600W with PFC and Parallel Function
Universal AC input / Full range
Built-in active PFC function
Protections: Short circuit / Overload / Over voltage / Over temperature
Forced air cooling by built-in DC fan
With DC OK Signal output
Current sharing up to 2400W(3+1)
Built-in remote ON-OFF control
Built-in remote sense function
Fixed switching frequency at PFC:88KHz PWM:100KHz
Operating altitude up to 3000 meters ( )Note.6
3 years warranty
Features :
■
PSP-600 series
SPECIFICATION
MODEL
DC VO LTAG E
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.)
OUTPUT VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE Note.3
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
POWER FACTOR (Typ.)
INPUT
PROTECTION
FUNCTION
ENVIRONMENT
SAFETY &
EMC
(Note 4)
NOTE
EFFICIENCY(Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
OVER VOLTAGE
OVER TEMPERATURE
REMOTE CONTROL
POK SIGNAL
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
EMC IMMUNITY
MTBF
DIMENSIONOTHERS
PACKING
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.360 360 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
6. The operating altitude is 2000 meters for CCC, 3000 meters for UL,TUV. The ambient temperature derating of 5 /1000m is needed for operating altitude℃
greater than 2000m (6500ft).
PSP-600-12PSP-600-5 PSP-600-13.5 PSP-600-15 PSP-600-24 PSP-600-27 PSP-600-48
12V5V 13.5V 15V 24V 27V
50A80A 44.5A 40A 25A 22.2A 12.5A
0 ~ 50A0 ~ 80A 0 ~ 44.5A 0 ~ 40A 0 ~ 25A 0 ~ 22.2A 0 ~ 12.5A
600W400W 600.75W 600W 600W 599.4W 600W
Note.2
1500ms, 50ms at full load
20ms at full load
Note.5
88 ~ 264VAC 124 ~ 370VDC
47 ~ 63Hz
0.95/230VAC 0.99/115VAC at full load
6.8A/115VAC 3.4A/230VAC
20A/115VAC 40A/230VAC
<1.3mA/240VAC
105 ~ 135% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, re-power on to recover
RC+/RC-: Short = power on ; Open = power off
PSU turn on: 3.3V ~ 5.6V PSU turn off: 0V ~ 1V
-20 ~ +60 (Refer to "Derating Curve")℃
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH℃
±℃ ℃0.03%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1, CCC GB4943.1 approved
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH℃
Compliance to EN55032 (CISPR32) Class B, EN61000-3-2,-3, GB9245, GB17625.1
Compliance to EN61000-4-2,3,4,5,6,8,11, light industry level, criteriaA
116.4K hrs min. MIL-HDBK-217F (25 )℃
170*120*93mm (L*W*H)
1.9Kg; 8pcs/15.5Kg/1.06CUFT
240mVp-p180mVp-p 240mVp-p 240mVp-p 240mVp-p 240mVp-p 300mVp-p
10 ~ 13.2V4.75 ~ 5.5V 12 ~ 15V 13.5 ~ 18V 20 ~ 26.4V 24 ~ 30V 41 ~ 56V
±1.0%±2.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0%
±0.5%±0.5%
±0.5%±1.0%
84%79% 85% 85% 86% 86%
13.8 ~ 16.2V5.75 ~ 6.75V 15.5 ~ 18.2V 18 ~ 21V 27.6 ~ 32.4V 31 ~ 36.5V 57.6 ~ 67.2V
±0.5%
±0.5%
non-condensing
±0.5%
±0.5%
±0.5%
±0.5%
( except for 5V,12V,13.5V )
48V
±0.5%
±0.5%
File Name:PSP-600-SPEC 2017-07-14
±0.5%
±0.5%
87%

600W with PFC and Parallel Function
PSP-600 series
Mechanical Specification
RS Connector(CN5) : JST B-XH or equivalent
Pin N o.
Assignment Mating Housing
RS+
1
2
RS-
JST XHP
or equivalent
Terminal Pin No. Assignment
Pin N o.
8~11
12~15
1
2
3
4
5
6
7
Assignment
AC/L
AC/N
FG
P(Current Share)
POK
R.C. G
R.C.
DC OUTPUT +V
DC OUTPUT -V
12
CN5
Block Diagram
I/P
FG
EMI
FILTER
ACTIVE
INRUSH
CURRENT
LIMITING
Terminal
JST SXH-001T
or equivalent
120
21
1098
9.5
RECTIFIERS
8
3
&
P. F.C .
4
1211
O.L.P.
5
13
76
15
14
11.5
11.5
POWER
SWITCHING
PWM
CONTROL
14 max.
2-M3 L=4mm max.
FAN
RECTIFIERS
&
FILTER
O.C.P.
DETECTION
CIRCUIT
O.V.P.
O.T.P.
2-M3 L=4mm max.
2-M3 L=4mm max.
SIGNAL CONTROL
150
185
170
150
2-M3 L=4mm max.
CURRENT
SHARING CIRCUIT
Case No.910A Unit:mm
Air flow
58.3
50
100
93
direction
PFC fosc : 88KHz
PWM fosc : 100KHz
POK
P
RS+
+V
-V
RC.G.
RC
R-S
Derating Curve Output Derating VS Input Voltage
100
80
60
50
40
LOAD (%)
20
-2001020304540 50 60 (HORIZONTAL)
Others
12V
AMBIENT TEMPERATURE ( )℃ INPUT VOLTAGE (V) 60Hz
100
90
80
70
60
50
LOAD(%)
40
11588 100 135 155 230 264
File Name:PSP-600-SPEC 2017-07-14

600W with PFC and Parallel Function
Control Terminal Instruction Manual
PSP-600 series
POK(+) RCG(-)
POK POK POK
RCG RCG RCG
LLLNNNFG FG FGPPP
+V +V +V
+V +V +V
+V +V +V+V +V +V-V -V -V-V -V -V-V -V -V-V
RS+ RS+ RS+
RS- RS- RS-
+++---
LOAD LOAD LOAD
POK Signal
POK Signal is the voltage difference between
"RCG" and "POK" pin output POK Signal forTTL level signal
PSU turn on: 3.3V ~ 5.6V
PSU turn off: 0V ~ 1V
RC RC RC
-V -V
Remote Sensing
Parallel Operation with Remote Sensing
(1)Parallel operation is available by connecting the units shown as below (+S,-S and P are connected mutually in parallel) :
(2)The voltage difference among each output should be minimized that less than 0.2V is required.
(3)The total output current must not exceed the value determined by the following equation (Output current at parallel operation)
=(The rated current per unit) x (Number of unit) x 0.9.
(4) In parallel operation 4 units is the maximum, please consult the manufacture for other applications.
(5) When remote sensing is used in parallel operation, the sensing wire must be connected only to the master unit.
(6) When in parallel operation, the minimum output load should be greater than 3% of total output load.
(Min. load > 3% rated current per unit x number of unit)
RCG RC
Remote Control
Power ON: RCG and RC for short
Power OFF: RCG and RC for open
LOAD
+V+S-V
-S
++++
----
PPPP
RCG RCG RCG RCG
RS+ RS+ RS+ RS+RS- RS- RS- RS-
PSU PSU PSU PSU
File Name:PSP-600-SPEC 2017-07-14