Datasheet RM487.5 Datasheet (cdtechno)

Page 1
Product Data Sheet
7.5 AMP
MODULAR SWITCH MODE RECTIFIER
RM487.5
FEATURES
• SWITCH MODE
• >.99 PFC
• >84% EFFICIENCY
• AUTOMATIC LOAD SHARING
• HOT-SWAP CAPABLE
DESCRIPTION
The RM487.5 Modular Switch-Mode Rectifier is one of C&D Technologies’ family of rectifiers that may be used in modular power plants. This unit will function in parallel with any rectifier with similar current sharing capacities. This compact, versatile and efficient unit is ideal for use in advanced telecommunications applications. Its small size allows the user to plan economically for system expansion at minimum cost and makes it ideal for use in fiber optic, microwave and other applications where space is at a premium.
• COMPACT SIZE
• SHELF MOUNTED
• SOFT START TURN-ON!
• TELECOM BULK POWER RATED
• BELLCORE COMPLIANT
µµ
µPROCESSOR INTELLIGENCE ALLOWS
µµ
EXPANSION TO REMOTE CONTROL FEATURES
• INFINITE, FULL CURRENT SHORT CIRCUIT CAPABLE
• THD <5%
AGENCY APPROVALS PENDING
RM4875 4/98 REV A
Power Electronics Division, United States
3400 E Britannia Drive, Tucson, Arizona 85706
Phone: 800.547.2537 Fax: 520.770.9369
Internet: http://www.cdpowerelectronics.com
Power Electronics Division, Europe
C&D Technologies (Power Electronics) Ltd.
132 Shannon Industrial Estate, Shannon, Co. Clare, Ireland
Tel: +353.61.474.133 Fax:+353.61.474.141
Page 1
Page 2
Input Specifications
Parameter Conditions Min Typ Max Units
Operating Range 45 - 65 Hz, single phase, no taps required 106 264 VAC
Current 106 VAC 4.6 A
208 VAC 2.55 A
240 VAC 2.12 A
Efficiency 84 %
Power Factor Correction (PFC) >.99
MEASUREMENTS OF RM4875
Module
Weight 2.88 lbs.
Height 2.4
Depth 11.0
Width 4.75
Shelf* Weight 15.5 lbs.
Height 3.5 with rectifiers mounted in shelf
Depth 12 maximum
Width 23 rack mount
* These measurements are specifically for the AGM25 List 1 up to 8 quantity RM 487.5.
Please contact factory for other shelf and power plant options.
GENERAL FEATURES
Hot Swappable Modules
These shelf-mounted modules are easy and safe to install or remove while system is operational without affecting the overall system’s performance.
Parallel Operation and Automatic Load Sharing
Forced share connection is made via a hard wire. Sharing is within ±10% of the average current for the load applied.
Remote Control Enable Signal
The rectifiers output voltage control may be changed from internal float and equalize pots to external remote control though a digital ground signal.
Current Limit
Upon reaching 110% of rated current, the rectifier will automatically limit the current down to short circuit conditions with no fold back.
Safety
UL/CUL Approved: UL 1950/CSA 950. File Number: E131694
Status Indicator
RFA Remote Control Equalize Front Panel Current Test Jacks Normal
Page 2
RM4875 4/98 REV A
Page 3
Output Specifications
Parameter Conditions Min Typ Max Units
Voltage Adjustment Range
float voltage 48 56 VDC
equalize voltage 52 60 VDC
Regulation 0-100% load within
specified input voltage and frequency range ± .5 %
Load Current within a 10 - 100% rating ±10 %
Hold-Up Time nominal AC line >16 mS
Filtering
Voice band <32 dBrnc
Wide band noise @ 20 MHz <250 mV p-p
ENVIRONMENTAL
Temperature
Operating -40 +65 °C
-40 149 °F
Storage -50 +85 °C
-58 185 °F
Humidity non-condensing 0 95 %
Altitude 0 7000 ft.
0 2133 m
Heat Dissipation @54V 264 Btu/hr
Audible Noise 5 ft. from any vertical surface <55 dBa
PROTECTION, ALARM AND CONTROL SYSTEMS
Rectifier Failure Alarm (RFA)
Problems occurring because of an unacceptable relation­ship between the output power and load conditions will cause a Rectifier Failure Alarm (RFA). This alarm consists of a red LED and a flashing green OK LED. Conditions which may lead to an RFA are:
Low Current - Output current has decreased to below 5% of its rated value. Unit Shutdown - Any shutdown occurrence due to overvoltage, external shutdown command, unacceptable ambient temperature conditions or low AC input voltage. Load Sharing Terminal Pin Out Of Range - The terminal pin is out of range. Remote Control Terminal Out Of Range - The remote control terminal pins are out of range. Line Sag - This condition occurs when the nominal voltage decreases below 180V. Normal range is 208­240V. Fan Malfunction - The fan has stopped operating or is not providing the airflow needed to cool the unit. Over Temperature - The ambient temperature has exceeded 65°C.
High Voltage Shutdown (HVSD)
The unit’s built-in high voltage limit is permanently set at 60V. When internal shutdown occurs, the unit may be restarted by a local switch or by a remote signal.
Surge Protection
The unit will withstand lightning and input surges of 6000V/3000A.
Under Voltage Protection
When input voltage is below 105 VAC, the rectifier’s operation is automatically power limited.
RM4875 4/98 REV A
Page 3
Page 4
Mechanical
2.90
ALL MEASUREMENTS ARE IN INCHES
I+
EQL FLT REM
HFM 48-7.5
4.750
EQL NORM RFA
OFF
I-
2.400
10.955
Standard Options are shown, consult factory for other available options.
The information provided herein is believed to be reliable; however, C&D Technologies assumes no responsibility for inaccuracies or omissions. C&D Technologies assumes no responsibility for the use of this information, and all use of such information shall be entirely at the users own risk. Prices and specifications are subject to change without notice. No patent rights or licenses to any of the circuits described herein are implied or granted to any third party. C&D Technologies does not authorize or warrant any C&D Technologies product for use in life support devices/systems or in aircraft control applications.