Datasheet SJ2-SN DataSheet (Pepperl Fuchs)

Page 1
Inductive slot sensor SJ2-SN
Technical Data
General specifications
Switching function Normally closed (NC) Output type NAMUR with safety function Slot width 2 mm Depth of immersion (lateral) 5 ... 7 typ. 6 mm Reference target 5 x 8 x 0.5 mm3, Al
0102
Model Number
SJ2-SN
Features
• Usable up to SIL 3 acc. to IEC 61
508
Application
Danger!
In security applications, the sen­sor must be operated on a quali-
fied safety switch amplifier from Pepperl+Fuchs (e.g., KFD2-SH-Ex1). Observe the "exida Functional Safety As­sessment" document, which belongs to this sensor and is available as part of the product documentation from www.pepperl­fuchs.com.
Attention!
NAMUR-compliant switch amplifiers can, due to a low current consumption at the re­corded measuring plate (0.2 mA ... 1 mA), in­correctly report cable breaks (required in accordance with EN 60947-5-6:2000: 0.4 mA ... 1 mA).
Safety Integrity Level (SIL) up to SIL3 acc. to IEC 61508 Danger! In safety-related applications
Output type 2-wire
Nominal ratings
Nominal voltage Uo8.2 V Switching frequency f 0 ... 5000 Hz Hysteresis H with NAMUR switch amplifier: 0.02 mm (e. g. Pepperl+Fuchs
Suitable for 2:1 technology yes , with reverse polarity protection diode Rate of current rise -11 mA / mm Current consumption
Measuring plate not detected Measuring plate detected
Functional safety related parameters
Safety Integrity Level (SIL) SIL 3 MTTFd 11800 a Mission Time (T Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -40 ... 100 °C (-40 ... 212 °F)
Mechanical specifications
Connection type flexible leads LIFYW , 500 mm Core cross-section 0.06 mm Housing material PBT Degree of protection IP67 Mass 2.5 g No
te adjustable
General information
Use in the hazardous area see instruction manuals
Compliance with standards and directives
Standard conformity
MUR
NA
Standards
Approvals and certificates
EAC conformity TR CU 012/2011 FM approval
Control drawing UL approval cULus Listed, General Purpose CCC approval CCC approval / marking not required for products rated 36 V
) 20 a
M
Dimensions
the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1. Consider the "exida Functional Safety Assessment" document which is available on www.pepperl-fuchs.com as an integral part of this product's documentation.
KCD2-SR-Ex1.LB) with safety switch amplifier 0.01 mm (e. g. Pepperl+Fuchs KFD2­SH-Ex1)
3 mA
0.2 ... 1 mA
2
stop
EN 60947-5-6:2000 IEC 60947-5-6:1999 EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
116-0165F
Release date: 2018-04-19 08:24 Date of issue: 2018-04-19 273025_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2
6
111
ø1.5
8
3.5
15
4.2
1
Page 2
Inductive slot sensor SJ2-SN
Electrical Connection
BN
BU
L+
L-
Release date: 2018-04-19 08:24 Date of issue: 2018-04-19 273025_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2
Page 3
Inductive slot sensor SJ2-SN
Data for application in connection with hazardous areas
Equipment protection level Ga , Gb , Gc (ic) , Da , Mb
Equipment protection level Ga
Type of protection intrinsic safety
CE marking 0102
Certificates
A
ppropriate type
ATEX certificate
ATEX marking
Standards
IECEx certificate
IECEx marking
Standards
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
for ATEX
for IECEx
SJ2-SN...
PTB 00 ATEX 2049 X ¬ II 1G Ex ia IIC T6...T1 Ga
EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx PTB 11.0092X
Ex ia IIC T6...T1 Ga
IEC 60079-0:2011 , IEC 60079-11:2011
30 nF A cable length of 10 m is considered.
100 µH A cable length of 10 m is considered.
Also observe the maximum permissible ambient temperature stated in the general technical data.
amb
Keep to the lower of the two values.
