Switching function Normally open (NO)
Output type NAMUR with safety function
Slot width 3.5 mm
Depth of immersion (lateral) 5 ... 7 typ. 6 mm
Reference target 10 x 7 x 0.3 mm3, Al
0102
Model Number
SJ3,5-S1N
Features
• 3.5 mm slot width
• Usable up to SIL 3 acc. to IEC 61
•
Nonferrous targets
508
Application
Danger!
In safety-related applications the
sensor must be operated with a
qualified fail safe interface from
Pepperl+Fuchs, such as KFD2-SH-EX1.
Consider the "exida Functional Safety Assessment" document which is available on
www.pepperl-fuchs.com as an integral part
of this product’s documentation.
Safety Integrity Level (SIL) up to SIL3 acc. to IEC 61508 Danger! In safety-related applications
Output type 2-wire
Nominal ratings
Nominal voltage Uo8.2 V
Switching frequency f0 ... 2500 Hz
Hysteresis Hwith NAMUR switch amplifier: 0.09 mm (e. g. Pepperl+Fuchs
Suitable for 2:1 technology yes , with reverse polarity protection diode
Rate of current rise 2.1 mA / mm
Current consumption
Measuring plate not detected
Measuring plate detected
Functional safety related parameters
Safety Integrity Level (SIL) SIL 3
MTTFd 11850 a
Mission Time (T
Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection type flexible leads LiY , 500 mm
Core cross-section 0.14 mm
Housing material PBT
Degree of protection IP67
Note only for non-ferrous metal
General information
Use in the hazardous area see instruction manuals
Compliance with standards and
directives
Standard conformity
MUR
NA
Standards
Approvals and certificates
EAC conformity TR CU 012/2011
FM approval
Control drawing
UL approval cULus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated ≤36 V
) 20 a
M
Dimensions
the sensor must be operated with a qualified fail safe interface from
Pepperl+Fuchs, such as KFD2-SH-EX1.
Consider the "exida Functional Safety Assessment" document
which is available on www.pepperl-fuchs.com as an integral part of
this product's documentation.
KCD2-SR-Ex1.LB)
with safety switch amplifier 0.05 mm (e. g. Pepperl+Fuchs KFD2SH-Ex1)
0.2 ... 1 mA
≥ 3 mA
2
Adjustable stop
EN 60947-5-6:2000
IEC 60947-5-6:1999
EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
116-0165F
Release date: 2018-04-19 08:24 Date of issue: 2018-04-19 273027_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
3.5
10
19
10
ø 1.85
5
152
0.9
6.95
3
1
Page 2
Inductive slot sensorSJ3,5-S1N
Electrical Connection
RD
GN
L+
L-
Release date: 2018-04-19 08:24 Date of issue: 2018-04-19 273027_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2
Page 3
Inductive slot sensorSJ3,5-S1N
Data for application in connection with hazardous
areas
Equipment protection level Ga , Gb , Gc (ic) , Da , Mb
Equipment protection level Ga
Type of protection intrinsic safety
CE marking 0102
Certificates
A
ppropriate type
ATEX certificate
ATEX marking
Standards
IECEx certificate
IECEx marking
Standards
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
for ATEX
for IECEx
SJ3,5-S1N...
PTB 00 ATEX 2049 X
¬ II 1G Ex ia IIC T6...T1 Ga
EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx PTB 11.0092X
Ex ia IIC T6...T1 Ga
IEC 60079-0:2011 , IEC 60079-11:2011
≤ 30 nF
A cable length of 10 m is considered.
≤ 100 µH
A cable length of 10 m is considered.
Also observe the maximum permissible ambient temperature stated in the general technical data.
amb
Keep to the lower of the two values.
