.57)
Page 11
http://www.tracopower.com Page 11
Specifications can be changed without notice
Optional Mounting Systems Dimensions mm (inches)
Industrial Power Supplies
TIS Series 75-600 Watt
Wall mounting
Tolerances: ±0.5 mm (±0.02)
Models Order code A B C D E
TIS 75W MK-75 37 (1.46) 14.5 (0.57) 134.5 (5.30) 150.5 (5.93) TIS 150W MK-150 132 (5.20) 13.5 (0.53) 105 (4.13) 134.5 (5.30) 150.5 (5.93) TIS 300W MK-300 132 (5.20) 13.5 (0.53) 105 (4.13) 134.5 (5.30) 150.5 (5.93) TIS 500W MK-500 132 (5.20) 13.5 (0.53) 105 (4.13) 134.5 (5.30) 150.5 (5.93) TIS 600W MK-600 190 (7.48) 37.5 (1.48) 115 (4.53) 197.0 (7.76) 207.0 (8.15)
Rugged DIN-Rail mounting
Models Order code A B C
TIS 150W RMK-150 t.b.a. t.b.a. t.b.a. TIS 300W RMK-300 t.b.a. t.b.a. t.b.a. TIS 500W RMK-500 t.b.a. t.b.a. t.b.a. TIS 600W standard 180 (7.09) 165 (6.50) 15.0 (0.59)
B
A
C
7.5
(0.30)
D
E
4.6
(0.18)
4.2 (0.17)
25 (0.98)
50.1 (1.97)
A
B
C
countersink M4
Page 12
Page 12
Specifications can be changed without notice
Outline Dimensions mm (inches)
Jenatschstrasse 1 CH-8002 Zurich Switzerland Tel. +41-1284 29 11 Fax +41-1201 1168 • e-mail: sales@traco.ch internet: http://www.tracopower.com
Rev . 05/01
Tolerances: ±0.5 mm (±0.02)
Industrial Power Supplies
TIS Series 75-600 Watt
TIS-24-32 AP
TIS-24-70 AP
Weight (incl. batteries): TIS-24-32 AP 4.6 kg
(10.1 lb)
TIS-24-70 AP 5.9 kg (13.0 lb)
A
B
A
B
204
(8
.0
3
)
184
(7
.2
4
)
69
(2.72)
Detail B
Detail A
9
(0.35)
5.8
(0.23
)
12
(0.47
)
14
(0
.5
5
)
7
(0.28)
100
(3.94)
135
(5.14
)
7
(0.28)
B
A
272
(1
0
.7
1
)
252
(9
.9
2
)
B
A
100
(3.94)
69
(2.72)
152
(5.98
)
Loading...