Datasheet SMT130, SMT130M, SMT150, SMT150D, SMT130H Datasheet (Delta Electronics)

Page 1
MODELS SMT130/SMT130H/SMT130M/SMT150/SMT150D
Page 1.
45°
45°
INSTALLATION AND OPERATING INSTRUCTIONS
VENTILATION FAN
READ AND SAVE THESE INSTRUCTIONS
1. Make sure that the electric service supply voltage is AC 120V, 60Hz.
2. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC) and the Occupational Safety and Health Act (OSH Act).
3. Always disconnect the power source before working on or near the ventilating fan, motor or junction box.
4. Protect the power cord from sharp edges, oil, grease, hot surfaces, chemicals or other objects.
5. Do
6. Do not install the unit where ducts are configured as
7. Provide suction parts with proper ventilation.
8. This unit is UL listed for use over a bathtub or shower
not kink the power cord.
shown in Fig. A.
when installed in a GFCI-protected branch circuit.
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the
anufacturer.
m
2. Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and construction.
4. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent back drafting. Follow
the heating equipment manufacturer’s guideline and
safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating Refrigeration and Air Conditioning Engineers (ASHRAE) and local code authorities.
When cutting or drilling into the wall or ceiling, do not
5. damage electrical wiring and other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
standards, including fire-rated
7. If this unit is to be installed over a tub or shower, it
8. Do not use this unit with any other solid-state control
9. NEVER place a switch where it can be reached from
10. Not to be installed in a ceiling thermally insulated to a
CAUTION
1. For general ventilating use only. Do not use to
2. Not for use in cooking areas. (Fig. B)
3. This product must properly connect to the grounding
4. To reduce the risk of injury to persons, install the fan
must be marked as appropriate for the application and be connected to a GFCI (Ground Fault Circuit Interrupter) – protected branch circuit.
device. Solid-state controls may caus distortion, which can cause a motor humming noise.
a tub or shower.
value greater than R40. (This is required for installation in Canada only).
Turning angle too large Duct shrink
Too many elbows
e harmonic
Elbow near the body
Body
Fig. A
exhaust hazardous or explosive materials and vapors.
conductor of the supply circuit.
at least 8.2 feet (2.5m) above the floor.
Cooking area
Do not install above or
inside this area
Cooking Equipment
floor
Fig. B
Page 2
MODELS SMT130/SMT130H/SMT130M/SMT150/SMT150D
Page 2.
Part name
Appearance
Quantity
Insert tab into hole in housing
Screw
SUPPLIED ACCESSORIES
Grille
Tapping Screw
(ψ4x25)
Screw
(#8-32x1/4”)
Duct connector
Suspension bracket I
13”(318.5mm)
Suspension bracket II
13”(318.5mm)
For models of: SMT130, SMT130H, SMT150, SMT150D
For model of: SMT130M
1
1
5
5
1
2
2
INSTALLATION
Proper insulation around the fan to minimize building heat loss and gain. The ducting from this fan to the outside of the building has a strong effect on the air flow, noise and energy use of the fan. Use the shortest, straightest duct routing possible for best performance, and avoid installing the fan with smaller ducts than recommended. Insulation around the ducts can reduce energy loss and inhibit mold growth. Fans installed with existing ducts may not achieve their rated air flow.
Install the housing (I)-using suspension brackets
1. Sliding suspension brackets are available to allow for positioning of the housing anywhere between joists up to a span of 24”.
2. Insert the suspension brackets into the channels on the housing. Make sure the tabs face up as shown. (Fig. C ) Extend the suspension brackets to fit the width of the joists. Hold the fan in place by wrapping the suspension bracket tabs around the bottom o
f the joist. Make sure the fan body is level and perpendicular to the joist. (Fig. D )
3. Ensure that the distance between the ceiling and fan body is appropriate for mounting the grille.
4. Secure the suspension brackets to the joists with nails or by using the tapping screws (ψ4x25) through holes near nails.
5. Secure the suspension bracket to the fan body using the screws (#8-32 x 1/4").
6. Follow steps 2 to 6 of the installation instructions to complete the installation work.
Suspension Bracket
Tab Face
Channel
Fig. C
Attach duct connector
Option1, attach the duct connector from outside, and secure by using one screw (#8-32x1/4” ).