= 16 V , Ii = 25 mA , Pi = 34 mW ,
at U
i
T6 : 56 °C (132.8 °F)
T5 : 68 °C (154.4 °F)
T4 : 96 °C (204.8 °F)
T3 : 96 °C (204.8 °F)
T2 : 96 °C (204.8 °F)
T1 : 96 °C (204.8 °F)
at U
= 16 V , Ii = 25 mA , Pi = 64 mW ,
i
T6 : 49 °C (120.2 °F)
T5 : 61 °C (141.8 °F)
T4 : 89 °C (192.2 °F)
T3 : 89 °C (192.2 °F)
T2 : 89 °C (192.2 °F)
T1 : 89 °C (192.2 °F)
at U
= 16 V , Ii = 52 mA , Pi = 169 mW ,
i
T6 : 28 °C (82.4 °F)
T5 : 40 °C (104 °F)
T4 : 68 °C (154.4 °F)
T3 : 68 °C (154.4 °F)
T2 : 68 °C (154.4 °F)
T1 : 68 °C (154.4 °F)
at U
= 16 V , Ii = 76 mA , Pi = 242 mW ,
i
T6 : 13 °C (55.4 °F)
T5 : 25 °C (77 °F)
T4 : 53 °C (127.4 °F)
T3 : 53 °C (127.4 °F)
T2 : 53 °C (127.4 °F)
T1 : 53 °C (127.4 °F)
at Ui= 16 V , Ii = 25 mA 34 mW ,
T6 : 73 °C (163.4 °F)
T5 : 88 °C (190.4 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at U
= 16 V , Ii = 25 mA , Pi = 64 mW ,
i
T6 : 66 °C (150.8 °F)
T5 : 81 °C (177.8 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at U
= 16 V , Ii = 52 mA , Pi = 169 mW ,
i
T6 : 45 °C (113 °F)
T5 : 60 °C (140 °F)
T4 : 89 °C (192.2 °F)
T3 : 89 °C (192.2 °F)
T2 : 89 °C (192.2 °F)
T1 : 89 °C (192.2 °F)
at U
= 16 V , Ii = 76 mA , Pi = 242 mW ,
i
T6 : 30 °C (86 °F)
T5 : 45 °C (113 °F)
T4 : 74 °C (165.2 °F)
T3 : 74 °C (165.2 °F)
T2 : 74 °C (165.2 °F)
T1 : 74 °C (165.2 °F)
Release date: 2018-04-19 08:24 Date of issue: 2018-04-19 273027_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
3
Page 4
Inductive slot sensorSJ3,5-S1N
Equipment protection level Gb
Type of protection intrinsic safety
CE marking 0102
Certificates
A
ppropriate type
ATEX certificate
ATEX marking
Standards
IECEx certificate
IECEx marking
Standards
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
Equipment protection level Gc (ic)
Type of protection intrinsic safety
CE marking
SJ3,5-S1N...
PTB 00 ATEX 2049 X
¬ II 1G Ex ia IIC T6…T1 Ga
EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx PTB 11.0092X
Ex ia IIC T6...T1 Ga
IEC 60079-0:2011 , IEC 60079-11:2011
≤ 30 nF
A cable length of 10 m is considered.
≤ 100 µH
A cable length of 10 m is considered.
Also observe the maximum permissible ambient temperature stated in the general technical data.
amb
Keep to the lower of the two values.
at U
= 16 V , Ii = 25 mA , Pi = 34 mW ,
i
T6 : 73 °C (163.4 °F)
T5 : 88 °C (190.4 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at U
= 16 V , Ii = 25 mA , Pi = 64 mW ,
i
T6 : 66 °C (150.8 °F)
T5 : 81 °C (177.8 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at U
= 16 V , Ii = 52 mA , Pi = 169 mW ,
i
T6 : 45 °C (113 °F)
T5 : 60 °C (140 °F)
T4 : 89 °C (192.2 °F)
T3 : 89 °C (192.2 °F)
T2 : 89 °C (192.2 °F)
T1 : 89 °C (192.2 °F)
at U
= 16 V , Ii = 76 mA , Pi = 242 mW ,
i
T6 : 30 °C (86 °F)
T5 : 45 °C (113 °F)
T4 : 74 °C (165.2 °F)
T3 : 74 °C (165.2 °F)
T2 : 74 °C (165.2 °F)
T1 : 74 °C (165.2 °F)
Certificates
ATE
X certificate
ATEX marking
Standards
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
PF 13 CERT 2895 X
¬ II 3G Ex ic IIC T6…T1 Gc
EN 60079-0:2012+A11:2013 , EN 60079-11:2012
≤ 30 nF
A cable length of 10 m is considered.