= 16 V , Ii = 25 mA , Pi = 34 mW ,
at U
i
T6 : 56 °C (132.8 °F) T5 : 68 °C (154.4 °F) T4 : 96 °C (204.8 °F) T3 : 96 °C (204.8 °F) T2 : 96 °C (204.8 °F) T1 : 96 °C (204.8 °F) at U
= 16 V , Ii = 25 mA , Pi = 64 mW ,
i
T6 : 49 °C (120.2 °F) T5 : 61 °C (141.8 °F) T4 : 89 °C (192.2 °F) T3 : 89 °C (192.2 °F) T2 : 89 °C (192.2 °F) T1 : 89 °C (192.2 °F) at U
= 16 V , Ii = 52 mA , Pi = 169 mW ,
i
T6 : 28 °C (82.4 °F) T5 : 40 °C (104 °F) T4 : 68 °C (154.4 °F) T3 : 68 °C (154.4 °F) T2 : 68 °C (154.4 °F) T1 : 68 °C (154.4 °F) at U
= 16 V , Ii = 76 mA , Pi = 242 mW ,
i
T6 : 13 °C (55.4 °F) T5 : 25 °C (77 °F) T4 : 53 °C (127.4 °F) T3 : 53 °C (127.4 °F) T2 : 53 °C (127.4 °F) T1 : 53 °C (127.4 °F)
at Ui= 16 V , Ii = 25 mA 34 mW , T6 : 73 °C (163.4 °F) T5 : 88 °C (190.4 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at U
= 16 V , Ii = 25 mA , Pi = 64 mW ,
i
T6 : 66 °C (150.8 °F) T5 : 81 °C (177.8 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at U
= 16 V , Ii = 52 mA , Pi = 169 mW ,
i
T6 : 45 °C (113 °F) T5 : 60 °C (140 °F) T4 : 78 °C (172.4 °F) T3 : 78 °C (172.4 °F) T2 : 78 °C (172.4 °F) T1 : 78 °C (172.4 °F) at U
= 16 V , Ii = 76 mA , Pi = 242 mW ,
i
T6 : 30 °C (86 °F) T5 : 45 °C (113 °F) T4 : 57 °C (134.6 °F) T3 : 57 °C (134.6 °F) T2 : 57 °C (134.6 °F) T1 : 57 °C (134.6 °F)
Release date: 2018-04-19 08:24 Date of issue: 2018-04-19 273025_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
3
Page 4
Inductive slot sensor SJ2-SN
Equipment protection level Gb
Type of protection intrinsic safety
CE marking 0102
Certificates
A
ppropriate type
ATEX certificate
ATEX marking
Standards
IECEx certificate
IECEx marking
Standards
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
Equipment protection level Gc (ic)
Type of protection intrinsic safety
CE marking
SJ2-SN...
PTB 00 ATEX 2049 X ¬ II 1G Ex ia IIC T6…T1 Ga
EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx PTB 11.0092X
Ex ia IIC T6...T1 Ga
IEC 60079-0:2011 , IEC 60079-11:2011
30 nF A cable length of 10 m is considered.
100 µH A cable length of 10 m is considered.
Also observe the maximum permissible ambient temperature stated in the general technical data.
amb
Keep to the lower of the two values. at U
= 16 V , Ii = 25 mA , Pi = 34 mW ,
i
T6 : 73 °C (163.4 °F) T5 : 88 °C (190.4 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at U
= 16 V , Ii = 25 mA , Pi = 64 mW ,
i
T6 : 66 °C (150.8 °F) T5 : 81 °C (177.8 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at U
= 16 V , Ii = 52 mA , Pi = 169 mW ,
i
T6 : 45 °C (113 °F) T5 : 60 °C (140 °F) T4 : 78 °C (172.4 °F) T3 : 78 °C (172.4 °F) T2 : 78 °C (172.4 °F) T1 : 78 °C (172.4 °F) at U
= 16 V , Ii = 76 mA , Pi = 242 mW ,
i
T6 : 30 °C (86 °F) T5 : 45 °C (113 °F) T4 : 57 °C (134.6 °F) T3 : 57 °C (134.6 °F) T2 : 57 °C (134.6 °F) T1 : 57 °C (134.6 °F)
Certificates
ATE
X certificate
ATEX marking
Standards
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
PF 13 CERT 2895 X ¬ II 3G Ex ic IIC T6…T1 Gc
EN 60079-0:2012+A11:2013 , EN 60079-11:2012
30 nF A cable length of 10 m is considered.