Option2, remove the motor assembly, attach the duct connector from the housing can inside, and secure by using one screw (#8-32x1/4” ). Insert and secure motor assembly.
Note: Remove the tape from the damper and before installation.
Pull existing ductwork into Housing
Screw from Parts Bag
Screw from Parts Bag
Insert tab into hole in housing
Joist
Joist
Bottom of Joist
Fig. D
Install the housing (II)-using mounting tabs
Slotted tabs are provided to locate housing ush with 1/2” ceiling material. Bend tabs outwards 90° (Use a screw driver if desired) and position housing so that tabs rest against bottom edge of the joists (or front of the stud). Nail the housing to the joist or stud using four screws to ensure a solid, quiet installation.
(Fig. E & F)
Tabs
Joist
Fig. E
Joist
Screw 4X25
Fig. F
Page 3
MODELS SMT130/SMT130H/SMT130M/SMT150/SMT150D
Page 3.
Install the housing (III)-existing ceiling installation
Position the housing so that it is centered in the existing ceiling opening; make sure the housing is flush with the finished ceiling. Nail the housing in place and then drive the nails (not provided) through the housing where indicated by arrows. (Fig. G)
Humidity Model: SMT130H Dual Speed Model: SMT150D
JUNCTION BOX
BLACK
WHITE
BLUE
WHITE
GREEN
SWITCH BOX
OFF
ON
POWER SWITCH
HI
MODE SWITCH
L
N
L
N
GRD
Nails
Fig. G
Duct connection
Inside
Outside
Tape
Body
Ceiling
Duct
Duct connector
Gradient 1°~2°
Fig. H
1. Insert the 6” duct (not provided) into the duct connector and tape all ductwork connections to make them secure and airtight. (Fig. H)
2. Install the duct with a gradient 1°~2° to the outside.
Connect wiring
1. Follow all local electrical and ANSI/NFPA70.
2. NEVER place a switch where it can be reached from
a tub or shower.
3. Connect wires as shown in wiring diagrams.
Motion Model: SMT130M Single Speed Models: SMT130, SMT150
JUNCTION BOX
BLACK
WHITE
GREEN
SWITCH BOX
OFF
ON
POWER SWITCH
L
N
GRD
BLACK WHITE
ON/OFF SWITCH
(purchase separately)
POWER SWITCH
SWITCH BOX
120 VAC
LINE IN
GROUND
(bare)
WIRING
PLATE
ON/OFF SWITCH
(purchase separately)
POWER
MODE
SWITCH
SWITCH
BLUE GROUND
(bare)
SWITCH BOX
120 VAC
LINE IN
BLACK WHITE
WIRING
PLATE
4. Using wire nuts (not provided), connect the house power cable to the ventilating fan wires.
5. 14 AWG (2.1 mm
2
) is the smallest conductor that shall
be used for branch-circuit wiring.
Grille attachment
1. Insert the motion sensor unit into the grille. (Fig. I) (only SMT130M)
2. Insert the mounting springs into the slots and mount the grille to the body. (Fig. J)
Celling
Sensor unit
Grille
Fig. I
Slots
Spring
Operation
Fig. J
Delay time control (SMT130M & SMT150D) or Humidity preset control (SMT130H).
Low speed air volume preset control (SMT130H, SMT130M, SMT150D).
%RH
90
80
70
60
50
TIME(min)
60
45
30
15
5
0.5
TIME(min)
60
45
30
15
5
0.5
90
110
CFM
90
CFM
70
CFM
90
70
50
0
70
0
SMT130H control options
50
0
SMT130M control options
SMT150D control options
Page 4
MODELS SMT130/SMT130H/SMT130M/SMT150/SMT150D
Page 4.
11.375" (289)
10.5"
(267)
14"
(356)
14"
(356)
Power
(W)
Air Flow
(CFM)
Single
Single Speed
Dual
Speed
DELTA ELECTRONICS THREE YEAR LIMITED WARRANTY
US Toll Free Number: 1-888-979-9889
Single Models: SMT130, SMT150
1. Single speed control mode: Turn the POWER switch on to operate at single speed mode - the LED indicator will be green.
Humidity Model: SMT130H
2. Humidity control mode: Turn the POWER switch on to operate at humidity control mode - the LED indicator will be blue. When the ambient humidity is higher than the user-adjustable set-point, the fan will run at full speed. When the ambient humidity is lower than the set-point, the fan
will continue to run at the full speed until a 10-minute time delay has elapsed, and then will automatically change to the user-adjustable low speed airflow.