≤ 100 µH
A cable length of 10 m is considered.
Also observe the maximum permissible ambient temperature stated in the general technical data.
amb
Keep to the lower of the two values.
at U
= 20 V , Ii = 25 mA , Pi = 34 mW ,
i
T6 : 70 °C (158 °F)
T5 : 85 °C (185 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at U
= 20 V , Ii = 25 mA , Pi = 64 mW ,
i
T6 : 66 °C (150.8 °F)
T5 : 81 °C (177.8 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at U
= 20 V , Ii = 52 mA , Pi = 169 mW ,
i
T6 : 45 °C (113 °F)
T5 : 60 °C (140 °F)
T4 : 89 °C (192.2 °F)
T3 : 89 °C (192.2 °F)
T2 : 89 °C (192.2 °F)
T1 : 89 °C (192.2 °F)
at U
= 20 V , Ii = 76 mA , Pi = 242 mW ,
i
T6 : 30 °C (86 °F)
T5 : 45 °C (113 °F)
T4 : 74 °C (165.2 °F)
T3 : 74 °C (165.2 °F)
T2 : 74 °C (165.2 °F)
T1 : 74 °C (165.2 °F)
Release date: 2018-04-19 08:24 Date of issue: 2018-04-19 273027_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
4
Page 5
Inductive slot sensorSJ3,5-S1N
Equipment protection level Da
Type of protection intrinsic safety
CE marking 0102
Certificates
A
ppropriate type
ATEX certificate
ATEX marking
Standards
IECEx certificate
IECEx marking
Standards
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
Equipment protection level Mb
Type of protection intrinsic safety
ificates
Cert
Appropriate type
IECEx certificate
IECEx marking
Standards
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
SJ3,5-S1N...
PTB 00 ATEX 2049 X
¬ II 1D Ex ia IIIC T135°C Da
EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx PTB 11.0092X
Ex ia IIIC T135°C Da
IEC 60079-0:2011 , IEC 60079-11:2011
≤ 30 nF ; a cable length of 10 m is considered.
≤ 100 µH
A cable length of 10 m is considered.
Also observe the maximum permissible ambient temperature stated in the general technical data.
amb
Keep to the lower of the two values.
at U
= 16 V , Ii = 25 mA , Pi = 34 mW : 100 °C (212 °F)
i
at U
= 16 V , Ii = 25 mA , Pi = 64 mW : 100 °C (212 °F)
i
at U
= 16 V , Ii = 52 mA , Pi = 169 mW : 89 °C (192.2 °F)
i
at U
= 16 V , Ii = 76 mA , Pi = 242 mW : 74 °C (165.2 °F)
i
SJ3,5-S1N...
IECEx PTB 11.0092X
Ex ia I Mb
IEC 60079-0:2011 , IEC 60079-11:2011
≤ 30 nF
A cable length of 10 m is considered.
≤ 100 µH
A cable length of 10 m is considered.
Also observe the maximum permissible ambient temperature stated in the general technical data.
amb
Keep to the lower of the two values.
at U
= 16 V , Ii = 25 mA , Pi = 34 mW : 100 °C (212 °F)
i
at U
= 16 V , Ii = 25 mA , Pi = 64 mW : 100 °C (212 °F)
i
at U
= 16 V , Ii = 52 mA , Pi = 169 mW : 89 °C (192.2 °F)
i
at U
= 16 V , Ii = 76 mA , Pi = 242 mW : 74 °C (165.2 °F)
i
Release date: 2018-04-19 08:24 Date of issue: 2018-04-19 273027_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
5
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.