100 µH A cable length of 10 m is considered.
Also observe the maximum permissible ambient temperature stated in the general technical data.
amb
Keep to the lower of the two values. at U
= 20 V , Ii = 25 mA , Pi = 34 mW ,
i
T6 : 70 °C (158 °F) T5 : 85 °C (185 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at U
= 20 V , Ii = 25 mA , Pi = 64 mW ,
i
T6 : 66 °C (150.8 °F) T5 : 81 °C (177.8 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at U
= 20 V , Ii = 52 mA , Pi = 169 mW ,
i
T6 : 45 °C (113 °F) T5 : 60 °C (140 °F) T4 : 78 °C (172.4 °F) T3 : 78 °C (172.4 °F) T2 : 78 °C (172.4 °F) T1 : 78 °C (172.4 °F) at U
= 20 V , Ii = 76 mA , Pi = 242 mW ,
i
T6 : 30 °C (86 °F) T5 : 45 °C (113 °F) T4 : 57 °C (134.6 °F) T3 : 57 °C (134.6 °F) T2 : 57 °C (134.6 °F) T1 : 57 °C (134.6 °F)
Release date: 2018-04-19 08:24 Date of issue: 2018-04-19 273025_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
4
Page 5
Inductive slot sensor SJ2-SN
Equipment protection level Da
Type of protection intrinsic safety
CE marking 0102
Certificates
A
ppropriate type
ATEX certificate
ATEX marking
Standards
IECEx certificate
IECEx marking
Standards
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
Equipment protection level Mb
Type of protection intrinsic safety
ificates
Cert
Appropriate type
IECEx certificate
IECEx marking
Standards
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
SJ2-SN...
PTB 00 ATEX 2049 X ¬ II 1D Ex ia IIIC T135°C Da
EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx PTB 11.0092X
Ex ia IIIC T135°C Da
IEC 60079-0:2011 , IEC 60079-11:2011
30 nF A cable length of 10 m is considered.
100 µH A cable length of 10 m is considered.
Also observe the maximum permissible ambient temperature stated in the general technical data.
amb
Keep to the lower of the two values. at U
= 16 V , Ii = 25 mA , Pi = 34 mW : 100 °C (212 °F)
i
at U
= 16 V , Ii = 25 mA , Pi = 64 mW : 100 °C (212 °F)
i
at U
= 16 V , Ii = 52 mA , Pi = 169 mW : 78 °C (172.4 °F)
i
at U
= 16 V , Ii = 76 mA , Pi = 242 mW : 57 °C (134.6 °F)
i
SJ2-SN...
IECEx PTB 11.0092X
Ex ia I Mb
IEC 60079-0:2011 , IEC 60079-11:2011
30 nF A cable length of 10 m is considered.
100 µH A cable length of 10 m is considered.
Also observe the maximum permissible ambient temperature stated in the general technical data.
amb
Keep to the lower of the two values. at U
= 16 V , Ii = 25 mA , Pi = 34 mW : 100 °C (212 °F)
i
at U
= 16 V , Ii = 25 mA , Pi = 64 mW : 100 °C (212 °F)
i
at U
= 16 V , Ii = 52 mA , Pi = 169 mW : 78 °C (172.4 °F)
i
at U
= 16 V , Ii = 76 mA , Pi = 242 mW : 57 °C (134.6 °F)
i
Release date: 2018-04-19 08:24 Date of issue: 2018-04-19 273025_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
5
Loading...