3. Full speed mode: Turn the MODE switch on to operate at full speed mode - the LED indicator will be amber.
Factory setting: low speed airflow 70CFM, humidity
60%RH.
Note: Humidity tolerance is about ±10%.
Motion Model: SMT130M
4. Motion control mode: Turn the POWER switch on to operate at mot
ion control mode. When motion is detected, the fan will run at full speed mode - the LED indicator will be amber. When motion is not detected, the fan will continue to run at the full speed until the user-adjustable time delay has elapsed, and then will automatically change to the user-adjustable low speed airflow - the LED indicator will be green.
Factory setting: low speed airflow 70CFM, time delay 15
minutes.
Dual Speed Model: SMT150D
5. Low s
peed control mode: Turn the POWER switch on (MODE switch is off) to operate at the user-adjustable low speed airflow - the LED will be green.
6. Full speed control mode: Turn the POWER switch & MODE switch on to operate at full speed mode - the LED indicator will be amber. When the user turns the MODE switch off, the fan will continue to run at the full speed until the user-adjustable time delay has elapsed, and then will automatically change t user-adjustable low speed airflow - the LED indicator will be green.
Factory setting: low speed airflow 70CFM, time delay 15
minutes.
MAINTENANCE WARNING:
Disconnect the power source before working on the unit. Routine maintenance must be done every year.
CAUTION:
1. Never use gasoline, benzene, thinner or any other such chemicals to clean the ventilating fan.
2. Do not allow water to enter the motor.
3. Do not soak resin parts in water
over 140°F (60°C).
o the
CLEANING
1. Pull down the springs to remove the grille.
2. Wash and clean the grille. (Use non-abrasive kitchen detergent and wipe dry with a new cloth.)
3. Using a cloth dampened with non-abrasive kitchen detergent, remove any dirt from the ventilating fan. Wipe dry with a new cloth.
4. Replace the grille.
DIMENSIONS
6"
(150)
7.675" (195)
Unit: Inches(mm)
SPECIFICATIONS
Voltage
Model No.
SMT130 120 60 11.6 130 10.4 28
SMT130H 120 60 11.6 130 10.4 28
SMT130M 120 60 11.6 130 10.4 28
SMT150 120 60 16.9 150 10.4 30
SMT150D 120 60 16.9 150 10.4 30
Note: Design and specifications subject to change without notice.
WARRANTY
Delta Electronics Inc. (“Delta Electronics”) warrants to the original consumer purchaser in the USA and Canada that the Breez ventilation fan products will be free from defects in material or workmanship. This warranty is limited to three (3) years from the original date of purchase. Limitations and Exclusions
1. During the warranty period, a replacement for any defective product will be supplied
free of charge for installation by the consumer. The warranty provided herein does not cover charges for labor or other costs incurred in the troubleshooting, repair, removal, and installation service.
2. All returns of defective parts or products must include the product model number, and
must be made through an authorized Delta Electronics distributor. Authorized returns must be shipped prepaid. Repaired or replacement products will be shipped by Delta Electronics F.O.B. shipping point.
3. Delta Electronics shall not be liable for any indirect, incidental, consequential,
punitive, or special damages arising out of or in connection with products use or performance, regardless of the form of action whether in contract, tort (including negligence), strict product liability or otherwise.
4. This warranty does not extend to fluorescent lamp starters and tubes.
5. The warranty does not cover i f user does not comply with manufacturer’s installation
manual.
6. To qualify for warranty service, you must notify Delta Electronics at the address or
telephone number below.
7. Delta Electronics shall have no liability to the original owner -user with respect to any
defect caused by abuse, misuse, neglect, improper transportation or storage, improper testing, improper installation, improper operation, improper use, improper maintenance, improper repair, improper alteration, improper modification, tampering or accident of products or parts thereof, or unusual deterioration or degradation of products or parts thereof due to a physical environment beyond the requirements of products’ specications.
Address: 46101 Fremont Boulevard, Fremont, CA 94538
(V)
Frequency
(Hz)
@ 0.1SP
@ 0.1SP
Weight
(lb.)
Power
(W)
Note
Speed
Humidity
Sensor
Motion Sensor
Loading...